Edwards Install
Edwards Install
Edwards Install
Issue L
Instruction Manual
1 INTRODUCTION 1
1.1 Scope and definitions 1
1.2 Description 1
1.2.1 Overview 1
1.2.2 The QDP pump 1
1.2.3 Gas system 2
1.2.4 Temperature control system 3
1.2.5 Electrical system 4
1.2.6 Exhaust system 4
1.3 Accessories 4
2 TECHNICAL DATA 5
2.1 General 5
2.2 Performance data 5
2.3 Services 10
2.4 Full load current ratings 11
2.5 Temperature control system 11
2.6 Electrical connectors 12
2.7 Lubrication system 12
2.7.1 Gearbox 12
2.7.2 High vacuum bearings 12
2.8 Exhaust system 12
2.8.1 Exhaust-silencer 12
2.8.2 Exhaust check-valve 12
3 INSTALLATION 13
3.1 Safety 13
3.2 Unpack and inspect 13
3.3 Height adjustment 14
3.4 Check the coolant-level 14
3.5 Check the gearbox oil-level 14
3.6 Locate the pump 14
3.7 Electrical connections 16
3.7.1 17-way connector 16
3.7.2 High and low voltage operation 19
3.7.3 Connect the electrical supply 19
3.7.4 Connect the thermal snap-switches 20
3.7.5 Connect the motor-protection thermistors 20
3.7.6 Check the pump rotation 23
3.8 Fit a mechanical booster pump 23
3.9 Connect the cooling-water supply 23
DBW 5642-96
4 OPERATION 29
4.1 Start-up procedure 29
4.2 Gas flow rates and pressures 29
4.3 Pump shutdown 29
5 MAINTENANCE 30
5.1 Safety 30
5.2 Maintenance plan 31
5.3 Check the gearbox oil-level 31
5.4 Check the coolant-level 32
5.5 Inspect and clean the exhaust-silencer 33
5.6 Inspect the pipelines and connections 35
5.7 Inspect the exhaust check-valve 35
5.8 Change the gearbox oil 37
5.9 Relubricate the rotor bearings 37
Tables
Read this manual before you install and operate the pump. Important safety information is
highlighted as WARNING and CAUTION instructions; you must obey these instructions. The
use of WARNINGS and CAUTIONS is defined below.
WARNING
Warnings are given where failure to observe the instruction could result in injury or death
to people.
CAUTION
Cautions are given where failure to observe the instruction could result in damage to the
equipment, associated equipment or process.
1.2 Description
1.2.1 Overview
The QDP pumps operate at pressures between atmospheric and ultimate vacuum with no
lubricating or sealing fluid in the pumping chamber. This ensures a clean pumping system
without back-migration of oil into the system being evacuated.
QDP pumps have enclosed, water-cooled motors and are therefore suitable for applications in
clean environments where fan cooling is unacceptable.
The QDP pumps are each fitted with a gas system, exhaust-silencer and check-valve. The pump
is fixed to the framework by vibration isolators. The framework has castors and levelling feet.
The pump shafts and rotors are made from cast-iron. The internal and external shaft-seals on
the motor drive-shaft are made of polytetrafluoroethylene (PTFE). Bearings are located on the
high vacuum end of the shaft, near to the pump-inlet. These bearings are packed with
perfluoropolyether (PFPE) grease.
• Inlet-purge
• Shaft-seal purge
• 2/3-interstage purge
• Exhaust-purge
• 3/4-interstage purge.
You will connect your nitrogen supplies to this gas system through connectors on the gas services
panel (see Figure 2).
The cooling-water manifold on the pump distributes the cooling-water to the pump cooling
circuit and to the pump-motor cooling circuit (and to the QMB pump-motor cooling circuit, if a
QMB pump is fitted). When a QMB pump is not fitted, the flow of cooling-water to the QDP
pump-motor is greater than the minimum required flow. When a QMB pump is fitted, the
cooling-water flow is distributed equally between the two pump-motors and the overall flow
requirement for the pumping combination increases (see Section 2.3).
Two thermal snap-switches are fitted to the pump-body. One of these snap-switches (the
warning switch) opens at 88 oC and the other snap-switch (the shut-down switch) opens at 95 oC.
Use the warning switch to provide a warning that the pump is too hot. Use the shut-down switch
to shut down the pump.
Three motor-protection thermistors are fitted to the pump-motor (one on each winding). These
thermistors are solid-state devices which have an electrical resistance of 100 to 500 Ω at normal
pump-motor operational temperature. When the pump-motor is too hot, the electrical resistance
rises quickly to 3000 Ω. The thermistors are connected in series and you can use the output of
the thermistors to shut down the pump because the motor is too hot.
You will connect your electrical supply cable to the pump through a cable-gland on the
terminal-box on the end of the pump-motor (see Figure 10). You must use a suitably rated
contactor (see Section 2.4). The electrical services panel has a connector to connect the outputs
of the thermal snap-switches and the motor-protection thermistors to your control equipment.
1.3 Accessories
A number of accessories are available for the QDP pump; use these to configure the pumps for
specific applications. These accessories are listed in Section 7.
2.1 General
QDP40 QDP80 (4 kW and 6 kW)
Overall dimensions See Figure 3 See Figure 4
Mass 172 kg 202 kg
Motor rating 2.2 kW 4 kW/6 kW
Warm-up time to nominal performance 15 min 15 min
Inlet connections ISO40 ISO63
Outlet connections NW40 NW40
-5 -1
Vacuum system maximum leak-rate 1 x 10 mbar.ls 1 x 10-5 mbar.ls-1
(1 x 10-3 Pa.ls-1) (1 x 10-3 Pa.ls-1)
-5 -1
Exhaust system maximum leak-rate 1 x 10 mbar.ls 1 x 10-5 mbar.ls-1
(1 x 10-3 Pa.ls-1) (1 x 10-3 Pa.ls-1)
Ambient operating temperature range 5 to 40 oC 5 to 40 oC
Maximum ambient operating humidity 90% RH 90% RH
Protection degree (as defined by IEC 529) IP44 IP44
Continuous A-weighted sound
pressure level (at 1 meter) < 70 dB(A) < 70 dB(A)
1. 60 Hz 2. 50 Hz
Figure 6 - Typical pumping speeds for QDP80: pumping speed against pressure
Electrical supply
Supply voltage 200-208/380-415 V at 50 Hz, 3-phase
200-230/460 V at 60 Hz, 3-phase
Voltage tolerance ±10% (except for 208 V and 415 V at 50 Hz
which are +6% and -10%)
Cooling-water
Maximum supply pressure 100 psi (6.9 bar absolute, 6.9 x 105 Pa)
Minimum required pressure differential
across supply and return 30 psi (2.1 x 105 Pa)
Typical heat removed from pump 1.75 kW (QDP40), 2.75 kW (QDP80)
Maximum water consumption See Table 1
Maximum particle size in supply 0.03 mm2
Nitrogen supply
Supply pressures and flow rates For recommendations, see Table 2
1
Fittings type /4 inch compression
Water-cooling system
Type Indirect water-to-coolant heat exchanger
Coolant capacity 1.7 litres
Thermostatic control-valve
Manufacturer Danfoss
Model AVTA DN15
Part number 003N2110
Working temperature range 50 to 90 oC
Maximum sensor temperature 130 oC
Thermal snap-switches
Manufacturer Fenwal Inc
Model 08-02
Opening temperatures 88 oC (warning switch)
95 oC (shut-down switch)
Closing temperatures 78 oC (warning switch)
85 oC (shut-down switch)
Contact rating
Maximum voltage 240 V
Maximum current (inductive load) 6.3 A
Maximum current (resistive load) 12 A
Motor-protection thermistors
Type Positive temperature coefficient
Reference temperature 160 oC
Compliant with IEC 34-11 (BS4999 part 111)
Recommended control-unit To comply with IEC 34-11
(BS4999 part 111)
Relay contact rating Suitable for use with your contactor
2.7.1 Gearbox
Oil capacity 0.4 litres
Grade of oil SAE 40
ISO viscosity grade 150
Recommended perfluoropolyether oils Fomblin Y25, Krytox 1525
2.8.1 Exhaust-silencer
Gas temperature 5 to 150 oC
Exhaust pulsation attenuation 30 dB(A)
Mass 5.5 kg
3.1 Safety
WARNING
Obey the safety instructions given below and take note of appropriate precautions. If you
do not, you can cause injury to people and damage to equipment
• A suitably trained and supervised technician must install the QDP pump.
• Ensure that the installation technician is familiar with the safety procedures which relate to
the products pumped. Wear the appropriate safety-clothing when you come into contact
with contaminated components. Dismantle and clean contaminated components inside a
fume-cupboard.
• Vent and purge the process system (if the QDP Pump is replace an existing pump) with
nitrogen for 15 minutes before you start installation work.
• Disconnect the other components in the pumping system from the electrical supply so that
they cannot be operated accidentally.
• Do not reuse ’O’ rings and do not allow debris to get into the QDP pump during installation.
WARNING
Ensure that the maximum angle between paired slings used to lift the pump is 60o.
1. Place the pallet in a convenient position with a fork-lift truck or a pallet truck.
2. Remove the staples which secure the cardboard box to the pallet then remove the cardboard
box; alternatively, open the top of the cardboard box. Tear open the foil bag around the
pump.
3. Refer to Figure 9. Remove the two nuts and washers (2) which secure the front of the pump
to the pallet. Dispose of the nuts and washers. Remove the two nuts and washers (2) which
secure the rear of the pump to the pallet.
4. Use suitable lifting-equipment to remove the pump from its pallet. Do not try to lift the pump
by hand (see Section 2 for the mass of the pump).
5. Inspect the pump. If the pump or any other item is damaged, notify your supplier and the
carrier in writing within three days; state the Item Number of the pump together with your
order number and your supplier’s invoice number. Retain all packing materials for
inspection. Do not use the pump if it is damaged.
7. If the pump is not to be used immediately, replace the packing materials. Store the pump in
suitable conditions as described in Section 6.
1. Unscrew and remove the combined filler-plug/level indicator (5). Use a clean lint-free cloth
to wipe the shaft of the indicator, then replace the combined filler-plug/level indicator in
the coolant header-tank.
2. Remove the combined filler-plug/level indicator again and check the coolant-level: the
coolant-level must be visible on the shaft of the indicator, but must not be above the notch
mark on the indicator shaft.
4. Check that the bonded seal on the combined filler-plug/level indicator (5) is in place. Refit
and tighten the combined filler-plug/level indicator.
2. Wheel the pump on its castors to move the pump into its operating position. The QDP pump
must be located on a firm, level surface.
3. Once located in its final operating position, adjust the levelling feet to make sure that the
QDP pump is level and is not supported by the castors.
WARNING
If you use gas dilution as a safety feature of your system, you must fit a suitable alarm and
interlock system to prevent operation of the QDP pump when the gas dilution system does
not work. If you do not, the concentration of dangerous process gases in the exhaust of the
pump may (without warning) exceed safe limits and may cause an explosion or injury to
people.
WARNING
Use a suitable cable-gland so that the seal of the electrical cable entry into the motor
terminal-box meets the requirements of IP44 in IEC 529. If you do not, condensation may
form inside the terminal-box and there may be a risk of electric shock.
WARNING
Do not turn on the cooling-water supply until after you complete the electrical installation
of the pump. If you do, condensation may form inside the motor terminal-box and there
may be a risk of electric shock.
• A mating-half for the 17-way connector is not supplied with the pump: refer to Section 7.3
for the Item Number of the connector mating-half.
• A 3-way mating-half for the flow-switch link (3) is supplied fitted to the connector on the
flying leads in the pump. You must remove this link if you fit a flow-switch.
• A 2-way mating-half for the QMB thermistors electrical connector (4) is supplied fitted to
the connector on the flying leads in the pump. If you fit a QMB mechanical booster pump,
you must remove the link from the mating-half and connect the QMB thermistors through
the mating-half of this 2-way connector.
We recommend that you use the pins of the 17-way connector as shown in Table 5.
To change the QDP80 Pump-motor to ’high voltage’ operation, remove the pump-motor
terminal-box cover, then remove the wires from the U1, V1 and W1 terminals. Reconnect the
wires to the W2, U2 and V2 terminals as shown in Figure 15.
CAUTION
The motor must be correctly configured and you must make the correct electrical
connections for your electrical supply. If you do not, you can damage the motor.
Connect the motor to the electrical supply as described below. Connect the supply through a
contactor which has overload-protection, or use a controller which incorporates a contactor. You
must use a contactor which has a manual reset control. If you do not, the pump could
automatically restart after an electrical overload or an electrical supply failure.
2. Check your electrical supply voltage and frequency. If necessary, configure the motor to
operate with your supply voltage (see Section 3.7.2).
5. Pass the supply cable through the cable-gland and connect the wires of the electrical supply
cable to the appropriate terminals (see Figures 12 to 14).
WARNING
Incorporate a manual reset device in your control equipment. If you do not (and a fault
which causes the shut-down thermal snap-switch to open is not corrected), the pump will
switch on again when it cools down.
You can connect the warning thermal snap-switch to your control equipment to provide an
indication that the pump is too hot. Connect the shut-down thermal snap-switch to your control
equipment to shut down the pump. Alternatively, you can connect the shut-down thermal
snap-switch to the electrical-overload control-loop of your contactor. If you do this, the contactor
will automatically switch off if the pump is too hot.
The thermal snap-switches will reset (that is, close again) when the pump cools down to a preset
temperature (see Section 2). We therefore recommend that your control equipment incorporates
a manual reset device to prevent the pump switching on again automatically when it cools down.
You can use a 17-way connector mating-half (not supplied: refer to Section 7.3) to connect the
thermal snap-switches to your control equipment; Table 5 defines the functions of the pins.
If you have a QMB mechanical booster pump in your pumping system, then :
• If you connect the QDP and QMB thermistors to a single control-unit (for example, an
Edwards Q Controller), you must connect the outputs in series not in parallel. The outputs
must not be short-circuited by any links or jumpers.
• If you connect the QMB thermistor outputs directly to an Edwards Q Controller (that is, you
do not use the 17-way connector on the QDP), either make sure that pins P and R on the
electrical connector on the QDP are not connected to the auxiliary socket of the Q Controller,
or make sure that the mating-half of the 2-way QMB thermistors electrical connector is
removed (refer to Section 3.7.1).
1. To electrical supply
2. To 17-way connector on electrical services panel
3. Links
Figure 13 - QDP40 high voltage configuration
1. To electrical supply
2. To 17-way connector on electrical services panel
2. Watch the pump-inlet blanking-plate and switch on the pump for one or two seconds, then
switch the pump off. If the blanking-plate lifts from the inlet, the direction of rotation is
incorrect. If the direction of rotation is incorrect, isolate the electrical supply and reverse any
two of the electrical supply phase-wires in the pump-motor terminal-box.
WARNING
Do not turn on the cooling-water supply until after you complete the electrical installation
of the pump. If you do, condensation may form inside the motor terminal-box and there
may be a risk of electric shock.
CAUTION
Drain the cooling-water from the pumping system, if you will transport or store it in
conditions where the cooling-water could freeze. If you do not, cooling-water may freeze
in the QDP pump and damage the pump.
Note: If you will transport or store the pumping system in conditions where the cooling-water could
freeze, you must ensure that all cooling-water is drained from the pumping system : refer to
Section 6.1
Connect the cooling-water supply as described below. If a QMB mechanical booster pump is
fitted, you must connect the QMB cooling-water supply and return to the cooling-water manifold
on the QDP as described in the instruction manual supplied with the QMB Connection Kit. When
you connect the hoses between the QDP cooling-water manifold and the QMB pump, remove
only the 3/8 BSP caps on the manifold (Figure 10, items 11 and 12). Do not remove the 3/8 to
1
/4 inch reducer fittings on the manifold.
If you need to connect more than one QDP pump to the water supply, you must connect them
in parallel and not in series.
2. Fit these connectors to your cooling-water supply and return hoses with 3/8 inch BSP male
pipe fittings (which you must supply). Fit the female quick-release connector to the water
supply hose and fit the male quick-release connector to the water return hose.
3. Remove the dust-caps from the cooling-water connectors on the water services panel
(Figure 2, items 4 and 6).
4. Connect your water return pipe to the water return connector on the water services panel,
then connect your water supply pipe to the water supply connector on the water services
panel.
6. To bleed air out of the water cooling system, use a screwdriver to lift up the spindle on the
top of the TCV (Figure 10, item 8) and hold it up for 15 to 30 seconds to allow a steady flow
of water to establish. Do not turn the spindle against the locking-wire.
7. Check the water hoses, pipelines and connections to ensure that there are no leaks.
8. Turn off the water supply while you complete the remainder of the installation procedures.
WARNING
If your vacuum system is not suitable for pressures above atmospheric, you must install a
suitable control-valve system. If you do not, your system could be pressurised up to the
nitrogen supply pressure.
Connect nitrogen supplies to the pump through the five connectors on the gas services panel
(see Figure 2). You must connect a nitrogen supply to the shaft-seals purge connector (Figure 2,
item 12) for all QDP pump applications. Use the other gas pipelines according to your
application.
The gas pipeline connections are 1/4 inch compression fittings. Use rigid metal supply pipelines
(such as stainless steel) with an outside diameter of 1/4 inch. If you have an acoustic enclosure
to fit, ensure that the pipelines will not obstruct the enclosure. Use the connectors in the general
fitting-kit to connect your pipelines to the pump. If you have a gas module accessory, the
necessary pipelines and connectors are supplied with the accessory.
Use a suitable regulator in the nitrogen supply pipeline to the shaft-seals purge to maintain a
constant supply pressure of 8 psig (0.55 bar gauge, 3.8 x 103 Pa) minimum and 10 psig (0.69 bar
gauge, 6.9 x 104 Pa) maximum.
If your vacuum system is not suitable for positive pressures, install an inlet-valve or nitrogen
supply solenoid-valve, interlocked to the pump-motor electrical supply, to prevent
over-pressurisation. To prevent over-pressurisation of the exhaust-line, install a facility to
monitor the exhaust pressure and to cut off the nitrogen supply automatically if this pressure
reaches 6 psi (4.1 x 104 Pa).
• To get the best pumping speed, ensure that the pipeline which connects the vacuum system
to the pump is the minimum length possible and has an internal diameter not less than the
pump-inlet port. Use a flexible connection in the pipeline to reduce vibration and stress in
the system pipelines.
• On very dusty applications, use an inlet-filter to minimise damage to the pump.
• You must be able to isolate the pump-inlet from the atmosphere and from your vacuum
system if you have pumped or produced corrosive chemicals.
• Vacuum pipelines must be adequately supported to stop the transmission of stress to
pipeline joints.
The QDP40 inlet-flange is ISO40 and the QDP80 inlet-flange is ISO63. Use the following
procedure to connect the QDP pump to your vacuum system. This procedure assumes that a
mechanical booster pump has not been fitted. If a mechanical booster pump has been fitted, use
the instructions given in the appropriate instruction manual supplied with the mechanical
booster pump.
1. Remove the four M8 x 45 mm cap-head bolts, nuts and washers. Remove the inlet
blanking-plate.
3. Use the trapped ’O’ ring supplied to connect the pump inlet-flange to your vacuum system.
Secure with the bolts provided in the general fitting-kit or the bolts removed in Step 1.
1. Remove the two screws (Figure 2, item 7) which secure the exhaust-silencer support-plate
to the pump and remove the support-plate.
2. Undo and remove the NW40 clamp which secures the inlet of the exhaust-silencer to the
outlet of the pump.
3. Remove the exhaust-silencer and turn it through 180o, so that the outlet is at the other end
of the pump (as in Figures 3 and 4).
• Remove the two NW40 clamps which secure the adaptor to the outlet of the
exhaust-silencer and the elbow and remove the adaptor.
• Use one of the clamps to secure the elbow to the outlet of the exhaust-silencer.
5. Use the clamp removed in Step 2 to secure the inlet of the exhaust-silencer to the outlet of
the pump.
6. Refit the exhaust-silencer support-plate and secure with the two screws removed in Step 1.
WARNING
Pipe the exhaust to a suitable treatment plant to prevent the discharge of dangerous gases
or vapours to the surrounding atmosphere.
WARNING
Do not operate the QDP pump with the exhaust pipeline blocked. If the exhaust pipeline is
blocked, the QDP pumps can generate exhaust pipeline pressures up to 7 bar (7 x 105 Pa).
CAUTION
Use a catchpot to prevent condensate draining back into the pump. Condensate which
drains back into the pump could damage the pump.
When you connect the pump to the exhaust system, take note of the following:
• Ensure that all components in the exhaust pipeline have a pressure rating which is greater
than the highest pressure that can be generated in your system.
• Incorporate flexible pipelines in the exhaust pipeline to reduce the transmission of vibration
and to prevent loading of coupling-joints. We recommend that you use Edwards flexible
pipelines.
• You must be able to isolate the exhaust-silencer outlet from the atmosphere if you have
pumped or produced corrosive chemicals.
• Exhaust pipelines must be adequately supported to stop the transmission of stress to pipeline
joints.
Connect the exhaust-silencer outlet to your exhaust system. The outlet has an NW40 flange.
WARNING
Leak-test the system after installation and maintenance and seal any leaks found to prevent
leakage of dangerous substances out of the system and leakage of air into the system.
Leak-test the system after installation and seal any leaks found. Dangerous substances which
leak from the system will be dangerous to people and there will be a danger of explosion if air
leaks into the system. We recommend that the leak rate is 1 x 10-5 mbar.ls-1 (1 x 10-3 Pa.ls-1)
helium or less.
WARNING
Do not adjust the TCV to a lower setting (that is, turn the adjuster spindle anticlockwise)
when the pump is hot. This will increase the flow of cooling-water which may damage the
pump because of the differential contraction of the pump rotor and case.
Note: The QDP pump can only be operated at pump temperatures above 88 oC if you configure the pump
so that the 88 oC thermal snap-switch gives a warning only, (that is, does not automatically shut
down the QDP pump), or if you fit the high temperature thermal snap-switch kit, which contains
a warning thermal snap-switch which opens at 95 oC and a shut-down thermal snap-switch which
opens at 115 oC.
The TCV regulates the flow of water through the water cooling system to maintain the pump at
the required operating temperature.
A pump operating temperature of 70 oC is suitable for most processes and, as supplied, the TCV
is factory set to maintain this temperature (measured at the thermal snap-switch position). The
adjuster spindle on the TCV is held at this setting by a locking-wire.
You can adjust the TCV to vary the operating temperature of the pump (measured at the
temperature measurement point - Figure 10, item 16) between approximately 55 oC (minimum)
and approximately 90 oC (maximum). If you need to adjust the TCV to suit your operating
conditions, refer to Figure 10 and use the following procedure. Note that it takes approximately
30 minutes for the pump to stabilise at its final operating temperature.
1. Cut and remove the locking-wire on the spindle on the top of the TCV (8).
2. Turn on the cooling-water supply, the nitrogen supply and your exhaust-extraction system
(if fitted).
3. Check all of the water, nitrogen system, exhaust-extraction system and vacuum system
connections.
Note: The following procedures assume that you have an inlet-isolation valve fitted to your pump.
3. Turn on the cooling-water supply, the nitrogen supply and the exhaust-extraction system (if
fitted).
4. Check all of the water, nitrogen system, exhaust-extraction system (if any) and vacuum
system connections.
6. Refer to Section 2.3 and Section 4.2 for operation of the gas system to suit your process
conditions.
During operation, you must set the flow rates of the 3/4-interstage purge and the 2/3-interstage
purge pipelines to the required values. These values are dependent on the process in which the
pump is used and you should adjust the flow rates according to your experience. If you exceed
the flow rates specified in Table 2, the performance of the pump may be reduced.
You must set the pressure of the shaft-seals purge as specified in Table 2 and Section 3.10. You
must not attempt to adjust the flow rate of the shaft-seals purge (which is determined by the
pump itself). The nominal flow rate of the shaft-seals purge is 12 l.min-1 . If the flow rate is
higher than the nominal value, you may reduce the flow rate of the 3/4-interstage purge by
[F-12] l.min-1 (where F is the actual shaft-seals flow rate). This will reduce the amount of nitrogen
exhausted from the pump.
1. Isolate the pump-inlet from your vacuum system and operate it for 15 minutes with the
nitrogen supply switched on.
3. Switch off the QDP pump (and the mechanical booster pump if fitted).
5.1 Safety
WARNING
Obey the safety instructions given below and take note of appropriate precautions. If you
do not, you can cause injury to people and damage to equipment.
• A suitably trained and supervised technician must maintain the QDP pump.
• Ensure that the maintenance technician is familiar with the safety procedures which relate
to the products handled by the pumping-system. Wear the appropriate safety-clothing when
you come into contact with contaminated components. Dismantle and clean contaminated
components inside a fume-cupboard.
• Allow the pump to cool to a safe temperature before you start maintenance work.
• Vent and purge the pumping system with nitrogen before you start any maintenance work.
• Isolate the pump and other components in the pumping system from the electrical supply
so that they can not be operated accidentally.
• Recheck the pump rotation direction if the electrical supply has been disconnected.
• Do not reuse ’O’ rings.
• Dispose of components, grease and oil safely (see Section 6.2).
• Take care to protect sealing-faces from damage.
• Do not touch or inhale the thermal breakdown products of fluorinated materials which may
be present if the pump has been overheated to 260 oC and above. These breakdown products
are very dangerous. Fluorinated materials in the pump may include oils, greases and seals.
The pump may have overheated if it was misused, if it malfunctioned or if it was in a fire.
Edwards Health and Safety Data sheets for fluorinated materials used in the pump are
available on request: contact your supplier or Edwards.
• Leak-test the system after maintenance work is complete if you have connected or
disconnected any vacuum or exhaust joints. Seal any leaks found to prevent leakage of
dangerous substances out of the system and leakage of air into the system.
When you maintain the pump, use Edwards maintenance and service kits. These contain all of
the necessary seals, lubricating grease and other components necessary to complete maintenance
operations successfully. The Item Numbers of the service kits are given in Section 7.2.
WARNING
Do not remove the oil filler-plug when the pump is operating. If you do, hot oil may be
ejected from the pump gearbox
Refer to Figure 10 and check that the pump gearbox oil-level is between the MIN and MAX marks
on the bezel of the oil-level sight-glass. If the oil-level is above the MAX mark, drain excess oil
from the pump as described in Section 5.7 until the oil-level is correct. If the oil-level is below
the MAX mark:
2. Pour oil into the gearbox until the oil-level is at the MAX mark on the bezel of the oil-level
sight-glass.
3. Make sure that the bonded seal is in place on the oil filler-plug. Screw the filler-plug back
in and tighten to finger tight. Use a spanner to tighten a further 1/16th of a turn.
The gearbox is vented and the loss of a small amount of oil during operation is normal. If you
need to pour oil into the gearbox frequently, or if there is a sudden loss of a large amount of oil,
this may indicate that the pump has a fault. In these circumstances, we recommend that you
shut down the pump as soon as possible and contact your supplier or Edwards for advice.
WARNING
Do not remove the combined filler-plug/level indicator when the QDP pump is hot. If you
do, hot coolant may be ejected from the header-tank and could cause injury.
CAUTION
Fill the QDP pump with the correct type and amount of coolant. If you do not, the pump
may overheat and it may not work correctly.
In addition to cooling the pump, the coolant acts as a corrosion inhibitor and anti-scaling agent.
Check the coolant-level and fill the pump with coolant as described below; new coolant is
available as a spare: refer to Section 7. The locations of the components of the cooling-water
system are shown in Figure 10.
1. Isolate the pump from the electrical supply and ensure that the cooling-water supply is off.
2. Unscrew and remove the combined filler-plug/level indicator (5). Use a clean lint-free cloth
to wipe the shaft of the indicator, then replace the combined filler-plug/level indicator in
the coolant header-tank.
3. Remove the combined filler-plug/level indicator again and check the coolant-level: the
coolant-level must be visible on the shaft of the indicator, but must not be above the notch
mark on the indicator shaft. If the coolant-level is acceptable, continue at Step 12, otherwise
continue at Step 4.
4. Remove the cap from a container of pump coolant and pour in de-ionised water until the 2.1
litre fill line on the container is reached.
5. Refit the cap firmly on the container. Shake the container gently to fully mix the fluids.
6. Check that the coolant drain-plug on the underside of the pump is securely fitted.
7. Fit a length of transparent flexible hose to the air bleed-valve, then unscrew the air
bleed-valve (7).
8. Use a clean funnel to slowly fill the pump with the coolant mixture until the coolant fluid
starts to flow through the hose fitted to the air bleed-valve.
9. Tighten the air bleed-valve (7), then remove the flexible hose.
10. Continue to fill the system slowly until you see the fluid in the bottom of the coolant
header-tank (4).
11. Refit the combined filler-plug/level indicator (5) and then remove it to check the fluid-level
on the shaft of the indicator: refer to Step 3.
12. Check that the bonded seal on the combined filler-plug/level indicator (5) is in place. Refit
and tighten the combined filler-plug/level indicator.
WARNING
Refer to Figure 16 and dismantle, inspect and clean the silencer as described below.
1. Release the NW40 clamps at the silencer inlet and outlet flanges to disconnect the silencer
from the check-valve and the pump.
2. Slide the silencer out towards the high-vacuum end of the pump to remove the silencer from
the pump. Alternatively, undo the two support-plate retaining screws (see Figure 2) and
slide the silencer complete with the support-plate towards the motor end of the pump.
3. Weigh the silencer. If the mass of the silencer is greater than 7.5 kg, dismantle, clean and
reassemble the silencer as in Steps 4 to 9 below. If you do not need to clean the silencer, refit
the silencer as in Step 12.
4. Remove and retain the six bolts and washers which secure each end-cover plate to the silencer
body. Pull the end-cover plates squarely from the outlet pipe to remove them.
5. Remove the three ’O’ rings from the silencer and discard.
6. Empty all loose deposits from the silencer body; take care not to damage the end-cover plate
sealing surfaces.
7. Use a suitable tool to dislodge remaining deposits, then wash the silencer body with steam
or water. Finally, glass-bead blast the silencer body. If required, use a cleaning solution
suitable for the nature of the deposits.
8. Inspect the silencer for internal corrosion and check that the wall of the silencer body is not
excessively eroded. Inspect the end-cover plate and inlet and outlet flange sealing-faces for
damage and refinish if necessary. If silencer damage is excessive, it should be replaced.
9. Check that the ’O’ ring grooves are clean. Apply a light wipe of vacuum grease and place
the new ’O’ rings in position.
10. Refit the end-cover plates and secure with the bolts and washers removed in Step 3. Tighten
the bolts progressively; alternate between bolts on opposite sides of the end-cover plate.
Tighten to a torque of 10 Nm.
12. Slide the silencer in from the high-vacuum end of the pump. Alternatively, slide the silencer
complete with the support-plate in from the motor end of the pump and tighten the
support-plate retaining screws (see Figure 2).
13. Reconnect the silencer to the pump and the check-valve with the new NW40 clamps and
trapped ’O’ rings supplied in the servicing kit.
2. Inspect all nitrogen supply connections and check that they are secure; tighten any loose
connection. Inspect all nitrogen supply pipelines and connections for leaks and damage.
Repair or replace any corroded or damaged components and seal any leaks found.
3. Inspect all electrical connections and check that they are secure; tighten any loose connection.
Inspect all electrical cables and check thay they are not damaged and have not overheated.
Repair or replace any cable that is damaged or has overheated.
4. Inspect all vacuum connections and check that they are secure; tighten any loose connection.
Inspect all vacuum pipelines for corrosion and damage and check that they do not leak.
Repair or replace any corroded or damaged components and seal any leaks found.
WARNING
Substances which accumulate in the check-valve may be dangerous. Do not allow these
substances to come into contact with your skin or eyes. Do not inhale vapours from these
substances. Fit blanking caps to the inlet and outlet flanges when you move the
check-valve around your workplace.
You must remove the exhaust check-valve from the silencer and your exhaust-extraction system
before you can inspect it. It is convenient, therefore, to inspect the exhaust check-valve at the
same time as you inspect the exhaust-silencer (see Section 5.5).
Use the procedure below to remove and inspect the valve. This procedure assumes that the
exhaust-silencer has already been disconnected from the pump and the exhaust check-valve has
been removed. Figure 17 shows the component parts of the exhaust check-valve.
1. Release the NW40 clamp at the exhaust check-valve outlet flange and remove the check-valve
from the system pipeline.
2. Unscrew the two halves of the check-valve body; use a strap wrench if necessary.
4. Use a cleaning solution suitable for the process products pumped to clean the valve body
and the fluoroelastomer ball. If necessary, replace the fluoroelastomer ball with a new one.
5. Inspect the ’O’ ring groove and the KF40 flange sealing-faces for damage and refinish if
necessary.
6. Apply a light wipe of vacuum grease and position the ’O’ ring in its groove in the valve body.
8. Refit the valve to the system pipeline with the NW40 clamp and trapped ’O’ ring. Ensure
that the flow direction arrow points away from the silencer (towards your exhaust-extraction
system).
2. Use a suitable pump or syringe to suck the oil out of the gearbox.
3. Discard the old bonded seal on the oil filler-plug and replace with a new one from the pump
maintenance kit.
4. Fill the gearbox through the filler hole, with the correct grade and quantity of oil. Allow the
oil to drain into the gearbox and then check the level on the oil sight-glass (refer to
Section 3.5).
5. Ensure that the new bonded seal is positioned correctly and refit the oil filler-plug.
1. Remove the six screws (2) which secure the bearing end-cover (1) to the high vacuum
head-plate (4).
2. Lift away the end-cover and remove the sealing ’O’ ring (3). Dispose of the ’O’ ring (see
Section 6.2).
3. Use a clean lint-free cloth or a plastic or wooden spatula to remove as much old grease as
possible from the end-cover and bearings. Do not use your fingers for this operation.
4. Inspect the bearings for obvious signs of wear or the presence of debris. If the bearings are
worn, return the pump to an Edwards Service Centre for repair.
5. If the bearings are in a satisfactory condition, force new PFPE grease (supplied in the
maintenance kit) into the bearings so that a smooth layer of grease covers the case and
bearings. Do not over-pack the bearings or the pump will run hot.
6. Apply a light wipe of PFPE grease to the new ’O’ ring seal and position it in its groove in the
head-plate. Refit the end-cover to the high vacuum head-plate.
6.1 Storage
CAUTION
Drain the cooling-water from the pumping system, if you will transport or store it in
conditions where the cooling-water could freeze. If you do not, cooling-water may freeze
in the QDP pump and damage the pump.
If you will transport or store the pumping system in conditions where the cooling-water could
freeze (for example, if you transport the pump as air freight), you must ensure that all
cooling-water is drained from the pumping system.
1. Remove the cooling-water connectors from the pump, or attach an open pair of
quick-connector halves to the connectors on the pump.
2. Blow compressed air through the cooling-water inlet, to force any water out of the cooling
system.
1. If applicable, ensure that the pump has been shut down as described in Section 4.3 and
disconnect all services, process and exhaust connections.
2. Fit blanking-plates to all vacuum inlets and outlets. Place protective covers over the pump
services connection points.
4. When required for use, prepare and install the pump as described in Section 3 of this manual.
6.2 Disposal
Dispose of the QDP pump and any components safely in accordance with all local and national
safety and environmental requirements.
• Fluoroelastomers which may have decomposed as the result of being subjected to high
temperatures
• Components which have been contaminated with dangerous process substances.
7.1 Introduction
Edwards products, spares and accessories are available from Edwards companies in Belgium,
Brazil, Canada, France, Germany, Hong Kong, Italy, Japan, Korea, Switzerland, United
Kingdom, U.S.A and a worldwide network of distributors. The majority of these centres employ
Service Engineers who have undergone comprehensive Edwards training courses.
Order spare parts and accessories from your nearest Edwards company or distributor. When
you order, please state for each part required:
7.2 Spares
The spare parts listed below are available for the QDP pumps :
Introduction
Before you return your equipment you must warn your supplier if the substances you used (and produced) in
the equipment can be dangerous. You must do this to comply with health and safety at work laws.
You must complete the Declaration (HS2) on the next page and send it to your supplier before you
dispatch the equipment. If you do not, your supplier will assume that the equipment is dangerous and he will
refuse to accept it. If the Declaration is not completed correctly, there may be a delay in processing your
equipment.
Guidelines
Take note of the following guidelines:
• Your equipment is ’uncontaminated ’ if it has not been used or if it has only been used with substances
that are not dangerous. Your equipment is ’contaminated ’ if it has been used with any dangerous
substances.
• If your equipment has been used with radioactive substances, you must decontaminate it before you
return it to your supplier. You must send independent proof of decontamination (for example a certificate
of analysis) to your supplier with the Declaration (HS2). Phone your supplier for advice.
• We recommend that contaminated equipment is transported in vehicles where the driver does not share
the same air space as the equipment.
PROCEDURE
Use the following procedure:
1. Contact your supplier and obtain a Return Authorisation Number for your equipment.
2. Turn to the next page(s), photocopy and then complete the Declaration (HS2).
3. Remove all traces of dangerous gases: pass an inert gas through the equipment and any accessories which
will be returned to your supplier. Drain all fluids and lubricants from the equipment and its accessories.
4. Disconnect all accessories from the equipment. Safely dispose of the filter elements from any oil mist
filters.
5. Seal up all of the equipment’s inlets and outlets (including those where accessories were attached). You
may seal the inlets and outlets with blanking flanges or heavy gauge PVC tape.
6. Seal contaminated equipment in a thick polythene bag. If you do not have a polythene bag large enough
to contain the equipment, you can use a thick polythene sheet.
7. If your equipment is a large pump (or any other large piece of equipment), strap the equipment and its
accessories to a wooden pallet. Preferably, the pallet should be no larger than 510mm x 915mm (20" x 35");
contact your supplier if you cannot meet this requirement.
8. If your equipment is too small to be strapped to a pallet, pack it in a suitable strong box.
9. If the equipment is contaminated, label the pallet (or box) in accordance with laws covering the transport
of dangerous substances.
10. Fax or post a copy of the Declaration (HS2) to your supplier. The Declaration must arrive before the
3A05010
equipment.
11. Give a copy of the Declaration to the carrier. You must tell the carrier if the equipment is contaminated.
P900-70-000 Issue E
12. Seal the original Declaration in a suitable envelope; attach the envelope securely to the outside of the
equipment package. WRITE YOUR RETURN AUTHORISATION NUMBER CLEARLY ON THE
OUTSIDE OF THE ENVELOPE OR ON THE OUTSIDE OF THE EQUIPMENT PACKAGE.
Return of Edwards Equipment - Declaration (Form HS2)
SECTION 1 : EQUIPMENT
FOR SEMICONDUCTOR APPLICATIONS ONLY :
Equipment model _______________________________________
Tool Reference Number ____________________________
Serial Number ___________________________________________
Process _________________________________________
Has the equipment been used, tested or operated?
Failure Date _____________________________________
yes ❏ Go to Section 2 no ❏ Go to Section 4
Serial Number of
Replacement Pump _______________________________
SECTION 5 : DECLARATION
P900-71-000 Issue E
_______________________________________________________________________________________
I have made reasonable enquiry and I have supplied accurate information in this Declaration. I have not withheld any
information. I have followed the Return of Edwards Equipment Procedure (HS1) on the previous page.
738-41 Panpo-Dong
Sochu-Gu, Seoul
Tel: +82 (0) 2 515 1811
Fax: +82 (0) 2 515 1818