Micromotion 2700 Transmitter
Micromotion 2700 Transmitter
Micromotion 2700 Transmitter
Chapter 2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Assigning function block channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Configuring the integrator function block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5 Configuring pressure compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5.1 Pressure compensation values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5.2 Enabling pressure compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5.3 Configuring a pressure source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.6 Configuring temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.6.1 Enabling external temperature compensation . . . . . . . . . . . . . . . . . . . . . 12
2.6.2 Configuring a temperature source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7 Zeroing the flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.1 Preparing for the zeroing procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.7.2 Zero procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.7.3 Restoring zero values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 3 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.2 Characterization, Smart Meter Verification, meter validation, and calibration . . . . . . 21
3.2.1 Characterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.2.2 Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.3 Meter validation and meter factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.4 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2.5 Comparison and recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3 Performing a characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3.1 Characterization parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3.2 How to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4 Performing Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4.1 Preparing for the Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . 27
3.4.2 Running the Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4.3 Reading and interpreting Smart Meter Verification test results . . . . . . . . 33
3.4.4 Setting up automatic or remote execution of the
Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.5 Performing meter validation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 4 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.2 Configuration map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.3 Configuring standard volume flow measurement for gas . . . . . . . . . . . . . . . . . . . . . 52
4.3.1 Configuring gas density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.4 Changing the measurement units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.5 Creating special measurement units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.6 Configuring the petroleum measurement application (API feature) . . . . . . . . . . . . . 64
4.6.1 About the petroleum measurement application . . . . . . . . . . . . . . . . . . . . 64
4.6.2 Configuration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4.7 Configuring the concentration measurement application . . . . . . . . . . . . . . . . . . . . . 69
4.7.1 About the concentration measurement application . . . . . . . . . . . . . . . . . 69
4.7.2 Configuration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4.8 Changing the linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4.9 Changing the output scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4.10 Changing process alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4.10.1 Alarm values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4.10.2 Alarm priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.10.3 Alarm hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.11 Configuring status alarm severity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.12 Changing the damping values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4.12.1 Damping and volume measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
4.13 Changing slug flow limits and duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
4.14 Configuring cutoffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4.14.1 Cutoffs and volume flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
4.15 Changing the flow direction parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
4.16 Changing device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
4.17 Configuring sensor parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4.18 Changing the display functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
4.18.1 Enabling and disabling display functions . . . . . . . . . . . . . . . . . . . . . . . . . 87
4.18.2 Changing the scroll rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
4.18.3 Changing the update period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
4.18.4 Changing the display password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4.18.5 Changing the display variables and precision . . . . . . . . . . . . . . . . . . . . . 95
4.18.6 Changing the display language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
4.19 Configuring PlantWeb Alert timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
4.20 Configuring write-protect mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
4.21 Enabling LD Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
1.1 Overview
This chapter provides an orientation to the use of this manual, and includes a configuration worksheet.
This manual describes the procedures required to start, configure, use, maintain, and troubleshoot
Micro Motion® Model 2700 transmitters with FOUNDATION™ fieldbus.
1.2 Safety
Startup
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
Calibration
Transmitter firmware View > Installed Options > DEVICE INFO block > OFF-LINE MAINT > VER
Software Revision Revision Numbers >
2000 Series SW Rev
Core processor Not available DEVICE INFO block > OFF-LINE MAINT > VER
firmware Revision Numbers >
Core Processor SW Rev
ProLink II Help > About ProLink II Not applicable Not applicable
Communicator device Not applicable See Section E.2 Not applicable
description
Configuration
Topic Document
Installing the sensor Sensor installation manual
Installing the transmitter Micro Motion Model 1700 and Model 2700 Transmitters:
Installation Manual
FOUNDATION fieldbus function block reference FOUNDATION Fieldbus Blocks
documentation (available via the Rosemount web site at
http://www.rosemount.com)
Startup
Calibration
Configuration
REQ. - P.O.
BY CHK'D APPR.
3 Location
4 Calibrated Flow Range, Units
5 Max Velocity, Units
6 Min. Flow Max. Flow Operating Flow
7 Min. Pressure Max. Pressure Operating Press.
FLUID
8 Min. Temp. Max. Temp. Operating Temp.
9 Spec. Gravity or Density (max)
10 Velocity (max)
11
12 Pipe Material
13 PIPE Pipe Size Upstream/Dnstream
14 DATA Schedule
15 Special Insulator
16 Process Connections
17 Approval
18 Wetted Parts
Mass Flow Accuracy @ Max
19
Flow Rate (% of rate)
20 Density Accuracy @ All Rates
21 Pressure Drop @ Max Flow
FLOW
22 Calibration Type
SENSOR
23 Cal. Rate Cal. Units
OPERATING 24 Custom Calibration Points
CONDITIONS 25 Dens. for Vol.to Mass Conv.
26 Spec. Unit Text Totalizer Text
27 Base Flow Unit Base Time Unit
28 Conversion Factor
29 Warning
30 Instrument Tag Number
31 Transmitter Style
32 Mass Unit Volume Unit
33 Dens. Unit Temp. Unit
34 Display
35 Safety
36 Conduit Adapters
37 Type Electronic microprocessor based
38 TRANS. Input Signal FOUNDATION fieldbus™ H1 ISA.50.02 IEC-61158
39 Baud Rate 31.25 Kbps
40 Physical Media Twisted pair wires, (H1) compliant
41 Power Supply 9–32 VDC, bus powered, 4 wires
42 Power Cons. on FF Bus 11.5 milliamps maximum
43 Input Voltage Model 2700: 18–100 VDC or 85–265 VAC
44 Device Class Link master ITK 4.60 minimum
45 Min. VCRs 20
46 Electrical Class ❑ FISCO ❑ Other
47 Device Function Block Fixed Type FOUNDATION fieldbus™ FF-891/FF-892 compliant
48 Resource Block (RB)
49 Transducer Block (TB)
50 Analog Input Block (AI) Exec. time 50 ms
51 Analog Output Block (AO) Exec. time 50 ms
FUNCTION
52 PID Block (PID) Exec. time 60 ms
BLOCKS
53 Integrator Block (INT) Exec. time 40 ms
54 Instantiable Function Blocks Model 2700: Not supported
❑ Measurement TB ❑ Calibration TB
55 Transducer Block Type ❑ Local Display TB ❑ Device Information TB
❑ Enhanced Density TB ❑ API TB
DIAGNOSTICS 56 ❑ Diagnostic TB
NOTES:
1 – The vendor must provide the Device Description according with the firmware revision of the field device. FOR REFERENCE ONLY. NOT FOR
2 – It is mandatory to provide the Capability Format File for each type of device. ISSUE.
3 – All devices must show FOUNDATION™ logo.
Chapter 2
2.1 Overview
This chapter describes the procedures you should perform the first time you start up the flowmeter.
You do not need to use these procedures every time you cycle power to the flowmeter.
The procedures in this section will enable you to:
• Apply power to the flowmeter (Section 2.2)
• Check the analog input (AI) function blocks channels and change if required (Section 2.3)
Startup
• Check the integrator (INT) function block mode and configure if required (Section 2.4)
• Configure pressure compensation (optional) (Section 2.5)
• Configure temperature compensation (optional) (Section 2.6)
• Zero the flowmeter (optional) (Section 2.7)
Note: All procedures provided in this chapter assume that you have established communication with
the transmitter and that you are complying with all applicable safety requirements. See Appendices E
and F.
Calibration
WARNING
Operating the flowmeter without covers in place creates electrical hazards
that can cause death, injury, or property damage.
Make sure safety barrier partition and covers for the field-wiring, circuit board
compartments, electronics module, and housing are in place before applying
power to the transmitter.
Turn on the electrical power at the power supply. The flowmeter will automatically perform
diagnostic routines. If the transmitter has a display, the status LED will turn green and begin to flash
when the transmitter has finished its startup diagnostics.
Note: If this is the initial startup, or if power has been off long enough to allow components to reach
Configuration
ambient temperature, the flowmeter is ready to receive process fluid approximately one minute after
power-up. However, it may take up to ten minutes for the electronics in the flowmeter to reach thermal
equilibrium. During this warm-up period, you may observe minor measurement instability or
inaccuracy.
If you need to change the channel configuration you must use a fieldbus host. Refer to Figure 2-1 and
Table 2-2.
AI Channel or AO Channel
AI or AO
Transducer Scale: Units Index
AI Channel – Set to the transducer block channel this block should report.
AO Channel – Set to the transducer block channel this block should report.
Transducer Scale: Units Index – Change the units (if necessary).
Output Scale: Units Index – If you change the units for Transducer Scale: Units Index, then change
the units here as well to match.
Startup
(2)
13 CM Specific Gravity Analog Input
(2)
14 CM Standard Volume Flow Analog Input
15(2) CM Net Mass Flow Analog Input
16(2) CM Net Volume Flow Analog Input
(2)
17 CM Concentration Analog Input
(2)
18 CM Baume Analog Input
(3)
19 Gas Standard Volume Analog Input
20 External temperature Analog Output
(1) Channels 7 through 11 are not selectable unless the petroleum measurement application is enabled.
(2) Channels 12 through 18 are not selectable unless the concentration measurement application is enabled.
(3) Channel 19 is selectable only if gas standard volume measurement is enabled (see Section 4.3).
Calibration
2.4 Configuring the integrator function block
The behavior of the INT function block can be configured in two ways:
• Mode – The INT function block mode can be configured as:
- Standard, which provides standard fieldbus INT function block behavior
- Any of the values in Table 2-3, which cause the INT function block to pass through the
specified totalizer value from the MEASUREMENT transducer block
• Resetting – The INT function block can be configured for manual or automatic resetting when
a setpoint is reached.
You can only configure the INT function block using a fieldbus host (Figures 2-2 and 2-3).
Configuration
MEASUREMENT
Integrator FB Configuration
Integrator FB Configuration – Set to the desired INT function block mode (see Table 2-3).
Total Setpoint
Startup
changes.
Not all sensors and applications require pressure compensation. Contact Micro Motion Customer
Service before you configure pressure compensation.
Configuring pressure compensation requires three steps:
1. Determining pressure compensation values (Section 2.5.1)
2. Enabling pressure compensation (Section 2.5.2)
3. Selecting a pressure source (Section 2.5.3)
Calibration
•
data sheet for your sensor for this value. You will need to reverse the sign of the flow factor.
For example, if the flow factor in the product data sheet is –0.001% per psi, the pressure
compensation flow factor would be +0.001% per psi.
• Density factor — The density factor is the change in fluid density, in g/cm3 per psi. Consult the
product data sheet for your sensor for this value. You will need to reverse the sign of the
density factor. For example, if the density factor in the product data sheet is –0.00004 g/cm3
per psi, the pressure compensation flow factor would be +0.00004 g/cm3 per psi.
• Flow calibration pressure — The pressure at which the flowmeter was calibrated. Refer to the
calibration document shipped with your sensor. If the data is unavailable, use 20 psi (1.4 bar).
You can enable pressure compensation with a fieldbus host (Figure 2-4) or ProLink II (Figure 2-5).
You will need the values of the three pressure compensation values from Section 2.5.1.
Pressure Comp
Flow Factor
CALIBRATION
Density Factor
Flowcal Pressure
Enabling Configuring
Enter values:
Apply • Flow factor in the Flow factor box
• Density factor in the Dens factor
box
• Flow calibration pressure in the Cal
pressure box
Apply
Note: If you configure a fixed pressure value, ensure that it is accurate. If you configure polling for
pressure, ensure that the external pressure measurement device is accurate and reliable.
AO Channel
Startup
Input
Output
Calibration
Section 2.5.2).
CALIBRATION
Pressure: Value
Apply
CALIBRATION
Startup
• Analog Output function block — This option allows you to poll for temperature data from an
external temperature source.
• Fixed temperature value — This option uses a known, constant temperature value.
Note: If you configure a fixed temperature value, ensure that it is accurate. If you configure polling
for temperature, ensure that the external temperature measurement device is accurate and reliable.
Note: You can configure the AO block for pressure compensation or temperature compensation, but
not both at the same time.
Calibration
Figure 2-11 External temperature source – Fieldbus host
AO Channel
Output
Process Value Scale: Units Index – Change the units to match the
temperature sensing device.
CALIBRATION
ProLink >
Configuration
Enter value in External
Temperature box
Temperature tab
Apply
CAUTION
If fluid is flowing through the sensor, the sensor zero calibration may be
inaccurate, resulting in inaccurate process measurement.
To improve the sensor zero calibration and measurement accuracy, ensure that
process flow through the sensor has completely stopped.
Startup
2.7.2 Zero procedure
You can perform the zero procedure with a fieldbus host (Figure 2-14), the display (Figure 2-15), or
ProLink II (Figure 2-16). If the zero procedure fails, see Section 6.5 for troubleshooting information.
Calibration
Configuration
CALIBRATION
Zero Calibration
Next
Set flow to zero
Calibration in progress
Next
Next
Next
Scroll
OFF-LINE MAINT
Select
Scroll
ZERO
Select
Startup
CAL ZERO
Select
ZERO/YES?
Select
………………….
Calibration
Troubleshoot
Select
ZERO
• See Section 6.5 for
troubleshooting.
Scroll
EXIT
Configuration
ProLink >
Calibration >
Zero Calibration
Calibration in Progress
LED turns red
Calibration
Red Green
Failure LED
Done
Troubleshoot
ProLink >
Calibration >
Startup
Zero Calibration
Calibration
Configuration
Scroll
OFF-LINE MAINT
Select
Scroll
ZERO
Select
Select
Scroll
Scroll
RESTORE ZERO
Scroll Select
Yes No
Scroll
Scroll Select Select
3.1 Overview
This chapter describes the following procedures:
• Characterization (Section 3.3)
• Smart Meter Verification (Section 3.4)
• Meter validation and adjusting meter factors (Section 3.5)
• Density calibration (Section 3.6)
Startup
• Temperature calibration (Section 3.7)
Note: All procedures provided in this chapter assume that you have established communication with
the transmitter and that you are complying with all applicable safety requirements. See Appendices E
and F.
Calibration
• Meter validation—confirming performance by comparing the sensor’s measurements to a
primary standard
• Calibration—establishing the relationship between a process variable (flow, density, or
temperature) and the signal produced by the sensor
Meter validation, characterization, and calibration are available on all Model 2700 transmitters. Smart
Meter Verification is available only if the Smart Meter Verification option was ordered with the
transmitter.
These four procedures are discussed and compared in Sections 3.2.1 through 3.2.5. Before performing
any of these procedures, review these sections to ensure that you will be performing the appropriate
procedure for your purposes.
3.2.1 Characterization
Configuration
Characterizing the flowmeter adjusts the transmitter to compensate for the unique traits of the sensor
it is paired with. Characterization parameters (sometimes called “calibration factors”) describe the
sensor’s sensitivity to flow, density, and temperature.
If the transmitter and the sensor were ordered together as a Coriolis flowmeter, then the flowmeter has
already been characterized. Under some circumstances (typically when pairing a sensor and
transmitter together for the first time), you may need to re-enter characterization data. If you are
unsure about whether you should characterize your flowmeter, contact Micro Motion Customer
Service.
3.2.4 Calibration
The flowmeter measures process variables based on fixed points of reference. Calibration adjusts
those points of reference. Three types of calibration can be performed:
• Zero (see Section 2.7)
• Density calibration
• Temperature calibration
Density and temperature calibration require two data points (low and high) and an external
measurement for each. Calibration produces a change in the offset and/or the slope of the line that
represents the relationship between process density and the reported density value, or the relationship
between process temperature and the reported temperature value.
Note: For density or temperature calibration to be useful, the external measurements must be
accurate.
Flowmeters are calibrated at the factory, and normally do not need to be calibrated in the field.
Calibrate the flowmeter only if you must do so to meet regulatory requirements. Contact Micro
Motion before calibrating your flowmeter.
Note: Micro Motion recommends using meter validation and meter factors, rather than calibration, to
prove the meter against a regulatory standard or to correct measurement error.
Startup
• External measurement requirements
- Smart Meter Verification does not require external measurements.
- Zero calibration does not require external measurements.
- Density calibration, temperature calibration, and meter validation require external
measurements. For good results, the external measurement must be highly accurate.
• Measurement adjustment
- Smart Meter Verification is an indicator of sensor condition, but does not change
flowmeter internal measurement in any way.
- Meter validation does not change flowmeter internal measurement in any way. If you
decide to adjust a meter factor as a result of a meter validation procedure, only the reported
measurement is changed—the base measurement is not changed. You can always reverse
the change by returning the meter factor to its previous value.
Calibration
- Calibration changes the transmitter’s interpretation of process data, and accordingly
changes the base measurement. If you perform a zero calibration, you can return to the
factory zero (or, if using ProLink II, the previous zero). However, if you perform a density
calibration or a temperature calibration, you cannot return to the previous calibration
factors unless you have manually recorded them.
Micro Motion recommends obtaining the Smart Meter Verification transmitter option and performing
Smart Meter Verification on a regular basis.
The characterization parameters are provided on the sensor tag. The format of the sensor tag varies
depending on your sensor’s date of purchase. See Figures 3-1 and 3-2 for illustrations of newer and
older sensor tags.
Sensor type
Characterization data Fieldbus parameter T-Series Other
K1 K1 ✓ ✓(1)
K2 K2 ✓ ✓(1)
FD FD ✓ ✓(1)
D1 D1 ✓ ✓(1)
D2 D2 ✓ ✓(1)
Temp coeff (DT)(2) Temperature Coefficient ✓ ✓(1)
Flow cal Flow Calibration Factor ✓(3)
FCF Flow Calibration Factor ✓
FT Temperature Coefficient for Flow ✓
FTG T-Series Flow TG Coeff ✓
FFQ T-Series Flow FQ Coeff ✓
DTG T-Series Density TG Coeff ✓
DFQ1 T-Series Density FQ Coeff 1 ✓
DFQ2 T-Series Density FQ Coeff 2 ✓
(1) See the section entitled “Density calibration factors.”
(2) On some sensor tags, shown as TC.
(3) See the section entitled “Flow calibration values.”
19.0005.13
12502142824.44
0.0010 12502.000 19.0005.13
0.9980 14282.000 12500142864.44
4.44000 310
Startup
line-condition density of the low-density calibration fluid. Micro Motion uses air.
• For D2, enter the Dens B or D2 value from the calibration certificate. This value is the
line-condition density of the high-density calibration fluid. Micro Motion uses water.
If your sensor tag does not show a K1 or K2 value:
• For K1, enter the first 5 digits of the density calibration factor. In the sample tag in Figure 3-1,
this value is shown as 12500.
• For K2, enter the second 5 digits of the density calibration factor. In the sample tag in
Figure 3-1, this value is shown as 14286.
If your sensor does not show an FD value, contact Micro Motion customer service.
If your sensor tag does not show a DT or TC value, enter the last 3 digits of the density calibration
factor. In the sample tag in Figure 3-1, this value is shown as 4.44.
Calibration
Flow calibration values
Two separate values are used to describe flow calibration: a 6-character FCF value and a 4-character
FT value. Both values contain decimal points. During characterization, these are entered as a single
10-character string that includes two decimal points. In ProLink II, this value is called the Flowcal
parameter; in the Communicator, it is called the FCF for T-Series sensors, and Flowcal for other
sensors.
To obtain the required value:
• For older T-Series sensors, concatenate the FCF value and the FT value from the sensor tag, as
shown below.
Flow FCF X.XXXX FT X.XX
Configuration
• For newer T-Series sensors, the 10-character string is represented on the sensor tag as the FCF
value. The value should be entered exactly as shown, including the decimal points. No
concatenation is required.
• For all other sensors, the 10-character string is represented on the sensor tag as the Flow Cal
value. The value should be entered exactly as shown, including the decimal points. No
concatenation is required.
DEVICE
INFORMATION
Sensor Type Code – Set to Curved Tube or Straight Tube to match sensor type.
CALIBRATION
* – Set each of the fieldbus parameters shown in Table 3-1 to the value of the associated sensor data
printed on the sensor’s calibration tag.
ProLink >
Configuration
Device
• Sensor type
Straight Curved
Sensor type?
tube tube
Flow Flow
Density Density
T Series Config
Transmitter configuration
Startup
Smart Meter Verification is not affected by any parameters configured for flow, density, or
temperature. It is not necessary to change the transmitter configuration.
Calibration
Configuration
DIAGNOSTIC
Start On-Line Smart – Method parameter that initiates the procedure below.
Meter Verification
Step 1
Set output state (optional)
Step 2
Manual abort (optional)
Start/abort procedure
Step 3
Check current algorithm state
Step 4
Running? Yes (>0)
Read percent complete
No (=0)
Step 8 Step 5
Check abort code Check algorithm abort state
Able to Step 6
No (<16) Yes (=16)
complete? Check inlet stiffness
Yes (=0)
Step 7
Check outlet stiffness
Yes (=0)
CAUTION PASS
Startup
6 Check inlet stiffness Block: Diagnostic
Index: 61
• 0: Within uncertainty limit
• 1: Outside uncertainty limit
7 Check outlet stiffness Block: Diagnostic
Index: 62
• 0: Within uncertainty limit
• 1: Outside uncertainty limit
8 Read abort code Block: Diagnostic
Index: 58
Codes: See Table 3-3
(1) Setting Index 85 (Start On-Line Smart Meter Verification) to 1 is equivalent to setting Index 54 to 6.
Calibration
Configuration
Tools >
Meter Verification >
Run Meter Verification
Verify configuration
View Previous Results
parameters
Next
Next
Configuration Changed
No Yes
or Zero Changed?
---------------------
Rerun
Yes No
test? Abort Next Back
Next
Report
Finish
Scroll
Select
RUN VERFY Scroll RESULTS READ Scroll SCHEDULE VERFY Scroll EXIT
Startup
Calibration
Configuration
RUN VERFY
Select
Select
Select
Scroll Select
Fail
Scroll
Scroll Select
To Runcount RERUN/YES?
(see Results Read)
Yes No
Startup
These actions might include removing the meter from service and physically inspecting
the tubes. At minimum, you should perform a flow validation and a density calibration.
• Abort – A problem occurred with the Smart Meter Verification test (e.g., process instability).
Abort codes are listed in Table 3-3, and suggested actions are provided for each code.
Calibration
8 Unstable flow Review the suggestions for stable flow in Section 3.4.1
and rerun the test.
13 No factory reference data for Smart Contact Micro Motion customer service and provide the
Meter Verification test performed on air abort code.
14 No factory reference data for Smart Contact Micro Motion customer service and provide the
Meter Verification test performed on abort code.
water
15 No configuration data for Smart Meter Contact Micro Motion customer service and provide the
Verification abort code.
Other General abort Repeat the test. If the test aborts again, contact
Micro Motion customer service and provide the abort
code.
Configuration
Synchronizing x out of y
Please wait
Note: If you request an action while synchronization is in process, ProLink II displays a message
asking whether or not you want to complete synchronization. If you choose No, the ProLink II
database may not include the latest test results from the transmitter.
Test results are available at the end of each test, in the following forms:
• A test result chart (see Figure 3-9).
• A test report that includes the descriptive information for the current test, the test result chart,
and background information about Smart Meter Verification. You can export this report to an
HTML file or print it to the default printer.
Note: To view the chart and the report for previous tests without running a test, click View Previous
Test Results and Print Report from the first Smart Meter Verification panel. See Figure 3-9. Test
reports are available only for tests initiated from ProLink II.
Startup
Calibration
The test result chart shows the results for all tests in the ProLink II database, plotted against the
specification uncertainty limit. The inlet stiffness and the outlet stiffness are plotted separately. This
helps to distinguish between local and uniform changes to the sensor tubes.
This chart supports trend analysis, which can be helpful in detecting meter problems before they
become severe.
Configuration
Select
RUNCOUNT x
Select Scroll
Fail
Startup
PASS CAUTION Abort Type
xx L STF% xx L STF%
Select Select
xx R STF% xx R STF%
Select Select
Calibration
xx SEC
RESULTS MORE?
Select Scroll
3.4.4 Setting up automatic or remote execution of the Smart Meter Verification test
There are two ways to execute a Smart Meter Verification test automatically:
• Set up a one-time automatic execution
• Set up a recurring execution
To set up a one-time automatic execution, set up a recurring execution, view the number of hours until
the next scheduled test, or delete a schedule:
- With ProLink II, choose Tools > Meter Verification > Schedule Meter Verification.
- With the display, see Figures 3-6 and 3-11.
- With a fieldbus host, Smart Meter Verification scheduling resides in the Diagnostic
transducer block. See Figure 3-12.
Note the following:
• If you are setting up a one-time automatic execution, specify the start time as a number of
hours from the present time. For example, if the present time is 2:00 and you specify 3.5 hours,
the test will be initiated at 5:30.
• If you are setting up a recurring execution, specify the number of hours to elapse between
executions. The first test will be initiated when the specified number of hours has elapsed, and
testing will be repeated at the same interval until the schedule is deleted. For example, if the
present time is 2:00 and you specify 2 hours, the first test will be initiated at 4:00, the next at
6:00, and so on.
• If you delete the schedule, both the one-time execution and the recurring execution settings are
deleted.
Select
Scroll
Scroll Select
Schedule deleted
HOURS LEFT
Startup
Scroll Select
xx HOURS
Select
Select Select
Scroll Select
Calibration
xx HOURS xx HOURS
SAVE/YES? SAVE/YES?
No Yes No Yes
Time Until First Run – Number of hours to wait before starting Smart Meter Verification
Time Between – Number of hours to wait between each Smart Meter Verification test, after the
Each Run first test is completed
Time Until Next Run – Number of hours until the next Smart Meter Verification test begins
ExternalStandard
NewMeterFactor = ConfiguredMeterFactor × -----------------------------------------------------------------------------------
ActualTransmitterMeasurement
Valid values for meter factors range from 0.8 to 1.2. If the calculated meter factor exceeds these
limits, contact Micro Motion customer service.
Example The flowmeter is installed and proved for the first time. The flowmeter
mass measurement is 250.27 lb; the reference device measurement is
250 lb. A mass flow meter factor is determined as follows:
250
MassFlowMeterFactor = 1 × ------------------ = 0.9989
250.27
One year later, the flowmeter is proved again. The flowmeter mass
measurement is 250.07 lb; the reference device measurement is
250.25 lb. A new mass flow meter factor is determined as follows:
250.25
MassFlowMeterFactor = 0.9989 × ------------------ = 0.9996
250.07
You can adjust meter factors with a fieldbus host (Figure 3-13), ProLink II (Figure 3-14), or the
display (Figure 3-15).
Mass Meter Factor – Set to the meter factor for mass flow.
Volume Meter Factor – Set to the meter factor for volume flow.
Density Meter Factor – Set to the meter factor for density.
Startup
ProLink >
Configuration
Flow tab
Set values:
• Mass Factor
• Dens Factor
• Vol Factor
Calibration
Apply
Configuration
Scroll
Select Scroll
Scroll
FACTOR VOL
CONFG
Scroll
Select
Select
Scroll Scroll
MTR F
EXIT
CAUTION
Startup
For T-Series sensors, the D1 calibration must be performed on air and the
D2 calibration must be performed on water.
For D3 density calibration, the D3 fluid must meet the following requirements:
• Minimum density of 0.6 g/cm3
• Minimum difference of 0.1 g/cm3 between the density of the D3 fluid and the density of water.
The density of the D3 fluid may be either greater or less than the density of water.
For D4 density calibration, the D4 fluid must meet the following requirements:
• Minimum density of 0.6 g/cm3
• Minimum difference of 0.1 g/cm3 between the density of the D4 fluid and the density of the D3
fluid. The density of the D4 fluid must be greater than the density of the D3 fluid.
Calibration
• Minimum difference of 0.1 g/cm3 between the density of the D4 fluid and the density of water.
The density of the D4 fluid may be either greater or less than the density of water
CALIBRATION
Low Density Calibration
Low Density Calibration – Method parameter that initiates the D1 procedure below.
High Density Calibration Method parameter that initiates the D2 procedure below.
D1 calibration D2 calibration
Next Next
Next Next
• If calibration fails, see
Section 6.5 for
troubleshooting
information. Enter the density of Enter the density of
the calibration fluid the calibration fluid
Next Next
Finish
Do Cal Do Cal
Startup
Calibration in Progress Calibration in Progress
light turns red light turns red
Close Close
Done
Calibration
Configuration
Figure 3-18 D3 (or D3 and D4) calibration (T-Series only) – Fieldbus host
CALIBRATION
D3 Density Calibration
D4 Density Calibration
D3 calibration D4 calibration
Next Next
Next Next
Finish Finish
Do Cal Do Cal
Startup
Calibration in Progress Calibration in Progress
light turns red light turns red
Close
Close
Done Done
Calibration
Section 6.5 for troubleshooting
information.
Configuration
CALIBRATION
Temp Low Calibration
Temp Low Calibration – Method parameter that initiates the low-temperature procedure below.
Temp High Calibration Method parameter that initiates the high-temperature procedure below.
Next Next
Next Next
Finish
Startup
Do Cal Do Cal
Close Close
Done
Calibration
• If calibration fails, see
Section 6.5 for troubleshooting
information.
Configuration
4.1 Overview
This chapter describes how to change the operating settings of the transmitter.
Note: All procedures provided in this chapter assume that you have established communication with
the transmitter and that you are complying with all applicable safety requirements. See Appendices E
and F.
Startup
4.2 Configuration map
Use the map in Table 4-1 to guide you through a complete or partial configuration of the transmitter.
Method
Topic Fieldbus host ProLink II Display Section
Gas standard volume ✓ ✓ 4.3
Measurement units ✓ ✓ ✓ 4.4
Special measurement units ✓ ✓ 4.5
Petroleum measurement application ✓ ✓ 4.6
Concentration measurement application ✓ ✓ 4.7
Calibration
Linearization ✓ 4.8
Output scale ✓ 4.9
Process alarms ✓ 4.10
Alarm severity ✓ ✓ 4.11
Damping ✓ ✓ 4.12
Slug flow ✓ ✓ 4.13
Cutoffs ✓ ✓ 4.14
Flow direction ✓ ✓ 4.15
Device settings ✓ ✓ 4.16
Sensor parameters ✓ ✓ 4.17
Display functionality ✓ ✓ ✓ 4.18
Configuration
MEASUREMENT
Enable Gas Standard Volume – Set to Enable to set volume flow to use gas standard volume. Set to
Disable to use liquid volume flow.
Flow tab
Apply
Startup
4.3.1 Configuring gas density
You have two choices for entering the standard density of the gas you are going to measure (i.e., the
density of the gas at reference conditions):
• If you know the standard density, you can enter that value into the transmitter. For optimal
standard volume measurement accuracy, be sure the standard density you enter is correct and
fluid composition is stable. You can enter the gas density with a fieldbus host (Figure 4-3) or
ProLink II (Figure 4-4).
• If you do not know the standard density of the gas, and you are using ProLink II, you can use
the Gas Wizard (Figure 4-5). The Gas Wizard can calculate the standard density of the gas that
you are measuring.
Calibration
Figure 4-3 Gas density – Fieldbus host
MEASUREMENT
Gas Density
Gas Density – Set to the standard density of the gas you are going to measure.
Configuration
ProLink >
Configuration
Flow tab
Apply
ProLink >
Configuration
Next
Startup
display (Figure 4-8). Refer to Tables 4-2 through 4-7 for complete lists of the units you can set for
each process variable.
Note: When the transmitter is configured for liquid volume flow, only liquid volume units are
available (Table 4-3). When the transmitter is configured for gas volume flow, only gas volume units
are available (Table 4-4).
Note: Changing the measurement units for a process variable automatically changes the associated
totalizer units as well. For example, setting the mass flow units to g/s will automatically set the mass
totalizer unit to grams.
Calibration
AI
AO
Configuration
Process Value Scale: Units Index – Set to the desired measurement units.
ProLink >
Configuration
Select unit from Dens Select unit from Vol Select unit from Mass Select unit from
Units list Flow Units(1) list Flow Units list Temp Units list
(1) If volume flow type is configured to gas standard volume, this list will appear as Std gas vol flow units.
Note: You must also change the units in the appropriate AI block. Failure to do so will cause
the AI block to get a configuration error.
Scroll
OFF-LINE MAINT
MASS
Select Scroll
Scroll
VOL(1)
CONFG
Scroll
Select Select
Startup
DENS
UNITS
Scroll
TEMP
Scroll
PRESS
(1) If volume flow type is configured to gas standard volume, this list will appear as GSV.
Calibration
Note: You must also change the units in the appropriate AI block. Failure to do so will cause the
AI block to get a configuration error.
Startup
Fieldbus host ProLink II Display Unit description
3
Nm /s Nm3/sec NM3/S Normal cubic meters per second
3
Nm /m Nm3/min NM3/MN Normal cubic meters per minute
3
Nm /h Nm3/hr NM3/H Normal cubic meters per hour
3
Nm /d Nm3/day NM3/D Normal cubic meters per day
NL/s NLPS NLPS Normal liter per second
NL/m NLPM NLPM Normal liter per minute
NL/h NLPH NLPH Normal liter per hour
NL/d NLPD NLPD Normal liter per day
SCFM SCFM SCFM Standard cubic feet per minute
SCFH SCFH SCFH Standard cubic feet per hour
Calibration
3
Sm /s Sm3/S SM3/S Standard cubic meters per second
3
Sm /m Sm3/min SM3/MN Standard cubic meters per minute
3
Sm /h Sm3/hr SM3/H Standard cubic meters per hour
3
Sm /d Sm3/day SM3/D Standard cubic meters per day
SL/s SLPS SLPS Standard liter per second
SL/m SLPM SLPM Standard liter per minute
SL/h SLPH SLPH Standard liter per hour
SL/d SLPD SLPD Standard liter per day
Density unit
Configuration
Density unit
Fieldbus host ProLink II Display Unit description
kg/m3 kg/m3 KG/M3 Kilograms per cubic meter
lb/gal lbs/Usgal LB/GAL Pounds per U.S. gallon
lb/ft3 lbs/ft3 LB/CUF Pounds per cubic foot
3
lb/in lbs/in3 LB/CUI Pounds per cubic inch
3
STon/yd sT/yd3 ST/CUY Short ton per cubic yard
degAPI degAPI D API Degrees API
SGU SGU SGU Specific gravity unit (not temperature
corrected)
Temperature unit
Fieldbus host ProLink II Display Unit description
°C °C °C Degrees Celsius
°F °F °F Degrees Fahrenheit
°R °R °R Degrees Rankine
K °K °K Kelvin
Although pressure units are listed in Table 4-7, the transmitter does not measure pressure. These units
are for configuring external pressure compensation. Refer to Section 2.5.
Pressure unit
Fieldbus host ProLink II Display Unit description
ftH20 (68°F) Ft Water @ 68°F FTH2O Feet water @ 68 °F
inH2O (4°C) In Water @ 4°C INW4C Inches water @ 4 °C
inH20 (68°F) In Water @ 68°F INH2O Inches water @ 68 °F
mmH2O (4°C) mm Water @ 4°C mmW4C Millimeters water @ 4 °C
mmH20 (68°F) mm Water @ 68°F mmH2O Millimeters water @ 68 °F
inHg (0°C) In Mercury @ 0°C INHG Inches mercury @ 0 °C
mmHg (0°C) mm Mercury @ 0°C mmHG Millimeters mercury @ 0 °C
psi PSI PSI Pounds per square inch
bar bar BAR Bar
mbar millibar mBAR Millibar
g/cm2 g/cm2 G/SCM Grams per square centimeter
kg/cm2 kg/cm2 KG/SCM Kilograms per square centimeter
Pa pascals PA Pascals
MPa megapascals MPA Megapascals
Startup
FOUNDATION Fieldbus Blocks manual, available from the Rosemount web site
(www.rosemount.com), for information about creating special units using this method.
The MEASUREMENT transducer block supports one special unit for mass flow, one special
measurement unit for liquid volume flow, and one special unit for gas volume flow. Special
measurement units consist of:
• Base unit — A combination of:
- Base mass or base volume unit — A standard measurement unit that the transmitter
already recognizes (e.g., kg, m3)
- Base time unit — A unit of time that the transmitter already recognizes
(e.g., seconds, days)
• Conversion factor — The number by which the base unit will be divided to convert to the
special unit
Calibration
• Special unit — A non-standard volume-flow or mass-flow unit of measure that you want to be
reported by the transmitter.
The terms above are related by the following formulae:
x [ Base units ]
Conversion factor = ------------------------------------------
y [ Special units ]
3. Name the new special mass-flow or volume-flow measurement unit and its corresponding
totalizer measurement unit:
a. Special volume-flow measurement unit name: pint/min
b. Volume totalizer measurement unit name: pints
Note: Special measurement unit names can be up to 8 characters long, but only the first 5 characters
appear on the display.
Special units can be created with a fieldbus host (Figures 4-9, 4-10, and 4-11) or with ProLink II
(Figure 4-12).
Figure 4-10 Special units for liquid volume flow – Fieldbus host
Startup
Vol flow special units str – Set to the name of the special unit. Unit names can be up to 8
characters in length (although only the first 5 are displayed).
Volume Tot/Inv Special Unit Str – Set to the name of the special totalizer unit. Unit names can be up
to 8 characters in length (although only the first 5 are displayed).
Figure 4-11 Special units for gas volume flow – Fieldbus host
Calibration
Std Gas Vol Flow Special Units Text
Std Gas Vol Flow Special Units Base – Set to a gas volume unit.
Std Gas Vol Flow Special Units Time – Set to a unit of time.
Std Gas Vol Flow Special Units Factor – Set to the conversion factor. When this parameter equals 1, the
transmitter will use normal gas volume units. When this
parameter is not equal to 1, the transmitter will use special gas
volume units.
Std Gas Vol Flow Special Units Text – Set to the name of the special unit. Unit names can be up to 8
characters in length (although only the first 5 are displayed).
Std Gas Vol Total Special Units Text – Set to the name of the special totalizer unit. Unit names can be up
to 8 characters in length (although only the first 5 are displayed).
Configuration
ProLink >
Configuration (1) These labels are slightly different when volume flow
is configured for gas standard volume: Base Gas Vol
Unit, Base Gas Vol Time, Gas Vol Flow Conv Fact,
Gas Vol Flow Text, and Gas Vol Total Text.
Special Units tab
Set the base, time, and Set the base, time, and
conversion factor: conversion factor:
• Base Mass Unit • Base Vol Unit(1)
• Base Mass Time • Base Vol Time(1)
• Mass Flow Conv Fact • Vol Flow Conv Fact(1)
Apply
Startup
API reference tables
Reference tables are organized by reference temperature, CTL derivation method, liquid type, and
density unit. The table selected here controls all the remaining options.
• Reference temperature:
- If you specify a 5x, 6x, 23x, or 24x table, the default reference temperature is 60 °F, and
cannot be changed.
- If you specify a 53x or 54x table, the default reference temperature is 15 °C. However, you
can change the reference temperature, as recommended in some locations (for example, to
14.0 or 14.5 °C).
• CTL derivation method:
- If you specify an odd-numbered table (5, 23, or 53), CTL will be derived using method 1
described above.
Calibration
- If you specify an even-numbered table (6, 24, or 54), CTL will be derived using method 2
described above.
• The letters A, B, C, or D that are used to terminate table names define the type of liquid that the
table is designed for:
- A tables are used with generalized crude and JP4 applications.
- B tables are used with generalized products.
- C tables are used with liquids with a constant base density or known thermal expansion
coefficient.
- D tables are used with lubricating oils.
• Different tables use different density units:
- Degrees API
Configuration
Variable Description
Table type Specifies the table that will be used for reference temperature and reference density unit. Select
the table that matches your requirements. See API reference tables.
User defined TEC(1) Thermal expansion coefficient. Enter the value to be used in CTL calculation.
(2)
Temperature units Read-only. Displays the unit used for reference temperature in the reference table.
Density units Read-only. Displays the unit used for reference density in the reference table.
Reference Read-only unless Table Type is set to 53x or 54x. If configurable:
temperature • Specify the reference temperature to be used in CTL calculation.
• Enter reference temperature in °C.
(1) Configurable if Table Type is set to 6C, 24C, or 54C.
(2) In most cases, the temperature unit used by the API reference table should also be the temperature unit configured for the transmitter
to use in general processing. To configure the temperature unit, see Section 4.4.
API
Startup
ProLink >
Configuration
Calibration
Apply
API
API Reference Temp – Set to the desired temperature (in the currently-configured temperature units).
ProLink >
Configuration
Apply
API
Apply
Startup
4.7 Configuring the concentration measurement application
Micro Motion sensors provide direct measurements of density, but not of concentration. The
concentration measurement application calculates concentration measurement process variables, such
as concentration or density at reference temperature, from density process data, appropriately
corrected for temperature.
Note: For a detailed description of the concentration measurement application, see the manual
entitled Micro Motion Enhanced Density Application: Theory, Configuration, and Use.
Note: The concentration measurement application requires liquid volume measurement units. If you
plan to use concentration measurement process variables, ensure that liquid volume flow
measurement is specified. See Section 4.3.
Calibration
4.7.1 About the concentration measurement application
The concentration measurement calculation requires a concentration measurement curve, which
specifies the relationship between temperature, concentration, and density for the process fluid being
measured. Micro Motion supplies a set of six standard concentration measurement curves (see
Table 4-10). If none of these curves is appropriate for your process fluid, you can configure a custom
curve or purchase a custom curve from Micro Motion.
The derived variable, specified during configuration, controls the type of concentration measurement
that will be produced. Each derived variable allows the calculation of a subset of concentration
measurement process variables (see Table 4-11). The available concentration measurement process
variables can be used in process control, just as mass flow rate, volume flow rate, and other process
variables are used. For example, an event can be defined on a concentration measurement process
variable.
Configuration
• For all standard curves, the derived variable is Mass Conc (Dens).
• For custom curves, the derived variable may be any of the variables listed in Table 4-11.
The transmitter can hold up to six curves at any given time, but only one curve can be active (used for
measurement) at a time. All curves that are in transmitter memory must use the same derived variable.
Startup
density
The mass, volume, weight, or number of
moles of solute or of material in
suspension in proportion to the total
solution, derived from reference density
Conc (SG) ✓ ✓ ✓ ✓
Concentration derived from specific gravity
The mass, volume, weight, or number of
moles of solute or of material in
suspension in proportion to the total
solution, derived from specific gravity
Calibration
Configuration
Linearization Type
Startup
Note: Although it is possible to set the Output Scale: Units Index parameter to a value different from
the Transducer Scale: Units Index parameter, this has no effect on output. The Output Scale: Units
Index parameter is primarily useful as a label.
The output scale is a function of the AI blocks, and is only used when linearization is set to Indirect
(see Section 4.8). If you choose to use output scaling, note that it has no effect on the process values
found in the MEASUREMENT transducer block. This results in the following behaviors:
• ProLink II and the display use the process values in the MEASUREMENT transducer block.
Therefore, the output of a scaled AI block may differ from the value reported by other
communication tools.
• Slug flow and flow cutoffs are configured in the MEASUREMENT block. Therefore, output
scaling has no effect on the behavior of the transmitter with regard to slug flow or flow cutoffs.
Calibration
Example
To create a special unit for pints per second, the AI block assigned to channel 4 (volume) can be
configured as follows:
• Transducer Scale: Units Index = gal/s
• Transducer Scale: EU at 0% = 0
• Transducer Scale: EU at 100% = 100
• Output Scale: Units Index = pints
• Output Scale: EU at 0% = 0
• Output Scale: EU at 100% = 800
• Linearization Type = Indirect
Configuration
You can change the output scale only with a fieldbus host (Figure 4-20).
AI
Output Scale: EU at 0%
Output Scale: EU at 0% – Set to process variable value at 0% of scale, in the configured units.
Output Scale: EU at 100% – Set to process variable value at 100% of scale, in the configured units.
High-high alarm
Process variable
High alarm
Low alarm
Low-low alarm
You can change the alarm values only with a fieldbus host (Figure 4-22).
High Limit
AI
Low Limit
High High Limit – Set to the value for the high-high alarm.
High Limit – Set to the value for the high alarm.
Low Limit – Set to the value for the low alarm.
Low Low Limit – Set to the value for the low-low alarm.
Startup
Each process alarm is assigned an alarm priority. A process alarm priority is a number from 0 to 15.
Higher numbers indicate higher alarm priorities. These values are for fieldbus network management
and do not affect transmitter operation.
You can change the process alarm priority values only with a fieldbus host (Figure 4-23).
High Priority
AI
Low Priority
Calibration
Low Low Priority
High High Priority – Set to the priority for the high-high alarm.
High Priority – Set to the priority for the high alarm.
Low Priority – Set to the priority for the low alarm.
Low Low Priority – Set to the priority for the low-low alarm.
HIGH ALARM
Process variable
Alarm created
Hysteresis value
LOW ALARM
You can change the alarm hysteresis value only with a fieldbus host (Figure 4-25).
AI
Alarm Hysteresis
Alarm Hysteresis – Set to the desired percentage of output scale, where scale is defined by either the
Transducer Scale or Output Scale values.
Default
Startup
Alarm code Description severity Configurable
A001 (E)EPROM Checksum Error (CP) Fault No
A002 RAM Error (CP) Fault No
A003 Sensor Failure Fault Yes
A004 Temperature Sensor Failure Fault No
A005 Input Overrange Fault Yes
A006 Not Configured Fault Yes
A008 Density Overrange Fault Yes
A009 Transmitter Initializing/warming Up Ignore Yes
A010 Calibration Failure Fault No
A011 Cal Fail - Too Low Fault Yes
A012 Cal Fail - Too High Fault Yes
Calibration
A013 Cal Fail - Too Noisy Fault Yes
A014 Transmitter Failed Fault No
A016 Line RTD Temperature Out-of-Range Fault Yes
A017 Meter RTD Temperature Out-of-Range Fault Yes
A018 (E)EPROM Checksum Error Fault No
A019 RAM or ROM Test Error Fault No
A020 Calibration Factors Unentered Fault Yes
A021 Incorrect Sensor Type (K1) Fault No
A025 Protected Boot Sector Fault (CP) Fault No
A026 Sensor/Transmitter Communication Error Fault No
A028 Core Processor Write Failure Fault No
Configuration
Default
Alarm code Description severity Configurable
(2)
A104 Calibration-in-Progress Informational Yes
A105 Slug Flow Informational Yes
A106 AI/AO Simulation Active Informational No
A107 Power Reset Occurred Informational Yes
A116 API: Temperature Outside Standard Range Informational Yes
A117 API: Density Outside Standard Range Informational Yes
A120 CM: Unable to Fit Curve Data Informational No
A121 CM: Extrapolation Alarm Informational Yes
A131 Smart Meter Verification In Progress Informational Yes
A132 Simulation Mode Active Informational Yes
(1) The severity changes automatically based on the configured output state of a Smart Meter Verification test. If the output state is set
to Last Measured Value (LMV), the alarm severity will be Informational. If the output state is set to Fault, the alarm severity will be
Fault.
(2) Can be set to either Informational or Ignore, but cannot be set to Fault.
Alarm severity can be configured with a fieldbus host (Figure 4-26) or ProLink II (Figure 4-27). Some
configurable alarms can be set to either Informational or Ignore, but not to Fault.
DIAGNOSTICS
Alarm Index
Alarm Severity
Alarm Index – Select an alarm for which you want to modify the severity. (You must write to the
transmitter before the Alarm Severity parameter becomes available.)
Alarm Severity – Select a severity for the alarm indicated by the Alarm Index parameter.
Alarm tab
Apply
Startup
4.12 Changing the damping values
A damping value is a period of time, in seconds, over which the process variable value will change to
reflect 63% of the change in the actual process. Damping helps the transmitter smooth out small,
rapid measurement fluctuations.
• A high damping value makes the output appear to be smoother because the output must change
slowly.
• A low damping value makes the output appear to be more erratic because the output changes
more quickly.
Damping can be configured for flow, density, and temperature using a fieldbus host (Figure 4-28) or
ProLink II (Figure 4-29).
Note: There is also a damping parameter in each AI block called Process Value Filter Time. In order
Calibration
to avoid having two (potentially conflicting) damping values, you should set damping values only in
the MEASUREMENT transducer block. The Process Value Filter Time parameter for each AI block
should be set to 0.
When you specify a new damping value, it is automatically rounded down to the nearest valid
damping value. Valid damping values are listed in Table 4-13.
Note: For gas applications, Micro Motion recommends a minimum flow damping value of 2.56.
Before setting the damping values, review Section 4.12.1 for information on how the damping values
affect other transmitter measurements.
Flow Damping
MEASUREMENT
Density Damping
Temperature Damping
Flow Damping – Set to the desired damping value for mass flow and volume flow measurement.
Density Damping – Set to the desired damping value for density measurement.
Temperature Damping – Set to the desired damping value for temperature measurement.
ProLink >
Configuration
Startup
for slug flow duration is 0.0 seconds. The valid range is 0.0–60.0 seconds.
Note: Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility
that slug flow conditions will be detected by the transmitter.
Note: The slug flow limits must be entered in g/cm3, even if another unit has been configured for
density. Slug flow duration must be entered in seconds.
Slug flow can be configured using a fieldbus host (Figure 4-30) or ProLink II (Figure 4-31).
Calibration
DIAGNOSTICS
Slug High Limit
Slug Duration
Slug Low Limit – Set to the density below which a condition of slug flow will exist.
Slug High Limit – Set to the density above which a condition of slug flow will exist.
Slug Duration – Set to the number of seconds to wait for a slug flow condition to clear before a slug flow
alarm is posted.
Configuration
ProLink >
Configuration
Density tab
Apply
Cutoffs can be configured with a fieldbus host (Figure 4-32) or ProLink II (Figure 4-33).
Density Cutoff
Mass Flow Cutoff – Set to the desired mass flow cutoff value.
Vol Flow Cutoff – Set to the desired (liquid) volume flow cutoff value.
Std Gas Vol Flow Cutoff – Set to the desired (gas) volume flow cutoff value.
Density Cutoff – Set to the desired density cutoff value.
Startup
ProLink >
Configuration
Calibration
Apply Apply
(1) When volume flow is configured for gas standard volume, this box is labeled
Std gas vol flow cutoff.
• The mass flow cutoff is not applied to the volume flow calculation. Even if the mass flow
drops below the cutoff, and therefore the mass flow indicators go to zero, the volume flow rate
will be calculated from the actual mass flow process variable.
If gas standard volume flow is enabled, neither the mass flow cutoff nor the density cutoff is applied
to the volume flow calculation.
You can change the flow direction parameter with a fieldbus host (Figure 4-34) or ProLink II
(Figure 4-35).
MEASUREMENT
Flow Direction
Flow Direction – Set to the desired value (refer to Flow direction value in Table 4-15).
Flow tab
Apply
Startup
4.16 Changing device settings
The device settings are used to describe the flowmeter components. The following information can be
entered:
• Tag
• Message
• Date
These parameters are for user convenience and network management. They are not used in transmitter
processing, and are not required.
You can set the tag with a fieldbus host by using the host’s tagging features. You can set the tag,
message, and date with ProLink II (Figure 4-36).
Calibration
CAUTION
Setting the software tag via ProLink II will cause the transmitter to restart.
Configuration
ProLink >
Configuration
Enter information in
the boxes provided
Apply
If you are entering a date, use the left and right arrows at the top of the calendar shown in ProLink II
to select the year and month, then click on a date.
Sensor Material
DEVICE
INFORMATION Liner Material
Flange
Sensor tab
Select the flange from
the Flange list
Enter the sensor
serial number in the
Sensor s/n box
Apply
Startup
4.18 Changing the display functionality
You can restrict the display functionality or change the variables that are shown on the display.
Calibration
Display Fieldbus
function parameter Display code Enabled Disabled
(1)
Totalizer reset Totalizer reset TOTAL RESET Resetting mass and volume Resetting mass and
totalizers is permitted. volume totalizers is not
possible.
Totalizer start/stop Totalizer start/stop TOTAL STOP Operator can start and stop Operator cannot start or
totalizers from the display. stop totalizers.
Auto scroll(2) Auto scroll AUTO SCRLL Display automatically Operator must Scroll to
scrolls through each view process variables.
process variable.
Offline menu Offline menu DISPLAY OFFLN Operator has access to the No access to the offline
offline menu. menu.
Alarm menu Alarm menu DISPLAY ALARM Operator has access to No access to the alarm
alarm menu. menu.
ACK all alarms ACK all alarms DISPLAY ACK Operator can acknowledge Alarms must be
Configuration
Display Fieldbus
function parameter Display code Enabled Disabled
Display backlight Display backlight DISPLAY BKLT Display backlight is ON. Display backlight is OFF.
Status LED Status LED Not accessible via Status LED will blink when Status LED will not blink.
blinking blinking the display there are unacknowledged
alarms active.
Alarm password(3) Alarm password CODE ALARM Password required for Alarm menu accessible
alarms menu. without a password.
(1) If the petroleum measurement application is installed on your transmitter, the display password is always required to start, stop, or
reset a totalizer, even if neither password is enabled. If the petroleum measurement application is not installed, the display password
is never required for these functions, even if one of the display passwords is enabled.
(2) If enabled, you may want to configure Scroll Rate. See Section 4.18.2.
(3) If enabled, the display password must also be configured. See Section 4.18.4.
LOCAL DISPLAY
* – Refer to the fieldbus parameters in Table 4-16. Each parameter can be set to Enabled or Disabled.
Display tab
Enable or disable
functions using the
checkboxes
Apply
Startup
Calibration
Configuration
Scroll
TOTALS RESET CODE OFFLN(3)
OFF-LINE MAINT
Scroll Scroll
Select
TOTALS STOP CODE ALARM(3)
Scroll
Scroll Scroll
CONFG
Scroll Scroll
UNITS
Select Scroll
DISPLAY
DISPLAY ACK
Scroll
Scroll
AUTO SCRLL(2)
(1) If you disable access to the offline menu, the offline menu will disappear as soon as you exit. To re-enable access, you must
use a fieldbus host or ProLink II.
(2) If Auto Scroll is enabled, a Scroll Rate screen is displayed immediately after the Auto Scroll screen.
(3) If either password is enabled, a Change Code screen will be displayed so that the password can be configured.
Display Scroll Rate – Set to the number of seconds each variable should be displayed.
ProLink >
Configuration
Startup
Display tab
Enter number of
seconds in Auto
Scroll Rate box
Apply
Calibration
4.18.3 Changing the update period
The update period (or display rate) parameter controls how often the display is refreshed with current
data. The default is 200 milliseconds. The range is 100 to 10000 milliseconds. The update period
value applies to all displayed process variables.
You can change the update period with a fieldbus host (Figure 4-44), ProLink II (Figure 4-45), or the
display (Figure 4-46).
Configuration
LOCAL DISPLAY
Update rate
Update Rate – Set to the number of milliseconds between updates to the display (100 to 10000,
default is 200).
ProLink >
Configuration
Display tab
Enter a value
between 100 and
10000 milliseconds in
the Update Period
box
Apply
Scroll
OFF-LINE MAINT
Select
CONFG Scroll
Select
DISPLAY RATE
UNITS
Select
Startup
Select
Scroll
Enter a value between
100 and 10000
DISPLAY milliseconds
Calibration
password before you can configure the password (see Section 4.18.1).
Note: If the petroleum measurement application is installed on your transmitter, the display password
is always required to start, stop, or reset a totalizer, even if neither password is enabled. If the
petroleum measurement application is not installed, the display password is never required for these
functions, even if one of the passwords is enabled.
You can change the password with a fieldbus host (Figure 4-47), Prolink II (Figure 4-48), or the
display (Figure 4-49).
LOCAL DISPLAY
Display Offline Password – Enter a 4-digit password between 0000 and 9999.
ProLink >
Configuration
Display tab
Enter a 4-digit
password in the
Offline Password
box
Apply
Scroll
Select
OFF-LINE MAINT
Scroll
Select
UNITS
Select
Scroll
Startup
Display variable Process variable
Display variable 1 Mass flow
Display variable 2 Volume flow
Display variable 3 Density
Display variable 4 Mass flow
Display variable 5 Volume flow
Display variable 6 Mass totalizer
Display variable 7 Mass flow
Display variable 8 Temperature
Display variable 9 Volume flow
Display variable 10 Volume totalizer
Display variable 11 Density
Calibration
Display variable 12 Temperature
Display variable 13 None
Display variable 14 None
Display variable 15 None
You can change the display variables and precision with a fieldbus host (Figure 4-50) or ProLink II
(Figure 4-51).
Configuration
LOCAL DISPLAY
Display Variable 1 through Display Variable 15
Number of Decimals
ProLink >
Configuration
Display tab
Apply
Language
ProLink >
Configuration
Startup
Display tab
Select a language
from the Display
Language list
Apply
Calibration
Configuration
Select
DISPLAY LANG
Scroll
Select
CONFG
ENG
Select
Scroll
UNITS
FREN
Scroll Select
Scroll
DISPLAY
GER
Scroll
SPAN
Alert Timeout
ProLink >
Configuration
Startup
Device (Fieldbus) tab
Apply
Calibration
4.20 Configuring write-protect mode
When the transmitter is in write-protect mode, the configuration data stored in the transmitter and
core processor cannot be changed until write-protect mode is disabled.
You can configure write-protect mode with a fieldbus host (Figure 4-57), ProLink II (Figure 4-58), or
the display (Figure 4-58).
RESOURCE
Configuration
Write Lock
Write Lock – Set to Locked to write-protect the transmitter. Set to Not Locked to allow configuration.
ProLink >
Configuration
Apply
Scroll
OFF-LINE MAINT
Select
Scroll
CONFIG LOCK
Select
ENABL/DISABL
CAUTION
If you send the transmitter to a calibration facility to perform a water
calibration, either during startup or any time thereafter, LD Optimization
must be disabled. When you have completed the calibration, re-enable LD
Optimization.
Startup
Calibration
Configuration
Scroll
OFF-LINE MAINT
Select
Scroll
CONFG
Select
FACTOR LD
Scroll
MTR F LD OPT
Operation
5.1 Overview
This section describes how to use the transmitter in everyday operation. The procedures in this section
will enable you to use a fieldbus host, the display, or ProLink II to:
• View process variables (Section 5.2)
• Use simulation mode (Section 5.3)
Troubleshooting
• Respond to alarms (Section 5.4)
• Use the totalizers and inventories (Section 5.5)
Note: All procedures provided in this chapter assume that you have established communication with
the transmitter and that you are complying with all applicable safety requirements. See Appendices E
and F.
PlantWeb Alerts
The transmitter has four fieldbus AI function blocks. Each AI function block reports the value of one
process variable, the associated units of measure, and a status value that indicates measurement
quality. For more information on the function blocks, refer to the FOUNDATION Fieldbus Blocks
manual, available at the Rosemount web site (www.rosemount.com).
To view a process variable, select the AI function block that measures that variable, and read the Out
parameter. The output of AI blocks may be influenced by output scaling (see Section 4.9).
You can also view each process variable by reading the MEASUREMENT transducer block
parameter for each process variable. Table 5-1 lists the process variables that correspond to each
MEASUREMENT transducer block parameter.
TB Reference
Operation
With ProLink II software
To view API process variables with ProLink II software, choose ProLink > API Process Variables.
Troubleshooting
You can also view all of the CM variables by examining their parameters in the CONCENTRATION
MEASUREMENT transducer block. Table 5-2 lists the CM process variables that correspond to each
CONCENTRATION MEASUREMENT transducer block parameter.
CONCENTRATION MEASUREMENT
CM process variable transducer block parameter
Density at reference CM Density At Ref: Value
Density (fixed specific gravity units) CM Density SG: Value
Standard volume flow rate CM Std Volume Flow: Value
Net mass flow rate CM Net Mass Flow: Value
Concentration CM Concentration: Value
PlantWeb Alerts
With the display
Refer to Appendix G for a detailed explanation of how to use the display to view process variables.
The process variables shown by the display may need to be configured. Refer to Section 4.18.5.
DEVICE
INFORMATION
Simulate Mode
ProLink >
Configuration
Select Simulate
Mode
Apply
Operation
ProLink >
Configuration Select a wave form
for mass flow,
density, and
temperature from the
Sensor Simulation tab Wave Form lists
Triangular or
Select Enable Fixed wave
sine wave
Simulation Mode
Troubleshooting
Fixed Value box Period box
Apply
PlantWeb Alerts
The transmitter broadcasts alarms when a process variable exceeds its defined limits or the transmitter
detects a fault condition. For instructions regarding all the possible alarms, see Section 6.9.
that AI block.
• The DIAGNOSTICS transducer block contains four parameters named Alarm Status 1
through Alarm Status 4. Each of these parameters has a short list of alarm bits (see
Appendix B).
Status LED
Alarms in the alarm queue are arranged according to priority. To view specific alarms in the queue,
see Figure 5-5.
Operation
for 4 seconds
SEE ALARM
Select
Select Scroll
Troubleshooting
EXIT
Select Scroll
Active/
unacknowledged
alarms?
Yes No
PlantWeb Alerts
Scroll Select Scroll
ACK EXIT
Yes No
Select Scroll
TB Reference
With ProLink II
ProLink II provides two ways to view alarm information:
• Choose ProLink > Status. This window shows the current status of all possible alarms,
independent of configured alarm severity. The alarms are divided into three categories:
Critical, Informational, and Operational. To view the indicators in a category, click on the
associated tab. A tab is red if one or more status indicators in that category is active. On each
tab, currently active alarms are shown by red indicators.
• Choose ProLink > Alarm Log. This window lists all active alarms, and all inactive but
unacknowledged Fault and Informational alarms. (The transmitter automatically filters out
Ignore alarms.) A green indicator means “inactive but unacknowledged” and a red indicator
means “active.” Alarms are organized into two categories: High Priority and Low Priority.
Note: The location of alarms in the Status and Alarm Log windows are not affected by the configured
alarm severity (see Section 4.11). Alarms in the Status window are predefined as Critical,
Informational, or Operational. Alarms in the Alarm Log window are predefined as High Priority or
Low Priority.
Operation
levels. Within each category:
• All active alarms are listed with a red status indicator.
• All alarms that are “cleared but unacknowledged” are listed with a green status indicator.
2. For each alarm that you want to acknowledge, select the ACK checkbox.
Troubleshooting
5.5.1 Viewing the totalizers and inventories
You can view the current value of the mass totalizer, volume totalizer, mass inventory, and volume
inventory with a fieldbus host, the display, or ProLink II.
PlantWeb Alerts
Totalizer/inventory Transducer block Parameter name
Mass totalizer MEASUREMENT Mass Total: Value
Volume totalizer MEASUREMENT Volume Total: Value
Mass inventory MEASUREMENT Mass Inventory: Value
Volume Inventory MEASUREMENT Volume Inventory: Value
(1)
Reference volume gas total MEASUREMENT Gas Volume Total: Value
(1)
Reference volume gas inventory MEASUREMENT Gas Volume Inventory: Value
Temperature corrected volume total API API Corr Volume Total: Value
Temperature corrected volume inventory API API Corr Vol Inventory: Value
(2)
Standard volume total CONCENTRATION CM Std Volume Total: Value
MEASUREMENT
Standard volume inventory(2) CONCENTRATION CM Std Vol Inventory: Value
TB Reference
MEASUREMENT
Net mass total(2) CONCENTRATION CM Net Mass Total: Value
MEASUREMENT
Operation
Current value
Process variable
Units of measure
Troubleshooting
With ProLink II
To view the current value of the totalizers and inventories with ProLink II, choose:
• ProLink > Process Variables to view standard totalizers and inventories
• ProLink > API Process Variables to view API totalizers and inventories
• ProLink > CM Process Variables to view CM totalizers and inventories
PlantWeb Alerts
Table 5-6 Totalizer and inventory control methods
(2) This function is available only if the corresponding totalizer is configured as a display variable (see Section 4.18.5).
(3) If enabled in the ProLink II preferences.
Select this
To accomplish this transducer block And use this method parameter
Stop all totalizers and inventories MEASUREMENT Stop All Totals
Start all totalizers and inventories MEASUREMENT Start Totals
Reset mass totalizer MEASUREMENT Reset Mass Total
Reset volume totalizer MEASUREMENT Reset Volume Total
Reset gas volume totalizer MEASUREMENT Reset Gas Standard Volume Total
Reset API totalizer API Reset API Volume Total
Reset CM standard volume totalizer CONCENTRATION Reset CM Std Volume Total
MEASUREMENT
Reset CM net mass totalizer CONCENTRATION Reset CM Net Mass Total
MEASUREMENT
Reset CM net volume totalizer CONCENTRATION Reset CM Net Volume Total
MEASUREMENT
Reset mass inventory MEASUREMENT Reset Mass Inventory
Reset volume inventory MEASUREMENT Reset Volume Inventory
Reset gas volume inventory MEASUREMENT Reset Gas Standard Volume Inventory
Reset API inventory API Reset API Inventory
Reset CM standard volume inventory CONCENTRATION Reset CM Volume Inventory
MEASUREMENT
Reset CM net mass inventory CONCENTRATION Reset CM Net Mass Inventory
MEASUREMENT
Reset CM net volume inventory CONCENTRATION Reset CM Net Volume Inventory
MEASUREMENT
Simultaneously reset all totalizers MEASUREMENT Reset Totalizers
Simultaneously reset all inventories MEASUREMENT Reset Inventories
With Prolink II
To control CM totalizers and inventories, choose ProLink > CM Totalizer Control. To control all
other totalizer and inventory functions, choose ProLink > Totalizer Control.
To reset inventories using ProLink II, you must first enable this capability. To enable inventory reset
using ProLink II:
1. Choose View > Preferences.
2. Select the Enable Inventory Totals Reset checkbox.
3. Click Apply.
Operation
• Starting or stopping totalizers and inventories will start or stop all totalizers and inventories
simultaneously.
• Resetting totalizers resets only the totalizer for which the reset is selected. Inventories cannot
be reset using the display.
Process variable
display
Scroll
API total(1)(2)
Troubleshooting
Mass total display(1) Scroll Volume total display(1)
ED total(1)(2)
Select
Select Select
PlantWeb Alerts
Yes No Yes No
Operation
6.1 Overview
This section describes guidelines and procedures for troubleshooting the flowmeter. The information
in this section will enable you to:
• Categorize the problem
• Determine whether you are able to correct the problem
Troubleshooting
• Take corrective measures (if possible)
Note: All procedures provided in this chapter assume that you have established communication with
the transmitter and that you are complying with all applicable safety requirements. See Appendices E
and F.
Topic Section
Transmitter does not operate Section 6.3
PlantWeb Alerts
Transmitter does not communicate Section 6.4
Zero or calibration failure Section 6.5
AI block configuration error Section 6.6
Output problems Section 6.7
Lost static data alarm Section 6.8
Status alarms Section 6.9
Diagnosing wiring problems Section 6.10
Checking slug flow Section 6.11
Restoring a working configuration Section 6.12
Checking the test points Section 6.13
Checking the core processor Section 6.14
Checking sensor coils and RTD Section 6.15
TB Reference
Operation
or low.
• Flow rate
• Density
• Temperature
• Tube frequency
• Pickoff voltage
• Drive gain
For troubleshooting, check the process variables under both normal flow and tubes-full no-flow
conditions. Except for flow rate, you should see little or no change between flow and no-flow
conditions. If you see a significant difference, record the values and contact Micro Motion Customer
Service for assistance.
Troubleshooting
Unusual values for process variables may indicate a variety of different problems. Table 6-2 lists
several possible problems and remedies.
PlantWeb Alerts
no-flow conditions installations)
Open or leaking valve Check or correct the valve mechanism.
Bad sensor zero Rezero the flowmeter. See Section 2.7.
Bad flow calibration factor Verify characterization. See Section 6.7.4.
TB Reference
Operation
Inaccurate flow rate Bad flow calibration factor Verify characterization. See Section 6.7.4.
Inappropriate measurement unit Check measurement units using a
fieldbus host.
Bad sensor zero Rezero the flowmeter. See Section 2.7.
Bad density calibration factors Verify characterization. See Section 6.7.4.
Bad flowmeter grounding See Section 6.10.3.
Slug flow See Section 6.11.
Incorrectly set linearization See Section 6.7.7.
Wiring problem Verify all sensor-to-transmitter wiring and
ensure the wires are making good
contact. Refer to the installation manual.
Inaccurate density reading Problem with process fluid Use standard procedures to check quality
Troubleshooting
of process fluid.
Bad density calibration factors Verify characterization. See Section 6.7.4.
Wiring problem Verify all sensor-to-transmitter wiring and
ensure the wires are making good
contact. Refer to the installation manual.
Bad flowmeter grounding See Section 6.10.3.
Slug flow See Section 6.11.
Sensor cross-talk Check environment for sensor with similar
(±0.5 Hz) tube frequency.
Plugged flow tube Check drive gain and tube frequency.
Purge the flow tubes. Sensor may need to
be replaced.
Temperature reading significantly RTD failure Check for alarm conditions and follow
different from process temperature troubleshooting procedure for indicated
alarm.
PlantWeb Alerts
Incorrect calibration factors Perform temperature calibration. See
Section 3.7.
Verify characterization. See Section 6.7.4.
Temperature reading slightly different Incorrect calibration factors Perform temperature calibration. See
from process temperature Section 3.7.
Verify characterization. See Section 6.7.4.
Unusually high density reading Plugged flow tube Check drive gain and tube frequency.
Purge the flow tubes. Sensor may need to
be replaced.
Incorrect K2 value Verify characterization. See Section 6.7.4.
Unusually low density reading Slug flow See Section 6.11.
Incorrect K2 value Verify characterization. See Section 6.7.4.
Unusually high tube frequency Sensor erosion Contact Micro Motion Customer Service.
Unusually low tube frequency Plugged flow tube Check drive gain and tube frequency.
TB Reference
6.7.1 Damping
An incorrectly set damping value may make the transmitter’s output appear too sluggish or too jumpy.
Adjust the Flow Damping, Temperature Damping, and Density Damping parameters in the
MEASUREMENT transducer block to achieve the damping effect you want. See Section 4.12.
6.7.4 Characterization
Incorrect characterization parameters can cause the transmitter to send unexpected output values.
However, you should suspect an incorrect characterization only in specific circumstances (e.g.,
pairing the transmitter and sensor together for the first time, replacing the core processor). Refer to
Section 3.3 for more information about characterization.
6.7.5 Calibration
Improper calibration may cause the transmitter to send unexpected output values. However, you
should suspect an improper calibration only if the transmitter has been field-calibrated recently. Refer
to Section 3.2.4 for more information about calibration.
Note: Micro Motion recommends using meter factors, rather than calibration, to prove the meter
against a regulatory standard or to correct measurement error. Contact Micro Motion before
calibrating your flowmeter. Refer to Section 3.5 for information about meter factors.
6.7.7 Linearization
The linearization parameter in each AI function block can affect the transmitter’s output. Verify that
the Linearization Type parameter is set correctly. See Section 4.8.
Operation
rest of the function blocks to also be out of service.)
This behavior is normal for an EEPROM initialization. Cycle power to the transmitter to clear the
condition.
Alarm
code Description Possible remedies
Troubleshooting
A001 (E)EPROM Checksum Error (CP) Cycle power to the transmitter.
The flowmeter might need service. Contact Micro Motion
Customer Service.
A002 RAM Error (CP) Cycle power to the transmitter.
The flowmeter might need service. Contact Micro Motion
Customer Service.
A003 Sensor Failure Check the test points. See Section 6.13.
Check the sensor coils. See Section 6.15.
Check wiring to sensor. See Section 6.10.2.
Check for slug flow. See Section 6.11.
Check sensor tubes.
A004 Temperature Sensor Failure Check the test points. See Section 6.13.
PlantWeb Alerts
Check the sensor coils. See Section 6.15.
Check wiring to sensor. See Section 6.10.2.
Verify process temperature range is within limits for
sensor and transmitter.
Verify flowmeter characterization. See Section 6.7.4.
Contact Micro Motion Customer Service.
A005 Input Overrange Check the test points. See Section 6.13.
Check the sensor coils. See Section 6.15.
Verify process conditions.
Verify that transmitter is configured to use appropriate
measurement units. See Section 4.4.
Verify flowmeter characterization. See Section 6.7.4.
Re-zero the flowmeter. See Section 2.7.
TB Reference
A006 Not Configured Check the characterization. Specifically, verify the FCF
and K1 values. See Section 3.3.
Contact Micro Motion Customer Service.
Alarm
code Description Possible remedies
A008 Density Overrange Check the test points. See Section 6.13.
Check the sensor coils. See Section 6.15.
Check for air in flow tubes, tubes not filled, foreign
material in tubes, coating in tubes.
Verify characterization. See Section 6.7.4.
A009 Transmitter Initializing/warming Up Allow the transmitter to warm up. The error should
disappear from the status words once the transmitter is
ready for normal operation. If alarm does not clear, make
sure sensor is completely full or completely empty. Verify
sensor configuration and transmitter wiring to sensor
(refer to installation manual).
A010 Calibration Failure If alarm appears during zero, ensure there is no flow
through the sensor, then retry.
Cycle power to the flowmeter, then retry.
A011 Cal - Too Low Ensure there is no flow through sensor, then retry.
Cycle power to the flowmeter, then retry.
A012 Cal - Too High Ensure there is no flow through sensor, then retry.
Cycle power to the flowmeter, then retry.
A013 Cal - Too Noisy Remove or reduce sources of electromechanical noise,
then attempt the calibration or zero procedure again.
Possible sources of noise include:
• Mechanical pumps
• Electrical interference
• Vibration effects from nearby machinery
Cycle power to the flowmeter, then retry.
A014 Transmitter Failed Cycle power to the transmitter.
The transmitter might need service. Contact Micro Motion
Customer Service.
A016 Line RTD Temperature Out-of-Range Check the test points. See Section 6.13.
Check the sensor coils. See Section 6.15.
Check wiring to sensor. Refer to installation manual.
Make sure the appropriate sensor type is configured.
See Section 3.3.1.
Contact Micro Motion Customer Service.
A017 Meter RTD Temperature Out-of-Range Check the test points. See Section 6.13.
Check the sensor coils. See Section 6.15.
Contact Micro Motion Customer Service.
A018 (E)EPROM Checksum Error Cycle power to the transmitter.
The transmitter might need service. Contact Micro Motion
Customer Service.
A019 RAM or ROM Test Error Cycle power to the transmitter.
The transmitter might need service. Contact Micro Motion
Customer Service.
A020 Calibration Factors Unentered Check the characterization. Specifically, verify the FCF
value. See Section 3.3.
Alarm
Operation
code Description Possible remedies
A021 Incorrect Sensor Type (K1) Check the characterization. Specifically, verify the K1
value. See Section 3.3.
A025 Protected Boot Sector Fault (CP) Cycle power to the meter.
The transmitter might need service. Contact
Micro Motion Customer Service.
A026 Sensor/Transmitter Communication Error Check wiring between transmitter and core processor
(see Section 6.10.2). The wires may be swapped. After
swapping wires, cycle power to the flowmeter.
Check for noise in wiring or transmitter environment.
Check core processor LED. See Section 6.14.2.
Perform the core processor resistance test. See
Section 6.14.3.
Troubleshooting
A028 Core Processor Write Failure Cycle power to the meter.
The transmitter might need service. Contact
Micro Motion Customer Service.
A031 Low Power The core processor is not receiving enough power.
Check the power supply to the transmitter, and check
power wiring between the transmitter and the core
processor (4-wire remote installations only).
A032 Smart Meter Verification In Progress and Allow the procedure to complete.
Outputs Fixed
If desired, abort the procedure and restart with outputs
set to Continue Measurement.
A033 Sensor OK / Tubes Stopped by Process No signal from LPO or RPO, suggesting that sensor
tubes are not vibrating. Verify process. Check for air in
the flow tubes, tubes not filled, foreign material in tubes,
or coating in tubes.
A034 Smart Meter Verification Failed Rerun the test. If the test fails again, see Section 3.4.3.
PlantWeb Alerts
A035 Smart Meter Verification Aborted If desired, read the abort code. See Section 3.4.3, and
perform the appropriate action.
A102 Drive Overrange/Partially Full Tube Excessive or erratic drive gain. See Section 6.13.3.
Check the sensor coils. See Section 6.15.
A103 Data Loss Possible (Tot and Inv) Cycle power to the transmitter.
The transmitter might need service. Contact Micro Motion
Customer Service.
A104 Calibration-in-Progress Allow the flowmeter to complete calibration.
A105 Slug Flow Allow slug flow to clear from the process.
See Section 6.11.
A106 AI/AO Simulation Active Disable simulation mode. See Section 5.3.1.
A107 Power Reset Occurred No action is necessary.
A116 API: Temperature Outside Standard Range Contact Micro Motion Customer Service.
TB Reference
A117 API: Density Outside Standard Range Contact Micro Motion Customer Service.
A120 CM: Unable to Fit Curve Data Contact Micro Motion Customer Service.
A121 CM: Extrapolation Alarm Contact Micro Motion Customer Service.
Alarm
code Description Possible remedies
A131 Smart Meter Verification In Progress Allow the procedure to complete.
If desired, abort the procedure and restart with outputs
set to Fault.
A132 Simulation Mode Active (sensor) Disable sensor simulation mode. See Section 5.3.2.
WARNING
Removing the wiring compartment covers in explosive atmospheres while
the power is on can cause an explosion.
Operation
To check the sensor-to-transmitter wiring, verify that:
• The transmitter is connected to the sensor according to the wiring information provided in the
installation manual.
• The wires are making good contact with the terminals.
• For 4-wire connections, the mating connector between the core processor and the transmitter is
securely plugged into its socket.
If the wires are incorrectly connected:
1. Power down the transmitter.
2. Wait five minutes before opening the transmitter compartment if the transmitter is in a
hazardous area.
3. Correct the wiring.
Troubleshooting
4. Restore power to the transmitter.
PlantWeb Alerts
• Wires are making good contact with the terminals.
too high or too low. The high limit is set by default to 5.0 g/cm3, and the low limit is set by default to
0.0 g/cm3. Lowering the high limit or raising the low limit will cause the transmitter to be more
sensitive to changes in density. If you expect occasional slug flow in your process, you may need to
increase the slug flow duration. A longer slug flow duration will make the transmitter more tolerant of
slug flow.
ProLink >
Configuration
Restore Factory
Configuration
With ProLink II
To obtain the test points with ProLink II:
1. Choose ProLink > Diagnostic Information.
2. Write down the value you find in the Tube Frequency box, the Left Pickoff box, the Right
Pickoff box, and the Drive Gain box.
Operation
• If the drive gain is at 100%, refer to Section 6.13.3.
• If the drive gain is unstable, refer to Section 6.13.4.
• If the value for the left or right pickoff does not equal the appropriate value from Table 6-4,
based on the sensor flow tube frequency, refer to Section 6.13.5.
• If the values for the left and right pickoffs equal the appropriate values from Table 6-4, based
on the sensor flow tube frequency, contact Micro Motion Customer Service for assistance.
Troubleshooting
Model CMF400 with booster amplifier 3.4 mV peak to peak per Hz based on flow tube frequency
Model D, DL, and DT sensors 3.4 mV peak to peak per Hz based on flow tube frequency
Model F025, F050, and F100 sensors 3.4 mV peak to peak per Hz based on flow tube frequency
Model F200 sensors (compact case) 2.0 mV peak to peak per Hz based on flow tube frequency
Model F200 sensors (standard case) 3.4 mV peak to peak per Hz based on flow tube frequency
Model H025, H050, and H100 sensors 3.4 mV peak to peak per Hz based on flow tube frequency
Model H200 sensors 2.0 mV peak to peak per Hz based on flow tube frequency
Model R025, R050, or R100 sensor 3.4 mV peak to peak per Hz based on flow tube frequency
Model R200 sensor 2.0 mV peak to peak per Hz based on flow tube frequency
Micro Motion T-Series sensors 0.5 mV peak to peak per Hz based on flow tube frequency
(1) If your sensor model is not listed, contact Micro Motion Customer Support.
PlantWeb Alerts
6.13.3 Excessive drive gain
The causes and possible solutions of excessive drive gain are listed in Table 6-5.
Cause Solution
Excessive slug flow Eliminate slugs.
Change the sensor orientation.
Plugged flow tube Purge the flow tubes. Sensor may need to be replaced.
Cavitation or flashing Increase inlet or back pressure at the sensor.
If a pump is located upstream from the sensor,
increase the distance between the pump and sensor.
Drive board or module failure, cracked Contact Micro Motion Customer Service.
TB Reference
Cause Solution
Wrong K1 characterization constant for sensor Re-enter the K1 characterization constant. See
Section 3.3.
Polarity of pick-off reversed or polarity of Contact Micro Motion Customer Service.
drive reversed
Slug flow Verify flow tubes are completely filled with process
fluid, and that slug flow limits and duration are properly
configured. See Section 6.11.
Foreign material caught in flow tubes Purge flow tubes. Sensor may need to be replaced.
Cause Solution
Faulty wiring runs between the sensor and core Refer to the sensor manual and the transmitter
processor installation manual.
Process flow rate beyond the limits of the sensor Verify that the process flow rate is not out of range of
the sensor
Slug flow Verify the flow tubes are completely filled with process
fluid, and that slug flow limits and duration are properly
configured. See Section 6.11.
No tube vibration in sensor Check for plugging.
Ensure sensor is free to vibrate (no mechanical
binding).
Verify wiring.
Test coils at sensor. See Section 6.15.
Process beyond the limits of the sensor Verify that the process flow rate is not out of range of
the sensor.
Moisture in the sensor electronics Eliminate the moisture in the sensor electronics.
The sensor is damaged Contact Micro Motion Customer Service.
Operation
• You can check the core processor LED. The core processor has an LED that indicates different
flowmeter conditions.
• You can perform the core processor resistance test to check for a damaged core processor.
For both tests you will need to expose the core processor.
Troubleshooting
3. If you have an integral installation:
a. Loosen the four cap screws that fasten the transmitter to the base (Figure 6-2).
b. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked
position.
c. Gently lift the transmitter straight up, disengaging it from the cap screws. Do not
disconnect or damage the wires that connect the transmitter to the core processor.
4. If you have a 9-wire remote installation:
a. Remove the end-cap.
b. Inside the core processor housing, loosen the three screws that hold the core processor
mounting plate in place. Do not remove the screws. Rotate the mounting plate so that the
screws are in the unlocked position.
c. Holding the tab on the mounting plate, slowly lower the mounting plate so that the top of
PlantWeb Alerts
the core processor is visible. Do not disconnect or damage the wires that connect the core
processor to the transmitter.
Transmitter
Core processor
TB Reference
4 × cap screws
When reassembling components, take care not to pinch or stress the wires. Grease all O-rings.
Table 6-8 Standard core processor LED behavior, flowmeter conditions, and remedies
Table 6-9 Enhanced core processor LED behavior, meter conditions, and remedies
Table 6-9 Enhanced core processor LED behavior, meter conditions, and remedies (continued)
Operation
Solid red High severity alarm Check alarm status.
Flashing red (80% on, Tubes not full If alarm A105 (slug flow) is active, see Section 6.11.
20% off)
If alarm A033 (tubes not full) is active, verify process. Check
for air in the flow tubes, tubes not filled, foreign material in
tubes, or coating in tubes.
Flashing red (50% on, Electronics failed Contact Micro Motion.
50% off)
Flashing red (50% on, Sensor failed Contact Micro Motion.
50% off, skips every
4th)
OFF Core processor • Verify power supply wiring to core processor. Refer to
receiving less than 5 Appendix D for diagrams.
volts • If transmitter status LED is lit, transmitter is receiving power.
Check voltage across terminals 1 (VDC+) and 2 (VDC–) in
Troubleshooting
core processor. If reading is less than 1 VDC, verify power
supply wiring to core processor. Wires may be switched.
See Section 6.10.1. Otherwise, contact Micro Motion.
• If transmitter status LED is not lit, transmitter is not
receiving power. Check power supply. See Section 6.10.1.
If power supply is operational, internal transmitter, display,
or LED failure is possible. Contact Micro Motion.
Core processor Contact Micro Motion.
internal failure
PlantWeb Alerts
3. Measure the resistance across the following terminal pairs:
• The resistance across terminals 3 and 4 (RS-485A and RS-485B) should be 40–50 kohms.
• The resistance across terminals 2 and 3 (VDC– and RS-485A) should be 20–25 kohms.
• The resistance across terminals 2 and 4 (VDC– and RS-485B) should be 20–25 kohms.
If any of the resistance measurements are lower than specified, the core processor may not be able to
communicate with a transmitter or remote host. Contact Micro Motion Customer Service. TB Reference
6.15.1 9-wire remote or remote core processor with remote transmitter installation
If you have a 9-wire remote or a remote core processor with remote transmitter installation:
1. Power down the transmitter.
2. If the transmitter is in a hazardous area, wait five minutes.
3. Remove the end-cap from the core processor housing.
4. Unplug the terminal blocks from the terminal board.
5. Using a digital multimeter (DMM), check the circuits listed in Table 6-10 by placing the
DMM leads on the unplugged terminal blocks for each terminal pair.
6. There should be no open circuits (i.e., no infinite resistance readings). The LPO and RPO
readings should be the same or very close (±5 ohms). If there are any unusual readings, repeat
the coil measurement tests at the sensor junction box to eliminate the possibility of faulty
cable. The readings for each coil pair should match at both ends.
If the cable is faulty, replace the cable.
7. Leave the core processor terminal blocks disconnected. At the sensor, remove the lid of the
junction box and test each sensor terminal for a short to case by placing one DMM lead on the
terminal and the other lead on the sensor case. With the DMM set to its highest range, there
should be infinite resistance on each lead. If there is any resistance at all, there is a short to
case.
Operation
• Red against all other terminals except Brown
• Green against all other terminals except White
• White against all other terminals except Green
• Blue against all other terminals except Gray
• Gray against all other terminals except Blue
• Orange against all other terminals except Yellow and Violet
• Yellow against all other terminals except Orange and Violet
• Violet against all other terminals except Yellow and Orange
Note: D600 sensors and CMF400 sensors with booster amplifiers have different terminal pairs.
Contact Micro Motion Customer Service for assistance.
There should be infinite resistance for each pair. If there is any resistance at all, there is a short
Troubleshooting
between terminals.
9. See Table 6-11 for possible causes and solutions.
10. If the problem is not resolved, contact Micro Motion Customer Service.
Note: When reassembling the meter components, be sure to grease all O-rings.
Table 6-11 Sensor and cable short to case possible causes and remedies
PlantWeb Alerts
Faulty cable Replace cable.
Improper wire termination Verify wire terminations inside sensor junction box. See the
Micro Motion 9-Wire Flowmeter Cable Preparation and
Installation Guide or the sensor documentation.
b. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked
position.
c. Gently lift the transmitter straight up, disengaging it from the base.
Note: You have the option of disconnecting the 4-wire cable or leaving it connected.
5. If you have a standard core processor, loosen the captive screw (2,5 mm) at the center of the
core processor. Carefully remove the core processor from the sensor by grasping it and lifting
it straight up. Do not twist or rotate the core processor.
6. If you have an enhanced core processor, loosen the two captive screws (2,5 mm) that hold the
core processor in the housing. Gently lift the core processor out of the housing, then
disconnect the sensor cable from the feedthrough pins. Do not damage the feedthrough pins.
CAUTION
If the core processor (feedthrough) pins are bent, broken, or damaged in
any way, the core processor will not operate.
7. Use a digital multimeter (DMM) to check the resistance across the right and left pickoff coils.
See Figure 6-3. Neither pair should be an open circuit (i.e., infinite resistance). The resistance
values should be the same or very close (±5 ohms).
8. Use the DMM to check the resistance across the RTD and LLC (lead length compensation)
circuits. See Figure 6-3. Neither pair should be an open circuit (i.e., infinite resistance).
9. Test for a ground to case by checking the resistance between each pin and the sensor case.
With the DMM set to its highest range, there should be infinite resistance on each lead. If there
is any resistance at all, there is a short to case.
If a short to case is indicated, check for moisture or corrosion. If you are unable to determine
the source of the problem, contact Micro Motion Customer Service.
10. Test for shorts across terminals by testing resistance across the following terminal pairs (see
Figures 6-3 and 6-4). There should be infinite resistance in each case. If there is any resistance
at all, there is a short between the terminals.
• Brown against all other terminals except Red
• Red against all other terminals except Brown
• Green against all other terminals except White
• White against all other terminals except Green
• Blue against all other terminals except Gray
• Gray against all other terminals except Blue
• Orange against all other terminals except Yellow and Violet
• Yellow against all other terminals except Orange and Violet
• Violet against all other terminals except Yellow and Orange
Note: D600 sensors and CMF400 sensors with booster amplifiers have different terminal pairs.
Contact Micro Motion Customer Service for assistance.
If a short between terminals is indicated, contact Micro Motion Customer Service.
Operation
Lead length compensator(1) Right pickoff
(+) (+)
Left pickoff
(–)
Resistance temperature detector return /
Lead length compensator
(common)
Left pickoff
(+)
Resistance temperature detector
Drive
(+)
(–)
Drive
(+)
Troubleshooting
(1) LLC for all sensors except T-Series and CMF400 I.S. For T-Series sensors, functions as
composite RTD. For CMF400 I.S. sensors, functions as fixed resistor.
Drive – Drive +
PlantWeb Alerts
RTD +
Right pickoff +
Left pickoff –
(1) Lead length compensator (LLC) for all sensors except T-Series, CMF400 I.S., and F300. For T-Series sensors,
functions as composite RTD. For CMF400 I.S. and F300 sensors, functions as fixed resistor.
Note: The pins are shown as they appear while looking at the feedthrough on the sensor.
TB Reference
Operation
A.1 PlantWeb Alerts explained
Intelligent Emerson Process Management field devices (such as the Micro Motion Model 2700 with
FOUNDATION fieldbus) possess advanced diagnostic features. PlantWeb Alerts help operators take
control of this diagnostic information by informing the operator of device issues and providing
support guidance for dealing with these issues.
PlantWeb Alerts are divided into three categories:
Troubleshooting
• Advisory – Allow maintenance to address a problem before it impacts operations. These alerts
are presented to maintenance personnel as an aid to maintenance planning.
• Maintenance – Indicate a malfunction has occurred (or is about to occur), and what the effects
might be.
• Failed – Indicate a failure has occurred which renders the device inoperative.
PlantWeb Alerts
Related
PlantWeb What the alert is Default alert parameters (and
Alert detecting category defaults) Guidelines for setting
Density out of The measured density has Failed D1, D2, K1, K2, FD, Refer to Section 3.3 for
range exceeded the sensor DTC, Tube Frequency, characterization information.
defined limits. Drive Gain, LPO,
RPO, process density
Mass flow out The measured mass flow Failed Process flow rate
of range has exceeded the sensor
defined limits.
Calibration The calibration attempted Failed Process flow rate, See Section 6.5.
failed by the user failed. process density,
process temperature
Tube not full There is no signal from the Failed Tube Frequency, Drive
left or right pickoffs. Gain, LPO, RPO,
process density
TB Reference
Slug flow Entrained gas in a liquid Maintenance Slug Low Limit (0.0), Refer to Sections 4.13 and
process or condensation in Slug High Limit (5.0), 6.11 for more information
a gas process has caused Slug Duration (1.0), about slug flow.
the density to exceed the Drive Gain, process
configured slug limits. density
Related
PlantWeb What the alert is Default alert parameters (and
Alert detecting category defaults) Guidelines for setting
Drive out of The drive needed to Maintenance Drive Gain, LPO,
range operate the sensors has RPO, process density
exceeded the optimal
point.
API: Process The process temperature Maintenance None
variable out of or density is outside the
range API-defined extrapolation
limits.
Sensor not The sensor is not Failed LPO, RPO, Live Zero,
responding functioning properly. Drive Gain, Tube
Frequency
Sensor Either the temperature Failed Line RTD, Meter RTD,
temperature reading from the RTD on process temperature
out of range the sensor tube or sensor
case is outside the normal
operating limits.
Transmitter not The transmitter has not Failed K1, K2, FCF Refer to Section 3.3 for
characterized had the proper flow or characterization information.
density calibration
parameters entered from
the sensor tag or flow
calibration sheet.
CM: Unable to The data entered as inputs Failed CM curve parameters Refer to Section 4.7.
fit curve data to the curve fit yield
unacceptable errors in the
fit.
Smart Meter The Smart Meter Maintenance None
Verification Verification procedure has
failed unexpectedly failed.
Smart Meter The Smart Meter Maintenance None
Verification Verification procedure was
aborted aborted by the user.
CM: The process temperature Maintenance Process density,
Extrapolation or process density is process temperature
alarm outside the user-defined
extrapolation limits.
Calibration in There is a calibration (zero, Advisory
progress density, temperature, or
Meter Verification) in
progress. If Meter
Verification is in progress,
the outputs are held at last
measured value.
PWA simulate PlantWeb Simulate Mode Advisory None
active is active.
Sensor Sensor simulate mode is Advisory None
simulate active active.
Electronics The core processor or Failed None
failure transmitter has
experienced either an
EEPROM, RAM, boot
sector or real-timer
interrupt failure.
Related
Operation
PlantWeb What the alert is Default alert parameters (and
Alert detecting category defaults) Guidelines for setting
Transmitter The transmitter is Failed None
initializing/ undergoing its initial
warming up startup routines.
Core There is a communication Failed None
processor/ failure between the core
transmitter processor and the
communication transmitter.
failure
ECP low The enhanced core Failed None Refer to Product Data Sheet
power processor is not receiving for transmitter power
enough power. requirements.
Possible data The core processor was Maintenance None
loss unable to successfully
Troubleshooting
store the totalizers on the
last power down.
NV writes A high number of writes Advisory All static or This condition usually exists
deferred has been detected to non-volatile because a program has been
non-volatile memory. parameters such as written that writes to function
HI_HI_LIM, block parameters not
LOW_CUT, SP, normally expected to be
TRACK_IN_D, OUT, written to on a cyclic basis.
IO_OPTS, BIAS, Any such automated write
STATUS_OPTS, sequence should be modified
SP_HI_LIM, and so to write the parameter(s) only
on. when needed.
PlantWeb Alerts
with FOUNDATION fieldbus. Table A-3 shows the status of AI and AO block outputs under various
combinations of transducer block modes and PlantWeb Alerts.
TB Reference
Default
PlantWeb What the Alert is alert Recommended
Alert detecting category Effect on device action/help
Density out of The measured density has Failed Density measurement • Check for partially filled
range exceeded the sensor defined unavailable. or blocked flow tubes.
limits. • Check process to ensure
density is correct.
• Verify all characterization
parameters are correct,
especially density
factors.
• Perform a density
calibration.
Mass flow out of The measured mass flow Failed Mass flow measurement • Check process to ensure
range has exceeded the sensor unavailable. mass flow is correct.
defined limits. • Verify characterization
parameters are correct.
• Zero the flowmeter.
Calibration failed The zero or density Failed Device may not be • If zeroing, verify there is
calibration attempted by the properly calibrated or no flow.
user failed. zeroed. • If performing an FD cal,
verify there is sufficient
flow.
• Cycle power to the
transmitter, then try
recalibrating the
transmitter.
• Eliminate mechanical
noise.
Tube not full There is no signal from the Failed Measurements are Check for air in the flow
left or right pickoffs. wrong or erratic. tubes, tubes not filled,
foreign material in tubes,
or coating in tubes.
Slug flow Entrained gas in a liquid Maintenance Measurements may be In a liquid process, check
process or condensation in a incorrect. If temporary or process for cavitation,
gas process has caused the expected, this can be flashing or leaks. In a gas
density to exceed the ignored. process, check
configured slug limits. temperature and pressure
to verify gas is not
condensing. If slug
condition occurred while
batching, actual product
delivered may not match
target. Monitor density and
try to resolve process
problems. If slug condition
persists, reconfigure slug
limits and/or slug timeout.
Drive out of range The drive needed to operate Maintenance Flowmeter continues to • Purge the flow tubes
the sensors has exceeded function normally, but • Increase inlet or back
the optimal point. there may be a problem. pressure at the sensor
• Change sensor
orientation
• If no other alert is active,
this condition can be
ignored.
API: Process The process temperature or Maintenance API measurements may Check the API
variable out of density is outside the be incorrect. configuration.
range API-defined extrapolation
limits.
Default
Operation
PlantWeb What the Alert is alert Recommended
Alert detecting category Effect on device action/help
Sensor not The sensor is not functioning Failed Incorrect or unusable • Check sensor wiring.
responding properly. data. • Check test points.
• Purge flow tubes.
Sensor Either the temperature Failed Bad temperature • Verify characterization
temperature out reading from the RTD on the reading. This may parameters are correct.
of range sensor tube or sensor case adversely affect CM and • Check sensor wiring.
is outside the normal API variables. There may be an open or
operating limits. short lead length
compensator or an open
or short RTD in the
sensor. If open or short
is at transmitter, repair. If
open or short is at
sensor, return to Micro
Troubleshooting
Motion.
• Verify process fluid
temperature is within
sensor specifications.
Transmitter not The transmitter has not had Failed Measurements may be Check the
characterized the proper flow or density incorrect. characterization.
calibration parameters Specifically, verify the Flow
entered from the sensor tag Cal Factors, K1 and K2
or flow calibration sheet. values.
CM: Unable to fit The data entered as inputs Failed This CM curve is not Check the curve data.
curve data to the curve fit yield usable.
unacceptable errors in the fit.
Meter verification The meter verification Failed Outputs held at last Wait until meter verification
in progress routine is in progress. measured values. routine is complete.
CM: Extrapolation The process temperature or Maintenance CM variables may be Check enhanced density
alarm process density is outside incorrect or unusable. configuration data.
PlantWeb Alerts
the user-defined
extrapolation limits.
Calibration in There is a calibration (zero, Advisory If meter verification is in Allow the calibration to
progress density, temperature, or progress, the outputs complete.
meter verification) in are held at last
progress. measured values.
Otherwise, no effect.
PWA simulate PlantWeb Simulate Mode is Advisory No effect. Disable PWA Simulate
active active. Mode.
Sensor simulate Sensor simulate mode is Advisory Outputs are fixed. Disable sensor simulate
active active. mode.
Electronics The core processor or Failed Inoperable. Cycle power to the
failure transmitter has experienced transmitter. If the problem
either an EEPROM, RAM, persists, contact Micro
boot sector or real-timer Motion.
interrupt failure.
Transmitter The transmitter is Failed Temporary unavailability. Allow the transmitter to
TB Reference
initializing/ undergoing its initial startup A valid measurement warm up. The error should
warming up routines. cannot be calculated go away when the
until the startup phase is transmitter is ready for
complete. normal operation.
Default
PlantWeb What the Alert is alert Recommended
Alert detecting category Effect on device action/help
Core processor/ There is a communication Failed Inoperable. Verify the wiring between
transmitter failure between the core the transmitter and the
communication processor and the core processor. Cycle
failure transmitter. power to the transmitter. If
the problem persists,
contact Micro Motion.
ECP low The enhanced core Failed Inoperable. Check the power supply to
power processor is not receiving the transmitter. Check the
enough power. wiring between the
transmitter and the core
processor.
Possible data The core processor was Maintenance Potential loss of Contact Micro Motion for a
loss unable to successfully store information. The core transmitter software
the totalizers on the last processor must rely on upgrade.
power down. the totals that were
previously saved in the
device up to 2 hours
before the power was
lost.
NV writes A high number of writes has Advisory Possibly delayed device Wait for deferred data to
deferred been detected to non-volatile configuration. To prevent be saved in NV cycle time,
memory. premature failure of the or write again in 24 hours.
memory, the write
operations have been
deferred. The deferred
data will be saved on a
daily basis or on a
non-volatile cycle time
period.
Transducer block
mode (Actual) Active PlantWeb Alerts AI / AO status AI / AO substatus
OOS No effect Bad Device failure
Man No effect Bad Non-specific
Auto Fail Bad Non-specific
Auto Maint., no Fail Uncertain Non-specific
Auto Advisory only Good Non-specific
Auto None Good Non-specific
Operation
B.1 Overview
The Micro Motion Model 2700 transmitter has seven separate transducer blocks.
Troubleshooting
Fieldbus hosts that do not support the use of tags as block names will instead show the name
TRANSDUCER followed by a numeric code. Table B-1 shows the relationship between transducer
block tag names and codes, and gives the table number where the parameters and views are described
in this appendix.
Table B-1 Transducer block tag names, code names, and table numbers
PlantWeb Alerts
API TRANSDUCER 900 Table B-12 Table B-13
CONCENTRATION TRANSDUCER 1000 Table B-14 Table B-15
MEASUREMENT
Initial Value
OD Index
Access
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
2 TAG_DESC The user description of STRING OCTET 32 S Spa R/W Any 32 Characters
the intended application STRING ces
of the block.
3 STRATEGY The strategy field can be VARIABLE Unsigned16 2 S 0 R/W N/A
used to identify grouping
of blocks. This data is not
checked or processed by
the block.
4 ALERT_KEY The identification number VARIABLE Unsigned8 1 S 0 R/W 0 to 255
of the plant unit. This
information may be used
in the host for sorting
alarms, etc.
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2/6 of FF-891
permitted and normal
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of FF-903
the error status STRING
associated with the
hardware or software
components associated
with a block.
7 XD_ERROR Used for all config, H/W, VARIABLE Unsigned8 1 D - R 18 = Process Error
connection failure or 19 = Configuration Error
system problems in the 20 = Electronics Failure
block. 21 = Sensor Failure
Process Variables Data
8 MFLOW Mass Flow Rate VARIABLE DS-65 5 D/20 0 R N/A
9 MFLOW_UNITS Standard or special mass ENUM Unsigned16 2 S g/s R/W 0000 = None
flow rate unit 1318 = g/s
1319 = g/min
1320 = g/hr
1322 = kg/s
1323 = kg/min
1324 = kg/hr
1325 = kg/day
1327 = t/min
1328 = t/h
1329 = t/d
1330 = lb/s
1331 = lb/min
1332 = lb/hr
1333 = lb/day
1335 = Ston/min
1336 = Ston/hr
1337 = Ston/day
1340 = Lton/hr
1341 = Lton/day
10 MFLOW_SPECIAL_UNIT_ Base Mass Unit ENUM Unsigned16 2 S g R/W 0000 = None
BASE 1089 = Grams
1088 = Kilograms
1092 = Metric Tons
1094 = Pounds
1096 = Short tons
11 MFLOW_SPECIAL_UNIT_ Base time unit for special ENUM Unsigned16 2 S s R/W 0000 = None
TIME mass unit 1058 = Minutes
1054 = Seconds
1059 = Hours
1060 = Days
12 MFLOW_SPECIAL_UNIT_ Special mass unit VARIABLE FLOAT 4 S 1 R/W N/A
CONV conversion factor
13 MFLOW_SPECIAL_UNIT_ Special mass flow unit STRING OCTET 8 S “NO R/W Any 8 characters
STR string STRING NE”
14 TEMPERATURE Temperature VARIABLE DS-65 5 D/20 – R N/A
15 TEMPERATURE_UNITS Temperature Unit ENUM Unsigned16 2 S C° R/W 0000 = None
1000 = K
1001 = Deg C
1002 = Deg F
1003 = Deg R
16 DENSITY Density VARIABLE DS-65 5 D/20 – R N/A
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
1349 = m3/hr
1350 = m3/day
1351 = L/s
1352 = L/min
1353 = L/hr
1355 = Ml/day
1356 = CFS
1357 = CFM
1358 = CFH
1359 = ft3/day
1362 = gal/s
1363 = GPM
1364 = gal/hour
1365 = gal/day
1366 = Mgal/day
1367 = ImpGal/s
1368 = ImpGal/min
1369 = ImpGal/hr
1370 = Impgal/day
1371 = bbl/s
1372 = bbl/min
1373 = bbl/hr
1374 = bbl/day
20 VOL_SPECIAL_UNIT_BASE Base Volume Unit ENUM Unsigned16 2 S l R/W 0000 = None
1048 = Gallons
1038 = Liters
PlantWeb Alerts
1049 = Imperial Gallons
1043 = Cubic Feet
1034 = Cubic Meters
1051 = Barrels
21 VOL _SPECIAL_UNIT_TIME Base time unit for special ENUM Unsigned16 2 S s R/W 0000 = None
volume unit 1058 = Minutes
1054 = Seconds
1059 = Hours
1060 = Days
22 VOL Special volume unit VARIABLE FLOAT 4 S 1 R/W N/A
_SPECIAL_UNIT_CONV conversion factor
23 VOL _SPECIAL_UNIT_STR Special volume unit string STRING OCTET 8 S “NO R/W Any 8 characters
STRING NE”
24 MASS_TOT_INV_SPECIAL_ Special mass total and STRING OCTET 8 S “NO R/W Any 4 characters
STR inventory unit string STRING NE”
25 VOLUME_TOT_INV_ Special volume total and STRING OCTET 8 S “NO R/W Any 4 characters
SPECIAL_ STR inventory unit string STRING NE”
26 FLOW_DAMPING Flow rate (Mass and VARIABLE FLOAT 4 S 0.8 R/W N/A
Volume) internal damping
(seconds)
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
32 MASS_LOW_CUT Mass flow cutoff for VARIABLE FLOAT 4 S 0.0 R/W N/A
internal totalizers
33 VOLUME_FLOW_LOW_ Volume flow cutoff for VARIABLE FLOAT 4 S 0.0 R/W N/A
CUTOFF internal totalizers
34 DENSITY_LOW_CUTOFF Density cutoff for internal VARIABLE FLOAT 4 S 0.2 R/W N/A
totalizers
35 FLOW_DIRECTION Flow direction ENUM Unsigned16 2 S 0 R/W 0 = Forward Only
1 = Reverse Only
2 = Bi-Directional
3 = Absolute Value
4 = Negate/Forward Only
5 = Negate/Bi-Directional
Totalizers
36 INTEGRATOR_FB_CONFIG Configuration of ENUM Unsigned16 2 S 0 R/W 0 = Standard
Integrator Function Block 1 = Internal Mass Total
2 = Internal Volume Total
3 = Internal Mass Inv.
4 = Internal Volume Inv.
5 = Int Gas Vol Tot
6 = Int Gas Vol Inv
7 = Int API Vol Tot
8 = Int API Vol Inv
9 = Int CM Std Vol Tot
10= Int CM Std Vol Inv
11= Int CM Net Mass Tot
12= Int CM Net Mass Inv
13= Int CM Net Vol Tot
14= Int CM Net Vol Inv
37 START_STOP_TOTALS Start/Stop all Totalizers METHOD Unsigned16 2 - 0 N/A 0x0000 = Stop Totals
0x0001 = Start Totals
38 RESET_TOTALS Reset all Totals METHOD Unsigned16 2 - 0 N/A 0x0000 = None
0x0001 = Reset
39 RESET_INVENTORIES Reset all Inventories METHOD Unsigned16 2 - 0 N/A 0x0000 = None
0x0001 = Reset
40 RESET_MASS_TOTAL Reset Mass Total METHOD Unsigned16 2 - 0 N/A 0x0000 = None
0x0001 = Reset
41 RESET_VOLUME_TOTAL Reset Volume Total METHOD Unsigned16 2 - 0 N/A 0x0000 = None
0x0001 = Reset
42 MASS_TOTAL Mass Total VARIABLE DS-65 5 D/20 – R N/A
43 VOLUME_TOTAL Volume Total VARIABLE DS-65 5 D/20 – R N/A
44 MASS_INVENTORY Mass Inventory VARIABLE DS-65 5 D/20 – R N/A
45 VOLUME_INVENTORY Volume Inventory VARIABLE DS-65 5 D/20 – R N/A
46 MASS_TOT_INV_UNITS Standard or special mass ENUM Unsigned16 2 S g R 0000 = None
total and mass inventory 1088 = Kg
unit 1089 = g
1092 = metric tons
1094 = lbs
1095 = short tons
1096 = long tons
47 VOLUME_TOT_INV_UNITS Standard or special ENUM Unsigned16 2 S l R 0000 = None
volume total or mass 1034 = m3
inventory unit. 1036 = cm3
1038 = l
1043 = ft3
1048 = gal
1049 = ImpGal
1051 = bbl
Gas Process Variables
48 GSV_Gas_Dens Gas Density used to VARIABLE FLOAT 4 S 0.00 R/W N/A
calculate Reference 1205
Volume Gas Flow and
Totals
49 GSV_Vol_Flow Reference Volume Gas VARIABLE DS-65 5 D/20 – R N/A
Flow Rate (not valid when
API or CM is enabled)
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
1523 = Nm3/m
1524 = Nm3/h
1525 = Nm3/d
1527 = Sm3/s
1528 = Sm3/m
1529 = Sm3/h
1530 = Sm3/d
1532 = NL/s
1533 = NL/m
1534 = NL/h
1535 = NL/d
1537 = SL/s
1538 = SL/m
1539 = SL/h
1540 = SL/d
54 SNS_GSV_TotalUnits Gas Standard Volume ENUM Unsigned16 R-26 S SCF R 0000 = None
Total and Inventory Engi- (2) 02 1053 = SCF
neering Units 1521 = Nm3
1526 = Sm3
1531 = NL
PlantWeb Alerts
1536 = SL
55 SNS_GSVflowBaseUnit Base Gas Standard Vol- ENUM Unsigned16 R-26 S SCF R/W 0000 = None
ume Unit (2) 03 (OOS) 1521 = Normal cubic
meter
1531 = Normal liter
1053 = Standard cubic ft
1536 = Standard liter
1526 = Standard cu meter
56 SNS_GSVflowBaseTime Base time unit for special ENUM Unsigned16 R-26 S min R/W 0000 = None
gas standard volume unit. (2) 04 (OOS) 1058 = Minutes
1054 = Seconds
1059 = Hours
1060 = Days
57 SNS_GSVflowFactor Special gas standard vol- VARIABLE FLOAT (4) R-26 S 1 R/W N/A
ume unit conversion fac- 05 - (OOS)
tor 2606
58 SNS_GSVflowText Special gas standard vol- STRING OCTET R-26 S “NO R/W Any 8 characters
ume unit string STRING (8) 07 - NE” (OOS)
TB Reference
2610
59 SNS_GSVtotText Special gas standard vol- STRING OCTET R-26 S “NO R/W Any 4 characters
ume total and inventory STRING (8) 11 - NE” (OOS)
unit string 2614
60 SNS_GSV_FlowCutoff Gas Standard Volume VARIABLE FLOAT (4) R-46 S 0 R/W Must be >=0.0
Low Flow Cutoff 1-46 (OOS)
2
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
61 SNS_ResetGSVolTotal Reset Gas Standard Vol- Method Unsigned16 C-63 S – R/W 0x0000 = No effect
ume Total (2) (Any) 0x0001 = Reset
62 SNS_ResetAPIGSVInv Reset Gas Standard Vol- Method Unsigned16 C-19 S – R/W 0x0000 = No Effect
ume Inventory (2) 4 (Any) 0x0001 = Reset
Other 4.0 additions
63 SNS_ResetMassInventory Reset Mass Inventory Method Unsigned16 C-19 S 0 R/W 0x0000 = No effect
(2) 2 (Any) 0x0001 = Reset
64 SNS_ResetVolumeInventory Reset Volume Inventory Method Unsigned16 C-19 S 0 R/W 0x0000 = No Effect
(2) 3 (Any) 0x0001 = Reset
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
Process Variables Data
8 MFLOW 5 5
9 MFLOW_UNITS 2
10 MFLOW_SPECIAL_UNIT_BASE 2
11 MFLOW_SPECIAL_UNIT_TIME 2
12 MFLOW_SPECIAL_UNIT_CONV 4
13 MFLOW_SPECIAL_UNIT_STR 8
14 TEMPERATURE 5 5
15 TEMPERATURE_UNITS 2
16 DENSITY 5 5
17 DENSITY_UNITS 2
18 VOL_FLOW 5 5
19 VOL_FLOW_UNITS 2
20 VOL_SPECIAL_UNIT_BASE 2
21 VOL _SPECIAL_UNIT_TIME 2
22 VOL _SPECIAL_UNIT_CONV 4
23 VOL _SPECIAL_UNIT_STR 8
24 MASS_TOT_INV_SPECIAL_ STR 8
25 VOLUME_TOT_INV_ SPECIAL_ STR 8
26 FLOW_DAMPING 4
27 TEMPERATURE_DAMPING 4
28 DENSITY_DAMPING 4
Operation
29 MFLOW_M_FACTOR 4
30 DENSITY_M_FACTOR 4
31 VOL_M_FACTOR 4
32 MASS_LOW_CUT 4
33 VOLUME_LOW_CUT 4
34 DENSITY_LOW_CUT 4
35 FLOW_DIRECTION 2
Totalizers
36 INTEGRATOR_FB_CONFIG 2
37 START_STOP_TOTALS 2
38 RESET_TOTALS 2
39 RESET_INVENTORIES 2
Troubleshooting
40 RESET_MASS_TOTAL 2
41 RESET_VOLUME_TOTAL 2
42 MASS_TOTAL 5 5
43 VOLUME_TOTAL 5 5
44 MASS_INVENTORY 5 5
45 VOLUME_INVENTORY 5 5
46 MASS_TOT_INV_UNITS 2
47 VOLUME_TOT_INV_UNITS 2
Gas Process Variables
48 GSV_Gas_Dens 4
49 GSV_Vol_Flow 5 5
50 GSV_Vol_Tot 5 5
51 GSV_Vol_Inv 5 5
52 SNS_EnableGSV 2
PlantWeb Alerts
53 SNS_GSV_FlowUnits 2
54 SNS_GSV_TotalUnits 2
55 SNS_GSVflowBaseUnit 2
56 SNS_GSVflowBaseTime 2
57 SNS_GSVflowFactor 4
58 SNS_GSVflowText 8
59 SNS_GSVtotText 8
60 SNS_GSV_FlowCutoff 2
61 SNS_ResetGSVolTotal 2
62 SNS_ResetAPIGSVInv 2
63 SNS_ResetMassInventory 2
64 SNS_ResetVolumeInventory 2
Totals 64 76 64 85
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of STRING OCTET 32 S Spa R/W Any 32 Characters
the intended application STRING ces
of the block.
3 STRATEGY The strategy field can be VARIABLE Unsigned16 2 S 0 R/W N/A
used to identify grouping
of blocks. This data is not
checked or processed by
the block.
4 ALERT_KEY The identification VARIABLE Unsigned8 1 S 0 R/W 0 to 255
number of the plant unit.
This information may be
used in the host for
sorting alarms, etc.
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2/6 of
permitted and normal FF-891
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of
the error status STRING FF-903
associated with the
hardware or software
components associated
with a block.
7 XD_ERROR Used for all config, H/W, VARIABLE Unsigned8 1 D - R 18 = Process Error
connection failure or 19 = Configuration Error
system problems in the 20 = Electronics Failure
block. 21 = Sensor Failure
Calibration
8 MASS_FLOW_GAIN Flow calibration factor VARIABLE FLOAT 4 S 1.0 R/W N/A
9 MASS_FLOW_T_COMP Temperature coefficient VARIABLE FLOAT 4 S 5.13 R/W N/A
for flow
10 ZERO_CAL Perform auto zero METHOD Unsigned16 2 - 0 N/A 0x0000 = Abort Zero Cal
0x0001 = Start Zero Cal
11 ZERO_TIME Maximum zeroing time VARIABLE Unsigned16 2 S 20 R/W N/A
12 ZERO_STD_DEV Standard deviation of VARIABLE FLOAT 4 S 0 R N/A
auto zero
13 ZERO_OFFSET Present flow signal offset at VARIABLE FLOAT 4 S 0 R N/A
zero flow in μsec
14 ZERO_FAILED_VAULE Value of the zero if the VARIABLE FLOAT 4 S 0 R N/A
zero cal failed
15 LOW_DENSITY_CAL Perform low density METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration 0x0001 = Start Cal
16 HIGH_DENSITY_CAL Perform high-density METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration 0x0001 = Start Cal
17 FLOWING_DENSITY_CAL Perform flowing-density METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration 0x0001 = Start Cal
18 D3_DENSITY_CAL Perform third point METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration 0x0001 = Start Cal
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
25 D1 Density 1 (g/cc) VARIABLE FLOAT 4 S 0 R/W N/A
26 D2 Density 2 (g/cc) VARIABLE FLOAT 4 S 1 R/W N/A
27 FD_VALUE Flowing Density (g/cc) VARIABLE FLOAT 4 S 0 R/W N/A
28 D3 Density 3 (g/cc) VARIABLE FLOAT 4 S 0 R/W N/A
29 D4 Density 4 (g/cc) VARIABLE FLOAT 4 S 0 R/W N/A
30 DENS_T_COEFF Density temperature VARIABLE FLOAT 4 S 4.44 R/W N/A
coefficient
31 T_FLOW_TG_COEFF T-Series: Flow TG VARIABLE FLOAT 4 S 0 R/W N/A
Coefficient (FTG)
32 T_FLOW_FQ_COEFF T-Series: Flow FQ VARIABLE FLOAT 4 S 0 R/W N/A
Coefficient (FFQ)
33 T_DENSITY_TG_COEFF T-Series: Density TG VARIABLE FLOAT 4 S 0 R/W N/A
Coefficient (DTG)
34 T_DENSITY_FQ_COEFF1 T-Series: Density FQ VARIABLE FLOAT 4 S 0 R/W N/A
Coefficient #1 (DFQ1)
35 T_DENSITY_FQ_COEFF2 T-Series: Density FQ VARIABLE FLOAT 4 S 0 R/W N/A
Coefficient #2 (DFQ2)
PlantWeb Alerts
36 TEMP_LOW_CAL Perform temperature METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration at the low 0x0001 = Start Cal
point (point 1)
37 TEMP_HIGH_CAL Perform temperature METHOD Unsigned16 2 - 0 N/A 0x0000 = None
calibration at the high 0x0001 = Start Cal
point (point 2)
38 TEMP_VALUE Temperature Value for VARIABLE FLOAT 4 S 0 R/W N/A
temp calibrations (in
degC)
39 TEMP_OFFSET Temperature calibration VARIABLE FLOAT 4 S 0.0 R/W N/A
offset
40 TEMP_SLOPE Temperature calibration VARIABLE FLOAT 4 S 1.0 R/W N/A
slope
Pressure Compensation
41 PRESSURE Pressure VARIABLE DS-65 5 D/20 0 R N/A
42 PRESSURE_UNITS Pressure Unit ENUM Unsigned16 2 S psi R/W 0000 = None
1148 = inch water @
68F
1156 = inch HG @ 0C
1154 = ft water @ 68F
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
Calibration
8 MASS_FLOW_GAIN 4
9 MASS_FLOW_T_COMP 4
10 ZERO_CAL 2
11 ZERO_TIME 2
12 ZERO_STD_DEV 4
13 ZERO_OFFSET 4
14 ZERO_FAILED_VAULE 4
15 LOW_DENSITY_CAL 2
16 HIGH_DENSITY_CAL 2
17 FLOWING_DENSITY_CAL 2
18 D3_DENSITY_CAL 2
19 D4_DENSITY_CAL 2
20 K1 4
21 K2 4
22 FD 4
23 K3 4
24 K4 4
25 D1 4
Operation
26 D2 4
27 FD_VALUE 4
28 D3 4
29 D4 4
30 DENS_T_COEFF 4
31 T_FLOW_TG_COEFF 4
32 T_FLOW_FQ_COEFF 4
33 T_DENSITY_TG_COEFF 4
34 T_DENSITY_FQ_COEFF1 4
35 T_DENSITY_FQ_COEFF2 4
36 TEMP_LOW_CAL 2
37 TEMP_HIGH_CAL 2
Troubleshooting
38 TEMP_VALUE 4
39 TEMP_OFFSET 4
40 TEMP_SLOPE 4
Pressure Compensation
41 PRESSURE 5 5
42 PRESSURE_UNITS 2
43 EN_PRESSURE_COMP 2
44 PRESSURE_FACTOR_FLOW 4
45 PRESSURE_FACTOR_DENS 4
46 PRESSURE_FLOW_CAL 4
Temperature Compensation
47 SNS_EnableExtTemp 2
48 SNS_ExternalTempInput 5
Totals 19 100 34 19
PlantWeb Alerts
B.4 DIAGNOSTICS transducer block parameters
Following are the parameters (Table B-6) and views (Table B-7) for the DIAGNOSTICS transducer
block.
Initial Value
OD Index
Access
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
12 ALARM2_STATUS Status Word 2 ENUM BIT 2 D/20 - R 0x0001 = Line RTD Over
STRING 0x0002 = Meter RTD
Over
0x0004 = CP Exception
0x0008 = API: Temp
OOL
0x0010 = API:Density
OOL
0x0020 = CM: Unable to
fit curve data
0x0040 = CM:
Extrapolation alarm
0x0080 = Not Used
0x0100 = EEPROM err
(2700)
0x0200 = RAM err
(2700)
0x0400 = Factory Config
Troubleshooting
err
0x0800 = Low Power
0x1000= Tube not full
0x2000 = Meter Verify
outputs set to fault
0x4000 = Not Used
0x8000 = Not Used
13 ALARM3_STATUS Status Word 3 ENUM BIT 2 D/20 - R 0x0001 = Drive
STRING Overrange
0x0002 = Slug Flow
0x0004 = Cal in
Progress
0x0008 = Data Loss
Possible
0x0010 = Upgrade
Series 2000
0x0020 = Simulation
Mode
0x0040 = Meter Verify
outputs set to LMV
0x0080 = Warming Up
0x0100 = Power Reset
0x0200 = Reverse Flow
0x0400 = Not Used
0x0800 = Not Used
PlantWeb Alerts
0x1000 = Not Used
0x2000 = Not Used
0x4000 = Not Used
0x8000 = Not Used
14 ALARM4_STATUS Status Word 4 ENUM BIT 2 D/20 - R 0x0001 = Cal Fail: Low
STRING 0x0002 = Cal Fail: High
0x0004 = Cal Fail: Noisy
0x0008 = Auto Zero IP
0x0010 = D1 IP
0x0020 = D2 IP
0x0040 = FD IP
0x0080 = Temp slope IP
0x0100 = Temp offset IP
0x0200 = D3 IP
0x0400 = D4 IP
0x0800 = Not Used
0x1000= Not Used
0x2000 = Not Used
0x4000 = Not Used
0x8000 = Not Used
15 FAULT_LIMIT Fault Limit Code ENUM Unsigned16 2 S 0 R/W 0 = Upscale
1 = Downscale
2 = Zero
3 = NAN
4 = Flow goes to zero
5 = None
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
Fingerprinting 0x0001 = enabled
37 MFP_UNITS Meter Fingerprint in SI (0) ENUM Unsigned16 2 S 0 R/W 0x0000 = SI
or English (1) units 0x0001 = English
38 MFP_TV_INDEX Meter Fingerprint VARIABLE Unsigned16 2 S 0 R/W 0 = Mass Flow Rate
Transmitter Variable 1 = Temperature
Index 3 = Density
5 = Volume Flow Rate
46 = Raw Tube
Frequency
47 = Drive Gain
48 = Case Temperature
49 = LPO Amplitude
50 = RPO Amplitude
51 = Board Temperature
52 = Input Voltage
54 = Live Zero
39 MFP_TYPE Fingerprint Type ENUM Unsigned16 2 S 0 R/W 0 = Current
1 = Factory Cal
2 = Installation
3 = Last Zero
40 MFP_TV_INST Transmitter Variable, VARIABLE FLOAT 4 D – R
Instantaneous (only valid
for Current print)
PlantWeb Alerts
41 MFP_TV_AVG Transmitter Variable, VARIABLE FLOAT 4 D – R
Average (1-min rolling)
42 MFP_TV_STD_DEV Transmitter Variable, Std VARIABLE FLOAT 4 D – R
Dev (1-min rolling)
43 MFP_TV_MAX Transmitter Variable, VARIABLE FLOAT 4 D – R
Maximum (since last
statistics reset)
44 MFP_TV_MIN Transmitter Variable, VARIABLE FLOAT 4 D – R
Minimum (since last
statistics reset)
v4.0 Additions
45 DIAG_FEATURE_KEY Enabled Features STRING BIT R-500 S – R 0x0000 = standard
STRING (2) 0 0x0010 = Meter Verify.
0x0080 = PID
0x0800 = Enh. Density
0x1000 = API
46 SYS_PowerOnTimeSec Power on time (Seconds VARIABLE R-262 D – R N/A
since last reset) UnsignedI3 5-262
2 (4) 6
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
calculated as a mean 3105-
3106
with
3100=
0
66 FRF_MassLpo_mean The current LPO mass VARIABLE FLOAT (4) R– S – R N/A
calculated as a mean 3107-
3108
with
3100=
0
67 FRF_MassRpo_mean The current RPO mass VARIABLE FLOAT (4) R– S – R N/A
calculated as a mean 3109-
3110
with
3100=
0
68 FRF_StiffnessLpo_stddev The current LPO stiffness VARIABLE FLOAT (4) R– S – R N/A
calculated as a standard 3101
deviation –
3102
PlantWeb Alerts
with
3100=
1
69 FRF_StiffnessRpo_stddev The current RPO VARIABLE FLOAT (4) R– S – R N/A
stiffness calculated as a 3103-
standard deviation 3104
with
3100=
1
70 FRF_Damping_stddev The current damping VARIABLE FLOAT (4) R– S – R N/A
calculated as a standard 3105-
deviation 3106
with
3100=
1
71 FRF_MassLpo_stddev The current LPO mass VARIABLE FLOAT (4) R– S – R N/A
calculated as a standard 3107-
deviation 3108
with
3100=
1
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
pass/fail, Bits6-4 = state,
Bits3-0 = Abort code)
Abort States are
compressed to fit in 3 bits
89 FRF_MV_Time FCF Datalog Item 3: VARIABLE Unsigned32 2987- S - R N/A
Time Initiated (4) 2988
90 FRF_MV_LPO_Norm FCF Datalog Item 4: LPO VARIABLE FLOAT (4) 2989- S - R N/A
Normalized Data 2990
91 FRF_MV_RPO_Norm FCF Datalog Item 5: RPO VARIABLE FLOAT (4) 2991- S - R N/A
Normalized Data 2992
92 FRF_MV_FirstRun_Time FCF Timers: Time Until VARIABLE FLOAT (4) 2993- S - RW N/A
First Run in Hours 2994 (Any)
93 FRF_MV_Elapse_Time FCF Timers: Time VARIABLE FLOAT (4) 2995- S - RW N/A
between each run after 2996 (Any)
the first run initiated in
hours
PlantWeb Alerts
94 FRF_MV_Time_Left FCF Timers: Time Until VARIABLE FLOAT (4) 2997- S - R N/A
Next Run in Hours 2998
95 FRF_ToneLevel Frf Tone Level (mA) VARIABLE FLOAT (4) 3083- S - RW N/A
3084 (OO
S)
96 FRF_ToneRampTime Tone Ramp Time VARIABLE FLOAT (4) 3085- S - RW N/A
(Seconds) 3086 (OO
S)
97 FRF_BlCoeff BL Coef. VARIABLE FLOAT (4) 3087- S - RW N/A
3088 (OO
S)
98 FRF_DriveTarget FRF Drive Target VARIABLE FLOAT (4) 3089- S - RW N/A
3090 (OO
S)
99 FRF_DrivePCoeff FRF Drive P Coefficient VARIABLE FLOAT (4) 3091- S - RW N/A
3092 (OO
S)
100 FRF_DriveCurr Drive Current VARIABLE FLOAT (4) 3113- S - R N/A
3114
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
Slug Flow Setup
8 SLUG_TIME 4
9 SLUG_LOW_LIMIT 4
10 SLUG_HIGH_LIMIT 4
Alarm Status
11 ALARM1_STATUS 2 2
12 ALARM2_STATUS 2 2
13 ALARM3_STATUS 2 2
14 ALARM4_STATUS 2 2
15 FAULT_LIMIT_CODE 2
16 LAST_MEASURED_VALUE_FAULT_TIMEOUT 2
17 ALARM_INDEX 2
Operation
18 ALARM_SEVERITY 2
Diagnostics
19 DRIVE_GAIN 5 5
20 TUBE_FREQUENCY 4
21 LIVE_ZERO 4
22 LEFT_PICKOFF_VOLTAGE 4
23 RIGHT_PICKOFF_VOLTAGE 4
24 BOARD_TEMPERATURE 4
25 ELECT_TEMP_MAX 4
26 ELECT_TEMP_MIN 4
27 ELECT_TEMP_AVG 4
28 SENSOR_TEMP_MAX 4
Troubleshooting
29 SENSOR_TEMP_MIN 4
30 SENSOR_TEMP_AVG 4
31 RTD_RESISTANCE_CABLE 4
32 RTD_RESISTANCE_METER 4
33 CP_POWER_CYCLE 2
Meter Fingerprinting
34 MFP_SAVE_FACTORY 2
35 MFP_RESET_STATS 2
36 EN_MFP 2
37 MFP_UNITS 2
38 MFP_TV_INDEX 2
39 MFP_TYPE 2
40 MFP_TV_INST 4
41 MFP_TV_AVG 4
PlantWeb Alerts
42 MFP_TV_STD_DEV 4
43 MFP_TV_MAX 4
44 MFP_TV_MIN 4
v4.0 Additions
45 DIAG_FEATURE_KEY 2
46 SYS_PowerOnTimeSec 4
47 SNS_InputVoltage 4
48 SNS_TargetAmplitude 4
49 SNS_CaseRTDRes 4
50 SYS_RestoreFactoryConfig 2
51 SNS_FlowZeroRestore 2
52 SNS_AutoZeroFactory 4
53 SYS_ResetPowerOnTime 2
54 FRF_EnableFCFValidation 2
TB Reference
55 FRF_FaultAlarm 2
56 FRF_StiffnessLimit 4
57 FRF_AlgoState 2
58 FRF_AbortCode 2
59 FRF_StateAtAbort 2
60 FRF_Progress 2
61 FRF_StiffOutLimLpo 2
62 FRF_StiffOutLimRpo 2
63 FRF_StiffnessLpo_mean 4
64 FRF_StiffnessRpo_mean 4
65 FRF_Damping_mean 4
66 FRF_MassLpo_mean 4
67 FRF_MassRpo_mean 4
68 FRF_StiffnessLpo_stddev 4
69 FRF_StiffnessRpo_stddev 4
70 FRF_Damping_stddev 4
71 FRF_MassLpo_stddev 4
72 FRF_MassRpo_stddev 4
73 FRF_StiffnessLpo_air 4
74 FRF_StiffnessRpo_air 4
75 FRF_Damping_air 4
76 FRF_MassLpo_air 4
77 FRF_MassRpo_air 4
78 FRF_StiffnessLpo_water 4
79 FRF_StiffnessRpo_water 4
80 FRF_Damping_water 4
81 FRF_MassLpo_water 4
82 FRF_MassRpo_water 4
83 ALERT_TIMEOUT 2
84 FRF_FCFValidCounter 2
85 FRF_StartMeterVer 2
86 FRF_MV_Index 2
87 FRF_MV_Counter 2
88 FRF_MV_Status 2
89 FRF_MV_Time 4
90 FRF_MV_LPO_Norm 4
91 FRF_MV_RPO_Norm 4
92 FRF_MV_FirstRun_Time 4
93 FRF_MV_Elapse_Time 4
94 FRF_MV_Time_Left 4
95 FRF_ToneLevel 4
96 FRF_ToneRampTime 4
97 FRF_BlCoeff 4
98 FRF_DriveTarget 4
99 FRF_DrivePCoeff 4
100 FRF_DriveCurr 4
101 FRF_DL_T 4
102 FRF_Temp 4
103 FRF_Density 4
104 FRF_DriveFreq 4
105 FRF_LpoFilt 4
Operation
106 FRF_RpoFilt 4
107 FRF_ToneSpacingMult 4
108 FRF_Freq_DriftLimit 4
109 FRF_Max_Current_mA 4
110 FRF_KFQ2 4
111 FRF_DataSetSelIndex 2
Totals 22 22 112 39 96 102
Troubleshooting
Table B-8 DEVICE INFORMATION transducer block parameters
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of STRING OCTET 32 S Spac R/W Any 32 Characters
PlantWeb Alerts
the intended application STRING es
of the block.
3 STRATEGY The strategy field can be VARIABLE Unsigned16 2 S 0 R/W N/A
used to identify grouping
of blocks. This data is not
checked or processed by
the block.
4 ALERT_KEY The identification number VARIABLE Unsigned8 1 S 0 R/W 0 to 255
of the plant unit. This
information may be used
in the host for sorting
alarms, etc.
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2/6 of
permitted and normal FF-891
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of
the error status STRING FF-903
associated with the
hardware or software
components associated
with a block.
7 XD_ERROR Used for all config, H/W, VARIABLE Unsigned8 1 D - R 18 = Process Error
connection failure or 19 = Configuration Error
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
35 SYS_DeviceType Transmitter Device Type VARIABLE Unsigned16 R-120 S 43 R N/A
(2)
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
PlantWeb Alerts
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
Transmitter Data
8 SERIAL_NUMBER 4
9 OPTION_BOARD_CODE 2
10 700_SW_REV 2
11 2700_SW_REV 2
12 CEQ_NUMBER 2
13 DESCRIPTION 16
Sensor Data
14 SENSOR_SN 4
15 SENSOR_TYPE 16
16 SENSOR_TYPE_CODE 2
17 SENSOR_MATERIAL 2
TB Reference
18 SENSOR_LINER 2
19 SENSOR_END 2
20 HIGH_MASS_LIMIT 4
21 HIGH_TEMP_LIMIT 4
22 HIGH_DENSITY_LIMIT 4
23 HIGH_VOLUME_LIMIT 4
24 LOW_MASS_LIMIT 4
25 LOW_TEMP_LIMIT 4
26 LOW_DENSITY_LIMIT 4
27 LOW_VOLUME_LIMIT 4
28 MASS_MIN_RANGE 4
29 TEMP_MIN_RANGE 4
30 DENSITY_MIN_RANGE 4
31 VOLUME_MIN_RANGE 4
32 SNS_PuckDeviceTypeCode 2
33 AI_SIMULATE_MODE 2
34 SNS_HartDeviceID 4
35 SYS_DeviceType 2
Totals 9 48 9 73
Initial Value
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of STRING OCTET 32 S Spac R/W Any 32 Characters
the intended application STRING es
of the block.
3 STRATEGY The strategy field can VARIABLE Unsigned16 2 S 0 R/W N/A
be used to identify
grouping of blocks. This
data is not checked or
processed by the block.
4 ALERT_KEY The identification VARIABLE Unsigned8 1 S 0 R/W 0 to 255
number of the plant unit.
This information may be
used in the host for
sorting alarms, etc.
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2/6 of
permitted and normal FF-891
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of
the error status STRING FF-903
associated with the
hardware or software
components associated
with a block.
7 XD_ERROR Used for all config, H/W, VARIABLE Unsigned8 1 D - R 18 = Process Error
connection failure of 19 = Configuration Error
system problems in the 20 = Electronics Failure
block. 21 = Sensor Failure
Store/Rate (HZ)
Operation
Initial Value
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
LDO
8 EN_LDO_TOT_RESET Enable/Disable LDO ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
Totalizer Reset 0x0001 = enabled
9 EN_LDO_TOT_START_STO Enable/Disable LDO ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
P Totalizer Start/Stop 0x0001 = enabled
option
10 EN_LDO_AUTO_SCROLL Enable/Disable LDO ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
Auto Scroll Feature 0x0001 = enabled
11 EN_LDO_OFFLINE_MENU Enable/Disable LDO ENUM Unsigned16 2 S 1 R/W 0x0000 = disabled
Offline Menu Feature 0x0001 = enabled
12 EN_LDO_OFFLINE_PWD Enable/Disable LDO ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
Offline Password 0x0001 = enabled
Troubleshooting
13 EN_LDO_ALARM_MENU Enable/Disable LDO ENUM Unsigned16 2 S 1 R/W 0x0000 = disabled
Alarm Menu 0x0001 = enabled
14 EN_LDO_ACK_ALL_ALARM Enable/Disable LDO ENUM Unsigned16 2 S 1 R/W 0x0000 = disabled
S Acknowledge All alarms 0x0001 = enabled
feature
15 LDO_OFFLINE_PWD LDO offline password VARIABLE Unsigned16 2 S 1234 R/W 0 - 9999
16 LDO_SCROLL_RATE LDO Scroll rate VARIABLE Unsigned16 2 S 10 R/W -
17 LDO_BACKLIGHT_ON LDO Backlight Control ENUM Unsigned16 2 S 1 R/W 0x0000 = off
0x0001 = on
18 UI_Language Display language ENUM Unsigned16 R-1359 S 0 R/W 0 = English
selection (2) (Any) 1 = German
2 = French
3 = Reserved
4 = Spanish
19 LDO_VAR_1_CODE Display the Variable ENUM Unsigned16 2 S 0 R/W Same as
associated with the (Any) LDO_VAR_2_CODE
code on the LDO
PlantWeb Alerts
TB Reference
Store/Rate (HZ)
Initial Value
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
20 LDO_VAR_2_CODE Display the Variable ENUM Unsigned16 2 S 2 R/W 0 = Mass Flow Rate
associated with the 1 = Temperature
code on the LDO 2 = Mass Total
3 = Density
4 = Mass Inventory
5 = Volume Flow Rate
6 = Volume Total
7 = Volume Inventory
15 = API: Corr Density
16 = API: Corr Vol Flow
17 = API: Corr Vol Total
18 = API: Corr Vol Inv
19 = API: Avg Density
20 = API: Avg Temp
21 = CM: Density At Ref
22 = CM: Density (SGU)
23 = CM: Std Vol Flow
Rate
24 = CM: Std Vol Total
25 = CM: Std Vol
Inventory
26 = CM: Net Mass Flow
27 = CM: Net Mass Total
28 = CM: Net Mass Inv
29 = CM: Net Vol Flow
Rate
30 = CM: Net Vol Total
31 = CM: Net Vol
Inventory
32 = CM: Concentration
33 = API: CTL
46 = Raw Tube
Frequency
47 = Drive Gain
48 = Case Temperature
49 = LPO Amplitude
50 = RPO Amplitude
51 = Board Temperature
52 = Input Voltage
53 = Ext. Input Pressure
54 = Live Zero
55 = Ext. Input Temp
56 = CM: Density
(Baume)
62 = Gas Std Vol Flow
63 = Gas Std Vol Total
64 = Gas Std Vol
Inventory
69 = Live Zero
251 = None
21 LDO_VAR_3_CODE Display the Variable ENUM Unsigned16 2 S 5 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
22 LDO_VAR_4_CODE Display the Variable ENUM Unsigned16 2 S 6 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
23 LDO_VAR_5_CODE Display the Variable ENUM Unsigned16 2 S 3 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
24 LDO_VAR_6_CODE Display the Variable ENUM Unsigned16 2 S 1 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
25 LDO_VAR_7_CODE Display the Variable ENUM Unsigned16 2 S 251 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
26 LDO_VAR_8_CODE Display the Variable ENUM Unsigned16 2 S 251 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
27 LDO_VAR_9_CODE Display the Variable ENUM Unsigned16 2 S 251 R/W Same as
associated with the LDO_VAR_2_CODE
code on the LDO
28 LDO_VAR_10_CODE Display the Variable ENUM Unsigned16 2 S 251 R/W Same as
associated with the LDO_VAR_2_CODE
29 LDO_VAR_11_CODE Display the Variable ENUM Unsigned16 2 S 251 R/W Same as
associated with the LDO_VAR_2_CODE
Store/Rate (HZ)
Operation
Initial Value
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
process variable
selected with index 34
36 UI_UpdatePeriodmsec The period in VARIABLE Unsigned16 R-2621 S 200 R/W 100 to 10000
milliseconds in which (2) (Any)
the display is updated
37 UI_EnableStatusLedBlinking Enable/Disable Display ENUM Unsigned16 C-235 S 1 R/W 0 = Disable
Status LED Blinking (2) (Any) 1 = Enable
38 UI_EnableAlarmPassword Enable/Disable Display ENUM Unsigned16 C-236 S 0 R/W 0 = Disable
Alarm Screen Password (2) (Any) 1 = Enable
Standard FF Parameters
0 BLOCK_STRUCTURE
PlantWeb Alerts
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
LDO
8 EN_LDO_TOT_RESET 2
9 EN_LDO_TOT_START_STOP 2
10 EN_LDO_AUTO_SCROLL 2
11 EN_LDO_OFFLINE_MENU 2
12 EN_LDO_OFFLINE_PWD 2
13 EN_LDO_ALARM_MENU 2
TB Reference
14 EN_LDO_ACK_ALL_ALARMS 2
15 LDO_OFFLINE_PWD 2
16 LDO_SCROLL_RATE 2
17 LDO_BACKLIGHT_ON 2
18 UI_Language 2
19 LDO_VAR_1_CODE 2
20 LDO_VAR_2_CODE 2
21 LDO_VAR_3_CODE 2
22 LDO_VAR_4_CODE 2
23 LDO_VAR_5_CODE 2
24 LDO_VAR_6_CODE 2
25 LDO_VAR_7_CODE 2
26 LDO_VAR_8_CODE 2
27 LDO_VAR_9_CODE 2
28 LDO_VAR_10_CODE 2
29 LDO_VAR_11_CODE 2
30 LDO_VAR_12_CODE 2
31 LDO_VAR_13_CODE 2
32 LDO_VAR_14_CODE 2
33 LDO_VAR_15_CODE 2
34 FBUS_UI_ProcVarIndex 2
35 UI_NumDecimals 2
36 UI_UpdatePeriodmsec 2
37 UI_EnableStatusLedBlinking 2
38 UI_EnableAlarmPassword 2
Totals 9 4 9 65
Initial Value
OD Index
Access
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of STRING OCTET 32 S Spac R/W Any 32 Characters
the intended STRING es
application of the block.
3 STRATEGY The strategy field can VARIABLE Unsigned16 2 S 0 R/W N/A
be used to identify
grouping of blocks.
This data is not
checked or processed
by the block.
4 ALERT_KEY The identification VARIABLE Unsigned8 1 S 0 R/W 0 to 255
number of the plant
unit. This information
may be used in the
host for sorting alarms,
etc.
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2/6 of
permitted and normal FF-891
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of
the error status STRING FF-903
associated with the
hardware or software
components
associated with a
block.
7 XD_ERROR Used for all config, VARIABLE Unsigned8 1 D - R 18 = Process Error
H/W, connection failure 19 = Configuration Error
or system problems in 20 = Electronics Failure
the block. 21 = Sensor Failure
API Process Variables
Troubleshooting
8 API_Corr_Density Temp Corrected VARIABLE DS-65 5 D/20 – R N/A
Density
9 API_Corr_Vol_Flow Temp Corrected VARIABLE DS-65 5 D/20 – R N/A
(Standard) Volume
Flow
10 API_Ave_Corr_Density Batch Weighted VARIABLE DS-65 5 D/20 – R N/A
Average Density
11 API_Ave_Corr_Temp Batch Weighted VARIABLE DS-65 5 D/20 – R N/A
Average Temperature
12 API_CTL CTL VARIABLE DS-65 5 D/20 – R N/A
13 API_Corr_Vol_Total Temp Corrected VARIABLE DS-65 5 D/20 – R N/A
(Standard) Volume
Total
14 API_Corr_Vol_Inv Temp Corrected VARIABLE DS-65 5 D/20 – R N/A
(Standard) Volume
Inventory
15 API_Reset_Vol_Total Reset API Reference METHOD Unsigned16 2 - – N/A 0x0000 = None
Volume Total 0x0001 = Reset
PlantWeb Alerts
API Setup Data
16 EN_API Enable/Disable API ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
0x0001 = enabled
17 API_Ref_Temp API Reference Temp VARIABLE FLOAT 4 S 0 R/W
18 API_TEC API Thermal VARIABLE FLOAT 4 S 0 R/W
Expansion Coeff
19 API_Table_Type API 2540 CTL Table ENUM Unsigned16 2 S 0 R/W 17 = Table 5A
Type 18 = Table 5B
19 = Table 5D
36 = Table 6C
49 = Table 23A
50 = Table 23B
51 = Table 23D
68 = Table 24C
81 = Table 53A
82 = Table 53B
83 = Table 53D
100 = Table 54C
20 API_FEATURE_KEY Enabled Features STRING BIT 2 S - R 0x0000 = standard
STRING 0x0010 = Meter Verify.
0x0080 = PID
0x0800 = Enh. Density
0x1000 = API
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
API Process Variables
8 API_Corr_Density 5 5
9 API_Corr_Vol_Flow 5 5
Operation
10 API_Ave_Corr_Density 5 5
11 API_Ave_Corr_Temp 5 5
12 API_CTL 5 5
13 API_Corr_Vol_Total 5 5
14 API_Corr_Vol_Inv 5 5
15 API_Reset_Vol_Total 2
API Setup Data
16 EN_API 2
17 API_Ref_Temp 4
18 API_TEC 4
19 API_Table_Type 2
20 API_FEATURE_KEY 2
Troubleshooting
21 SNS_ResetAPIGSVInv 2
22 API_TEMPERATURE_UNITS 2
23 API_DENSITY_UNITS 2
24 API_VOL_FLOW_UNITS 2
Totals 44 12 44 19
Initial Value
PlantWeb Alerts
OD Index
Access
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the VARIABLE DS_64 5 S N/A R/W N/A
transducer block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A
static data associated
with the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of STRING OCTET 32 S Spac R/W Any 32 Characters
the intended application STRING es
of the block.
3 STRATEGY The strategy field can be VARIABLE Unsigned16 2 S 0 R/W N/A
used to identify grouping
of blocks. This data is
not checked or
processed by the block.
4 ALERT_KEY The identification VARIABLE Unsigned8 1 S 0 R/W 0 to 255
TB Reference
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
6 BLOCK_ERR This parameter reflects STRING BIT 2 D/20 - R See section 4.8 of
the error status STRING FF-903
associated with the
hardware or software
components associated
with a block.
7 XD_ERROR Used for all config, H/W, VARIABLE Unsigned8 1 D - R 18 = Process Error
connection failure or 19 = Configuration Error
system problems in the 20 = Electronics Failure
block. 21 = Sensor Failure
CM Process Variables
8 CM_Ref_Dens Density At Reference VARIABLE DS-65 5 D/20 – R N/A
9 CM_Spec_Grav Density (Fixed SG Units) VARIABLE DS-65 5 D/20 – R N/A
10 CM_Std_Vol_Flow Standard Volume Flow VARIABLE DS-65 5 D/20 – R N/A
Rate
11 CM_Net_Mass_Flow Net Mass Flow Rate VARIABLE DS-65 5 D/20 – R N/A
12 CM_Net_Vol_Flow Net Volume Flow Rate VARIABLE DS-65 5 D/20 – R N/A
13 CM_Conc Concentration VARIABLE DS-65 5 D/20 – R N/A
14 CM_Baume Density (Fixed Baume VARIABLE DS-65 5 D/20 – R N/A
Units)
CM Totals
15 CM_Std_Vol_Total Standard Volume Total VARIABLE DS-65 5 D/20 – R N/A
16 CM_Std_Vol_Inv Standard Volume VARIABLE DS-65 5 D/20 – R N/A
Inventory
17 CM_Net_Mass_Total Net Mass Total VARIABLE DS-65 5 D/20 – R N/A
18 CM_Net_Mass_Inv Net Mass Inventory VARIABLE DS-65 5 D/20 – R N/A
19 CM_Net_Vol_Total Net Volume Total VARIABLE DS-65 5 D/20 – R N/A
20 CM_Net_Vol_Inv Net Volume Inventory VARIABLE DS-65 5 D/20 – R N/A
21 CM_Reset_Std_Vol_Total Reset CM Standard METHOD Unsigned16 2 - 0 N/A 0x0000 = None
Volume Total 0x0001 = Reset
22 CM_Reset_Net_Mass_Total Reset CM Net Mass METHOD Unsigned16 2 - 0 N/A 0x0000 = None
Total 0x0001 = Reset
23 CM_Reset_Net_Vol_Total Reset CM Net Volume METHOD Unsigned16 2 - 0 N/A 0x0000 = None
Total 0x0001 = Reset
CM Setup Data
24 EN_CM Enable/Disable ENUM Unsigned16 2 S 0 R/W 0x0000 = disabled
Concentration 0x0001 = enabled
Measurement
25 CM_Curve_Lock Lock Concentration ENUM Unsigned16 2 S 0 R/W 0x0000 = not locked
Measurement Tables 0x0001 = locked
26 CM_Mode Concentration ENUM Unsigned16 2 S 0 R/W 0 = None
Measurement Mode 1 = Dens @ Ref Temp
2 = Specific Gravity
3 = Mass Conc (Dens)
4 =Mass Conc (SG)
5 = Volume Conc (Dens)
6 = Volume Conc (SG)
7 = Concentration (Dens)
8 = Concentration (SG)
27 CM_Active_Curve Active Calculation Curve VARIABLE Unsigned16 2 S 0 R/W 0 through 5
28 CM_Curve_Index Curve Configuration VARIABLE Unsigned16 2 S 0 R/W 0 through 4
Index (n)
29 CM_Temp_Index Curven Temperature VARIABLE Unsigned16 2 S 0 R/W 0 through 5
Isotherm Index (x-axis)
30 CM_Conc_Index Curven Concentration VARIABLE Unsigned16 2 S 0 R/W 0 through 5
Index (y-axis)
Store/Rate (HZ)
Operation
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Troubleshooting
Temp)
36 CM_Dens_At_Conc_Coeff Curven (5x1) Coeff at VARIABLE FLOAT 4 S 0 R/W
ConcentrationY (at Ref
Temp)
37 CM_Conc_Label_51 Curven (5x1) VARIABLE FLOAT 4 S 0 R/W
ConcentrationY Value
(y-axis)
38 CM_Ref_Temp Curven Reference VARIABLE FLOAT 4 S 0 R/W
Temperature
39 CM_SG_Water_Ref_Temp Curven SG Water VARIABLE FLOAT 4 S 0 R/W
Reference Temperature
40 CM_SG_Water_Ref_Dens Curven SG Water VARIABLE FLOAT 4 S 0 R/W
Reference Density
41 CM_Slope_Trim Curven Slope Trim VARIABLE FLOAT 4 S 0 R/W
42 CM_Slope_Offset Curven Offset Trim VARIABLE FLOAT 4 S 0 R/W
43 CM_Extrap_Alarm_Limit Curven Extrapolation VARIABLE FLOAT 4 S 0 R/W
Alarm Limit: %
44 CM_Curve_Name Curven ASCII String – VARIABLE OCTET 12 S ““ R/W
PlantWeb Alerts
Name of Curve – 12 STRING
chars supported
45 CM_Max_Fit_Order Maximum Fit Order for VARIABLE Unsigned16 2 S 0 R/W 2, 3, 4, 5
5x5 curve
46 CM_Fit_Results Curven Curve Fit Results ENUM Unsigned16 2 S 0 R 0 = Good
1 = Poor
2 = Failed
3 = Empty
47 CM_Conc_Unit_Code Curven Concentration ENUM Unsigned16 2 S 0 R/W 1110 = Degrees Twaddell
Units Code 1426 = Degrees Brix
1111 = Deg Baume
(heavy)
1112 = Deg Baume (light)
1343 = % sol/wt
1344 = % sol/vol
1427 = Degrees Balling
1428 = Proof Per Volume
1429 = Proof Per mass
1346 = Percent Plato
48 CM_Expected_Acc Curven Curve Fit VARIABLE FLOAT 4 S 0 R
Expected Accuracy
49 CM_FEATURE_KEY Enabled Features STRING BIT 2 S - R 0x0000 = standard
STRING 0x0010 = Meter Verify.
TB Reference
0x0080 = PID
0x0800 = Enh. Density
0x1000 = API
v4.0 Additions
50 SNS_ResetCMVolInv Reset CM Volume Method Unsigned16 C-019 S 0 R/W 0x0000 = No Effect
Inventory (2) 5 (Any) 0x0001 = Reset
51 SNS_ResetCMNetMassInv Reset CM Net Mass Method Unsigned16 C-019 S 0 R/W 0x0000 = No Effect
Inventory (2) 6 (Any) 0x0001 = Reset
Store/Rate (HZ)
Initial Value
OD Index
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
52 SNS_ResetCMNetVolInv Reset CM Net Volume Method Unsigned16 C-019 S 0 R/W 0x0000 = No Effect
Inventory (2) 7 (Any) 0x0001 = Reset
53 SNS_CM_ResetFlag Reset All Concentration Method Unsigned16 C-249 S 1 R/W 0x0000 = Not used
Measurement Curve (2) (OOS) 0x0001 = Reset
Information
54 SNS_CM_EnableDensLow Enable Low Density ENUM Unsigned16 C-250 S 1 R/W 0x0000 = Disable
Extrap Extrapolation Alarm (2) (Any) 0x0001 = Enable
55 SNS_CM_EnableDensHigh Enable High Density ENUM Unsigned16 C-251 S 1 R/W 0x0000 = Disable
Extrap Extrapolation Alarm (2) (Any) 0x0001 = Enable
56 SNS_CM_EnableTempLow Enable Low ENUM Unsigned16 C-252 S 1 R/W 0x0000 = Disable
Extrap Temperature (2) (Any) 0x0001 = Enable
Extrapolation Alarm
57 SNS_CM_EnableTempHigh Enable High ENUM Unsigned16 C-253 S 1 R/W 0x0000 = Disable
Extrap Temperature (2) (Any) 0x0001 = Enable
Extrapolation Alarm
58 CM_TEMPERATURE_ Temperature Unit ENUM Unsigned16 R-004 S C° R 0000 = None
UNITS (2) 1 1000 = K
1001 = Deg C
1002 = Deg F
1003 = Deg R
59 CM_DENSITY_UNITS Density Unit ENUM Unsigned16 R-004 S g/cm3 R 0000 = None
(2) 0 1097 = kg/m3
1100 = g/cm3
1103 = kg/L
1104 = g/ml
1105 = g/L
1106 = lb/in3
1107 = lb/ft3
1108 = lb/gal
1109 = Ston/yd3
1113 = DegAPI
1114 = SGU
60 CM_VOL_FLOW_UNITS Standard or special ENUM Unsigned16 R-004 S l/s R 0000 = None
volume flow rate unit (2) 2 1347 = m3/s
1348 = m 3/min
1349 = m3/hr
1350 = m3/day
1351 = L/s
1352 = L/min
1353 = L/hr
1355 = Ml/day
1356 = CFS
1357 = CFM
1358 = CFH
1359 = ft3/day
1362 = gal/s
1363 = GPM
1364 = gal/hour
1365 = gal/day
1366 = Mgal/day
1367 = ImpGal/s
1368 = ImpGal/min
1369 = ImpGal/hr
1370 = Impgal/day
1371 = bbl/s
1372 = bbl/min
1373 = bbl/hr
1374 = bbl/day
Operation
Standard FF Parameters
0 BLOCK_STRUCTURE
1 ST_REV 2 2 2 2
2 TAG_DESC
3 STRATEGY 2
4 ALERT_KEY 1
5 MODE_BLK 4 4
6 BLOCK_ERR 2 2
7 XD_ERROR 1 1
CM Process Variables
8 CM_Ref_Dens 5 5
9 CM_Spec_Grav 5 5
Troubleshooting
10 CM_Std_Vol_Flow 5 5
11 CM_Net_Mass_Flow 5 5
12 CM_Net_Vol_Flow 5 5
13 CM_Conc 5 5
14 CM_Baume 5 5
CM Totals
15 CM_Std_Vol_Total 5 5
16 CM_Std_Vol_Inv 5 5
17 CM_Net_Mass_Total 5 5
18 CM_Net_Mass_Inv 5 5
19 CM_Net_Vol_Total 5 5
20 CM_Net_Vol_Inv 5 5
21 CM_Reset_Std_Vol_Total 2
22 CM_Reset_Net_Mass_Total 2
PlantWeb Alerts
23 CM_Reset_Net_Vol_Total 2
CM Setup Data
24 EN_CM 2
25 CM_CURVE_LOCK 2
26 CM_Mode 2
27 CM_Active_Curve 2
28 CM_Curve_Index 2
29 CM_Temp_Index 2
30 CM_Conc_Index 2
31 CM_Temp_ISO 4
32 CM_Dens_At_Temp_ISO 4
33 CM_Dens_At_Temp_Coeff 4
34 CM_Conc_Label_55 4
35 CM_Dens_At_Conc 4
TB Reference
36 CM_Dens_At_Conc_Coeff 4
37 CM_Conc_Label_51 4
38 CM_Ref_Temp 4
39 CM_SG_Water_Ref_Temp 4
40 CM_SG_Water_Ref_Dens 4
41 CM_Slope_Trim 4
42 CM_Slope_Offset 4
43 CM_Extrap_Alarm_Limit 4
44 CM_Curve_Name 12
45 CM_Max_Fit_Order 2
46 CM_Fit_Results 2
47 CM_Conc_Unit_Code 2
48 CM_Expected_Acc 4
49 CM_FEATURE_KEY 2
v4.0 Additions
50 SNS_ResetCMVolInv 2
51 SNS_ResetCMNetMassInv 2
52 SNS_ResetCMNetVolInv 2
53 SNS_CM_ResetFlag 2
54 SNS_CM_EnableDensLowExtrap 2
55 SNS_CM_EnableDensHighExtrap 2
56 SNS_CM_EnableTempLowExtrap 2
57 SNS_CM_EnableTempHighExtrap 2
v6.0 Additions
58 CM_TEMPERATURE_UNITS 2
59 CM_DENSITY_UNITS 2
60 CM_VOL_FLOW_UNITS 2
Totals 74 24 76 99
RB Reference
Model 2700 Resource Block Reference
Store/Rate (HZ)
Initial Value
OD Index
Diagrams
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Standard FF Parameters
0 BLOCK_STRUCTURE Beginning of the resource VARIABLE DS_64 5 S N/A R/W N/A 1.0
block
1 ST_REV The revision level of the VARIABLE Unsigned16 2 S 0 R N/A 1.0
static data associated with
the function block.
Incremented with each
write of static store.
2 TAG_DESC The user description of the STRING OCTET 32 S Spac R/W Any 32 Characters 1.0
intended application of the STRING es
block.
3 STRATEGY The strategy field can be VARIABLE Unsigned16 2 S 0 R/W N/A 1.0
used to identify grouping
of blocks. This data is not
checked or processed by
375 Communicator
the block.
4 ALERT_KEY The identification number VARIABLE Unsigned8 1 S 0 R/W 0 to 255 1.0
of the plant unit. This
information may be used
in the host for sorting
alarms, etc.
5 MODE_BLK The actual, target, RECORD DS-69 4 mix Auto R/W See section 2.6 of FF-891 1.0
permitted and normal
modes of the block.
6 BLOCK_ERR This parameter reflects STRING BIT STRING 2 D/20 - R bit 0 = Other 1.0
the error status associated bit 1 = Block Config Error
with the hardware or bit 3 = Simulate Active
software components bit 6 = Maintenance Soon
associated with a block. bit 7 = Input Failure
bit 8 = Output Failure
bit 9 = Memory Failure
bit 11 = Lost NV Data
bit 13 = Maintenance Now
bit 15 = Out of Service
7 RS_STATE Contains the operational VARIABLE Unsigned8 1 D/20 - R 0 = Invalid State 1.0
state of the Function Block 1 = Start/Restart
Application. 2 = Initialization
3 = On-Line Linking
4 = On-Line
5 = Standby
6 = Failure
ProLink
Store/Rate (HZ)
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
10 MANUFAC_ID Manufacturer identification ENUM Unsigned32 4 S 0x00 R 0x000310 = Micro Motion 1.0
number - used by an 0310
interface device to locate
the DD file for the
resource.
11 DEV_TYPE Manufacturer’s model ENUM Unsigned16 2 S 0x20 R 0x2000 = 2700 1.0
number associated with 00
the resource - used by
interface devices to locate
the DD file for the
resource.
12 DEV_REV(1) Manufacturer revision VARIABLE Unsigned8 1 S 4 R 1.0
number associated with
the resource - used by an
interface device to locate
the DD file for the
resource.
13 DD_REV(1) Revision of the DD VARIABLE Unsigned8 1 S 1 R 1.0
associated with the
resource - used by an
interface device to locate
the DD file for the
resource.
14 GRANT_DENY Options for controlling RECORD DS-70 2 S 0.0 R/W 1.0
access of host computer
and local control panels to
operating, tuning and
alarm parameters of the
block.
15 HARD_TYPES The types of hardware ENUM Bit String 2 S 0x80 R 0x80 = SCALAR_INPUT 1.0
available as channel
numbers.
16 RESTART Allows a manual restart to ENUM Unsigned8 1 D 1 R/W 1 = Run 1.0
be initiated. Several 2 = Restart resource
degrees of restart are 3 = Restart with defaults
possible. 4 = Restart processor
17 FEATURES Used to show supported ENUM Bit String 2 S 0x10 R 0x0010 = SoftWriteLock 1.0
resource block options. | 0x0020 = FailSafe
0x20 0x0040 = Report
| 0x0080 = Unicode
0x40
|
0x80
18 FEATURE_SEL Used to select resource ENUM Bit String 2 S 0x10 R/W 0x0010 = SoftWriteLock 1.0
block options. 0x0020 = FailSafe
0x0040 = Report
0x0080 = Unicode
19 CYCLE_TYPE Identifies the block ENUM Bit String 2 S 0x80 R 0x0080 = CycleScheduled 1.0
execution methods | 0x0040 = BlockComplete
available for this resource. 0x40
20 CYCLE_SEL Used to select the block ENUM Bit String 2 S 0 RW 0x0080 = CycleScheduled 1.0
execution method for this 0x0040 = BlockComplete
resource.
21 MIN_CYCLE_T Time duration of the VARIABLE Unsigned32 4 S 8000 R 1.0
shortest cycle interval of
which the resource is
capable. Measured in 1/32
millisecond.
22 MEMORY_SIZE Available configuration VARIABLE Unsigned16 2 S 8 R 1.0
memory in the empty
resource in Kbytes. To be
checked before attempting
a download.
Store/Rate (HZ)
RB Reference
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Diagrams
25 FREE_TIME Percent of the block VARIABLE Float 4 D - R 0-100 Percent 1.0
processing time that is
free to process additional
blocks.
26 SHED_RCAS Time duration in 1/32 VARIABLE Unsigned32 4 S 6400 R/W 1.0
millisec at which to give up 00
on computer writes to
function block RCas
locations. Shed from
RCas shall never happen
when SHED_RCAS = 0.
27 SHED_ROUT Time duration in 1/32 VARIABLE Unsigned32 4 S 6400 R/W 1.0
millisec at which to give up 00
on computer writes to
function block ROut
locations. Shed from Rout
shall never happen when
SHED_ROUT = 0.
28 FAULT_STATE Condition set by loss of ENUM Unsigned8 1 N 1 R 1 = Clear 1.0
communication to an 2 = Active
output block, fault
375 Communicator
promoted to an output
block or a physical
contact. When Fault State
condition is set, Then
output function blocks will
perform their FSTATE
actions.
29 SET_FSTATE Allows the Fault State ENUM Unsigned8 1 D 1 R/W 1 = Off 1.0
condition to be manually 2 = Set
initiated by selecting Set.
30 CLR_FSTATE Writing a Clear to this ENUM Unsigned8 1 D 1 R/W 1 = Off 1.0
parameter will clear the 2 = Set
device fault state if the
field condition, if any, has
cleared.
31 MAX_NOTIFY Maximum number of VARIABLE Unsigned8 1 S 5 R 1.0
unconfirmed notify
messages possible.
32 LIM_NOTIFY Maximum number of VARIABLE Unsigned8 1 S 5 R/W 0 to MAX_NOTIFY 1.0
unconfirmed alert notify
messages allowed.
33 CONFIRM_TIME The time in 1/32 millisec VARIABLE Unsigned32 4 S 6400 R/W 1.0
the resource will wait for 00
confirmation of receipt of a
report before trying again.
ProLink
Store/Rate (HZ)
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Store/Rate (HZ)
RB Reference
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Diagrams
neck label.
61 DETAILED_STATUS Additional status. ENUM bit string 4 D - R 0x00000001 = RAM Err 1.0
0x00000002 = ROM Err
0x00000008 = NV Err
0x00000020 = Mfg Blk Err
0x00000040 = TB Err
0x00002000 = Lost
Deferred NV Data
0x00004000 = NV Writes
Deferred
62 SUMMARY_STATUS An enumerated value of ENUM unsigned8 1 D - R 0 = Uninitialized 1.0
repair analysis 1 = No repair needed
2 = Repairable
3 = Call service center
63 MESSAGE_DATE Date associated with the RECORD time of day 6 S 0 R/W 1.0
MESSAGE_TEXT
parameter
64 MESSAGE_TEXT Used to indicate changes STRING octet string 96 S spac R/W 1.0
made by the user to the es
device’s installation,
375 Communicator
configuration, or
calibration.
65 SELF_TEST Allows a manual self test ENUM unsigned8 1 D 1 R/W 0 = Uninitialized 1.0
to be initiated. 1 = No test
2 = Self-test
66 DEFINE_WRITE_LOCK Enumerated value ENUM unsigned8 1 S 1 R/W 0 = Uninitialized 1.0
describing the 1 = Everything locked
implementation of the 2 = Only the resource and
WRITE_LOCK. transducer locked
(physical device)
67 SAVE_CONFIG_NOW Allows a user to write any ENUM unsigned8 1 D 1 R/W 0 = Uninitialized 1.0
pending values to 1 = No Save
non-volatile memory. 2 = Burn EEPROM with
latest values
68 SAVE_CONFIG_BLOCKS Number of EEPROM VARIABLE unsigned8 1 D 0 R 1.0
blocks that have been
modified since last burn.
This value will count down
to zero when the
configuration is saved.
START_WITH_DEFAULT Indicates action taken ENUM unsigned8 1 D 0 R/W 0 = Uninitialized 1.0
S when a device is power 1 = do not power-up with
cycled. NV defaults
2 = power-up with default
node address
ProLink
Store/Rate (HZ)
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
SECURITY_IO Micro Motion 2700 does ENUM unsigned8 1 D 0 R 1 = switch in “off” position 1.0
not use this. 2 = switch in “on” position
Status of Security switch
SIMULATE_STATE The state of the simulate ENUM unsigned8 1 D 0 R 1 = switch off, simulation 1.0
jumper not allowed
2 = switch on, simulation
not allowed (need to cycle
switch)
3 = switch on, simulation
allowed
DOWNLOAD_MODE Micro Motion 2700 does ENUM unsigned8 1 D 1 0 = Uninitialized 1.0
not use this. 1 = Run Mode
Gives access to the boot 2 = Download Mode
block code for over the
wire downloads.
RECOMMENDED_ACTI Enumerated list of VARIABLE unsigned16 2 D - R 0 = Uninitialized 3.0
ON recommended actions 1 = No action required
displayed with a device 2 = Electronics Fail
alert. 3 = Xmtr Initializing
4 = CP/Xmtr Err
5 = Xmtr not Charize
6 = Sensor Failed
7 = Mass Flow OOR
8 = Density OOR
9 = Temp OOR
10 = Tube Not Full
11 = CM Bad Curve fit
12 = Low Power
13 = Meter Verification err
14 = Cal Failed
15 = Slug Flow
16 = Drive OOR
17 = Possible Data Loss
18 = API PV OOR
19 = CM Extrapolation Err
20 = Sensor Simulate
21 = PWA Simulate
22 = NV Write Deferred
23 = Cal in progress
FAILED_PRI Designates the alarming VARIABLE unsigned8 1 S 0 R/W 0 - 15 3.0
priority of the
FAILED_ALM.
FAILED_ENABLE Enabled FAILED_ALM ENUM bit string 4 D 0 R bit 0 = No error 3.0
alarm conditions. bit 2 = Electronics Fail
Corresponds bit for bit to bit 3 = Xmtr Initializing
the FAILED_ACTIVE. A bit bit 4 = CP/Xmtr Err
on means that the bit 5 = Xmtr not Charize
corresponding alarm bit 6 = Sensor Failed
condition is enabled and bit 7 = Mass Flow OOR
will be detected. A bit off bit 8 = Density OOR
means the corresponding bit 9 = Temp OOR
alarm condition is disabled bit 10 = Tube not Full
and will not be detected. bit 11 = CM Bad Curve fit
bit 12 = Low Power
bit 13 = Meter Verif. Error
bit 14 = Cal Failed
bit 16 = Slug Flow
bit 17 = Drive OOR
bit 18 = Data loss possible
bit 19 = API PV OOR
bit 20 = CM Extrapolation
bit 26 = Sensor Simulate
bit 27 = PWA Simulate
bit 28 = NV Write Deferred
bit 29 = Cal in progress
FAILED_MASK Mask of Failure Alarm. ENUM bit string 4 D 0 R/W See FAILED_ENABLE 3.0
Corresponds bit for bit to
the FAILED_ACTIVE. A bit
on means that the failure
is masked out from
alarming.
FAILED_ACTIVE Enumerated list of failed ENUM bit string 4 D 0 R/W if See FAILED_ENABLE 3.0
conditions within a device. PWA
Bits that are set indicate simulat
that condition exists. e on,
else R
Store/Rate (HZ)
RB Reference
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
Diagrams
MAINT _MASK Mask of Maintenance ENUM bit string 4 D 0 R/W See FAILED_ENABLE 3.0
Alarm. Corresponds bit for
bit to the MAINT_ACTIVE.
A bit on means that the
failure is masked out from
alarming.
MAINT _ACTIVE Enumerated list of ENUM bit string 4 D 0 R/W if See FAILED_ENABLE 3.0
Maintenance conditions PWA
within a device. Bits that simulat
are set indicate that e on,
condition exists. else R
MAINT _ALM Alarm indicating the RECORD DS-72 13 D - 3.0
device needs
maintenance soon. If the
condition is ignored, the
device will eventually fail.
ADVISE_PRI Designates the alarming VARIABLE unsigned8 1 S 0 R/W 0 - 15 3.0
priority of the
ADVISE_ALM.
375 Communicator
ADVISE_ENABLE Enabled ADVISE_ALM ENUM bit string 4 D 0 R See FAILED_ENABLE 3.0
alarm conditions.
Corresponds bit for bit to
the ADVISE_ACTIVE. A
bit on means that the
corresponding alarm
condition is enabled and
will be detected. A bit off
means the corresponding
alarm condition is disabled
and will not be detected.
ADVISE _MASK Mask of Advisory Alarm. ENUM bit string 4 D 0 R/W See FAILED_ENABLE 3.0
Corresponds bit for bit to
the ADVISE_ACTIVE. A
bit on means that the
failure is masked out from
alarming.
ADVISE _ACTIVE Enumerated list of ENUM bit string 4 D 0 R/W if See FAILED_ENABLE 3.0
advisory conditions within PWA
a device. Bits that are set simulat
indicate that condition e on,
exists. else R
ProLink
Store/Rate (HZ)
Initial Value
OD Index
Release
Access
Message Data Type/ Enumerated List of
Parameter Mnemonic Definition Type Structure Size Values
(1) The initial value is based on transmitter software version 4.0. If the transmitter contains a later version of software, the initial value
may be different.
0 ST_REV 2 2 2 2 2 2 2
1 TAG_DESC
2 STRATEGY 2
3 ALERT_KEY 1
4 MODE_BLK 4 4
5 BLOCK_ERR 2 2
6 RS_STATE 1 1
7 TEST_RW
8 DD_RESOURCE
9 MANUFAC_ID 4
10 DEV_TYPE 2
11 DEV_REV 1
12 DD_REV 1
13 GRANT_DENY 2
14 HARD_TYPES 2
RB Reference
Index Parameter Mnemonic View 1 View 2 View 3 View 3_1 View 4 View 4_1 View 4_2
15 RESTART
16 FEATURES 2
17 FEATURE_SEL 2
18 CYCLE_TYPE 2
19 CYCLE_SEL 2
20 MIN_CYCLE_T 4
21 MEMORY_SIZE 2
22 NV_CYCLE_T 4
23 FREE_SPACE 4
24 FREE_TIME 4 4
25 SHED_RCAS 4
26 SHED_ROUT 4
27 FAULT_STATE 1 1
Diagrams
28 SET_FSTATE
29 CLR_FSTATE
30 MAX_NOTIFY 1
31 LIM_NOTIFY 1
32 CONFIRM_TIME 4
33 WRITE_LOCK 1
34 UPDATE_EVT
35 ST_REV 2 2 2 2 2 2 2
36 BLOCK_ALM
37 ALARM_SUM 8 8
38 ACK_OPTION 2
39 WRITE_PRI 1
40 WRITE_ALM
375 Communicator
41 ITK_VER 2
42 DISTRIBUTOR 4
43 DEV_STRING 32
44 XD_OPTIONS 4
45 FB_OPTIONS 4
46 DIAG_OPTIONS 4
47 MISC_OPTIONS 4
48 RB_SFTWR_REV_MAJOR
49 RB_SFTWR_REV_MINOR
50 RB_SFTWR_REV_BUILD
51 RB_SFTWR_REV_ALL 48
52 HARDWARE_REV 1
53 OUTPUT_BOARD_SN 4
54 FINAL_ASSY_NUM 4
55 DETAILED_STATUS 4
ProLink
56 SUMMARY_STATUS 1
57 MESSAGE_DATE 6
58 MESSAGE_TEXT 96
59 SELF_TEST 1
60 DEFINE_WRITE_LOCK 1
61 SAVE_CONFIG_NOW 1
62 SAVE_CONFIG_BLOCKS 1 1
63 START_WITH_DEFAULTS 1 1
64 SIMULATE_IO 1
65 SECURITY_IO 1
66 SIMULATE_STATE 1
67 DOWNLOAD_MODE
68 RECOMMENDED_ACTION 2
69 FAILED_PRI 1
70 FAILED_ENABLE 4
71 FAILED_MASK 4
72 FAILED_ACTIVE 4
73 FAILED_ALM 13
74 MAINT_PRI 1
75 MAINT_ENABLE 4
76 MAINT _MASK 4
77 MAINT _ACTIVE 4
78 MAINT _ALM 13
79 ADVISE_PRI 1
80 ADVISE_ENABLE 4
81 ADVISE _MASK 4
82 ADVISE _ACTIVE 4
83 ADVISE _ALM 13
84 HEALTH_INDEX 1
85 PWA_SIMULATE 1
Totals 25 31 22 67 31 117 126
RB Reference
Flowmeter Installation Types and Components
D.1 Overview
This appendix provides illustrations of different flowmeter installations and components for the
Model 2700 transmitter.
Diagrams
• Integral
• 4-wire remote
• 9-wire remote
• Remote core processor with remote transmitter
See Figure D-1.
375 Communicator
Figure D-4 shows the transmitter/core processor assembly in 9-wire remote installations.
In remote core processor with remote transmitter installations, the core processor is installed
stand-alone. See Figure D-5.
Sensor
4-wire cable
Core processor
(standard or enhanced)
Transmitter
9-wire remote
Sensor
Core processor
(standard only)
9-wire cable
Junction box
4-wire cable
Sensor
Core processor
(standard only)
9-wire cable
Junction box
RB Reference
Transmitter
Transition ring
Core processor
Base
Sensor
Diagrams
Figure D-3 Transmitter components, junction end-cap removed – 4-wire remote and remote core processor
with remote transmitter installations –
Ground lug
Main enclosure
Conduit opening
for 4-wire cable
Mounting bracket
375 Communicator
Junction housing
4 X Cap screws
(4 mm)
Junction end-cap
Mating connector
socket
Mating connector
ProLink
Figure D-4 Transmitter/core processor assembly exploded view – 9-wire remote installations
Transmitter
Core processor
Conduit opening
for 9-wire cable
End-cap
Mounting bracket
Mounting bracket
End-cap
Figure D-6 4-wire cable between Model 2700 transmitter and standard core processor
RB Reference
Core processor User-supplied or Mating connector
terminals factory-supplied 4-wire cable (transmitter)
VDC+ (Red)
RS-485/B (Green)
RS-485/A (White)
VDC– (Black)
Diagrams
Figure D-7 4-wire cable between Model 2700 transmitter and enhanced core processor
VDC+ (Red)
ProLink
Figure D-8 9-wire cable between sensor junction box and core processor
Fieldbus terminals 1
2
9 (–, N)
10 (+, L)
Equipment
ground
7
8
Service port
RB Reference
Connecting with the Field Communicator
E.1 Overview
The Field Communicator is a handheld configuration and management tool for FOUNDATION
fieldbus-compatible devices, including the Micro Motion Model 2700 transmitter. This appendix
provides basic information for connecting the Field Communicator to your transmitter.
The instructions in this manual assume that users are already familiar with the Communicator and can
perform the following tasks:
Diagrams
• Turn on the Communicator
• Navigate the Communicator menus
• Transmit and receive configuration information between the Communicator and FOUNDATION
fieldbus-compatible devices
• Use the alpha keys to type information
If you are unable to perform the tasks listed above, consult the Communicator manual before
attempting to use the Communicator. The documentation is available on the Micro Motion web site
(www.micromotion.com).
Note: In this manual, procedures identified as performed with a fieldbus host can be accomplished
with a Field Communicator.
375 Communicator
E.2 Viewing the device descriptions
To access all of the features of the Model 2700 transmitter with FOUNDATION fieldbus, the Field
Communicator must have the device description (DD) for version 6.x devices. DD files are available
in the Products section of the Micro Motion web site (www.micromotion.com).
To view the Model 2700 device descriptions that are installed on your Field Communicator:
1. In the Foundation fieldbus application menu, choose Utility, then Available Device
Descriptions List.
2. Expand the Micro Motion, Inc. branch, then expand the 2000 branch.
3. If you do not have a Dev Rev 6 device description installed, you will need to obtain it in order
to use the functionality described in this manual. Contact Micro Motion.
+ + + +
– +– – – –
Communicator
Transmitters
–
Terminator Terminator
Fieldbus host
control system
24 VDC power
supply Communicator
RB Reference
Connecting with ProLink II or Pocket ProLink
Software
F.1 Overview
ProLink II is a Windows-based configuration and management tool for Micro Motion transmitters. It
provides complete access to transmitter functions and data.
This chapter provides basic information for connecting ProLink II to your transmitter. The following
Diagrams
topics and procedures are discussed:
• Requirements (see Section F.2)
• Configuration upload/download (see Section F.3)
• Connecting to a Model 2700 transmitter (see Section F.4)
The instructions in this manual assume that users are already familiar with ProLink II software. For
more information on using ProLink II, see the ProLink II manual.
F.2 Requirements
To use ProLink II with a Model 2700 transmitter, the following are required:
• ProLink II v2.0 or later for most basic functions
375 Communicator
• ProLink II v2.91 or later for access to many advanced functions, such as Smart Meter
Verification
• An RS-485 to RS-232 signal converter, to convert the PC port’s signal to the signal used by the
transmitter. For computers without serial ports, certain USB to RS-232 converters can be used
in conjunction with the RS-232 to RS-485 converter. Both types of converter are available
from Micro Motion.
• 25-pin to 9-pin adapter (if required by your PC)
Note: If you are using the enhanced core processor and you connect directly to the core processor’s
RS-485 terminals (see Appendix D) instead of to the transmitter, ProLink II v2.4 or later is required.
This connection type is sometimes used for troubleshooting.
WARNING
Opening the wiring compartment in a hazardous area can cause an
explosion.
Because the wiring compartment must be open to make this connection, the
service port should be used only for temporary connections, for example, for
configuration or troubleshooting purposes.
When the transmitter is in an explosive atmosphere, do not use the service port
to connect to the transmitter.
RB Reference
WARNING
Opening the power supply compartment can expose the operator to
electric shock.
To avoid the risk of electric shock, do not touch the power supply wires or
terminals while using the service port.
4. Connect the signal converter leads to the service port terminals. See Figure F-2.
Diagrams
RS-485B 25 to 9 pin serial port
adapter (if necessary)
RS-485A
RS-485 to RS-232
Service port signal converter
375 Communicator
5. Start ProLink II. Choose Connection > Connect to Device. In the screen that appears,
specify:
• Protocol: Service Port
• COM Port: as appropriate for your PC
All other parameters are set to service port required values and cannot be changed.
6. Click Connect.
7. If an error message appears:
a. Swap the leads between the two service port terminals and try again.
b. Ensure that you are using the correct COM port.
c. Check all the wiring between the PC and the transmitter.
ProLink
Display
G.1 Overview
This appendix describes the basic use of the display and provides a menu tree for the display. You can
use the menu tree to locate and perform display commands quickly.
Note that Model 2700 transmitters can be ordered with or without displays. Not all configuration and
use functions are available through the display. If you need the added functionality, or if your
transmitter does not have a display, you must use either a fieldbus host or ProLink II.
NE53 History
G.2 Components
Figure G-1 illustrates the display components.
Index
Scroll optical switch
Select optical switch
CAUTION
Attempting to activate an optical switch by inserting an object into the
opening can damage the equipment.
To avoid damage to the optical switches, do not insert an object into the openings.
Use your fingers to activate the optical switches.
Display
ProLink II
To enter the display menu system:
1. Activate Scroll and Select simultaneously.
2. Hold Scroll and Select until the words SEE ALARM or OFF-LINE MAINT appear.
Note: Access to the display menu system may be enabled or disabled. If disabled, the OFF-LINE
MAINT option does not appear. For more information, see Section 4.18.1.
If no optical switch activity occurs for two minutes, the transmitter will exit the off-line menu system
and return to the process variable display.
To move through a list of options, activate Scroll.
To select from a list or to enter a lower-level menu, scroll to the desired option, then activate Select. If
a confirmation screen is displayed:
NE53 History
• To confirm the change, activate Select.
• To cancel the change, activate Scroll.
To exit a menu without making any changes:
• Use the EXIT option if available.
• Otherwise, activate Scroll at the confirmation screen.
Index
• If only one password is enabled, the user can access the top-level off-line menu, but will be
prompted for the password when he or she attempts to access the alarm menu or the off-line
maintenance menu (depending on which password is enabled). The user can access the other
menu without a password.
• If neither password is enabled, the user can access all parts of the off-line menu without a
password.
For information about enabling and setting the display password, refer to Section 4.18.
Note: If the petroleum measurement application is installed on your transmitter, the display password
is always required to start, stop, or reset a totalizer, even if neither password is enabled. If the
petroleum measurement application is not installed, the display password is never required for these
functions, even if one of the passwords is enabled.
If a password is required, the word CODE? appears at the top of the password screen. Enter the digits
of the password one at a time by using Scroll to choose a number and Select to move to the next
digit.
If you encounter the display password screen but do not know the password, wait 30 seconds without
activating any of the display optical switches. The password screen will timeout automatically and
you will be returned to the previous screen.
SX.XXXX
Sign Digits
For positive numbers, leave this space Enter a number (maximum length: eight
blank. For negative numbers, enter a digits, or seven digits and a minus sign).
minus sign (–). Maximum precision is four.
SX.XXXEYY
Display
Sign Digit (0–9)
Digits
Enter a four-digit
number; three digits Sign or Digit (0–3)
must fall to the right E
of the decimal point. Exponent
indicator
NE53 History
2. Scroll to d.
3. Select. The display changes to remove the exponent.
To exit the menu:
• If the value has been changed, Select and Scroll simultaneously until the confirmation screen
is displayed.
- Select to apply the change and exit.
- Scroll to exit without applying the change.
• If the value has not been changed, Select and Scroll simultaneously until the previous screen
is displayed.
Index
G.5 Abbreviations
The display uses a number of abbreviations. Table G-1 lists the abbreviations used by the display.
Display
H.1 Overview
This appendix documents the change history of the Model 2700 transmitter with FOUNDATION
fieldbus software.
NE53 History
Table H-1 describes the change history of the transmitter software. Operating instructions are English
versions. Instructions in other languages have different part numbers but matching revision letters.
Software Operating
Date version Changes to software instructions
09/2000 1.0 Initial product release 20000326 Rev. A
06/2001 2.0 Software expansion 20000326 Rev. B
Added support to configure the process variable units for mass flow,
volume flow, density and temperature from the display.
Software adjustment
Clarified the interaction of the digital fault setting and the last
measured value timeout.
Feature addition
Index
Added backup link active scheduler (LAS).
Added PID function block.
Added analog output function block for pressure compensation.
Added support for pressure compensation to the transducer block.
Added drive gain as a selectable channel for AI blocks.
Added ability to enable fieldbus simulate mode through the service
port.
2/2002 2.2 Software adjustment 20000326 Rev. C
Improved the handling of RS-485 communication via the service port.
Improved the user experience with the display.
Feature additions
Added protections against low-power conditions.
Software Operating
Date version Changes to software instructions
7/2004 3.x Software expansion 20000326 Rev. D
Software version information available via the display or Modbus.
Totalizers can be disabled in addition to start/stop.
Doubled the number of virtual communication relationships (VCRs).
Software adjustment
Improved the handling of AI block status when slug flow is detected.
Some fieldbus parameters made persistent across power resets.
Introduced finer-grained control over operator access to display
functions.
Feature addition
Petroleum measurement application added.
Added gas standard volume functionality.
Enhanced density application added.
Added support for enabling fieldbus simulation mode via the display.
Added support for 32-character tagnames configurable via Modbus.
Added support for Analog Input Block configurable via Modbus.
06/2007 4.0 Software expansion 20000326 Rev. E
Added temperature and density units to API transducer block.
Additional configuration ability for the display.
Feature addition
Added configurable alarm severity.
Added more support for gas standard volume functionality.
Added meter verification as an option.
Added multiple display language selections.
Implemented PlantWeb Alerts II.
Added the ability to enable simulate mode through the Device
Information Transducer Block.
Added default values for AI blocks:
• AI1: mass flow in g/s
• AI2: temperature in °C
• AI3: density in g/cm3
• AI4: volume flow in l/s
01/2008 5.0 Software adjustment 20000326 Rev. EA
Improved handling of Gas Standard Volume cutoffs.
Improved local display functionality for API and concentration
measurement variables.
Feature addition
Added support for Meter Verification AMS Snap-On.
Added extra security for local display off-line menu access.
03/2009 5.1 Software adjustment 20000326 Rev. EA
Resolved non-volatile memory (NVM) reliability issue present in
version 4.0 and 5.0 software.
Software Operating
Date version Changes to software instructions
Display
06/2010 6.0 Software adjustment 20000326 Rev. EA
Smart Meter Verification
Improved representation of gas volume on local display
Harmonized behavior of gas volume density parameter with other gas
standard volume parameters
NE53 History
Index
Display
A Cutoffs 82
Acknowledging alarms 87, 109, 110 troubleshooting 122
AI block
channels 6 D
configuration error 118 Damping 79
Alarm log 110, 111 troubleshooting 122
Alarm menu 87 Decimal notation 208
password 88, 93, 207 Default values 145–177, ??–181, 183–??
Alarm severity 77 Density
Alarms cutoff 82
See Process alarms or Status alarms measurement units
NE53 History
Auto scroll 87, 206 configuring 55
list 59
B Density calibration procedure 22, 42
Backlight (display) 88 Device description 2, 199
Button Device settings 85
See Optical switch Display 2
acknowledging alarms 109
C alarm menu 87
Calibration 21, 22 backlight 88
density calibration procedure 22, 42 codes 210
temperature calibration procedure 22, 48 components 205
troubleshooting 118, 122, 124 decimal notation 208
zero decimals 95
See Zero calibration exponential notation 209
Channels 6 language 96, 206
Characterizing 21, 23 off-line menu 87
Index
density calibration factors 25 overview 205
flow calibration values 25 password 87, 88, 93, 207
parameters 23 precision 95
sample calibration tags 24, 25 scroll rate 90
troubleshooting 122, 123 Smart Meter Verification tools 36
CODE? 207 update period 91
Codes using display menus 207
display codes 210 variables 95
status alarm codes 123 viewing alarms 109
Communicator viewing process variables 206
See Field Communicator Documentation 2
Configuration files (ProLink II) 201 Drive gain
Configuration worksheet 2 troubleshooting 129
Core processor 194
LED 132 E
sensor pins 137 Enabling/disabling display functions 87
terminals 197, 198 Enhanced density application 69
troubleshooting 131 Exponential notation 209
Customer service 3
Display
pressure correction factors 9 ProLink II tools 34
pressure source 10 results 33
values 9 scheduling 38
Prior zero 18 Software history 211
Priorities Software tag 85
alarm priorities 75 Status alarms
Process alarms 74 acknowledging 87, 109, 110
assigning values 74 codes 123
hysteresis 75 responding to 107
priorities 75 severity 77
responding to 107 troubleshooting 123
viewing 107 viewing 107
Process variables Status LED 108
channels 6
NE53 History
troubleshooting 119 T
viewing values 103 Tag 85
ProLink II 2, 201 Temperature
alarm log 110, 111 measurement units
configuration files 201 configuring 55
connecting to a transmitter 202 list 60
language 204 Temperature calibration procedure 22, 48
requirements 201 Temperature compensation 12
Smart Meter Verification tools 34 enabling 12
version 2, 201 temperature source 13
Terminals 198
R Timeout (PlantWeb Alerts) 98
Restoring factory configuration 128 Totalizers
Restoring zero 18 definition 111
Revision history 211 measurement units 55
Index
parameter names 111
S resetting 113
Safety 1 starting and stopping 113
Scroll (optical switch) 113, 205 viewing values 111
Scroll rate 90 Transducer blocks
Select (optical switch) 113, 205 channels 6
Sensor material 86 reference 145
Sensor parameters 86
Serial number 86 U
Service port 202 Units 55
Severity Update period (display) 91
of alarms 77
Simulation mode 105 V
fieldbus 105 Variables
sensor 106 viewing values 103
Slug flow 81 Volume flow
definition 81 cutoff 82
duration 81 measurement units
limits 81 configuring 55
troubleshooting 127 list 58
W
Wiring problems 126
Write-protect mode 99
Z
Zero calibration 14
procedure 15
restoring zero 18
troubleshooting 118, 124
*20000326*
For the latest Micro Motion product specifications, view the
PRODUCTS section of our web site at www.micromotion.com