CP1H
CP1H
CP1H
CP1H-X@@D@-@/CP1H-Y@@D@-@
CP1H-XA@@D@-@
4 Axis Position Control and Comprehensive Programmable Controller
• The CP1H-X with pulse outputs for 4 axes.
• The CP1H-Y with 1-MHz pulse I/O.
• The CP1H-XA with pulse outputs for 4 axes and built-in analog I/O.
Features
• Pulse output for 4 axes. Advanced power for high-precision positioning control.
• High-speed counters. Differential phases for 4 axes.
Easily handles multi-axis control with a single unit.
• Eight interrupt inputs are built in. Faster processing of approximately 500 instructions speeds up the entire system.
• Serial communications. Two ports. Select Option Boards for either RS-232C or RS-485 communications.
• Ethernet Communications. Enabled by using an Option Board. Two ports can be used as an Ethernet port to
perform. Ethernet communications between the CP1H and a host computer.
• Built-in Analog I/O. XA CPU Units provide 4 input words and 2 output words.
• USB Peripheral Port. Another standard feature.
• The structured text (ST) language. Makes math operations even easier.
• Can be used for the CP1W series and CJ series Unit. The extendibility of it is preeminently good.
• LCD displays and settings. Enabled using Option Board.
1
CP1H
Model Number Structure
■ Model Number Legend (Not all models that can be represented with the model number legend can necessarily be produced.)
CP1H-@@D@-@
(1) (2) (3) (4)
Ordering Information
Applicable standards
Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most recent applicable standards for each
model.
■ CPU Units
Specifications
CPU Unit Power Model
CPU type Output method Inputs Outputs
supply
RS-422A/485 Option Board Can be mounted in either CPU Unit Option Board slot 1 or 2. CP1W-CIF11
RS-422A/485 (Isolated-type)
CP1W-CIF12-V1
Option Board
Ethernet Option Board Can be mounted in either CPU Unit Option Board slot 1 or 2. * CP1W-CIF41
LCD Option Board Can be mounted only in the CPU Unit Option Board slot 1. CP1W-DAM01
Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
2
CP1H
■ Programming Devices
Specifications
Name Number of Model
Media
licenses
CX-One Lite is a subset of the complete
CX-One package that provides only the Support Software required
for micro PLC applications.
CX-One Lite runs on the following OS.
FA Integrated Tool
OS: Windows XP (Service Pack 3 or higher, 32-bit version) / Win-
Package CX-One Lite 1 license DVD CXONE-LT01C-V4
dows Vista (32-bit/64-bit version) / Windows 7 (32-bit/64-bit ver-
Version 4.@ sion) / Windows 8 (32-bit/64-bit version) / Windows 8.1 (32-
bit/64-bit version) / Windows 10 (32-bit/64-bit version)
CX-One Lite Ver. 4.@ includes Micro PLC Edition CX-Programmer
Ver. 9.@.
CX-One is a package that integrates the Support Software for
OMRON PLCs and components. CX-One runs on the following OS.
FA Integrated Tool OS: Windows XP (Service Pack 3 or higher, 32-bit version) / Win-
1 license
Package CX-One dows Vista (32-bit/64-bit version) / Windows 7 (32-bit/64-bit ver- DVD CXONE-AL01D-V4
sion) / Windows 8 (32-bit/64-bit version) / Windows 8.1 (32- (See note 3.)
Ver. 4.@
bit/64-bit version) / Windows 10 (32-bit/64-bit version)
CX-One Ver. 4.@ includes CX-Programmer Ver. 9.@.
Programming Device Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m) XW2Z-200S-CV
Connecting Cable for For anti-static connectors
Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m) XW2Z-500S-CV
CP1W-CIF01 RS-232C
Option Board Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m) XW2Z-200S-V
(See note 4.) Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m) XW2Z-500S-V
Note: 1. CP1H PLCs are supported by CX-Programmer version 6.1 or higher.
Update The CX-Programmer version automatically from the website using CX-Programmer version 7.0 (included with CX-One version 2.0).
2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer.
3. Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.
4. Cannot be used with a peripheral USB port.
To connect to a Personal Computers via a peripheral USB port, use commercially-available USB cable (A or B type, male).
The following tables lists the Support Software that can be installed from CX-One
CX-One Lite CX-One CX-One Lite CX-One
Support Software in CX-One Support Software in CX-One
Ver.4.@ Ver.4.@ Ver.4.@ Ver.4.@
Micro PLC Edition CX-Programmer Ver.9.@ Yes No CX-Drive Ver.1.@ Yes Yes
CX-Programmer Ver.9.@ No Yes CX-Process Tool Ver.5.@ No Yes
CX-Integrator Ver.2.@ Yes Yes Faceplate Auto-Builder for NS Ver.3.@ No Yes
Switch Box Utility Ver.1.@ Yes Yes CX-Designer Ver.3.@ Yes Yes
CX-Protocol Ver.1.@ No Yes NV-Designer Ver.1.@ Yes Yes
CX-Simulator Ver.1.@ Yes Yes CX-Thermo Ver.4.@ Yes Yes
CX-Position Ver.2.@ No Yes CX-ConfiguratorFDT Ver.1.@ Yes Yes
CX-Motion-NCF Ver.1.@ No Yes CX-FLnet Ver.1.@ No Yes
CX-Motion-MCH Ver.2.@ No Yes Network Configurator Ver.3.@ Yes Yes
CX-Motion Ver.2.@ No Yes CX-Server Ver.4.@ Yes Yes
Note: For details, refer to the CX-One Catalog (Cat. No: R134).
3
CP1H
■ Expansion Units
Product name Inputs Outputs Output type Model
Input Unit 8 -- 24 VDC Input CP1W-8ED
Output Units Relay CP1W-8ER
4
CP1H
5
CP1H
6
CP1H
General Specifications
Type AC power supply models DC power supply models
Item Model CP1H-@@@-A CP1H-@@@-D
Power supply 100 to 240 VAC 50/60 Hz 24 VDC
20.4 to 26.4 VDC
Operating voltage range 85 264 VAC (with 4 or more Expansion Units and Expansion I/O Units: 21.6
to 26.4 VDC)
Power consumption 100 VA max. (CP1H-@@@-A)(page 28) 50 W max. (CP1H-@@@-D)(page 28)
100 to 120 VAC inputs:
20 A max. (for cold start at room temperature)
30 A max. (for cold start at room temperature)
Inrush current (See note.) 8 ms max.
20 ms max.
200 to 240 VAC inputs:
40 A max. (for cold start at room temperature), 8 ms max.
External power supply 300 mA at 24 VDC None
20 MΩ min. (at 500 VDC) between the external AC terminals No insulation between primary and secondary for DC power
Insulation resistance
and GR terminals supply
2,300 VAC at 50/60 Hz for 1 min between the external AC and No insulation between primary and secondary for DC power
Dielectric strength
GR terminals, leakage current: 5 mA max. supply
Noise immunity Conforms to IEC 61000-4-4. 2 kV (power supply line)
Conforms to JIS C60068-2-6. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for
Vibration resistance
80 minutes each. Sweep time: 8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistance Conforms to JIS C60068-2-27. 147 m/s2 three times each in X, Y, and Z directions
Ambient operating tempera-
0 to 55°C
ture
Ambient humidity 10% to 90% (with no condensation)
Ambient operating environ-
No corrosive gas
ment
Ambient storage temperature −20 to 75°C (Excluding battery.)
Power holding time 10 ms min. 2 ms min.
Note: The above values are for a cold start at room temperature for an AC power supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteristics) is used in the inrush current control circuitry for the AC power supply. The thermistor
will not be sufficiently cooled if the ambient temperature is high or if a hot start is performed when the power supply has been OFF for only a short time. In
those cases the inrush current values may be higher (as much as two times higher) than those shown above. Always allow for this when selecting fuses and
breakers for external circuits.
• A capacitor charge-type delay circuit is used in the inrush current control circuitry for the DC power supply. The capacitor will not be charged if a hot start is
performed when the power supply has been OFF for only a short time, so in those cases the inrush current values may be higher (as much as two times
higher) than those shown above.
7
CP1H
Performance Specifications
Type CP1H-XA CPU Units CP1H-X CPU Units CP1H-Y CPU Units
Item Models CP1H-XA@@@-@ CP1H-X@@@-@ CP1H-Y@@@-@
Control method Stored program method
I/O control method Cyclic scan with immediate refreshing
Program language Ladder diagram
Maximum number of function block definitions: 128 Maximum number of instances: 256
Function blocks
Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length 1 to 7 steps per instruction
Instructions Approx. 500 (function codes: 3 digits)
Instruction execution time Basic instructions: 0.10 μs min. Special instructions: 0.15 μs min.
Common processing time 0.7 ms
Program capacity 20K steps
Number of tasks 288 (32 cyclic tasks and 256 interrupt tasks)
Scheduled
1 (interrupt task No. 2, fixed)
interrupt tasks
Input interrupt 8 (interrupt task No. 140 to 147, fixed) 6 (interrupt task No. 140 to 145, fixed)
tasks (Interrupt tasks can also be specified and executed for high-speed counter interrupts.)
Maximum subroutine number 256
Maximum jump number 256
Input bits 272bits (17 words) : CIO 0.00 to 16.15
Output bits 272bits (17 words) : CIO 100.00 to 116.16
Built-in Analog
CIO 200 to CIO 203 ---
I/O areas Inputs
(See note.) Built-in Analog
CIO 210 to CIO 211 ---
Outputs
Serial PLC Link
1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189)
Area
8,192 bits (512 words): W0.00 to W511.15 (W0 to W511)
Work bits
CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143)
TR Area 16 bits: TR0 to TR15
Holding Area 8,192 bits (512 words): H0.00 to H511.15 (H0 to H511)
Read-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447)
AR Area
Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
Timers 4,096 bits: T0 to T4095
Counters 4,096 bits: C0 to C4095
DM Area 32 Kwords: D0 to D32767
Data Register Area 16 registers (16 bits): DR0 to DR15
Index Register Area 16 registers (32 bits): IR0 to IR15
Task Flag Area 32 flags (32 bits): TK0000 to TK0031
Trace Memory 4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
A special Memory Cassette (CP1W-ME05M) can be mounted.
Memory Cassette
Note: Can be used for program backups and auto-booting.
Supported. Accuracy (monthly deviation): −4.5 min to −0.5 min (ambient temperature: 55°C),
Clock function
−2.0 min to +2.0 min (ambient temperature: 25°C), −2.5 min to +1.5 min (ambient temperature: 0°C)
One built-in peripheral port (USB 1.1): For connecting Support Software only.
A maximum of two Serial Communications Option Boards can be mounted.
Communications functions
A maximum of two Ethernet Option Boards can be mounted. When using CP1W-CIF41 Ver.1.0, one Ethernet Option Board can be
mounted.
Flash memory: User programs, parameters (such as the PLC Setup), comment data, and the entire DM Area can be saved to flash
Memory backup memory as initial values.
Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up by a battery.
Battery service life 5 years at 25°C. (Use the replacement battery within two years of manufacture.)
20 (12 inputs, 8 outputs)
Built-in input terminals 40 (24 inputs, 16 outputs) Line-driver inputs: Two axes for phases A, B, and Z
Line-driver outputs: Two axes for CW and CCW
Number of connectable
CP Expansion I/O Units: 7 max.; CJ-series Special I/O Units or CPU Bus Units: 2 max.
Expansion (I/O) Units
Max. number of I/O points 320 (40 built in + 40 per Expansion (I/O) Unit × 7 Units) 300 (20 built in + 40 per Expansion (I/O) Unit × 7 Units)
8 inputs (Shared by the external interrupt inputs (counter mode) and 6 inputs (Shared by the external interrupt inputs (counter
Interrupt inputs
the quick-response inputs.) mode) and the quick-response inputs.)
8 inputs (Response frequency: 5 kHz max. for all interrupt inputs), 6 inputs (Response frequency: 5 kHz max. for all interrupt
Interrupt input counter mode 16 bits inputs), 16 bits
Up or down counters Up or down counters
Quick-response inputs 8 points (Min. input pulse width: 50 μs max.) 6 points (Min. input pulse width: 50 μs max.)
Scheduled interrupts 1
8
CP1H
Type CP1H-XA CPU Units CP1H-X CPU Units CP1H-Y CPU Units
Item Models CP1H-XA@@@-@ CP1H-X@@@-@ CP1H-Y@@@-@
2 inputs: Differential phases (4x),
500 kHz or Single-phase,
4 inputs: Differential phases (4x), 50 kHz or 1 MHz and
Single-phase (pulse plus direction, up/down, increment), 2 inputs: Differential phases (4x), 50 kHz or Single-phase
High-speed counters 100 kHz (pulse plus direction, up/down, increment),
Value range: 32 bits, Linear mode or ring mode 100 kHz
Interrupts: Target value comparison or range comparison Value range: 32 bits, Linear mode or ring mode
Interrupts: Target value comparison or range
comparison
Trapezoidal or S-curve acceleration and deceleration
(Duty ratio: 50% fixed)
Trapezoidal or S-curve acceleration and deceleration
Pulse outputs Pulse out- 2 outputs, 1 Hz to 1 MHz (CCW/CW or pulse plus
(Duty ratio: 50% fixed)
(models with puts direction)
4 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus direction)
transistor out- 2 outputs, 1 Hz to 100 kHz (CCW/CW or pulse plus
puts only) direction)
PWM out- Duty ratio: 0.0% to 100.0% (Unit: 0.1%)
puts 2 outputs, 0.1 to 6553.5 Hz (Accuracy: ±5% at 1 kHz)
4 analog inputs and 2 analog
Built-in analog I/O terminals None
outputs
Analog control 1 (Setting range: 0 to 255)
External analog input 1 input (Resolution: 1/256, Input range: 0 to 10 V), not isolated
Note: The memory areas for CJ-series Special I/O Units and CPU Bus Units are allocated at the same as for the CJ-series. For details, refer to the CJ Series catalog
(Cat. No. P052).
9
CP1H
Built-in Inputs / Built-in Outputs
■ Terminal Block Arrangement
● CP1H-XA and X CPU Units with AC Power Supply ● CP1H-XA and X CPU Units with DC Power supply
CIO 0 CIO 1 CIO 0 CIO 1
L1 L2/N COM 01 03 05 07 09 11 01 03 05 07 09 11 (Input + − COM 01 03 05 07 09 11 01 03 05 07 09 11 (Input
● 00 02 04 06 08 10 00 02 04 06 08 10 ● terminals) ● NC 00 02 04 06 08 10 00 02 04 06 08 10 ● terminals)
+ 00 01 02 03 04 06 00 01 03 04 06 ● (Output NC 00 01 02 03 04 06 00 01 03 04 06 ● (Output
● − COM COM COM COM 05 07 COM 02 COM 05 07 terminals) ● NC COM COM COM COM 05 07 COM 02 COM 05 07 terminals)
CIO 100 CIO 101 CIO 100 CIO 101
10
CP1H
These areas are for line-driver inputs, so they can be used only for high-speed counters (1 MHz) and not for other purposes, such as normal inputs.
■ Built-in Output Area
● CP1H-Y CPU Units
When the When the origin search function is set to
instructions to When a pulse output instruction be used in the PLC Setup, and an origin When the PWM instruction is
Instructions
the right are not (SPED, ACC, PLS2, or ORG) is executed search is executed by the ORG executed
executed instruction
Fixed duty ratio pulse output Variable duty ratio pulse output
PLC Setup Normal output
CW/CCW Pulse plus direction When the origin search function is used PWM output
Pulse output 0 (CW) Pulse output 0 (pulse)
CW0 Not supported.
fixed fixed
Pulse output 0 (CCW) Pulse output 1 (pulse)
CCW0 Not supported.
fixed fixed
Pulse output 0 (direction)
CW1 Not supported. Pulse output 1 (CW) fixed
fixed
Pulse output 1 (CCW) Pulse output 1 (direction)
CCW1 Not supported.
fixed fixed
CIO Bit 04 100.04 Pulse output 2 (CW) Pulse output 2 (pulse)
100 Bit 05 100.05 Pulse output 2 (CCW) Pulse output 2 (direction)
Bit 06 100.06 Pulse output 3 (CW) Pulse output 3 (pulse)
Bit 07 100.07 Pulse output 3 (CCW) Pulse output 3 (direction)
CIO Bit 00 101.00 Origin search 2 (Error counter reset output) PWM output 0
101 Bit 01 101.01 Origin search 3 (Error counter reset output) PWM output 1
Bit 02 101.02 Origin search 0 (Error counter reset output)
Bit 03 101.03 Origin search 1 (Error counter reset output)
These areas are for line-driver inputs, so they can be used only for high-speed counters (1 MHz) and not for other purposes, such as normal inputs.
11
CP1H
I/O Specifications for CPU Units
■ Input Specifications
Specifications
ITEM High-speed counter inputs Interrupt inputs and
Normal inputs
(phases A and B) quick-response inputs
CP1H-XA/X CPU CIO 0.00 to CIO 0.03 and
CIO 0.04 to CIO 0.11 CIO 1.04 to CIO 1.11
Units CIO 1.00 to CIO 1.03
CIO 0.00, CIO 0.01 and
CP1H-Y CPU Units CIO 0.04, CIO 0.05, CIO 0.10, CIO 0.11 CIO 1.04, CIO 1.05
CIO 1.00 to CIO 1.03
Input voltage 24 VDC +10%/–15%
Applicable sensors 2-wire sensors or 3-wire sensors
Input impedance 3.0 kΩ 4.7 kΩ
Input current 7.5 mA typical 5 mA typical
ON voltage 17.0 VDC min. 14.4 VDC min.
OFF voltage/current 1 mA max. at 5.0 VDC
ON delay 2.5 μs max. 50 μs max. 1 ms max.
OFF delay 2.5 μs max. 50 μs max. 1 ms max.
IN IN IN
Input LED Input LED Input LED
1000 pF 1000 pF
4.3 kΩ
910 Ω
750 Ω
3.0 kΩ Internal 3.0 kΩ Internal 4.7 kΩ Internal
Circuit configuration IN
circuits
IN
circuits
IN
circuits
COM COM COM
ON 90% ON 90%
50% Phase A 50%
OFF 10% OFF 10%
T1 T2 T3 T4
50 μs min. 50 μs min.
330 Ω 180 Ω
+ +
6800 pF
680 Ω 330 pF 560 Ω
Circuit configuration Internal
Internal circuits
− circuits −
330 Ω 180 Ω
12
CP1H
■ Output Specifications
● CPU Units with Relay Outputs
Item Specifications Note: Under the worst conditions, the service life of output contacts is as shown
on the left.
Max. switching capacity 2 A, 250 VAC (cosφ = 1), 2 A, 24 VDC 4 A/common) The service life of relays is as shown in the following diagram as a guide-
Min. switching capacity 5 VDC, 10 mA line.
500
Resis- 125 VAC resistive load
Life (x 104 )
30
Mechanical 20,000,000 operations
20
ON delay 15 ms max. 10 0 47 55
OFF delay 15 ms max. Ambient temperature (˚C)
5 125 VAC cos φ = 0.4
3 250 VAC cos φ = 0.4
2
Output LED OUT
L
0.1 0.2 0.3 0.5 0.7 1 2 3 5 10
Contact current (A)
L
Circuit configuration OUT
Internal circuits
COM Maximum
250 VAC: 2 A,
24 VDC: 2 A
OUT OUT
L L
OUT OUT
L Internal L
Internal Internal circuits
4.5 to 30 VDC 4.5 to 30 VDC
circuits circuits
COM (+)
COM (+)
Internal Internal 4.5 to 30 VDC Internal
circuits circuits circuits 4.5 to 30 VDC
OUT
L OUT
OUT L
L OUT
L
Note: 1. Do not apply a voltage or connect a load to an output terminal exceeding the maximum switching capacity.
*1 Also do not exceed 0.9 A for the total for CIO 100.00 to CIO 100.03. (CIO 100.00 to CIO 100.03 is different common.) 0.9
*2 A maximum of 0.9 A per common can be switched at an ambient temperature of 50 °C. Common
*3 Fuses cannot be replaced by the user. terminal 0.6
current
(A)
0 50 55
Ambient temperature (˚C)
13
CP1H
ton
4 ms min. 2 ms min. ON duty = × 100%
T
Note: 1. The above values assume a resistive load and do not consider the im-
pedance of the cable connecting the load. Note: 1. The above values assume a resistive load and do not consider the im-
2. The pulse widths during actual use may be smaller than the ones shown pedance of the cable connecting the load.
above due to pulse distortion caused by connecting cable impedance. 2. The pulse widths during actual use may be smaller than the ones shown
3. The OFF and ON refer to the output transistor. The output transistor is ON above due to pulse distortion caused by connecting cable impedance.
at level “L”. 3. The OFF and ON refer to the output transistor. The output transistor is ON
at level “L”.
● Pulse Outputs (Line-driver Outputs)
CP1H-Y CPU Units
Item Specifications
Pulse outputs Line-driver outputs, Am26LS31 or equivalent
Max. output current 20 mA
Max. output frequency 1 MHz
Internal circuits
CWn+
Circuit configuration CWn−
CCWn+
CCWn−
Note: Connect a load of 20 mA or less to the output. The Unit may be damaged
if a current of more than 20 mA is output.
Built-in Analog Input Switch (Factory Settings) Built-in Analog I/O Terminal Block Arrangement
AD1 AD2 AD3 AD4 AD1+ AD1-- AD2+ AD2-- AD3+ AD3-- AD4+ AD4--
ON
Current input
OFF Voltage input VOUT1 IOUT1 COM1 VOUT2 IOUT2 COM2 AG AG
14
CP1H
External Interfaces
■ CPU Unit Nomenclature
Front Option Board Slot 1
Back
Input Indicators Terminal Block (Removable) Option Board Slot 2
Battery Cover
Operation Indicators IN
AC100-240V
Peripheral USB Port L1 L2/N COM
00
01
02
03
04
05
06
07
08
09
10
11
00
01
02
03
04
05
06
07
08
09
10
11
POWER
Seven-segment ERR/ALM
BKUP
EXP
LED Display
Analog Control
External Analog
Settings Input 00 01 02 03 04 06 00 01 03 04 06
COM COM COM COM 05 07 COM 02 COM 05 07
Connector DC24V0.3A 100CH 101CH
1CH
OUTPUT
OUT
DIP Switch
Built-in Analog I/O
Terminal Block (See note.)
Built-in Analog Memory Cassette Slot Terminal Block Expansion Unit and CJ Unit Adapter Connector
Input Switch (See note.) (Removable) Expansion I/O Unit
Connector
Note: XA CPU Units only.
Output Indicators
15
CP1H
Option Unit Specifications
■ Serial Communications Specifications (CP1W-CIF01/-CIF11)
Item Function Interface
Peripheral USB port For connecting Peripheral Device. Conforms to USB 1.1, B-type connector
CP1W-CIF12-V1
Serial port 2 RS-422A/485(Isolated-type) Option Board
(Option board slot 2) (Maximum transmission distance 500m)
Note: Serial PLC Link can be used with either serial port 1 or serial port 2.
16
CP1H
● LCD Functions
Operation Description
Changing operating modes Change the PLC operating mode without using the CX-Programmer.
I/O memory Read and change the present values in the memory areas and force-set or force-reset bits.
PLC Setup operations Read and change the PLC Setup.
Analog I/O monitor Monitor the analog adjustment and present value for the external analog setting input.
Error log display Read the log of errors that have occurred.
Memory cassette operation Transfer and verify user programs between the PLC and memory cassette.
User monitor settings Read the status of up to 16 words and bits with comments. You can use this setting to read data on the startup display.
Message display function Display a user-set message of up to 48 characters on the LCD Option Board when a specified bit turns ON.
settings A maximum of 16 screens can be registered for display.
Operation:
Use this timer for ON/OFF switching at a Starting day of the week Ending day of the week
Example: Monday Example: Friday
specified times every day from the starting
Day timer day of the week to the ending day of the ON
week. Sixteen timers cam be set from OFF
timer 01 to timer 16.
Starting time Ending time Starting time Ending time Starting time Ending time
Example: 9:00 Example: 17:00 9:00 17:00 9:00 17:00
Operation:
Starting day of the week Ending day of the week
Use this timer for ON/OFF operation in Example: Monday Example: Friday
Timers
intervals of one week that starts one day
Weekly timer ON
and ends another day. Sixteen timers cam
OFF
be set from timer No. 01 to timer No. 16.
Starting time Ending time Starting time Ending time
Example: 12:00 Example: 8:00 12:00 8:00
Operation:
Use the calendar timers for ON or OFF ON
operation in intervals of one year from the
Calendar timer OFF
starting day to the ending day. Sixteen
timers can be set from timer 01 to timer 16. Starting day Ending day Set September 1
July 1 August 31 as the ending day.
Save the various settings that you set with the LCD Option Board to the DM Area of the PLC. You can also write the settings
Saving setting
saved in the PLC to the LCD Option Board.
Language Changing the display language (Japanese/English)
• Setting the time of the PLC's built-in clock
• Reading system data (e.g., unit version and lot number)
• Setting the backlight lighting time
Other functions
• Adjusting LCD contrast
• Reading cycle time (e.g., average, maximum, and minimum)
• Clearing data for the LCD Option Board
17
CP1H
Expansion I/O Unit Specifications
■ CP1W-40EDR/40EDT/40EDT1/32ER/32ET/32ET1/20EDR1/20EDT/20EDT1/16ER/16ET/16ET1/8ED/8ER/8ET/8ET1 Expansion I/O Units
Expansion I/O Units can be connected to the CPU Unit to configure the required number of I/O points.
● DC Inputs (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)
Item Specifications
Input voltage 24 VDC +10%/−15%
Input impedance 4.7 kΩ
Input current 5 mA typical
ON voltage 14.4 VDC min.
OFF voltage 5.0 VDC max.
ON delay 0 to 32 ms max. (Default: 8 ms) (See note 1.)
OFF delay 0 to 32 ms max. (Default: 8 ms) (See note 1.)
IN
Input LED
750 Ω
4.7 kΩ Internal
Circuit configuration IN
circuits
COM
Note: 1. Do not apply a voltage exceeding the rated voltage to an input terminal.
2. Can be set in the PLC Setup to 0, 0.5, 1, 2, 4, 8, 16 or 32 ms. The CP1W-
40EDR/EDT/EDT1 are fixed at 16 ms.
300
Service Elec- load 24 VDC τ = 7 mA Output Load Current and
200 120 VAC cos φ = 0.4
life of trical Inductive 240 VAC cos φ = 0.4 Ambient Temperature
100,000 operations (24 VAC cos = 0.4) 100 24 VDC/240- VAC
relay load resistive load
(CP1W-16ER/32ER)
50
Mechanical 20,000,000 operations
5 50
Output LED OUT
L 3
2
L
Circuit configuration OUT
0 43 55
Internal 0.1 0.2 0.3 0.5 0.7 1 2 3 5 10 Ambient temperature (˚C)
circuits Contact current (A)
COM Maximum
250 VAC: 2 A, Switching frequency: 1,800 operations/h When using the CP1W-32ER, do not
24 VDC: 2 A
allow more than 24 outputs to be ON
simultaneously regardless of the
ambient temperature.
18
CP1H
COM (−) L 0 50 55
OUT Ambient temperature (°C)
19
CP1H
20
CP1H
21
CP1H
22
CP1H
● Main Specifications
Item CP1W-TS003
Thermocouples or analog input *1
Temperature sensors
Switchable between K and J, but same type must be used for all inputs.
Thermocouples inputs :4 , Analog inputs :2
Number of inputs
Two analog inputs can be shared with thermocouples inputs.
Thermocouple inputs (The larger of ±0.5% of converted value or ±2°C) ±1 digit max. *2
Accuracy at 25°C Analog voltage inputs 0.5% full scale
Analog inputs 0.6% full scale
Thermocouple inputs (The larger of ±1% of converted value or ±4°C) ±1 digit max. *3
Accuracy at 0 to
Analog voltage inputs 1.0 % full scale
55°C
Analog inputs 1.2 % full scale
K: -200.0 to 1300.0°C or .300.0 to 2300.0°F
Thermocouple inputs
J: -100.0 to 850.0°C or .100.0 to 1500.0°F
Input signal range
Analog voltage inputs 0 to 10V/1 to 5V
Analog inputs 4 to 20mA
Thermocouple inputs 0.1°C or 0.1°F
Resolution
Analog inputs 1/12000 (full scale)
Analog voltage inputs ±15V
Max. rated input
Analog inputs ±30mA
SW Setting
Temperature input
Input type Range (°C) Range (°F)
K -200.0 to 1300.0 -300 to 2300
J -100.0 to 850.0 -100.0 to 1500
23
CP1H
● Main Specifications
Item CP1W-TS004
Thermocouples
Temperature sensors
Switchable between K and J, but same type must be used for all inputs.
Number of inputs 12
25°C (The larger of ±0.5% of converted value or ±2°C) ±1 digit max. *1
Accuracy
0 to 55°C (The larger of ±1% of converted value or ±4°C) ±1 digit max. *2
Conversion time 500 ms for 12 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature and analog input signals
Current consumption 5 VDC: 80 mA max., 24 VDC: 50 mA max.
*1 Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max.
*2 Accuracy for a K-type sensor at -100°C or less is ±10°C ±1 digit max.
SW Setting
ON J
SW 1 2 1 Input type
ON
OFF K
ON °F
OFF 2 Temperature unit
OFF °C
Temperature input
Input type Range (°C) Range (°F)
K -200.0 to 1300.0 -300 to 2300
J -100.0 to 850.0 -100.0 to 1500
COMM
ERR Number of words 1 input word, 1 output word
SRT21
occupied in CP1H (Allocated in the same way as for
BD H NC(BS+)
EXP I/O memory other Expansion Units)
BD L NC(BS-) NC
24
CP1H
I/O Bits and I/O Allocations
With CP1H CPU Units, the beginning input and output words (CIO 0 and CIO 100) are allocated by the CPU Unit one or two words at a time. I/O
bits are allocated in word units in order of connection to Expansion Units and Expansion I/O Units connected to a CPU Unit.
Allocated words
CPU Unit
Inputs Outputs
CP1H CPU Unit with 40 I/O points CIO 0 and CIO 1 CIO 100 and CIO 101
Note: For details on the number of words allocated to Expansion Units and Expansion I/O Units, refer to Words Allocated to CP1W Expansion Units and Expansion I/O
Units on page 26.
16 outputs 16 outputs
Outputs CIO 100.00 to CIO 100.07 CIO 102 CIO 106.00 to CIO 106.07
None
CIO 101.00 to CIO 101.07 to CIO 105 CIO 107.00 to CIO 107.07
25
CP1H
Expansion Unit and Expansion I/O Units Specifications
■ Maximum Number of CP1W Expansion Unit and Expansion I/O Units
● CP1H CPU Unit
■ Restrictions on the Number of CP1H Expansion Unit and I/O Unit Connections
Up to seven Expansion Units and Expansion I/O Units can be connected when a CP1H CPU Unit is used, but the following restrictions apply.
Observe these restrictions when using the models in the shaded areas in the following tables. A maximum total of 15 input words is allocated for
Expansion Units and a maximum total of 15 output words is allocated for Expansion Units and Expansion I/O Units.
A/D: 4 points
Analog I/O Unit CP1W-MAD42 4 2
D/A: 2 points
A/D: 4 points
D/A: 4 points CP1W-MAD44 4 4
CP1W-TS001 2
Thermocouple (J or K) ---
CP1W-TS002 4
Thermocouple (J or K) CP1W-TS003 4 ---
Temperature Thermocouple (J or K)
Sensor Unit A/D: 2 points CP1W-TS004 2 1
26
CP1H
■ Using CJ-series Special I/O Units or CPU Bus Units with a CP1H CPU Unit
Up to two CJ-series Special I/O Units or CPU Bus Units can be connected by using a CP1W-EXT01 CJ Unit Adapter. The number of Units that
can be used is as described below.
● CJ-series Special I/O Units and CPU Bus Units (For details, refer to the CJ1 Catalog (Cat. No. P052)).
5 V Current 5 V Current
CJ Unit Adapter End Cover Unit name Model consumption Unit name Model consumption
CP1W-EXT01 (A) (A)
CJ1W-AD042 0.52 A CJ1W-NC113
0.25 A
Analog Input Units CJ1W-AD081-V1 CJ1W-NC213
0.42 A
CJ1W-AD041-V1 CJ1W-NC413 0.36 A
Position Control Units
CJ1W-DA042V 0.40 A CJ1W-NC133
0.25 A
CJ1W-DA08V CJ1W-NC233
Up to two CJ-series 0.14 A
Special I/O Units or Analog Output Units CJ1W-DA08C CJ1W-NC433 0.36 A
CPU Bus Units can CJ1W-DA041 High-speed Counter
0.12 A CJ1W-CT021 0.25 A
be connected. Unit
CJ1W-DA021
0.26 A
Analog I/O Unit CJ1W-MAD42 0.58 A
CJ1W-V680C11 (24 VDC
CJ1W-PH41U 0.30 A 0.13 A)
CJ1W-AD04U 0.32 A 0.32 A
CJ1W-V680C12 (24 VDC
CJ1W-PTS51
Process Input Units 0.25 A 0.26 A)
CJ1W-PTS52 ID Sensor Units
0.26 A
7 max. CJ1W-PTS15 CJ1W-V600C11 (24 VDC
Use CP1W-CN811 I/O Connecting Cable when 0.18 A 0.12 A)
CJ1W-PDC15
using CP1W Expansion Units and Expansion I/O 0.32 A
Units at the same time as a CJ Unit Adapter. In CJ1W-TC001
CJ1W-V600C12 (24 VDC
this situation, the number of CP1W Expansion CJ1W-TC002 0.24 A)
Unit and Expansion I/O Units that can be CJ1W-TC003 CJ1W-SCU42 0.38 A*
connected is subject to the restrictions described
Temperature Control CJ1W-TC004 CJ1W-SCU22 0.29 A*
above. Only one I/O Connecting Cable can be 0.25 A
Units CJ1W-TC101 CJ1W-SCU32 0.46 A
used. Serial Communications
CJ1W-TC102 Units CJ1W-SCU41-V1 0.38 A*
CJ1W-TC103 CJ1W-SCU21-V1 0.28 A*
CJ1W-TC104 CJ1W-SCU31-V1 0.38 A
CompoBus/S Master Unit CJ1W-SRM21 0.15 A Ethernet Unit CJ1W-ETN21 0.37 A
CompoNetTM Master EtherNet/IPTM Unit CJ1W-EIP21 0.41 A
CJ1W-CRM21 0.40 A
Unit
DeviceNetTM Unit CJ1W-DRM21 0.33 A
Controller Link Unit CJ1W-CLK23 0.35 A
CJ1W-NC271
MECHATROLINK-II CJ1W-NC471
0.36 A
Position Control Unit CJ1W-NCF71
CJ1W-NCF71-MA
MECHATROLINK-II
CJ1W-MCH71 0.6 A
Motion Control Unit
FL-net Unit CJ1W-FLN22 0.37 A
High-speed Data
CJ1W-SPU01-V2 0.56 A
Storage Unit
* The current consumption increases by 0.15 A/Adapt-
er when NT-AL001 Link Adapters are used.
27
CP1H
Current Consumption
● Based on the current consumption when CJ-series Special I/O Units or CPU Bus Units are used with a CP1H CPU Unit, the
maximum number of Units that can be used is two CJ-series Units and seven CP1W Expansion Units and Expansion I/O
Units.
The current consumption for the CP1H must be no more than 2 A for 5 V and 1 A for 24 V, and the total current consumption must be
no more than 30 W.
Check the total current consumption to be sure these limits are not exceeded referring to page 28 for the CP1H CPU Unit and CP1W
Expansion Unit and Expansion I/O Unit current consumptions and to the above table for CJ-series Unit current consumptions.
● CPU Units
Current consumption External power supply
Model
5 VDC 24 VDC 24 VDC (See note 5.)
CP1H-X40DR-A 0.42 A 0.07 A 0.3 A max. (0.9 A max.)
CP1H-X40DT-D 0.50 A 0.01 A ---
CP1H-X40DT1-D 0.50 A 0.02 A ---
CP1H-XA40DR-A 0.43 A 0.18 A 0.3 A max. (0.8 A max.)
CP1H-XA40DT-D 0.51 A 0.12 A ---
CP1H-XA40DT1-D 0.51 A 0.15 A ---
CP1H-Y20DT-D 0.55 A --- ---
Note: 1. The current consumption of the CP1W-ME05M Memory Cassette and the CP1W-CIF01/CIF11 Option Boards are included in the current consumption of the
CPU Unit.
2. CPU Units with DC power do not provide an external power supply.
3. The current consumptions given in the following table must be added to the current consumption of the CPU Unit if an Expansion Unit or Expansion I/O Unit
is connected.
4. The external power supply cannot be used if an Expansion Unit or Expansion I/O Unit is connected to a CPU Unit with 14 or 20 I/O points.
5. Values in parentheses are the maximum external power supply for a CPU Unit to which an Expansion I/O Unit is not connected. Refer to the CP1H CPU Unit
Operation Manual (Cat. No. W450) for details.
● Option Units
Current consumption
Unit name Model
DC5V 24 VDC
RS-232C Option Board CP1W-CIF01 --- * ---
RS-422A/485 Option Board CP1W-CIF11 --- * ---
RS-422A/485 (Isolated-type) Option Board CP1W-CIF12-V1 0.075A ---
Ethernet Option Board CP1W-CIF41 0.130A ---
LCD Option Board CP1W-DAM01 0.020A ---
Memory Cassette CP1W-ME05M --- * ---
CJ Unit Adapter CP1W-EXT01 --- * ---
* The current consumption of the following is included with the current consumption of the CPU Unit:
CP1W-ME05M Memory Cassette, CP1W-CIF01 or CP1W-CIF11 Option Board, and CP1W-EXT01 CJ Unit Adapter.
28
CP1H
29
CP1H
Dimensions (Unit: mm)
■ CPU Units
CP1H CPU Units (X/XA/Y Types)
150 85
140 8
Weight:
CP1H-@@@-A (AC power supply):
740 g max.
CP1H-@@@-D DC power supply):
110 100 90 590 g max.
COM 01 03 05 07 09 11 COM 01 03
NC 00 02 04 06 08 10 00 02
IN CH
IN
CH 00 01 02 03 04 05 06 07
CH 00 01 02 03
08 09 10 11
08 09 10 11
20EDR1 90 8ED 90
OUT
CH 00 01 02 03 04 05 06 07
CH EXP EXP
NC 00 01 02 04 05 07 04 06
NC COM COM COM 03 COM 06 COM 05 07
86 66 50
50
CH
00
00
01
01
02
02
03
03
04
04
05
05
06
06
07
07
08
08
09
09
10
10
11
11 CP1W-8ER/-8ET/-8ET1 250 g
OUT 00 01 02 03 04 05 06 07
110 100 90 CH
00 01 02 03 04 05 06 07 40EDR
CP1W-AD041/-DA041/-DA021 200 g
CP1W-AD042/-DA042 250 g
CH CH EXP Analog Units
NC
NC
COM
00
COM
01
COM
02
03
04
COM
05
06
07
COM
00
01
02
03
04
COM
05
06
07
CP1W-MAD11 150 g
CP1W-MAD44/-MAD42 250 g
CP1W-TS001/-TS002/
Four, -TS101/-TS102 250 g
8 Temperature
4.5 dia.
50 Sensor Units CP1W-TS003 240 g
CP1W-TS004 570 g
CompoBus/S
CP1W-SRT21 200 g
I/O Link Unit
30
CP1H
■ CJ-series Special I/O Units and CPU Bus Units ■ CJ Unit Adaptor
CP1W-EXT01
16.4
2.7 2.7 65.5
5.7 7.6 65
90 90
95.4 90
2.7 31 65 2.7 31
89
65.5
Note: It takes an example about the size.
■ CP1H
Example: Two CJ-series Units (31-mm widths) Connected Using a CJ Unit Adapter
234.3
SYSMAC
CP1H IN
L1 L2/N COM 01 03 05 07 09 11 01 03 05 07 09 11
BATTERY 00 02 04 06 08 10 00 02 04 06 08 10
POWER
PERIPHERAL ERR/ALM EXP
BKUP
MEMORY
+ 00 01 02 03 04 06 00 01 03 04 06
− COM COM COM COM 05 07 COM 02 COM 05 07
100CH 101CH
1CH
OUT
150 31 31
7.6 14.7
31
CP1H
Related Manuals
Cat. No. Model numbers Manual name Description
CP1H-X40D@-@ CP Series Provides the following information on the CP Series:
CP1H-XA40D@-@ CP1H CPU Unit • Overview, design, installation, maintenance, and other basic specifications
CP1H-Y20DT-D Operation Manual • Features
• System configuration
W450 • Mounting and wiring
• I/O memory allocation
• Troubleshooting
Use this manual together with the CP1H Programmable Controllers Programming
Manual (W451).
CP1H-X40D@-@ CP Series Provides the following information on the CP Series:
CP1H-XA40D@-@ CP1H CPU Unit • Programming instructions
CP1H-Y20DT-D Programming Manual • Programming methods
W451 • Tasks
• File memory
• Functions
Use this manual together with the CP1H Programmable Controllers Operation
Manual (W450).
CS1G/H-CPU@@H CS/CJseries Describes commands addressed to CS-series and CJ-series CPU Units, including
CS1G/H-CPU@@-V1 Communications C-mode commands and FINS commands.
CS1D-CPU@@HA Commands Reference Note: This manual describes on commands address to CPU Units regardless of the
CS1D-CPU@@SA Manual communications path. (CPU Unit serial ports, Serial Communications
CS1D-CPU@@H Unit/Board ports, and Communications Unit ports can be used.)
CS1D-CPU@@S Refer to the relevant operation manuals for information on commands ad-
W342 CS1W-SCU21 dresses to Special I/O Units and CPU Bus Units.
CS1W-SCB21-V1/41-V1
CJ1G/H-CPU@@H
CJ1G-CPU@@P
CP1H-CPU@@
CJ1G-CPU@@
CJ1W-SCU21-V1/41-V1
32
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2012-2017 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_11_7_1118 Printed in Japan
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. P080-E1-03 1117 (0312)