1. SCOPE
This section covers the specification of 11kV voltage station Lightning (Surge) Arrestors for
installation on outdoor type 11kV switchgear, transmission lines, transformers etc. 11kV side
of which is not enclosed in a cable box. Station class surge arrestors shall be complete with
fasteners for stacking units.
2. STANDARDS
The design, manufacture and performance of Surge Arrestors shall comply with IS: 3070
Part-3 and other specific requirements stipulated in the specification. Unless otherwise
specified, the equipment, material & processes shall conform to the latest amendments of the
following:
IS:2071-1993 (Part- Methods of High Voltage Testing General Definitions & Test
1) Requirements.
IS:2071-1974 (Part- Test Procedures.
2)
IS: 2629-1985 Recommended Practice for hot dip galvanizing on Iron & Steel.
IS: 2633-1986 Method for Testing uniformity of coating of zinc coated Articles.
IS:3070-1993 (Part – Specification for surge arrestor for alternating current systems.
3) Metal-Oxide lightening Arrestors without gaps.
IS: 4759-1996 Specification for hot dip zinc coating on structural steel and other
allied products.
IS: 5621-1980 Hollow Insulators for use in Electrical Equipment.
IS: 6209-1982 Methods of Partial discharge measurement.
IS: 6745 Method for determination of mass of zinc coating on zinc coated
iron and steel articles.
ANSI/IEEE-C.62.11 Metal oxide, Surge Arrestor for AC Power Circuits.
IEC –60099-4 Surge Arrestors.
The equipment complying with any other internationally accepted standards shall also be
considered if it ensures performance equivalent to or superior to the Indian Standards.
3. GENERAL REQUIREMENT
3.1. The metal oxide gap less Surge Arrestor without any series or shunt gap shall be suitable
for protection of 11 kV side of power transformers, associated equipment and 11kV lines
from voltage surges resulting from natural disturbance like lightning as well as system
disturbances.
3.2. The surge arrestor shall draw negligible current at operating voltage and at the same
time offer least resistance during the flow of surge current.
3.3. The surge arrestor shall consist of non-linear resistor elements placed in series and housed
in electrical grade porcelain housing / silicon polymeric of specified Creepage distance.
3.4. The assembly shall be hermetically sealed with suitable rubber gaskets with effective
sealing system arrangement to prevent ingress of moisture.
3.5. The surge arrestor shall be provided with line and earth terminals of suitable size. The
ground side terminal of surge arrestor shall be connected with 25x6 mm galvanized
strip, one end connected to the surge arrestor and second end to a separate ground
electrode. The bidder shall also recommend the procedure which shall be followed in
providing the earthing system to the Surge Arrestor.
3.6. The surge arrestor shall not operate under power frequency and temporary over voltage
conditions but under surge conditions, the surge arrestor shall change over to the
conducting mode.
3.7. The surge arrestor shall be suitable for circuit breaker performing 0-0.3 min-CO-3 min-CO-
duty in the system.
3.8. Surge arrestors shall have a suitable pressure relief system to avoid damage to the
porcelain/ silicon polymeric housing and providing path for flow of rated fault currents
in the event of arrestor failure.
3.9. The reference current of the arrestor shall be high enough to eliminate the influence of
grading and stray capacitance on the measured reference voltage.
3.10. The Surge Arrestor shall be thermally stable and the bidder shall furnish a copy of
thermal stability test with the bid.
3.11. The arrestor shall be capable of handling terminal energy for high surges, external
pollution and transient over voltage and have low losses at operating voltages.
4. TECHNICAL PARTICULARS: The surge arrestors shall conform to the following standard
technical requirements. The Insulation values shall be enhanced considering the altitude of
operation & other atmospheric conditions.
4.1. System Parameters
i) Nominal system voltage 11kV
ii) Highest system voltage 12 kV
iii) System earthing Effectively earthed
system
iv) Frequency (Hz) 50
v) Lightning Impulse withstand 75 Voltage (kVP)
vi) Power frequency withstand 28 Voltage (kV rms)
vii) Arrestor duty
-- Connection to system Phase to earth
-- Type of equipment to be protected transformers & switchgear
4.4. Galvanisation
i) Fabricated Steel Articles
a) 5 mm thick cover 610 g/m2
b) Under 5 mm but not less than 2 mm thickness 460 g/m2
c) Under 2 mm but not less than 1.2 mm thickness 340 g/m2
ii) Castings
Grey Iron, malleable iron 610 g/m2
iii) Threaded works other than tubes & tube fittings
a) Under 10 mm dia 270 g/m2
b) 10 mm dia & above 300 g/m2
5. TESTS
5.1. Test on Surge Arrestors
The Surge Arrestors offered shall be type tested and shall be subjected to routine and
acceptance tests in accordance with IS : 3070 (Part-3)-/IEC:600994. In addition, the
suitability of the surge arresters shall also be established for the following:
i) Acceptance tests :
a) Measurement of power frequency reference voltage of arrester units.
b) Lightning impulse residual voltage on arrester units (IEC clause 6.3.2).
c) Internal ionization or partial discharge test
ii) Special Acceptance tests :
a) Thermal stability test (IEC clause 7.2.2).
b) Watt loss test.
iii) Routine tests :
a) Measurement of reference voltage.
b) Residual voltage test of arrester unit.
c) Internal ionization or partial discharge test.
d) Sealing test.
e) Verticality check on completely assembled surge arresters as a sample test
on each lot if applicable.
iv) Type Tests :
Following shall be type test as per IS 3070 (Part 3): 1993 or its latest amendment :
SN Description of test
Insulation Withstand test
1 a) Lightning Impulse
b) Power Frequency (Dry/Wet)
Residual Voltage Test
a) Steep current impulse residual voltage test
2
b) Lightning impulse residual voltage test
c) Switching Impulse Residual voltage test
3 Long duration current impulse withstand test
4 Switching surge operating duty test
Power frequency voltage Vs. Time
5
characteristics
6 Accelerated Ageing test
Pressure relief test
7 a) High Current
b) Low Current
8 Artificial pollution test (for porcelain housing)
9 Seismic Test
10 Partial Discharge test
11 Bending test
a) Temperature cycle test (for porcelain
12 housing)
b) Porosity test (for porcelain housing)
13 Galvanising test on metal parts
14 Seal Leakage test (for porcelain housing)
Seal leak test and operation tests ( for surge
15
monitor)
16 Weather ageing test (for polymer housing)
6. NAME PLATE
6.1. The name plate attached to the arrestor shall carry the following information:
- Rated Voltage
- Continuous Operation Voltage
- Normal discharge current
- Pressure relief rated current
- Manufacturers Trade Mark
- Name of Sub-station
- Year of Manufacturer
- Name of the manufacture
- Name of Client
- Purchase Order Number along with date
7. DRAWINGS AND INSTRUCTION MANUALS
Within 15 days of receipt of the order, the successful tenderer shall furnish to the
purchaser, the following drawings and literature for approval:
(i) Outline dimensional drawings of Surge Arrestor and all accessories.
(ii) Assembly drawings and weights of main component parts.
(iii) Drawings of terminal clamps.
(iv) Arrangement of earthing lead.
(v) Minimum air clearance to be maintained of line components to ground.
(vi) Name plate.
(vii) Surge monitor, if applicable.
(viii) Instructions manual.
(ix) Drawing showing details of pressure relief valve.
(x) Volt-time characteristics of surge arrestors.
(xi) Detailed dimensional drawing of porcelain housing/Silicon polymeric i.e. internal
diameter, external diameter, thickness, height, profile, creepage distance, dry arcing
distance etc.
GUARANTEED TECHNICAL PARTICULARS OF 11KV 10KA LIGHTNING (SURGE) ARRESTOR
Sl. Bidder's
Description Unit
No. Offer
A
1 Name & Address of the manufacture
2 Type & Model
3 Catalogue Number
4 Standards with which it complies
B
1 Frequency Hz
2 Rate Voltage KV ms
3 Continuous operating voltage KV ms
4 Nominal discharge current, 8/20 µs KA ms
5 Long duration discharge class Class
6 Temporary over voltage capability
a) 1 second KV Peak
b) 10 Seconds KV Peak
c) 3 Hours KV Peak
Release voltage KV ms
7 Maximum lightening impulse residual voltage with:
a) 1.5 KA, 8/20 μs KV Peak
b) 5.0 KA, 8/20 μs wave form KV Peak
c) 10 KA, 8/20 μs wave form KV Peak
8 Steep current impulse residual voltage, 1/20 μs KV Peak
9 Long duration impulse withstand capability:
a) Peak KA As per Type Test KA ms
b) Virtual Duration μs
10 High current impulse withstand value, 4/10 μs KA Peak
11 Leakage current through arrester:
100% of rated voltage mA
60% of rated voltage mA
40% of rated voltage mA
22% of rated voltage mA
12 Partial Discharge Level pC
13 Energy Absorption capacity KJ/KV
C
1 Impulse withstand voltage (1.2/50 μs wave-peak) KV Peak
One minute power frequency withstand voltage
2 KV Peak
(Wet)
Power frequency voltage vs Time curve (Attach
3
Curve)
4 Creepage distance mm
5 Type of materials & Grade of Housing Porcelain
D
1 Type of materials & Grade of MOV Discs
2 Filling medium
3 Pressure relief class
4 Type of mounting arrangement
5 Type of moisture sealing
6 Cantilever strength of lightning arrester KN/m
7 Colour of Insulator
8 Height of Lightning arrestor mm
9 Weight of lightning arrester in service Kg
E
1 Type of materials & grade of terminals
2 Type of terminal corrosion protection
3 Range of conductor type & size it suits mm²
4 Bi-metallic or not Yes/No
5 Material of earth terminal
6 Size of earth terminal mm²
F
Recommended minimum clearances of arresters,
1 mm
centre to centre
Recommended minimum clearances from centre to
2 mm
arrester to nearest earthed object
3 Clearance from live parts to earth mm
G
1 Method to be adopted for seal leakage test
H
1 Surface preparation
2 Rust inhibition
3 Galvanization - Weight deposited Kg/m²
4 Treatment of fasteners