Promag 50P2H
Promag 50P2H
Promag 50P2H
Application Electromagnetic flowmeter for bidirectional measurement of liquids with a minimum conductivity of 5 S/cm: Acid, alkalis Paints Pastes Water, wastewater etc. Flow measurement up to 9600 m/h (42268 gal/min) Fluid temperature up to +180 C (356 F) Process pressures up to 40 bar (580 psi) Lengths in accordance with DVGW/ISO
Connection to process control system: HART PROFIBUS DP/PA FOUNDATION Fieldbus MODBUS RS485
Your benefits Promag measuring devices offer you cost-effective flow measurement with a high degree of accuracy for a wide range of process conditions. The uniform Proline transmitter concept comprises: Modular device and operating concept resulting in a higher degree of efficiency Software options for batching, electrode cleaning and for measuring pulsating flow High degree of reliability and measuring stability Uniform operating concept The tried-and-tested Promag sensors offer: No pressure loss Not sensitive to vibrations Simple installation and commissioning
Application-specific lining materials: PTFE PFA Approvals for hazardous area: ATEX IECEx FM CSA NEPSI TIIS
TI047D/06/en/11.09 71106271
Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 25
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measuring tube specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Material load diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fitted electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Surface roughness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 36 37 38 38 40 40 40
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Measuring ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Low flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Language groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 41 41 41
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical connection, measuring unit . . . . . . . . . . . . . . . . . . . . . . 7 Electrical connection, terminal assignment . . . . . . . . . . . . . . . . . . 8 Electrical connection, remote version . . . . . . . . . . . . . . . . . . . . . . 9 Supply voltage (power supply) . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Remote version cable specifications . . . . . . . . . . . . . . . . . . . . . . . . 9 Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance characteristics. . . . . . . . . . . . . . . . . . . . 13
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Endress+Hauser
Ue I
V B I L
A0003191
Ue = B L v Q=Av Ue B L v Q A I Induced voltage Magnetic induction (magnetic field) Electrode spacing Flow velocity Volume flow Pipe cross-section Current strength
Measuring system
The measuring system consists of a transmitter and a sensor. Two versions are available: Compact version: Transmitter and sensor form a mechanical unit. Remote version: Sensor is mounted separate from the transmitter. Transmitter: Promag 50 (user interface with push buttons for operation, two-line display, illuminated) Promag 53 ("Touch Control" without opening the housing, four-line display, unilluminated) Sensor: Promag P (DN 15 to 600 / to 24")
Endress+Hauser
Input
Measured variable Measuring ranges Flow velocity (proportional to induced voltage) Measuring ranges for liquids Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy Over 1000 : 1 Status input (auxiliary input) U = 3 to 30 V DC, Ri = 5 k, galvanically isolated Configurable for: totalizer(s) reset, measured value suppression, error-message reset Status input (auxiliary input) with PROFIBUS DP and MODBUS RS485 U = 3 to 30 V DC, Ri = 3 k, galvanically isolated Switching level: 3 to 30 V DC, independent of polarity Configurable for: totalizer(s) reset, measured value suppression, error-message reset, batching start/stop (optional), batch totalizer reset (optional) Current input (only Promag 53) active/passive selectable, galvanically isolated, full scale value selectable, resolution: 3 A, temperature coefficient: typ. 0.005% o.r./C (o.r. = of reading) active: 4 to 20 mA, Ri 150 , max. 24 V DC, short-circuit-proof passive: 0/4 to 20 mA, Ri < 150 , max. 30 V DC
Output
Output signal Promag 50 Current output active/passive selectable, galvanically isolated, time constant selectable (0.01 to 100 s), full scale value selectable, temperature coefficient: typ. 0.005% o.r./C (o.r. = of reading), resolution: 0.5 A active: 0/4 to 20 mA, RL < 700 (HART: RL 250 ) passive: 4 to 20 mA, operating voltage VS : 18 to 30 V DC, Ri 150 Pulse/frequency output passive, open collector, 30 V DC, 250 mA, galvanically isolated Frequency output: full scale frequency 2 to 1000 Hz (fmax = 1250 Hz), on/off ratio 1:1, pulse width max. 10s Pulse output: pulse value and pulse polarity selectable, max. pulse width configurable (0.5 to 2000 ms) PROFIBUS DP interface Transmission technology (Physical Layer): RS485 in accordance with ANSI/TIA/EIA-485-A: 1998, galvanically isolated Profil version 3.0 Data transmission rate: 9,6 kBaud to 12 MBaud Automatic data transmission rate recognition Function blocks: 1 analog Input, 1 totalizer Output data: volume flow, totalizer Input data: positive zero return (ON/OFF), totalizer control, value for local display Cyclic data transmission compatible with previous model Promag 33 Bus address adjustable via miniature switches or local display (optional) at the measuring device PROFIBUS PA interface Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated Profil version 3.0 Current consumption: 11 mA Permissible supply voltage: 9 to 32 V Bus connection with integrated reverse polarity protection Error current FDE (Fault Disconnection Electronic): 0 mA Function blocks: 1 analog input, 2 totalizer Output data: volume flow, totalizer Input data: positive zero return (ON/OFF), control totalizer, value for local display Cyclic data transmission compatible with previous model Promag 33 Bus address adjustable via miniature switches or local display (optional) at the measuring device
Endress+Hauser
Promag 53 Current output active/passive selectable, galvanically isolated, time constant selectable (0.01 to 100 s), full scale value selectable, temperature coefficient: typ. 0.005% o.r./C (o.r. = of reading), resolution: 0.5 A active: 0/4 to 20 mA, RL < 700 (HART: RL 250 ) passive: 4 to 20 mA, operating voltage VS : 18 to 30 V DC, Ri 150 Pulse/frequency output active/passive selectable, galvanically isolated (Ex i version: only passive) active: 24 V DC, 25 mA (max. 250 mA during 20 ms), RL > 100 passive: open collector, 30 V DC, 250 mA Frequency output: full scale frequency 2 to 10000 Hz (fmax = 12500 Hz), EEx-ia: 2 to 5000 Hz; on/off ratio 1:1, pulse width max. 10 s Pulse output: pulse value and pulse polarity selectable, max. pulse width configurable (0.05 to 2000 ms) PROFIBUS DP interface Transmission technology (Physical Layer): RS485 in accordance with ANSI/TIA/EIA-485-A: 1998, galvanically isolated Profil version 3.0 Data transmission rate: 9,6 kBaud to 12 MBaud Automatic data transmission rate recognition Function blocks: 2 analog Input, 3 totalizer Output data: volume flow, calculated mass flow, totalizer 1 to 3 Input data: positive zero return (ON/OFF), totalizer control, value for local display Cyclic data transmission compatible with previous model Promag 33 Bus address adjustable via miniature switches or local display (optional) at the measuring device Available output combination 8 PROFIBUS PA interface Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated Profil version 3.0 Current consumption: 11 mA Permissible supply voltage: 9 to 32 V Bus connection with integrated reverse polarity protection Error current FDE (Fault Disconnection Electronic): 0 mA Function blocks: 2 analog input, 3 totalizer Output data: volume flow, calculated mass flow, totalizer 1 to 3 Input data: positive zero return (ON/OFF), totalizer control, value for local display Cyclic data transmission compatible with previous model Promag 33 Bus address adjustable via miniature switches or local display (optional) at the measuring device MODBUS RS485 interface Transmission technology (Physical Layer): RS485 in accordance with ANSI/TIA/EIA-485-A: 1998, galvanically isolated MODBUS device type: Slave Adress range: 1 to 247 Bus address adjustable via miniature switches or local display (optional) at the measuring device Supported MODBUS function codes: 03, 04, 06, 08, 16, 23 Broadcast: supported with the function codes 06, 16, 23 bertragungsmodus: RTU oder ASCII Supported baudrate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud Response time: Direct data access = typically 25 to 50 ms Auto-scan buffer (data range) = typically 3 to 5 ms Available output combination 8
Endress+Hauser
FOUNDATION Fieldbus interface FOUNDATION Fieldbus H1 Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated ITK version 5.01 Current consumption: 12 mA Error current FDE (Fault Disconnection Electronic): 0 mA Bus connection with integrated reverse polarity protection Function blocks: 5 Analog Input (execution time: 18 ms each) 1 PID (25 ms) 1 Digital Output (18 ms) 1 Signal Characterizer (20 ms) 1 Input Selector (20 ms) 1 Arithmetic (20 ms) 1 Integrator (18 ms) Output data: volume flow, calculated mass flow, temperature, totalizer 1 to 3 Input data: positive zero return (ON/OFF), reset totalizer Link Master (LM) functionality is supported Signal on alarm Current output failure response selectable (e.g. in accordance with NAMUR recommendation NE 43) Pulse/frequency output failure response selectable Status output (Promag 50) non-conductive by fault or power supply failure Relay output (Promag 53) de-energized by fault or power supply failure
see "Output signal" Switch points for low flow cutoff are selectable. All circuits for inputs, outputs and power supply are galvanically isolated from each other. Status output (Promag 50, Promag 53) Open collector, max. 30 V DC / 250 mA, galvanically isolated. Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values. Relay outputs (Promag 53) Normally closed (NC or break) or normally open (NO or make) contacts available (default: relay 1 = NO, relay 2 = NC), max. 30 V / 0,5 A AC ; 60 V / 0,1 A DC, galvanically isolated. Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values, batching contacts.
Endress+Hauser
Power supply
Electrical connection, measuring unit
d g b a a b d/(g) (d) HART* PROFIBUS PA* FOUNDATION Fieldbus*
PA()/FF() PA(+)/FF(+) + f + + 27 26 25 24 23 22 21 20
A d g b
27 + 26 25 + 24 23 + 22 21 + 20
d e
d e
N (L-) 2 L1 (L+)1
c b
N (L-) 2 L1 (L+) 1
c b
PROFIBUS DP*
A (RxD/TxD-N) 27 B (RxD/TxD-P) 26 25 + 24 f 23 + 22 21 + 20
d e g c b
d e g c b
A0002441
N (L-) 2 L1 (L+) 1
N (L-) 2 L1 (L+) 1
Connecting the transmitter, cable cross-section max. 2.5 mm2 (14 AWG) A B C *) **) a b View A (field housing) View B (stainless steel field housing) View C (wall-mount housing) fixed communication boards flexible communication boards Connection compartment cover Cable for power supply: 85 to 260 V AC / 20 to 55 V AC / 16 to 62 V DC - Terminal No. 1: L1 for AC, L+ for DC - Terminal No. 2: N for AC, L for DC Ground terminal for protective conductor Signal cable: see "Electrical connection, terminal assignment" 8 Fieldbus cable: - Terminal No. 26: DP (B) / PA + / FF + / MODBUS RS485 (B) / (PA, FF: with polarity protection) - Terminal No. 27: DP (A) / PA / FF / MODBUS RS485 (A) / (PA, FF: with polarity protection) Ground terminal for signal cable shield / Fieldbus cable / RS485 line Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare) Signal cable: see "Electrical connection, terminal assignment" 8 Cable for external termination (only for PROFIBUS DP with fixed assignment communication board): - Terminal No. 24: +5 V - Terminal No. 25: DGND
c d
e f g
Endress+Hauser
Terminal assignment, Promag 53 The inputs and outputs on the communication board can be either permanently assigned or variable, depending on the version ordered (see table). Replacements for modules which are defective or which have to be replaced can be ordered as accessories.
Order variant 20 (+) / 21 () Terminal No. (inputs/outputs) 22 (+) / 23 () 24 (+) / 25 () 26 (+) / 27 ()
Fixed communication boards (fixed assignment) 53***-***********A 53***-***********B 53***-***********F 53***-***********G 53***-***********H 53***-***********J 53***-***********K 53***-***********Q 53***-***********S 53***-***********T Flexible communication boards 53***-***********C 53***-***********D 53***-***********L 53***-***********M 53***-***********N 53***-***********P 53***-***********V 53***-***********2 53***-***********4 53***-***********5 53***-***********7 Ground terminal 7 Relay output 2 Status input Status input Status input Current output Current output Relay output 2 Relay output Current input Status input Relay output 2 Relay output 1 Relay output Relay output 2 Frequency output Frequency output Frequency output Relay output 1 Current output Relay output Current input Relay output 1 Frequency output Frequency output Relay output 1 Frequency output Status input Status input Status input Frequency output Frequency output Frequency output Status input Current output HART Current output HART Current output HART Current output HART MODBUS RS485 PROFIBUS DP PROFIBUS DP Current output HART Current output HART Current output HART MODBUS RS485 Relay output 2 Relay output 1 Frequency output Frequency output Status input Frequency output, Ex i Frequency output, Ex i Current output HART Current output HART PROFIBUS PA, Ex i FOUNDATION Fieldbus, Ex i PROFIBUS PA PROFIBUS DP FOUNDATION Fieldbus MODBUS RS485 Current output, Ex i, passive, HART Current output, Ex i, passive, HART
Endress+Hauser
GND
S2
6 a
4 37 36
42 41
n.c. b 5
n.c. 7 4 37
n.c. 42 41
E1
GND
E2
A0011722
Connecting the remote version a Wall-mount housing connection compartment b Sensor connection housing cover c Signal cable d Coil current cable n.c. Not connected, insulated cable shields Terminal no. and cable colors: 6/5 = brown; 7/8 = white; 4 = green; 36/37 = yellow
Cable entry
Power supply and signal cables (inputs/ outputs): Cable entry M20 1.5 (8 to 12 mm / 0.31 to 0.47") Sensor cable entry for armoured cables M20 1.5 (9.5 to 16 mm / 0.37 to 0.63") Thread for cable entries, " NPT, G " Connecting cable for remote version: Cable entry M20 1.5 (8 to 12 mm / 0.31 to 0.47") Sensor cable entry for armoured cables M20 1.5 (9.5 to 16 mm / 0.37 to 0.63") Thread for cable entries, " NPT, G "
Coil cable 2 0.75 mm2 (18 AWG) PVC cable with common, braided copper shield ( 7 mm / 0.28") Conductor resistance: 37 /km ( 0.011 /ft) Capacitance core/core, shield grounded: 120 pF/m ( 37 pF/ft) Operating temperature: 20 to +80 C (68 to +176 F) Cable cross-section: max. 2.5 mm2 (14 AWG) Test voltage for cable insulation: 1433 AC r.m.s. 50/60 Hz or 2026 V DC Signal cable 3 0.38 mm2 (20 AWG) PVC cable with common, braided copper shield ( 7 mm / 0.28") and individual shielded cores With empty pipe detection (EPD): 4 0.38 mm2 (20 AWG) PVC cable with common, braided copper shield ( 7 mm / 0.28") and individual shielded cores Conductor resistance: 50 /km ( 0.015 /ft) Capacitance core/shield: 420 pF/m ( 128 pF/ft) Operating temperature: 20 to +80 C (68 to +176 F) Cable cross-section: max. 2.5 mm2 (14 AWG)
Endress+Hauser
1 2 3 4 5 6 7 a b
A0003194
a b 1 2 3 4 5 6 7
Signal cable Coil current cable Core Core insulation Core shield Core jacket Core reinforcement Cable shield Outer jacket
Operation in zones of severe electrical interference The measuring device complies with the general safety requirements in accordance with EN 61010 and the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.
"
Power consumption
Caution! Grounding is by means of the ground terminals provided for the purpose inside the connection housing. Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible. AC: < 15 VA (incl. sensor) DC: < 15 W (incl. sensor) Switch-on current: Max. 3 A (< 5 ms) for 260 V AC Max. 13.5 A (< 50 ms) for 24 V DC
Lasting min. cycle frequency: EEPROM saves measuring system data EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number, calibration factor, zero point etc.)
10
Endress+Hauser
Potential equalization
Warning! The measuring system must be included in the potential equalization. Perfect measurement is only ensured when the fluid and the sensor have the same electrical potential. This is ensured by the reference electrode integrated in the sensor as standard. The following should also be taken into consideration for potential equalization: Internal grounding concepts in the company Operating conditions, such as the material/ grounding of the pipes (see table) Standard situation
Operating conditions When using the measuring device in a: Metal, grounded pipe Potential equalization takes place via the ground terminal of the transmitter. Note! When installing in metal pipes, we recommend you connect the ground terminal of the transmitter housing with the piping.
A0011892
Potential equalization
Special situations
Operating conditions When using the measuring device in a: Metal pipe that is not grounded This connection method also applies in situations where: Customary potential equalization cannot be ensured. Excessively high equalizing currents can be expected. Both sensor flanges are connected to the pipe flange by means of a ground cable (copper wire, at least 6 mm / 0.0093 in) and grounded. Connect the transmitter or sensor connection housing, as applicable, to ground potential by means of the ground terminal provided for the purpose. DN 300 (12"): the ground cable is mounted directly on the conductive flange coating with the flange screws. DN 350 (14"): the ground cable is mounted directly on the transportation metal support. Note! The ground cable for flange-to-flange connections can be ordered separately as an accessory from Endress+Hauser.
A0011893
Potential equalization
DN 300
DN 350
Via the ground terminal of the transmitter and the flanges of the pipe When using the measuring device in a: Plastic pipe Pipe with insulating lining This connection method also applies in situations where: Customary potential equalization cannot be ensured. Excessively high equalizing currents can be expected. Potential equalization takes place using additional ground disks, which are connected to the ground terminal via a ground cable (copper wire, at least 6 mm / 0.0093 in). When installing the ground disks, please comply with the enclosed Installation Instructions.
A0011895
Via the ground terminal of the transmitter and the optionally available ground disks
Endress+Hauser
11
Operating conditions When using the measuring device in a: Pipe with a cathodic protection unit The device is installed potential-free in the pipe. Only the two flanges of the pipe are connected with a ground cable (copper wire, at least 6 mm / 0.0093 in). Here, the ground cable is mounted directly on the conductive flange coating with flange screws. Note the following when installing: The applicable regulations regarding potential-free installation must be observed. There should be no electrically conductive connection between the pipe and the device. The mounting material must withstand the applicable torques.
Potential equalization
A0011896
Potential equalization and cathodic protection 1 2 Power supply isolation transformer Electrically isolated
12
Endress+Hauser
Performance characteristics
Reference operating conditions As per DIN EN 29104 and VDI/VDE 2641: Fluid temperature: +28 C 2 K (+82 F 2 K) Ambient temperature: +22 C 2 K (+72 F 2 K) Warm-up period: 30 minutes Installation conditions: Inlet run > 10 DN Outlet run > 5 DN Sensor and transmitter grounded. The sensor is centered in the pipe. Maximum measured error Promag 50: Current output: also typically 5 A Pulse output: 0.5% o.r. 1 mm/s (0.5% o.r. 0.04 in/s) optional: 0.2% o.r. 2 mm/s (0.2% o.r. 0.08 in/s) (o.r. = of reading) Promag 53: Current output: also typically 5 A Pulse output: 0.2% o.r. 2 mm/s (0.2% o.r. 0.08 in/s) (o.r. = of reading) Fluctuations in the supply voltage do not have any effect within the specified range.
[%] 2.5 2.0 0.5 % 1.5 1.0 0.5 0 0 1 2 4 6 8 10 [m/s] v [ft] A0005531 0.2 %
10
15
20
25
30
32
Repeatability
Max. 0.1% o.r. 0.5 mm/s (0.1% o.r. 0.02 in/s) (o.r. = of reading)
Endress+Hauser
13
h 2 x DN
A0011899
Mounting location
Installation of pumps Sensors may not be installed on the pump suction side. This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. Information on the pressure tightness of the measuring tube lining 22, Section "Pressure tightness". Pulsation dampers may be needed when using piston pumps, piston diaphragm pumps or hose pumps. Information on the shock and vibration resistance of the measuring system 20, Section "Shock and vibration resistance".
A0011900
Installation of pumps
14
Endress+Hauser
Partially filled pipes Partially filled pipes with gradients necessitate a drain-type configuration. The empty pipe detection function (EPD) provides additional security in detecting empty or partially filled pipes.
"
Caution! Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to install a cleaning valve.
2 x DN 5 x DN
A0011901
Down pipes Install a siphon or a vent valve downstream of the sensor in down pipes h 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. This measure also prevents the liquid current stopping in the pipe which could cause air locks. Information on the pressure tightness of the measuring tube lining 22, Section "Pressure tightness".
A0011902
Installation measures for vertical pipes 1 2 h Vent valve Pipe siphon Length of the down pipe
Endress+Hauser
15
Orientation An optimum orientation helps avoid gas and air accumulations and deposits in the measuring tube. However, the measuring device also offers the additional function of empty pipe detection (EPD) for detecting partially filled measuring tubes or if outgassing fluids or fluctuating operating pressures are present. Vertical orientation This is the ideal orientation for self-emptying piping systems and for use in conjunction with empty pipe detection.
A0011903
Vertical orientation
Horizontal orientation The measuring electrode axis should be horizontal. This prevents brief insulation of the two measuring electrodes by entrained air bubbles.
"
Caution! Empty pipe detection only works correctly with horizontal orientation if the transmitter housing is facing upwards. Otherwise there is no guarantee that empty pipe detection will respond if the measuring tube is only partially filled or empty.
A
1
A
3
A0011904
Horizontal orientation 1 2 3 EPD electrode for empty pipe detection Measuring electrodes for signal detection Reference electrode for potential equalization
16
Endress+Hauser
"
Caution! If vibrations are too severe, we recommend the sensor and transmitter be mounted separately. Information on the permitted shock and vibration resistance 20, Section "Shock and vibration resistance".
L
A0011906
"
Foundations, supports If the nominal diameter is DN 350, mount the transmitter on a foundation of adequate load-bearing strength. Caution! Do not allow the casing to take the weight of the sensor. This would buckle the casing and damage the internal magnetic coils.
A0003209
Endress+Hauser
17
If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows etc. Note the following inlet and outlet runs to comply with measuring accuracy specifications: Inlet run: 5 DN Outlet run: 2 DN
5 x DN
2 x DN
A0011905
Adapters
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids. The nomogram shown here can be used to calculate the pressure loss caused by reducers and expanders.
Note! The nomogram only applies to liquids of viscosity similar to water. 1. 2. Calculate the ratio of the diameters d/D. From the nomogram read off the pressure loss as a function of flow velocity (downstream from the reduction) and the d/D ratio.
[mbar] 100
8 m/s 7 m/s 6 m/s
10
5 m/s
max. 8 d D
1
1 m/s
d/D
Pressure loss due to adapters
0.5
0.6
0.7
0.8
0.9
A0011907
18
Endress+Hauser
When mounting the remote version, please note the following to achieve correct measuring results: Fix cable run or lay in armored conduit. Cable movements can falsify the measuring signal especially in the case of low fluid conductivities. Route the cable well clear of electrical machines and switching elements. If necessary, ensure potential equalization between sensor and transmitter. The permitted cable length Lmax is determined by the fluid conductivity. A minimum conductivity of 20 S/cm is required for measuring demineralized water. When the empty pipe detection function is switched on (EPD), the maximum connecting cable length is 10 m (33 ft).
[S/cm] 200
100 L max
Permitted length of connecting cable for remote version Area marked in gray = permitted range; Lmax = length of connecting cable in [m] ([ft]); fluid conductivity in [S/cm]
Endress+Hauser
19
! "
Caution! The permitted temperature range of the measuring tube lining may not be undershot or overshot 21, Section "Medium temperature range". Please note the following points: Install the device in a shady location. Avoid direct sunlight, particularly in warm climatic regions. The transmitter must be mounted separate from the sensor if both the ambient and fluid temperatures are high.
Storage temperature
The storage temperature corresponds to the operating temperature range of the measuring transmitter and the appropriate measuring sensors.
"
Caution! The measuring device must be protected against direct sunlight during storage in order to avoid unacceptably high surface temperatures. A storage location must be selected where moisture does not collect in the measuring device. This will help prevent fungus and bacteria infestation which can damage the liner. Do not remove the protective plates or caps on the process connections until the device is ready to install. Standard: IP 67 (NEMA 4X) for transmitter and sensor. Optional: IP 68 (NEMA 6P) for sensor for remote version. For information regarding applications where the device is buried directly in the soil or is installed in a flooded wastewater basin please contact your local Endress+Hauser Sales Center. Acceleration up to 2 g following IEC 600 68-2-6 As per IEC/EN 61326 and NAMUR recommendation NE 21.
Degree of protection
20
Endress+Hauser
TA [F] 140
[C] 60
HT
100
40
n
20
0 0
PFA
-20
-40
-40
PTFE
m
0 20 40 100 60 80 100 120 140 160 180 200 300 [C] TF 360 [F]
A0002660
Compact version (with PFA or PTFE lining) TA = Ambient temperature, TF = Fluid temperature, HT = High temperature version with insulatio Gray shaded area temperature range from 10 to 40 C (14 to 40 F) applies only to stainless steel flanges n HE + IP 68 to 130 C (266 F) only
TA [F] 140
[C] 60
HT
100
40
n
20
0 0
PFA
-20
-40
-40
PTFE
m
0 20 40 100 60 80 100 120 140 160 180 200 300 [C] TF 360 [F]
A0002671
Remote version (with PFA or PTFE lining) TA = Ambient temperature, TF = Fluid temperature, HT = High temperature version with insulatio Gray shaded area temperature range from 10 to 40 C (14 to 40 F) applies only to stainless steel flanges n HE + IP 68 to 130 C (266 F) only
Endress+Hauser
21
Conductivity
!
Medium pressure range (nominal pressure)
The minimum conductivity is: 5 S/cm for fluids generally 20 S/cm for demineralized water Note! In the remote version, the necessary minimum conductivity also depends on the cable length ( 19, Section "Length of connecting cable"). EN 1092-1 (DIN 2501) PN 10 (DN 200 to 600 / 8 to 24") PN 16 (DN 65 to 600 / 3 to 24") PN 25 (DN 200 to 600 / 8 to 24") PN 40 (DN 15 to 150 / to 6") ANSI B 16.5 Class 150 (DN to 24") Class 300 (DN to 6") JIS B2220 10 K (DN 50 to 300 / 2 to 12") 20 K (DN 15 to 300 / to 12") AS 2129 Table E (DN 25, 50 / 1", 2") AS 4087 PN 16 (DN 50 / 2") Measuring tube lining: PTFE
Nominal diameter Limit values for abs. pressure [mbar] ([psi]) at fluid temperatures: 25 C (77 F) [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 [inch] " 1" 1" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" Partial vacuum is impermissible! [mbar] 0 0 0 0 0 0 0 0 135 135 200 330 400 470 540 [psi] 0 0 0 0 0 0 0 0 1.96 1.96 2.90 4.79 5.80 6.82 7.83 80 C (176 F) [mbar] 0 0 0 0 0 * * * * * * * * * * [psi] 0 0 0 0 0 * * * * * * * * * * 100 C (212 F) [mbar] 0 0 0 0 0 40 40 135 240 240 290 400 500 600 670 [psi] 0 0 0 0 0 0.58 0.58 1.96 3.48 3.48 4.21 5.80 7.25 8.70 9.72 130 C (266 F) [mbar] 100 100 100 100 100 130 130 170 385 385 410 530 630 730 800 [psi] 1.45 1.45 1.45 1.45 1.45 1.89 1.89 2.47 5.58 5.58 5.95 7.69 9.14 10.6 11.6
Pressure tightness
22
Endress+Hauser
Limiting flow
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum flow velocity is between 2 to 3 m/s (6.5 to 9.8 ft/s). The velocity of flow (v), moreover, has to be matched to the physical properties of the fluid: v < 2 m/s (6.5 ft/s): for abrasive fluids such as potter's clay, lime milk, ore slurry etc. v > 2 m/s (6.5 ft/s): for fluids causing build-up such as wastewater sludges etc.
Flow characteristic values (SI units) Diameter [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 [inch] " 1" 1" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" Recommended flow rate Min./max. full scale value (v ~ 0.3 or 10 m/s) 4 to 100 dm3/min 9 to 300 dm3/min 15 to 500 dm3/min 25 to 700 dm3/min 35 to 1100 dm3/min 60 to 2000 dm3/min 90 to 3000 dm3/min 145 to 4700 dm3/min 220 to 7500 dm3/min 20 to 600 m3/h 35 to 1100 m3/h 55 to 1700 m3/h 80 to 2400 m3/h 110 to 3300 m3/h 140 to 4200 m3/h 180 to 5400 m3/h 220 to 6600 m3/h 310 to 9600 m3/h Factory settings Full scale value, current output (v ~ 2.5 m/s) 25 dm3/min 75 dm3/min 125 dm3/min 200 dm3/min 300 dm3/min 500 dm3/min 750 dm3/min 1200 dm3/min 1850 dm3/min 150 m3/h 300 m3/h 500 m3/h 750 m3/h 1000 m3/h 1200 m3/h 1500 m3/h 2000 m3/h 2500 m3/h Pulse value (~ 2 pulses/s) 0.20 dm3 0.50 dm3 1.00 dm3 1.50 dm3 2.50 dm3 5.00 dm3 5.00 dm3 10.0 dm3 15.0 dm3 0.03 m3 0.05 m3 0.05 m3 0.10 m3 0.10 m3 0.15 m3 0.25 m3 0.25 m3 0.30 m3 Low flow cut off (v ~ 0.04 m/s) 0.50 dm3/min 1.00 dm3/min 2.00 dm3/min 3.00 dm3/min 5.00 dm3/min 8.00 dm3/min 12.0 dm3/min 20.0 dm3/min 30.0 dm3/min 2.50 m3/h 5.00 m3/h 7.50 m3/h 10.0 m3/h 15.0 m3/h 20.0 m3/h 25.0 m3/h 30.0 m3/h 40.0 m3/h
Endress+Hauser
23
Flow characteristic values (US units) Diameter [inch] " 1" 1" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" [mm] 25 25 40 50 80 100 150 200 250 300 350 400 450 500 600 Recommended flow rate Min./max. full scale value (v ~ 0.3 or 10 m/s) 1.0 to 26 gal/min 2.5 to 80 gal/min 7 to 190 gal/min 10 to 300 gal/min 24 to 800 gal/min 40 to 1250 gal/min 90 to 2650 gal/min 155 to 4850 gal/min 250 to 7500 gal/min 350 to 10600 gal/min 500 to 15000 gal/min 600 to 19000 gal/min 800 to 24000 gal/min 1000 to 30000 gal/min 1400 to 44000 gal/min Factory settings Full scale value, current output (v ~ 2.5 m/s) 6 gal/min 18 gal/min 50 gal/min 75 gal/min 200 gal/min 300 gal/min 600 gal/min 1200 gal/min 1500 gal/min 2400 gal/min 3600 gal/min 4800 gal/min 6000 gal/min 7500 gal/min 10500 gal/min Pulse value (~ 2 pulses/s) 0.10 gal 0.20 gal 0.50 gal 0.50 gal 2.00 gal 2.00 gal 5.00 gal 10.0 gal 15.0 gal 25.0 gal 30.0 gal 50.0 gal 50.0 gal 75.0 gal 100.0 gal Low flow cut off (v ~ 0.04 m/s) 0.15 gal/min 0.25 gal/min 0.75 gal/min 1.25 gal/min 2.50 gal/min 4.00 gal/min 12.0 gal/min 15.0 gal/min 30.0 gal/min 45.0 gal/min 60.0 gal/min 60.0 gal/min 90.0 gal/min 120.0 gal/min 180.0 gal/min
Pressure loss
No pressure loss if the sensor is installed in a pipe with the same nominal diameter. Pressure losses for configurations incorporating adapters according to DIN EN 545 ( 18, Section "Adapters").
24
Endress+Hauser
Mechanical construction
Design, dimensions Transmitter remote version, wall-mount housing (non Ex-zone and II3G/Zone 2)
Esc
D C B
F A H J E K
L
A0001150
Endress+Hauser
25
A A* B B* C D
e r Sp annu ht unt ng Nic ffnen
Nicht-eigensichere Stromkreise durch IP40-Abdeckung geschtzt Non-intrinsically safe circuits Ip40 protected Boucles de courant sans scurit intrinsque protges par Ip40
Esc
E J K L M
G H
A0002128
26
Ne
Endress+Hauser
There is a separate mounting kit for the wall-mounted housing. It can be ordered from Endress+Hauser as an accessory. The following installation variants are possible: Panel-mounted installation Pipe mounting Installation in control panel
210 (8.27)
245 (9.65)
mm (inch)
~110 (~4.33)
A0001131
Pipe mounting
2070 ( 0.792.75)
Endress+Hauser
27
A A*
B C
Esc
D F
H K L
A0005423
110 (4.33)
D1
E1
mm (inch)
A0005529
Measurement D1, E1 = Measurement D, E of the standard compact version plus 110 mm (4.33")
28
Endress+Hauser
L 1)
A*
200 200 200 200 200 200 200 250 250 300 350 450 500 227 207 187 168 160
341 341 341 341 341 391 391 391 472 472 527 577 627
257 257 257 257 257 282 282 282 322 322 347 372 397
120 120 120 120 120 180 180 180 260 260 324 400 460
The length is regardless of the pressure rating selected. Fitting length to DVGW. Only DN 25 and DN 50 are available for flanges according to AS. All dimensions in [mm]
L 1)
A*
7.87 7.87 7.87 7.87 7.87 8.94 9.84 11.8 13.8 17.7 19.7 8.15 7.36 6.61 6.30
13.4 13.4 13.4 13.4 15.4 15.4 18.6 20.8 22.7 24.7
10.1 10.1 10.1 10.1 11.1 11.1 12.7 13.7 14.7 15.6
3.31 3.31 3.31 3.31 4.29 4.29 5.91 7.09 8.07 9.06
3.70 3.70 3.70 3.70 3.70 3.70 5.51 6.14 6.54 6.54
4.72 4.72 4.72 4.72 7.09 7.09 10.2 12.8 15.8 18.1
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [inch]
Endress+Hauser
29
A A*
B C
Esc
F
J H L
A0005424
L 1)
A*
G
G
E
H
550 600 650 650 780 227 207 187 168 160
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [mm]
L 1)
A*
21.7 23.6 25.6 25.6 30.7 8.94 8.15 7.36 6.61 6.30
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [inch]
30
Endress+Hauser
B C
D F
J H L
A0012462
110 (4.33)
D1
E1
mm (inch)
A0005570
Measurement D1, E1 = Measurement D, E of the standard remote version plus 110 mm (4.33")
Endress+Hauser
31
L 1)
200 200 200 200 200 200 200 250 250 300 350 450 500 129 163 143 102
286 286 286 286 286 336 336 336 417 417 472 522 572
202 202 202 202 202 227 227 227 267 267 292 317 342
120 120 120 120 120 180 180 180 260 260 324 400 460
The length is regardless of the pressure rating selected. Fitting length to DVGW. Only DN 25 and DN 50 are available for flanges according to AS. All dimensions in [mm]
L 1)
7.87 7.87 7.87 7.87 7.87 5.08 9.84 11.8 13.8 17.7 19.7 6.42 5.63 4.02
11.3 11.3 11.3 11.3 13.2 13.2 16.4 18.6 20.6 22.5
7.95 7.95 7.95 7.95 8.94 8.94 10.5 11.5 12.5 13.5
3.31 3.31 3.31 3.31 4.29 4.29 5.91 7.08 8.07 9.06
4.72 4.72 4.72 4.72 7.09 7.09 10.2 12.8 15.8 18.1
3.70 3.70 3.70 3.70 3.70 3.70 5.51 6.14 6.54 6.54
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [inch]
32
Endress+Hauser
B C
F
J H L
E
A0003220
L 1)
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [mm]
L 1)
The length is regardless of the pressure rating selected. Fitting length to DVGW. All dimensions in [inch]
Endress+Hauser
33
DN 300 (12")
DN 350 (14")
B
A
C
A PTFE, PFA 16 26 35 41 52 68 80 104 130 158 206 260 312 310 343 393 439 493 593
43 62 80 82 101 121 131 156 187 217 267 328 375 375 433 480 538 592 693
61.5 77.5 87.5 101 115.5 131.5 154.5 186.5 206.5 256 288 359 413 404 479 542 583 650 766
73 87.5 94.5 103 108 118 135 6.5 153 160 184 205 240 273 268 365 395 417 460 522 9.0 2
disks at DN 15 to 250 ( to 10") can be used for all flange standards/pressure ratings. Only DN 25 and DN 50 are available for flanges according to AS. 3) PN 10/16 4) PN 25, JIS 10K/20K All dimensions in [mm]
34
Endress+Hauser
D
A0003221
A PTFE, PFA 0.63 1.02 1.61 2.05 3.15 4.09 6.22 8.11 10.2 12.3 13.5 15.45 17.3 19.4 23.4
1.69 2.44 3.23 3.98 5.16 6.14 8.54 10.5 12.9 14.8 17.1 18.9 21.2 23.3 27.3
2.42 3.05 3.98 4.55 6.08 7.34 10.08 11.3 14.1 16.3 18.9 21.3 23.0 25.6 30.1
2.87 3.44 4.06 4.25 5.31 0.26 6.02 7.24 8.07 9.45 10.8 14.4 15.6 16.4 18.1 20.6 0.35 0.08
disks can be used for all flange standards/pressure ratings. All dimensions in [inch]
Endress+Hauser
35
Weight
Weight in SI units
Weight data in kg Nominal diameter [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600
1)
Compact version
Remote version (without cable) Sensor Transmitter ANSI 4.5 5.3 7.4 8.6 12.0 14.0 Class 150 6.0 23.5 43 73 108 173 203 253 283 403 Wall-mount housing
[inch] EN (DIN) / AS 1) " 1" PN 40 1" 2" 3" PN 16 4" 6" 8" 10" 12" PN 10 14" 16" 18" 20" 24" 6.5 7.3 8.0 9.4 10.6 12.0 10K 14.0 16.0 21.5 25.5 45 65 70 115 135 175 175 235
JIS 6.5 7.3 7.3 8.3 9.3 11.1 12.5 14.7 21.0 24.5 41.9 69.4 72.3 Class 150
EN (DIN) / AS 1) 4.5 5.3 PN 40 6.0 7.4 8.6 10.0 12.0 PN 16 14.0 19.5 23.5 43 63 68 PN 10 113 133 173 173 233 10K
JIS 4.5 5.3 5.3 6.3 7.3 9.1 10.5 12.7 19.0 22.5 39.9 67.4 70.3
Transmitter (compact version): 3.4 kg, high temperature version: +1.5 kg Weight data valid for standard pressure ratings and without packaging material.
36
Endress+Hauser
Transmitter (compact version): 7.50 lbs, high temperature version: +3.31 lbs Weight data valid for standard pressure ratings and without packaging material.
Diameter EN (DIN) [mm] 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 [inch] " 1" 1" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" [bar] PN 40 PN 40 PN 40 PN 40 PN 40 PN 16 PN 16 PN 16 PN 16 PN 16 PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 PN 10 Table E Table E AS 2129
Pressure rating AS 4087 ANSI [lbs] PN 16 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 Cl.150 20K 20K 20K 20K 10K 10K 10K 10K 10K 10K 10K 10K 10K JIS
Internal diameter PFA [mm] 23 32 36 48 63 75 101 126 154 201 [inch] 0.91 1.26 1.42 1.89 2.48 2.95 3.98 4.96 6.06 7.91 23 PTFE [mm] 15 26 35 41 52 67 80 104 129 156 202 256 306 337 387 432 487 593 [inch] 0.59 1.02 1.38 1.61 2.05 2.64 3.15 4.09 5.08 6.14 7.95 10.1 12.0 13.3 15.2 17.0 19.2 23.3
Endress+Hauser
37
Material
Transmitter housing Compact housing: powder-coated die-cast aluminum Wall-mount housing: powder-coated die-cast aluminum Sensor housing DN 25 to 300 (1 to 12"): powder-coated die-cast aluminum DN 350 to 600 (14 to 24"): with protective lacquering Measuring tube DN 300 (12"): stainless steel 1.4301 or 1.4306/304L; DN 350 (14"): stainless steel 1.4301 or 1.4306/304L;
(for flanges made of carbon steel with Al/Zn protective coating) (for flanges made of carbon steel with protective lacquering)
Electrodes: 1.4435, Platinum, Alloy C-22, Tantalum, Titanium Flanges EN 1092-1 (DIN 2501): 1.4571/316L; RSt37-2 (S235JRG2); C22; FE 410W B (DN 300 (12"): with Al/Zn protective coating; DN 350 (14") with protective lacquering) ANSI: A105; F316L (DN 300 (12"): with Al/Zn protective coating; DN 350 (14") with protective lacquering) AWWA: 1.0425 JIS: RSt37-2 (S235JRG2); HII; 1.0425/316L (DN 300 (12"): with Al/Zn protective coating; DN 350 (14") with protective lacquering) AS 2129 DN 25 (1"): A105 or RSt37-2 (S235JRG2) DN 40 (1 "): A105 or St44-2 (S275JR) AS 4087: A105 or St44-2 (S275JR) Seals: to DIN EN 1514-1 Ground disks: 1.4435/316L or Alloy C-22 Material load diagram
"
Caution! The following diagrams contain material load diagrams (reference curves) for flange materials with regard to the medium temperature. However, the maximum medium temperatures permitted always depend on the lining material of the sensor and/or the sealing material ( 21).
Flange connection to EN 1092-1 (DIN 2501) Material: RSt37-2 (S235JRG2) / C22 / Fe 410W B
[psi] 600
500 400
[bar]
40
PN 40
35 30 25
PN 25
38
Endress+Hauser
[bar]
40 35 30 25 20 15 10 5 0
PN 40
PN 25
PN 16 PN 10 PN 6
50 40 30 20 10 0
Class 300
Class 150
-40 -20
-40 0
50 40 30 20 10 0 -40 -20
-40 0
Class 150 Class 300
Endress+Hauser
39
Flange connection to JIS B2220 Material: RSt37-2 (S235JRG2) / HII / 1.0425 / 316L
[psi] [bar]
30
400 300 200
20K
20
10
100 0
10K
-40 -20
-40 0
Flange connection to AS 2129 Table E or AS 4087 PN 16 Material: A105 / RSt37-2 (S235JRG2) / St44-2 (S275JR)
[psi] [bar]
300 200 100 0
20
PN 16
15
Table E
10 5 0
-40 -20
-40 0
Fitted electrodes
Measuring electrodes, reference electrodes and empty pipe detection electrodes: Standard available with 1.4435, Alloy C-22, tantalum, platinum/rhodium 80/20, titanium Optional: measuring electrodes made of platinum/rhodium 80/20 Flange connection: EN 1092-1 (DIN 2501), DN 300 (12") form A, DN 350 (14") form B (Dimensions to DIN 2501, DN 65 PN 16 and DN 600 (24") PN 16 exclusively to EN 1092-1) ANSI B16.5 JIS B2220 AS 2129 Table E AS 4087 PN 16 PFA liner: 0.4 m (15.7 in) Elektroden 1.4435, Alloy C-22, titanium: 0.3 to 0.5 m ( 11.8 to 19.7 in) Tantal, Platin/Rhodium: 0.3 to 0.5 m ( 11.8 to 19.7 in) (All data refer to parts in contact with medium)
Process connections
Surface roughness
40
Endress+Hauser
Human interface
Display elements Liquid crystal display: backlit, two lines (Promag 50) or four lines (Promag 53) with 16 characters per line Custom configurations for presenting different measured-value and status variables Totalizer Promag 50: 2 totalizers Promag 53: 3 totalizers Unified operation concept for both types of transmitter: Promag 50: Local operation via three keys (S, O, F) Quick Setup menus for straightforward commissioning Promag 53: Local operation via three keys (S, O, F) Application-specific Quick Setup menus for straightforward commissioning Language groups Language groups available for operation in different countries: Promag 50, Promag 53: Western Europe and America (WEA): English, German, Spanish, Italian, French, Dutch, Portuguese Eastern Europe and Scandinavia (EES): English, Russian, Polish, Norwegian, Finnish, Swedish, Czech South and east Asia (SEA): English, Japanese, Indonesian Promag 53: China (CN): English, Chinese You can change the language group via the operating program "FieldCare". Remote operation Promag 50: Remote control via HART, PROFIBUS DP/PA Promag 53: Remote control via HART, PROFIBUS DP/PA, MODBUS RS485, FOUNDATION Fieldbus
Operating elements
Endress+Hauser
41
C-tick mark
Ex approval
The measuring device meets all the requirements of the MODBUS/TCP conformity test and has the MODBUS/TCP Conformance Test Policy, Version 2.0. The measuring device has successfully passed all the test procedures carried out and is certified by the MODBUS/TCP Conformance Test Laboratory of the University of Michigan. The flow device has successfully passed all the test procedures carried out and is certified and registered by the PNO (PROFIBUS User Organisation). The device thus meets all the requirements of the following specifications: Certified to PROFIBUS PA, profile version 3.0 (device certification number: on request) The device can also be operated with certified devices of other manufacturers (interoperability)
42
Endress+Hauser
Ordering information
Your Endress+Hauser service organization can provide detailed ordering information and information on the order codes on request.
Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. Your Endress+Hauser service organization can provide detailed information on the order codes in question.
Documentation
Flow Measurement (FA005D/06) Operating Instructions Promag Promag 50 (BA046D/06 and BA049D/06) Operating Instructions Promag Promag 50 PROFIBUS PA (BA055D/06 and BA056D/06) Operating Instructions Promag Promag 53 (BA047D/06 and BA048D/06) Operating Instructions Promag Promag 53 FOUNDATION Fieldbus (BA051D/06 and BA052D/06) Operating Instructions Promag Promag 53 MODBUS RS485 (BA117D/06 and BA118D/06) Operating Instructions Promag Promag 53 PROFIBUS DP/PA (BA053D/06 and BA054D/06) Supplementary documentation on Ex-ratings: ATEX, IECEx, FM, CSA, NEPSI
Registered trademarks
HART Registered trademark of the HART Communication Foundation, Austin, USA PROFIBUS Registered trademark of the PROFIBUS Nutzerorganisation e.V., Karlsruhe, D FOUNDATION Fieldbus Registered trademark of the Fieldbus Foundation, Austin, USA MODBUS Registered trademark of the MODBUS Organisation HistoROM, S-DAT, T-DAT, F-CHIP, FieldCare, Fieldcheck, FieldXpert, Applicator Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
Endress+Hauser
43
Instruments International