Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Foam Calculations

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Design calculation sheet

Project no: S08050 Date: 15/10/09 Sheet no.: 1 of 4 Computed by: B.S.K

Subject: Foam Fire Extinguishing System Calculations Checked by: B.H

jeddah site- fuel tanks Approved by: T.Q

General Assumptions:

1- The calculation presented here below are for reference and guidance only,
as foam system is a pre-engineered system to come complete from the supplier.

2- The system used is an automatic sprinkler systems utilizing


foam/water sprinkler heads, integrated into a complete deluge system.

1- Electrical Sub-station No. 39.2:

1.1- Generator Room No. (G001):

Design Criteria and Preliminary Estimation:

Discharge Criteria = 6.5 l/min.m2 = 0.16 gpm/ft2 (Refer to NFPA 16, section 4-3.2)

Discharge Duration = 10 min. (Refer to NFPA 16, section 4-3.3.1)

Foam Concentrate = 3 % (Refer to Wilson fire equipment,


warehouse foam fire protection systems
design bulliten attached)

Room Area = 207.3 m2

Min. Area per Sprinkler = 9 m2 (Refer to NFPA 16, section 4-3.7.2)

Min. No. of sprinklers = 23.03 = 24 Sprinklers

But for the maximum spacing between sprinklers not to exceed 3.7 m
(Refer to NFPA 16, section 4-3.7.2)

Actual No. of sprinklers = 25 Sprinklers (Refer to attached drawings)

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: S08050 Date: 15/10/09 Sheet no.: 2 of 4 Computed by: B.S.K

Subject: Foam Fire Extinguishing System Calculations Checked by: B.H


jeddah site- fuel tanks Approved by: T.Q

And hence,

Flow of foam solution = Discharge Criteria x Room Area


(Refer to NFPA 16, section 4-3.3.1)

Flow of foam solution = 1348 l/min.

Volume of foam solution = Flow Of Foam Solution x Discharge Duration

Volume of foam solution = 13480 l

Quantity of Foam Concentrate = Volume Of Foam Solution x Foam Concentration

Quantity of foam Conc. = 404.4 l = 106.8 Gallons

Foam Tank Capacity = 107 Gallons

Design Pressure at Nozzle = 207.6 kPa = 30 psi

Hydraulic Calculations: (Refer to NFPA 16, section 4-4.1.3)

Nozzle minimum operating pressure= 30 psi (Refer to NFPA 15, section A.8.1.2)
(Refer to ANSUL foam systems
design and applications manual attached)
(Refer to Viking design data, attached)

Type of foam concentrate used is AFFF (Refer to NFPA 11, section 4.3.1.4)

Density of foam concentrate (ρ) = 1.011 g/ml (Refer to ANSUL design data, attached)

Absolute Viscosity of foam concentrate (μ) = 1.8 cps


(Refer to Hypro design data, attached)
From the sprinkler distribution:

Coverage area per sprinkler = 8.31 m2 = 89.3548 ft2

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: S08050 Date: 15/10/09 Sheet no.: 3 of 4 Computed by: B.S.K

Subject: Foam Fire Extinguishing System Calculations Checked by: B.H


jeddah site- fuel tanks Approved by: T.Q

Since,

For open type sprinklers dedicated for foam/water deluge systems,

Q (gpm) = K √P (psi)
And,
K= 3 (Refer to ANSUL foam systems design and applications manual attached)

and since we have two approaches, one is to satisfy the density and the other is to satisfy
the minimum pressure required; we'll calculate both and apply the one with the greater demand.

i. Taking the design density as the governing constraint:

Discharge Criteria = 0.16 gpm/ft2

Q= 14.3 gpm

P= 22.7 psi (refused)

ii. Taking the minimum operating pressure as the governing constraint:

P= 30.0 psi

Q= 16.4 gpm

Discharge Criteria = 0.18 gpm/ft2 (accepted)

Therefore,

Sp. No. (gpm) Pipe Diam.(in) Eq. Pipe length (ft) C Pf (psi/ft) Pt (psi)
S1 16.40 0.500 8.00 120 3.33 57
N1-N2 32.80 1.000 28.00 120 0.41 68
N2-N3 65.60 1.500 18.00 120 0.21 72
N3-N4 98.40 2.000 9.00 120 0.11 73
N4-
System 98.40 2.000 15.00 120 0.11 74
outlet

Adding the static pressure:

Pr = 79 psi

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: S08050 Date: 15/10/09 Sheet no.: 4 of 4 Computed by: B.S.K

Subject: Foam Fire Extinguishing System Calculations Checked by: B.H


jeddah site- fuel tanks Approved by: T.Q

Assuming that the induction causes a pressure drop of 30 % of the required pressure:

Pt = 103 psi

Based on the final Design Criteria:

System Summary:

Tank Capacity = 123 Gal.

No. of Sprinklers = 25 Sprinklers

Minimum Pressure Required at Input Point = 103 psi

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: K0065 Date: 21/4/03 Sheet no.: 1 of 4 Computed by: A.R

Subject: Foam Fire Extinguishing System Calculations Checked by: A.G

Approved by:

General Assumptions:

1- The calculation presented here below are for reference and guidance only,
as foam system is a pre-engineered system to come complete from the supplier.

2- The system used is an automatic sprinkler systems utilizing


foam/water sprinkler heads, integrated into a complete deluge system.

2- Electrical Sub-station No. 39A To E:

2.1- Generator Room No. (G001):

Design Criteria and Preliminary Estimation:

Discharge Criteria = 6.5 l/min.m2 = 0.16 gpm/ft2 (Refer to NFPA 16, section 4-3.2)

Discharge Duration = 10 min. (Refer to NFPA 16, section 4-3.3.1)

Foam Concentrate = 3 % (Refer to Wilson fire equipment,


warehouse foam fire protection systems
design bulliten attached)

Room Area = 38.7 m2

Min. Area per Sprinkler = 9.3 m2 (Refer to NFPA 16, section 4-3.7.2)

Min. No. of sprinklers = 4.16 = 5 Sprinklers

But for the maximum spacing between sprinklers not to exceed 3.7 m
(Refer to NFPA 16, section 4-3.7.2)

Actual No. of sprinklers = 6 Sprinklers (Refer to attached drawings)

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: K0065 Date: 21/4/03 Sheet no.: 2 of 4 Computed by: A.R

Subject: Foam Fire Extinguishing System Calculations Checked by: A.G


Approved by:

And hence,

Flow of foam solution = Discharge Criteria x Room Area


(Refer to NFPA 16, section 4-3.3.1)

Flow of foam solution = 252 l/min.

Volume of foam solution = Flow Of Foam Solution x Discharge Duration

Volume of foam solution = 2520 l

Quantity of Foam Concentrate = Volume Of Foam Solution x Foam Concentration

Quantity of foam Conc. = 75.6 l = 19.97 Gallons

Foam Tank Capacity = 20 Gallons

Design Pressure at Nozzle = 207.6 kPa = 30 psi

Hydraulic Calculations: (Refer to NFPA 16, section 4-4.1.3)

Nozzle minimum operating pressure= 30 psi (Refer to NFPA 15, section A.8.1.2)
(Refer to ANSUL foam systems
design and applications manual attached)
(Refer to Viking design data, attached)

Type of foam concentrate used is AFFF (Refer to NFPA 11, section 4.3.1.4)

Density of foam concentrate (ρ) = 1.011 g/ml (Refer to ANSUL design data, attached)

Absolute Viscosity of foam concentrate (μ) = 1.8 cps


(Refer to Hypro design data, attached)
From the sprinkler distribution:

Coverage area per sprinkler = 6.3 m2 = 67.7419 ft2

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: K0065 Date: 21/4/03 Sheet no.: 3 of 4 Computed by: A.R

Subject: Foam Fire Extinguishing System Calculations Checked by: A.G


Approved by:

Since,

For open type sprinklers dedicated for foam/water deluge systems,

Q (gpm) = K √P (psi)
And,
K= 3 (Refer to ANSUL foam systems design and applications manual attached)

and since we have two approaches, one is to satisfy the density and the other is to satisfy
the minimum pressure required; we'll calculate both and apply the one with the greater demand.

i. Taking the design density as the governing constraint:

Discharge Criteria = 0.16 gpm/ft2

Q= 10.8 gpm

P= 13.1 psi (refused)

ii. Taking the minimum operating pressure as the governing constraint:

P= 30.0 psi

Q= 16.4 gpm

Discharge Criteria = 0.24 gpm/ft2 (accepted)

Therefore,

Sp. No. (gpm) Pipe Diam.(in) Eq. Pipe length (ft) C Pf (psi/ft) Pt (psi)
S1 16.40 0.500 8.00 120 3.33 57
N1-N2 32.80 1.000 31.00 120 0.41 69
N2-N3 65.60 1.500 20.00 120 0.21 73
N3-N4 98.40 2.000 9.00 120 0.11 74
N4-
System 98.40 2.000 15.00 120 0.11 76
outlet

Adding the static pressure:

Pr = 81 psi

K0065-CLC-ME-02-REVA
Design calculation sheet
Project no: K0065 Date: 21/4/03 Sheet no.: 4 of 4 Computed by: A.R

Subject: Foam Fire Extinguishing System Calculations Checked by: A.G


Approved by:

Assuming that the induction causes a pressure drop of 30 % of the required pressure:

Pt = 106 psi

Based on the final Design Criteria:

System Summary:

Tank Capacity = 31 Gal.

No. of Sprinklers = 6 Sprinklers

Minimum Pressure Required at Input Point = 106 psi

K0065-CLC-ME-02-REVA

You might also like