Manual Liebert Ds
Manual Liebert Ds
Liebert DS
User Manual28-105kW, 8-30 Tons, Upflow and Downflow, 50/60Hz
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 2.0 3.0
3.1 3.2 3.3 3.4 3.5
4.0 5.0
5.1
SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2 Unpacking the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2.1 5.2.2 5.2.3 5.2.4 Removing the Unit from the Skid With a Forklift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Moving the Unit to the Installation Location with Piano Jacks . . . . . . . . . . . . . . . . . . . . . . . Removing Piano Jacks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing Liebert DS from Skid Using Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 40 40 41
5.3 5.4
Semi-Hermetic Compressor Spring Isolation System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Placing the Unit on a Floor Stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.0
6.1 6.2
7.0
7.1 7.2
ReassemblyDownflow Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3.1
7.6 7.7
8.0
8.1
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Variable Speed Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.1.1 8.1.2 8.1.3 VSD Power SupplyField-Adjustment May Be Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Wye-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Delta-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.0
9.1
PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Fluid Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
9.1.1 9.1.2 9.1.3 9.1.4 Condensate PipingField-Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Humidifier Supply WaterOptional Infrared . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Humidifier Supply WaterOptional Steam Generating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Requirements of Systems Using Water or Glycol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 84 84 84
9.2
Refrigeration Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.2.1 9.2.2 Piping GuidelinesAir-Cooled Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Scroll and Digital ScrollAdditional Oil Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Air-Cooled Condenser with Variable Fan Speed Head Pressure Control Systems . . . . . . . . 89 Air-Cooled Condenser with Liebert Lee-Temp Flooded Condenser Head Pressure Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Water/Glycol Cooled System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.3
10.0 11.0
11.1 11.2 11.3 11.4
12.0
12.1 12.2 12.3 12.4
INITIAL STARTUP CHECKS AND COMMISSIONING PROCEDURE FOR WARRANTY INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Information for Warranty InspectionRemove Power From Unit Disconnect . . . . . . . . . 127 Startup Checks With Panels Removed and Main Disconnect Off . . . . . . . . . . . . . . . . . . . . 127
12.2.1 Inspect and Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
13.0
13.1
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.1.1 Filter Replacement ProcedureDownflow Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 13.1.2 Filter Replacement ProcedureUpflow Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
ii
13.2
13.3
13.4
HumidifierInfrared . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
13.4.1 Cleaning Humidifier Pan and Float Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 13.4.2 Changing Humidifier Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.5 13.6
Air-Cooled Condenser and Drycoolers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 ReheatElectric Reheat (Three-Stage and SCR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
13.9.1 Determine Suction Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 13.9.2 Adjust Superheat Setting with the TEV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
13.12 Facility Fluid and Piping Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 13.13 ParadenserWater-Cooled Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
13.13.1 Cleaning Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
14.0
iii
FIGURES
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Downflow model component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Upflow model component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Liebert DS model number nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Downflow unit ducting and plenum ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Upflow ducting configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Cabinet and floor planning dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Cabinet and floor planning dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Cabinet and floor planning dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Cabinet and floor planning dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Cabinet and floor planning dimensionsdownflow, air-cooled, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Cabinet and floor planning dimensionsupflow, air-cooled 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Cabinet and floor planning dimensionsupflow, air-cooled 28-42kW (8-12 ton), scroll or digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Cabinet and floor planning dimensionsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Cabinet and floor planning dimensionsupflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Cabinet and floor planning dimensionsupflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Cabinet and floor planning dimensionsupflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Cabinet and floor planning dimensionsupflow, air-cooled, 105kW (30 ton), all . . . . . . . . . . . . 25 Cabinet and floor planning dimensionsupflow water/glycol/GLYCOOL 105kW (30 ton), all compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Floor stand dimensionsdownflow, 28-42kW (8-12 ton) models. . . . . . . . . . . . . . . . . . . . . . . . . . 27 Floor stand dimensionsdownflow, 53-77kW (15-22 ton) models. . . . . . . . . . . . . . . . . . . . . . . . . 28 Floor stand and floor planning dimension, downflow 53-77kW (15-22 tons) models with EC fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Floor stand dimensionsdownflow, 105kW (30 ton) models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Floor stand and floor planning dimension, downflow 105kW (30 tons) models with EC fans . . . 31 Blower outlet and deck dimensionsupflow, 28-42kW (8-12 ton). . . . . . . . . . . . . . . . . . . . . . . . . 32 Blower outlet and deck dimensionsupflow, 53-77kW (15-22 ton). . . . . . . . . . . . . . . . . . . . . . . . 33 Blower outlet and deck dimensionsupflow 105kW (30ton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Rear return filter box dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Upflow unit plenum dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Equipment recommended for handling Liebert DS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Removing packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Remove the unit from the skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Moving the unit to its installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Locate center of gravity marker and place slings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
iv
Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure 48 Figure 49 Figure 50 Figure 51 Figure 52 Figure 53 Figure 54 Figure 55 Figure 56 Figure 57 Figure 58 Figure 59 Figure 60 Figure 61 Figure 62 Figure 63 Figure 64 Figure 65 Figure 66 Figure 67 Figure 68 Figure 69 Figure 70 Figure 71
Using rigging to lift Liebert DS off skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the unit on a floor stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lowering EC fans into floor stand, Steps 1 through 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lowering EC fans into floor stand, Steps 7 through 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the EC fans, Steps 1 through 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the EC fans, Steps 6 through 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow air-cooled, 53-77kW (15-22 ton), scroll/digital scroll compressor models; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow water/glycol, GLYCOOL, 53-77kW (15-22 ton), all compressor models; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, air-cooled, 105kW (30 ton), semi-hermetic compressor models; forward-curved and EC fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, air-cooled, 105kW (30 ton), scroll compressor models; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), forward-curved and EC fan, all compressor models; forward-curved and EC fan . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 53-77kw (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 53-77kw (15-22 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow water/glycol/GLYCOOL 53-77kw (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 105kW (30 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, air-cooled, 105kW (30 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component dimensionsupflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical field connections for upflow and downflow models . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wye-connected power diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Delta-connected power diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Disconnecting EMC filter for operation with Delta-connected power size C & D inverters. . . . . Figure bb Disconnecting EMC filter for operation with Delta-connected power Type 2 inverters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gravity drain for downflow and upflow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping schematicair-cooled, semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . Piping schematicair-cooled, scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Piping schematicwater/glycol, semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . Piping schematicwater/glycol with scroll compressor models. . . . . . . . . . . . . . . . . . . . . . . . . . . Piping schematicGLYCOOL semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . .
42 43 45 46 48 49 55 56 57 58 59 60 61 62 63 67 68 69 70 71 72 73 74 75 77 79 80 81 81 83 94 95 96 97 98
Figure 72 Figure 73 Figure 74 Figure 75 Figure 76 Figure 77 Figure 78 Figure 79 Figure 80 Figure 81 Figure 82 Figure 83 Figure 84 Figure 85 Figure 86 Figure 87 Figure 88 Figure 89 Figure 90 Figure 91 Figure 92 Figure 93 Figure 94 Figure 95 Figure 96 Figure 97 Figure 98 Figure 99 Figure 100 Figure 101 Figure 102 Figure 103 Figure 104 Figure 105 Figure 106
Piping schematicGLYCOOL with scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Piping schematicwater/glycol with digital scroll compressor models. . . . . . . . . . . . . . . . . . . . 100 GLYCOOL with digital scroll compressor models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Optional piping schematic for Econ-O-Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Primary connection locationsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Primary connection locationsdownflow, air-Cooled, 28-42kW (8-12 ton) with scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Primary connection locationsdownflow water/glycol/GLYCOOL 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Primary connection locations downflow air cooled 53-77kW (15-22 tons) semi-hermetic compressor models, with EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton) with scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton) with scroll compressor models, with EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Primary connection locationsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Primary connection locationsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models, with EC fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Primary connection locationsdownflow, air-cooled, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Primary connection locationsdownflow, air-cooled, 105kW (30 ton), all compressor models, with EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Primary connection locationsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Primary connection locations downflow water/glycol/GLYCOOL 105kW (30 tons) all compressor models, with EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Primary connection locationsupflow, air-cooled, 28-42kw (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Primary connection locationsupflow, air-Cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Primary connection locationsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Primary connection locationsupflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 Primary connection locationsupflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Primary connection locationsupflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Primary connection locationsupflow, air-cooled, 105kW (30 ton), all. . . . . . . . . . . . . . . . . . . . 122 Primary connection locationsupflow, water/glycol/GLYCOOL, 105kW (30 ton), all . . . . . . . . 123 Proper filter pleat direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Upflow motor access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 Auto-belt tensioning motor base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Correct orientation of float switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 Infrared humidifier lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 Steam generating humidifier canister . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Removing the old canister . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 Drain valve assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Canister plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Circuit board diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
vi
TABLES
Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 Table 27 Table 28 Table 29 Table 30 Table 31 Table 32 Table 33 Table 34 Table 35 Table 36 Table 37 Table 38 Table 39 Shipping dimensionsdomestic and export, inches (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shipping weightsapproximate, kg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights for downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . Weights for downflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models . . . . . . . . . . . . Weights for downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . Weights for downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . Weights for downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models . . . . . . . . . . . Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights for downflow, air-Cooled, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . Weights for downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models . . . . . . Weight for upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . Weight for upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . Weights for upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models . . . . . . Weight for upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models . . . . Weightsupflow, air-cooled, 105kW (30 ton), all . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weightsupflow water/glycol/GLYCOOL 105kW (30 ton), all compressors. . . . . . . . . . . . . . . . . Floor stand and floor planning dimensionsdownflow, 28-42kW (8-12 ton) models . . . . . . . . . . Floor stand and floor planning dimensionsdownflow, 53-77kW (15-22 ton) models . . . . . . . . . Floor stand and floor planning dimensionsdownflow, 53-77kW (15-22 ton) models with EC fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Floor stand and floor planning dimensionsdownflow, 105kW (30 ton) models . . . . . . . . . . . . . Floor stand and floor planning dimensionsdownflow, 105kW (30 ton) models with EC fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Blower outlet and deck dimensional data for upflow, 28-42kW (8-12 ton) . . . . . . . . . . . . . . . . . . Blower outlet and deck dimensional data upflow, 53-77kW (15-22 tons) . . . . . . . . . . . . . . . . . . . Blower outlet and deck dimensionsupflow 105kW (30ton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rear return filter box dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Upflow unit plenum dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic . . . . . . . . . . . . . Component weightsdownflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll. . . . . . . . . . Component weightsdownflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all . . . . . . . . . . . Component weightsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsdownflow, air-cooled, 53-77kW (15-22 ton), scroll/digital scroll; forward-curved and EC fan59 Component weightsdownflow water/glycol, GLYCOOL, 53-77kW (15-22 ton), all . . . . . . . . . . Component weightsdownflow, air-cooled, 105kW (30 ton), semi-hermetic compressors; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsdownflow, air-cooled, 105kW (30 ton), scroll compressor models; forward-curved and EC fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models; forward-curved and EC fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsupflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component weightsupflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
vii
10 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 55 56 57 58
60 61 62 63 67 68
Table 40 Table 41 Table 42 Table 43 Table 44 Table 45 Table 46 Table 47 Table 48 Table 49 Table 50 Table 51 Table 52 Table 53 Table 54 Table 55 Table 56 Table 57 Table 58 Table 59 Table 60 Table 61 Table 62 Table 63 Table 64 Table 65 Table 66 Table 67 Table 68 Table 69
Component weightsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Component weightsupflow air-cooled 53-77kw (15-22 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Component weightsupflow, air-cooled, 53-77kw (15-22 ton), scroll /digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Component weightsupflow water/glycol/GLYCOOL, 53-77kW (15-22 ton) all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Component weightsupflow, air-cooled, 105kW (30 ton), semi-hermetic compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Component weightsupflow, air-cooled, 105kW (30 ton), scroll/digital scroll compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Component weightsupflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Electrical field connection descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Inverter type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Recommended refrigerant line sizes - OD copper (inches)* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Indoor unit approximate refrigerant charge for R-22 or R-407C . . . . . . . . . . . . . . . . . . . . . . . . . . 86 R-22 and R-407C refrigerant required, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Interconnecting piping refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Additional oil required per refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Fan speed suction pressure transducer settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Lee-Temp suction pressure transducer settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Water/Glycol-cooled and GLYCOOL suction pressure transducer settings . . . . . . . . . . . . . . . . . 93 Piping dataupflow, air-cooled 105kW (30 ton), all. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Piping dataupflow, upflow, water/glycol/GLYCOOL, 105kW (30 ton), all . . . . . . . . . . . . . . . . 123 Filter quantities, downflow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Filter quantities, upflow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Humidifier canister part numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 Steam generating humidifier status lamps: causes, corrective action. . . . . . . . . . . . . . . . . . . . . 142 Steam generating humidifier troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Compressor oil types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Recommended refrigerant pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Water/glycol system conditions requiring optional settings for aquastats . . . . . . . . . . . . . . . . . 149 Aquastat settingstwo-fan through four-fan drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Aquastat settingssix-fan drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Aquastat settingseight-fan drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
viii
! WARNING from high-pressure refrigerant. Can cause injury or death. Risk of explosive discharge
This unit contains fluids and gases under high pressure. Relieve pressure before working with piping.
! WARNING rupture or explosion from overpressurization. Can cause Risk of refrigerant system
equipment damage, injury or death. For systems requiring EU CE compliance (50Hz), the system installer must provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and the field installed relief valve. The pressure relief valve must be CE-certified to the EU Pressure Equipment Directive by an EU Notified Body.
! WARNING Risk of contact with high-speed moving parts. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Do not operate unit with any or all cabinet panels removed. Do not operate upflow units without installing a plenum, ductwork or guard over the blower opening(s) on the top surface of the unit cabinet. Ductwork must be connected to the blower(s), or a plenum must be installed on the blower deck for protection from rotating blower wheel(s) on upflow units.
! CAUTION and lengthy parts. Can cause personal injury and equipment damage. Risk of handling heavy
Cabinet panels can exceed 5ft. (1.5m) in length and weigh more than 35lb. (15.9kg). Follow relevant OSHA lifting recommendations and consider using a two-person lift for safe and comfortable removal and installation of cabinet panels. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves and shoes should attempt to remove or install cabinet panels. NOTE The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp condensers. Consult local building codes to determine whether the Liebert Fan Speed Control and VFD condensers will require field provided pressure relief devices.
NOTICE
Risk of clogged or leaking drain lines. Can cause equipment and building damage. This unit requires a water drain connection. Drain lines must be inspected regularly and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson recommends installing leak detection equipment for unit and supply lines.
NOTICE
Risk of a leaking coil due to freezing and/or corrosion. Can cause equipment and serious building damage. Cooling and heat rejection coils, heat exchangers and piping systems that are connected to open cooling towers or other open water/glycol systems are at high risk for freezing and premature corrosion. Fluids in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil corrosion. The water or water/glycol solution must be analyzed by a competent water treatment specialist before startup to establish the inhibitor requirement. The water or water/glycol solution must be analyzed every six months to determine the pattern of inhibitor depletion. The complexity of water-caused problems and their correction makes it important to obtain the advice of a water treatment specialist and follow a regularly scheduled maintenance program.
1.0
Figure 1
14 3 17 11 2 9 1
13 15 4 16 10 12 6 8 5
1. Liebert iCOM 2. Electric Box 3. Filters 4. Evaporator Coil 5. Motor 6. Blower 7. Fan Pulley 8. Motor Sheave and Belts 9. Compressor Section
18 10. Infrared Humidifier, optional 11. Disconnect, optional 12. Condensate Pump, optional 13. Smoke Sensor, optional 14. Condenser Cleanout Plugs, fluid-cooled units only 15.Condenser Drain Plugs, fluid-cooled units only 16. Econ-O-Coil Valve, GLYCOOL/Dual Cooling 17. Variable Frequency Drive (optional on DPN000958 digital scroll units only) Rev. 3 18. EC Fans, optional
18
Figure 2
14
6 11 7 8 9 1 2 5
15 16
17 12 13
10
1. Liebert iCom Control Display 2. Electric Box 3. Filters 4. Evaporator Coil 5. Motor 6. Blower 7. Fan Pulley 8. Motor Sheave and Belts
9. Compressor Section 10. Infrared Humidifier (optional) 11. Disconnect (optional) 12. Condensate Pump (optional) 13. Smoke Sensor (optional) 14. Condenser Cleanout Plugs (fluid cooled units only) 15. Condenser Drain Plugs ( fluid cooled units only) 16. Econ-O-Coil Valve (GLYCOOL/Dual Cooling) 17. Variable Frequency Drive (optional on DPN001222 Digital Scroll units only)
Rev. 1
Figure 3
Air Distribution DS = Downflow Standard VS = Upflow Standard Nominal kW 028,035, 042, 053, 070, 077, 105 Cooling Type A = Air-Cooled D = Dual-Cooling, Air-Cooled W = Water/Glycol K = GLYCOOL H = Dual-Cooling (Water/Glycol) Compressor Type U - Semi-hermetic with four-step, R-407C S - Scroll, R-407C D - Digital Scroll, R-407C Voltage M - Semi-hermetic A - 460/3/60 with four-step, R-22 B - 575/3/60 R - Scroll, R-22 C - 208/3/60 G - Digital Scroll, R-22 D - 230/3/60 2 - 380/3/60 J - 200/3/50 M - 380-415/3/50
Cooling Configurations
2.0
COOLING CONFIGURATIONS
NOTE All field-installed piping must comply with applicable local, state and federal codes.
Air-Cooled Air-cooled unit piping is spun closed from the factory and contain a nitrogen holding charge. Each installation requires refrigerant piping to a condenser.
Glycol-Cooled Glycol-cooled units are factory-charged and tested. Field-installed piping is required from the unit to the drycooler and pump package.
GLYCOOL GLYCOOL units are factory-charged and tested. Field-installed piping is required from the unit to the drycooler and pump package. An additional coil is included for use when fluid temperatures are sufficiently low (below room temperature). Cooling is provided by circulating cold glycol through this second coil, reducing compressor operation.
Water-Cooled Water-cooled units are factory-charged and tested. Field-installed water piping is required from the unit to the cooling tower.
Dual-Cool This system has all of the features of a compressorized system, but adds a second cooling coil that is connected to a source of chilled water. Cooling is provided by circulating water through this second coil and reducing compressor operation.
Pre-Installation Guidelines
3.0
3.1
PRE-INSTALLATION GUIDELINES
Room Preparation
Verify that the floor is level, solid and sufficient to support the unit. See Table 2 for unit weights. Confirm that the room is properly insulated and has a sealed vapor barrier. For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of total air circulated in the room). Do not install Liebert DS units in an alcove or at the end of a long, narrow room. Install the units as close as possible to the largest heat load. Allow at least the minimum recommended clearances for maintenance and service. See Figures 6 through 21 for dimensions. Emerson recommends installing an under-floor water detection system. Contact your local Emerson representative for information.
3.2
Figure 4
Field-Fabricated Ductwork
Provided Condenser Access (water, glycol and GLYCOOL units only) Liebert Plenum - Refer to plenum installation sheet 186582P1 included in the plenum package.
7
PLENUM DUCTING
Pre-Installation Guidelines
3.3
For in-room applications with supply and return grilles, several feet of clearance must be maintained at the intake and discharge of the unit. Upflow rear-return configurations use a filter box attached to the back of the Liebert DS. Allow 25" (635 mm) on one side of the unit for access to the rear return filter box. Refer to the rear return installation sheet, 187230P1, inside the rear return filter box package.
1 1
1 Straight section of duct off of unit to be 1.5 to 2.5 times the longest blower dimension. 2 Typical ducting shown; ducting may run to either side. * Follow standard practices on all duct work.
DPN001156 Rev. 0
NOTE Drain traps are qualified to a return duct static of negative 1.5 i.w.g. (-1.5 i.w.g).
8
Pre-Installation Guidelines
3.4
3.5
Operating Conditions
The Liebert DS must be operated in a conditioned space within the operating envelope ASHRAE recommends for data centers: Maximum temperature of 77F (25C) DB and 55% RH or maximum WB of 65.5F (18.6C). Operating outside this envelope can decrease equipment reliability. Return air to the unit must be no cooler than the ASHRAE recommendation of 68F (20C) DB and 40% RH or minimum WB of 54F (12.2C) for proper unit operation. Operating below this can decrease equipment reliability. Refer to ASHRAEs publication, Thermal Guidelines for Data Processing Environments.
4.0
105 Lx W x H, in (mm)
L x W xH, in (mm)
90x42x82 (2286x1067x2083)
114x42x82 (2896x1067x2083)
136x42x82 (3454x1067x2083)
Table 2
Size
Shipping weightsapproximate, kg
Cooling Type
Air Air D/C
Compressor Type
Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll Semi Scroll
Export
2088 1778 2238 1928 2238 2088 2388 2238 2712 2260 2892 2440 3012 2582 3192 2762 2762 2310 942 2490 3062 2632 3242 2812 2812 2360 2992 2540 3112 2660 3292 2840 3443 3323 3803 3683 3813 3693 4173 4053
Export
2138 1828 2288 1978 2288 2138 2438 2288 2712 2410 2892 2590 3012 2732 3192 2912 2862 2410 3042 2590 3162 2732 3342 2912 2862 2410 3042 2590 3162 2732 3342 2912 3403 3283 3733 3613 3773 3653 4103 3983
8-12 Ton
W/G G/C Air Air D/C
15 Ton
W/G G/C Air Air D/C
20 Ton
W/G G/C Air Air D/C
22 Ton
W/G G/C Air Air D/C
30 Ton
W/G G/C
10
Figure 6
Cabinet and floor planning dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
Secondary Refrigerant Piping Entrance 56-7/8" Opening (1445mm)
Notes: Filters are accessible through top of unit only. 24-3/8" Opening (619mm) Downflow electrical connections can be made from top or bottom of unit.
Top View
Secondary Entrance High Volt Connection(s) 86" (2184mm)
15" (381mm)
76" (1930mm)
2" (51mm)
Front View
85" (2159mm)
34" (864mm)
DPN000795 Rev. 3
Table 3
Weights for downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models Dry Weight - lb. (kg), Approximate
11
Figure 7
Cabinet and floor planning dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models
Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made 24-3/8" from top or bottom of unit. (619mm) Opening
Top View
73" (1854mm)
3/4" Bezels (19mm) Minimum required Secondary Entrance for filter replacement Low Volt Connections
15" (381mm) 76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. DPN000796 Rev. 2
2" (51mm)
Table 4
Weights for downflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models
Dry Weight, lb (kg), Approximate Model No. Air-Cooled Dual-Cool 028, 035, 042 1470 (668) 1620 (736)
12
Figure 8
Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Notes: Filters are accessible through top of unit only. Downflow electrical 24-3/8" connections can be made (619mm) from top or bottom of unit. Opening 3/4" Bezels (19mm) Required for condenser cleanout
Secondary Condenser Top View Fluid Piping Entrance Secondary Entrance High Volt Connection(s) 86" (2184mm)
24" (610mm)
76" (1930mm) 34" (864mm) Shaded area indicates a recommended minimum clearance for component access. DPN000894 Rev. 3
2" (51mm)
Table 5
Weights for downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models Dry Weight - lb. (kg), Approximate
Compressor Type Model Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 028, 035, 042 1930 (877) 2080 (945) 1780 (809) 1930 (877)
13
Figure 9
Cabinet and floor planning dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
Second Refrigerant Piping Entrance 80" Opening (2032mm)
Notes: Filters are accessible through top of unit onl y. Downflow electrical connections can be made 24-3/8" Opening from top or bottom of unit. (619mm) 3/4" Bezels (19mm) Secondary Entrance Low Volt Connections Minimum required for filter replacement
15" (381mm)
76" (1930mm)
34" (864mm) Front View 108" (2743mm) Shaded area indicates a recommended minimum clearance for component yaccess.
2" (51mm)
DPN000924 Rev. 2
Table 6
Model Air-Cooled Dual-Cool
Weights for downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
Dry Weight, lb (kg) Approximate 053 2350 (1069) 2530 (1150) 070 2400 (1091) 2580 (1173) 077 2450 (1114) 2630 (1196)
14
Figure 10 Cabinet and floor planning dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models
Secondary Refrigerant Piping Entrance Notes: Filters are accessible only through top of unit. Downflow electrical connections can be made from top or bottom of unit. 24-5/8" (625mm Opening 3/4" (19mm) Bezels Secondary Entrance High Volt Connection(s)
Top View
98" (2489mm)
15" (381mm)
76" (1930mm)
34" (864mm) 2" (51mm) Shaded area indicates a recommended minimum clearance for component access.
97" (2464mm)
Front View
Table 7
Model No. Air-Cooled Dual-Cool Dry Weight, lb (kg) Approximate 053 1920 (873) 2100 (955) 070 1970 (896) 2150 (978) 077 2020 (919) 2200 (1000)
DPN000925 Rev. 1
Weights for downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models
15
Figure 11 Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Condenser Cleanout Access 80" (2032mm) Opening 33" (838mm) 35" (889mm Notes: Filters are accessible through top of unit onl y. Downflow electrical connections can be made from top or bottom of unit. 3/4" (20mm) Bezels Required for condenser cleanout Minimum required for filter replacement
Secondary Condenser Fluid Piping Entrance Secondary Entrance High Volt Connection(s)
Top View
109" (2769mm)
24" (610mm)
15" (381mm)
76" (1930mm)
Front View
34" (864mm)
DPN000931 Rev. 3
Table 8
Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Dry Weight, lb (kg), Approximate Model Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 053 2650 (1205) 2830 (1287) 2220 (1010) 2400 (1091) 070 2700 (1228) 2880 (1310) 2270 (1032) 2450 (1114) 077 2750 (1250) 2930 (1332) 2320 (1055) 2500 (1137)
16
Figure 12 Cabinet and floor planning dimensionsdownflow, air-cooled, 105kW (30 ton), all compressor models
Secondary Refrigerant Piping Entrance 102-13/16" (2611mm)
Opening 33" (838mm) 35" (889mm)
Notes: Filters are accessible only through top of unit. Downflow electrical connections can be made from top or bottom of unit. 24-3/8" Opening (619mm) 3/4" Bezels (19mm)
Secondary Entrance Low Volt Connections
Top View
Secondary Entrance High Volt Connection(s)
132" (3353mm)
76" (1930mm)
34" (864mm)
Front View
131" (3327mm)
DPN001012 Rev. 3
Table 9
Weights for downflow, air-Cooled, 105kW (30 ton), all compressor models
Dry Weight, lb (kg) approximate Model 105 Forward-Curved Fans 3040 (1382) 3400 (1545) 2920 (1327) 3280 (1491) EC Fans 2774 (1258) 3134 (1422) 2654 (1204) 3014 (1367)
17
Figure 13 Cabinet and floor planning dimensionsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models
Condenser Cleanout Access 102-13/16" (2611mm) Opening
33" (838mm)
Notes: Filters are accessible through top of unit onl y. Downflow electrical connections can be made from top or bottom of unit 24-3/8" (619mm) Opening 3/4" (19mm) Bezels Secondary Entrance Low Volt Connections 24" (610mm)
35" (889mm)
TOP VIEW Secondary Condenser Fluid Entrance Secondary Entrance High Volt Connection(s)
76" (1930mm)
34" (864mm)
DPN001013 Rev. 3
Table 10
Weights for downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models
Dry Weight, lb (kg) approximate Model Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 105 3410 (1550) 3770 (1714) 3290 (1495) 3650 (1659)
18
Figure 14 Cabinet and floor planning dimensionsupflow, air-cooled 28-42kW (8-12 ton), semi-hermetic compressor models
Alternate Refrigerant Piping Entrance
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
3/4" (19mm) Bezels
Top View
High Volt Connection(s) Low Volt Connection(s) Minimum required for blower replacement
1-1/2" (38mm)
86" (2184mm)
24" (610mm)
76" (1930mm)
34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 2" (51mm) 85" (2159mm)
Front View
Dry Weight, lb (kg) approximate
DPN001162 Rev. 1
Table 11
Weight for upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
19
Figure 15 Cabinet and floor planning dimensionsupflow, air-cooled 28-42kW (8-12 ton), scroll or digital scroll compressor models
Alternate Refrigerant Piping Entrance
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
TOP VIEW
High Volt Connection(s) 1-1/2" (38mm) 73" (1854mm) Low Volt Connection(s)
24" (610mm)
76" (1930mm)
34" (864mm) Shaded area indicates a recommended minimum clearance for component access. 2" (51mm) 72" (1829mm)
FRONT VIEW
Dry Weight, lb (kg) approximate
DPN001163 Rev. 1
Table 12
Weight for upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressor models
20
Figure 16 Cabinet and floor planning dimensionsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Condenser Cleanout Access
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30
3/4" (19mm) Bezels Alternate Refrigerant Piping Entrance High Volt Connection(s) 1-1/2" (38mm)
TOP VIEW
Low Volt Connection(s) 86" (2184mm)
24" (610mm)
76" (1930mm)
Shaded area indicates a recommended minimum clearance for component access. 2" (51mm) 85" (2159mm)
34" (864mm)
FRONT VIEW
Dry Weight, lb (kg) approximate
DPN001164 Rev. 1
Table 13
Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Model Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 028-042 1980 (898) 2130 (966) 1830 (830) 1980 (898)
21
Figure 17 Cabinet and floor planning dimensionsupflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
35" (889mm)
3/4" (19mm) Bezels TOP VIEW Low Volt Connection(s) High Volt Connection(s)
1-1/2" (38mm)
109" (2769mm)
24" (610mm)
2" (51mm)
Table 14
DPN001165 Rev. 1
Weights for upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
Model
053
070, 077
Air-Cooled Dual-Cool
22
Figure 18 Cabinet and floor planning dimensionsupflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
35" (889mm)
3/4" (19mm) Bezels High Volt Connection(s) TOP VIEW 98" (2489mm) Low Volt Connection(s)
1-1/2" (38mm)
24" (610mm)
76" (1930mm)
34" (864mm)
Shaded area indicates a recommended minimum clearance for component access.
2" (51mm)
Table 15
DPN001166 Rev. 1
Weight for upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models
Dry Weight, lb (kg) approximate 053, 070, 077 2070 (939) 2250 (1021)
23
Figure 19 Cabinet and floor planning dimensionsupflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
33" (838mm)
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
35" (889mm)
Alternate Condenser Fluid Piping Entrance High Volt Connection(s) 1-1/2" (38mm)
TOP VIEW
3/4" Required for (19mm) condenser cleanout Bezels Minimum required for blower replacement Low Volt Connection(s)
109" (2769mm)
24" (610mm)
2" (51mm)
Table 16
DPN001167 Rev. 1
Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Dry Weight, lb (kg) approximate Model Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool 053 2650 (1205) 2830 (1287) 070, 077 2800 (1270) 2980 (1352)
24
Figure 20 Cabinet and floor planning dimensionsupflow, air-cooled, 105kW (30 ton), all
Alternate Refrigerant Piping Entrance 33" (838mm) 35" (889mm)
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
3/4" (19mm) Bezels
TOP VIEW
132" (3353mm)
FRONT VIEW
DPN001168 REV 0
Table 17
Model
Semi- Hermetic, Air-Cooled Semi-Hermetic, Dual-Cool Scroll or Digital Scroll, Air-Cooled Scroll or Digital Scroll, Dual-Cool
105
25
Figure 21 Cabinet and floor planning dimensionsupflow water/glycol/GLYCOOL 105kW (30 ton), all compressors
Alternate Refrigerant Piping Entrance 33" (838mm) 35" (889mm) Alternate Condenser Fluid Piping Entrance High Volt Connection(s) 1-1/2" (38mm) 132" (3353mm)
Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 30.
Required for condenser cleanout
TOP VIEW
Low Volt Connection(s)
24" (610mm)
76" (1930mm)
2" (51mm)
131" (3327mm)
FRONT VIEW
Table 18
26
Gussets supplied on floor stands 12" (305 mm) tall and greater
7/8" (23mm)
3" (76mm)
Turning vane air outlet Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge.
Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height C.
DPN000820 REV 2
Table 19
Floor stand and floor planning dimensionsdownflow, 28-42kW (8-12 ton) models
Dimensions, in. (mm) Model A 85 (2159) B 26 (660) Height, in. (mm) C* 9 (229) D Turning Vane 4 (111) 7 (187) 10 (264) 13 (340) 16 (416) 19 (492)
72 (1829)
13 (330)
21 (533) 24 (610)
27
A+1-1/2" (38mm) (with feet) A B 69-3/4" (1772mm) 4-1/2" (114mm) 16-3/4" (425mm)
1" (25mm) TYP. Gussets supplied on floor stands 12" (305 mm) tall and greater
7/8" (23mm) 3" Turning vane air outlet (76mm) Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height C. Optional turning vane shown as front air discharge.
DPN000930 REV 1
Table 20
Floor stand and floor planning dimensionsdownflow, 53-77kW (15-22 ton) models
Dimensions, in. (mm) Model A 108 (2743) B 26 (660) Height, in. (mm) C* 9 (229) D Turning Vane 4 (111) 7 (187) 10 (264) 13 (340) 16 (416) 19 (492)
97 (2464)
15 (381)
21 (533) 24 (610)
28
Figure 24 Floor stand and floor planning dimension, downflow 53-77kW (15-22 tons) models with EC fans
A B 3/4" (19mm) Piping access area
31-1/2" (800mm)
98-1/2" (2502mm) NOTES: 1) This floor stand should be used when EC fans are intended to be C* lowered under a raised floo r. The standard Liebert DS floor stand can be used if the fans are to remain in their original, raised position. 2) Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). 3) The floor stand used with EC units is not symmetrical, and its orientation to the Liebert DS is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and used to lower or raise that fan as needed. *Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height C.
DPN002151 REV 0
Table 21
Floor stand and floor planning dimensionsdownflow, 53-77kW (15-22 ton) models with EC fans
Height, Dimension C in. (mm) 24 (610) 30 (762) 36 (914) 42 (1067) 48 (1219)
29
26" (660mm)
Gussets supplied on floor stands 12" (305 mm) tall and greater 7/8" (23mm) Optional turning vane shown as front air discharge. Turning vane air outlet C* Optional turning vane can be field-installed in supply air discharge opening for front or rear air discharge. Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). * Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height C. 3" (76mm)
D
DPN001059 REV 1
Table 22
C* 9 (229) 12 (305) 15 (381) 18 (457) 21 (533) 24 (610)
Floor stand and floor planning dimensionsdownflow, 105kW (30 ton) models
D turning vane 4 (111) 7 (187) 10 (264) 13 (340) 16 (416) 19 (492)
30
Figure 26 Floor stand and floor planning dimension, downflow 105kW (30 tons) models with EC fans
132-1/2" (3366mm) (with feet) 131" (3327mm) 25" (635mm) 34-1/2" (876mm) 33" (with feet) (838mm) 74" (1880mm) Gussets supplied on floor stands 12" (305 mm) tall and greater 1" (25mm) Typ.
7/8" (23mm) 3" (76mm) NOTE: 1) This floor stand should be used when EC fans are intended to be lowered under a raised floor. The standard Liebert DS floor stand can be used if the fans are to remain in their original raised position. 2) Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm). 3) The floor stand used with EC units is not symmetrical and its orientation to the Liebert DS is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand. 4) Jack and jack support are shipped loose and are intended to be placed into position under each fan and utilized to lower or raise that fan as needed. * Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height A See Note 4
A*
DPN002152 Rev. 0
Table 23
Floor stand and floor planning dimensionsdownflow, 105kW (30 ton) models with EC fans
31
Top of Unit
Blower Deck
D
1-1/2" (38mm)
DPN001120 Rev. 2
Blower outlet and deck dimensional data for upflow, 28-42kW (8-12 ton)
Dimensional data, in. (mm) Blower 15 x 15 Supply Front Throw Rear Throw Front Throw Rear Throw A 15-7/8 (404) 15-7/8 (404) 15-7/8 (404) 15-7/8 (404) B 18-5/8 (472) 18-5/8 (472) 14-1/2 (368) 14-1/2 (368) C 2-1/8 (54) 11-5/8 (295) 2-1/8 (54) 11-5/8 (295) D 25-5/8 (651) 25-5/8 (651) 25-5/8 (651) 25-5/8 (651) E 25 (635) 25 (635) 25 (635) 25 (635)
28-42kW (8-12ton) 15 x 11
32
Front of Unit
2-1/8" (54mm)
Front of Unit
1-1/2" (38mm)
Table 25
Models
Blower outlet and deck dimensional data upflow, 53-77kW (15-22 tons)
Dimensional Data, inches (mm) Blower 15 x 15 Supply Front Throw Rear Throw Front Throw Rear Throw A 15-7/8 (404) 15-7/8 (404) 15-7/8 (404) 15-7/8 (404) B 18-5/8 (472) 18-5/8 (472) 14-11/16 (373) 14-11/16 (373) C 2-1/8 (54) 11-5/8 (295) 2-1/8 (54) 11-5/8 (295) D 25-5/8 (651) 25-5/8 (651) 25-5/8 (651) 25-5/8 (651) E 27-3/4 (705) 27-3/4 (705) 31-3/8 (797) 31-3/8 (797) F 55-1/2 (1410) 55-1/2 (1410) 58-7/16 (1484) 58-7/16 (1484) G 25-1/8" (638mm) 25-1/8" (638mm) 27-3/4" (705mm) 27-3/4" (705mm) H 50-1/2" (1283mm) 50-1/2" (1283mm) 47" (1194mm) 47" (1194mm)
33
A B
A B
A B
Blower Outlet Location TOP VIEW * Duct Flanges Not Provided Top of Unit Blower Deck D 1-1/2" (38mm) 76" (1930mm) Ref Front or Rear Throw Air Supply
Table 26
Models 105kW (30 ton)
Front of Unit
DPN001192 Rev. 0
15 x 11
34
3-1/2" (89mm)
D Duct Size C
A B NOTES: 1. Filters can be accessed from either side. 2. 25" (635mm) minimum clearance provided on one side for filter access. 3. Filter boxes are shipped flat and must be field assembled.
Table 27 Rear return filter box dimensions
Dimensions, in (mm) Compressor Type 28-42kW (8-12 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 28-42kW (8-12 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 53-77kW (15-22 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 53-77kW (15-22 ton) Semi-Hermetic and all Water/Glycol/GLYCOOL Models 105kW (30 ton) All Models A 4-1/4 (108) 4-1/4 (108) 3-1/4 (83) 3-1/4 (83) 2-1/4 (57) B 50-3/4 (1289) 50-3/4 (1289) 75-1/2 (1918) 75-1/2 (1918) 100-1/4 (2546) C 18 (457) 31 (787) 19-1/4 (489) 30-1/4 (768) 29-1/2 (749) D
DPN001196 Rev. 0
# Filters 4 4 6 6 8
47-5/8 (1210) 47-5/8 (1210) 72-3/8 (1838) 72-3/8 (1838) 97-1/8 (2467)
35
With Grille
With Grille
Without Grille Left Side Views Check One (1): 34" (864mm) 1" (25mm) With Grille
Panel removable for condenser cleanout access (water/glycol / GLYCOOL models only) B A
Without Grille Right Side Views Check One (1): H With Grille 76" (1930mm)
Without Grille
Without Grille
Front View Unit With Plenum Notes: 1. Typical 53-77kW (15-22ton) unit orientation shown with grille plenum . View varies by unit size and plenum selection . 2. All plenums are shipped flat and must be field assembled . 3. Optional grille plenum kits must include front or rear grille . 4. Non-grille plenums are open on the top and not designed with duct flange .
Table 28 Upflow unit plenum dimensions
Plenum Dimensions, in (mm) A 28-42kW (8-12 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models B H 20 (508)
DPN001187 Rev. 0
Grille Size, in (mm) - Nominal
Front/Rear Grilles 18 x 55 (457 x 1397) 18 x 55 (457 x 1397) 18 x 78 (457 x 1981) 18 x 78 (457 x 1981) (1) 18 x 20 (457 x 508) (1) 18 x 78 (457 x 1981)
Side Grille 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508) 18 x 20 (457 x 508)
28-42kW (8-12 ton) Semi-Hermetic 59-1/4 (1505) 26-3/4 (679) and all Water/Glycol/GLYCOOL Models 53-77kW (15-22 ton) Air-Cooled Scroll and Air-Cooled Digital Scroll Models 82-1/4 (2089) 15-3/4 (400)
53-77kW (15-22 ton) Semi-Hermetic 82-1/4 (2089) 26-3/4 (679) and all Water/Glycol/GLYCOOL Models 105kW (30 ton) All Models 105-1/4 (2673) 26-3/4 (679)
24 (610) 36 (914)
36
5.0
5.1
Packaging Material
All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
SAFETY INFORMATION
! WARNING falling over. Can cause equipment damage, injury or death. Risk of top-heavy unit
Read all of the following instructions before attempting to move the unit, lift it, remove packaging or prepare the unit for installation.
! CAUTION splinters and exposed fasteners. Can cause personal injury. Risk of sharp edges,
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move the unit, lift it, remove packaging or prepare the unit for installation.
NOTICE
Risk of overhead interference. The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans to verify clearances prior to moving the unit. If the Liebert DS is too large to fit through doors, halls or other tight spaces, the unit can be partly dismantled as detailed in 7.0 - Disassembling the Liebert DS for Transport.
NOTICE
Risk of damage from forklift. Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of damage from forklift. Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the Liebert DS upright, indoors and protected from dampness, freezing temperatures and contact damage. Figure 32 Equipment recommended for handling Liebert DS
Forklift
Pallet Jack
If possible, transport the Liebert DS with a forklift or pallet jacks. If that is not possible, use a crane with belts or cables, slings and spreader bars. If using a forklift or pallet jack, make sure that the forks (if adjustable) are spread to the widest allowable distance that will fit under the skid. Ensure the fork length is suitable for the unit length. When moving the packaged Liebert DS with a forklift, lift the unit from the designated heavy side of the unit no higher than 6" (152mm) off the ground. Ensure that the opposite end still touches the ground. The unit is to be pulled by the forkliftIf the unit must be lifted higher than 6" (152mm) great care must be exercised: Personnel who are not directly involved in moving the unit must be kept 20' (5m) or farther from the lift point of the unit. Always refer to the location of the center of gravity indicators when lifting the Liebert DS (see Figure 36).
5.2
Step 1
Step 2
38
5.2.1
! WARNING Can cause equipment damage, injury or death. Risk of improper moving.
Use the center of gravity indicators on the unit to determine the entry points for the tines (see Figure 36). The center of gravity varies depending on the unit size and selected options. The forklifts tines must be equally spaced on either side of the center of gravity indicator. 2. Insert the tines of the forklift completely under the base of the Liebert DS.
! WARNING Can cause equipment damage, injury or death. Risk of improper moving.
Ensure that the tines are level, not angled up or down. The tines must be at a height that will allow proper clearance under the unit. Ensure the tines extend beyond the opposite side of the unit. 3. Remove the lag bolts from each bracket holding the Liebert DS to the skid. 4. Lift the unit off the skidno more than 6" (152mm)and remove the skid. Figure 34 Remove the unit from the skid
Step 1 Step 2
Step 3 Step 4
181659P1 Rev. 5
39
5.2.2
Step 2
Step 3
181659P1 Rev. 5
5.2.3
40
5.2.4
! WARNING Can cause equipment damage, injury or death. Risk of improper moving.
Use the center of gravity indicators (see Figure 36) on the unit to determine the position of the slings. The center of gravity varies depending on the unit size and selected options. The forklifts tines must be equally spaced on either side of the center of gravity indicator. 1. Space the slings equidistant on either side of the center of gravity indicator (see Figure 36). Figure 36 Locate center of gravity marker and place slings
Lifting Sling
Lifting Sling
Illustration shows one possible center of gravity. The center of gravity on the Liebert DS varies with the options and the models size.
Equal Distance
Equal Distance
181659P1 Rev. 5
2. Place the slings between the bottom rails of the Liebert DS and the top of the skid. NOTE Unit is shown without packaging. These instructions may be applied with the outer packaging in place. 3. Use spreader bars or a similar device and padding to ensure the Liebert DS will not be damaged when the unit is lifted. Lifting will force the slings toward the Liebert DS and the slings may damage the unit unless it is properly protected. 4. Remove the lag bolts from the bracket securing the Liebert DS to the shipping skid. 5. Remove the brackets. NOTE Depending on final installation location, the skid may need to remain under the unit. Therefore, the lag bolts and brackets would not yet be removed. 6. Lift the Liebert DS off the skid. 7. Move the skid from under the unit.
41
Lifting Sling
Lifting Sling
Equal Distance
Equal Distance
181659P1 Rev. 5
42
5.3
5.4
Welded Tab
DETAIL A
NOTE The floor stand for Liebert DS units equipped with EC fans is not symmetrical. Its orientation to the Liebert DS unit is critical for lowering the EC fans. Unless the floor stand is installed in the correct position, shown in Figures 24 and 26, the fans will not lower into the floor stand.
43
6.0
! WARNING and high speed rotating fan blades. Can cause injury or death. Risk of electric shock
Disconnect all local and remote electric power supplies and verify that fan blades have stopped rotating before working within.
! WARNING modules dropping downward suddenly. Can cause injury or death. Risk of very heavy fan
Support fan modules before removing mounting hardware. Use caution to keep body parts out of the fan modules pathway during repositioning. Only properly trained and qualified personnel should work on this equipment. Fan modules weigh in excess of 100 lbs (45.4kg) each. NOTE The Liebert DS unit should be used with the fans either in their original raised position or with the fans in their fully lowered position. Suspension of fans in an intermediate position will directly affect product performance and is not recommended.
6.1
44
Jack Location
Tabs
Detail A
Fan Deck Z Bracket (not present on Liebert DS) Remove Hex Head Screws Remove Hex Head Screws Z Bracket (not present on Liebert DS) Wiring Loop Raise Jack to Support Section Fan Not Shown
Section B-B
45
7. Using the jack, lower the fan module slowly until it rests on the frame of the unit.
NOTICE
Risk of equipment snagging cables and wiring. Can damage the Liebert DS components. Monitor the position of the fan harnesses and other parts while lowering the fan to be sure that they are not caught or pinched. 8. Secure the fan module in the fully lowered position by re-installing the hex head screws directly to the frame. Screw clearance holes are provided in the fan module. NOTE Not all hardware retained will be used to secure the fans in the lowered positioned. 9. Repeat Steps 3 through 8 to lower remaining fan modules. Figure 40 Lowering EC fans into floor stand, Steps 7 through 9
C
Lowered Fan Module Resting on Frame
6
Use Removed Hex Head Screws to Secure Lowered Fan to Frame Z Brackets (not present on Liebert DS)
SECTION C-C
Fan Deck and Side Panels Not Shown
46
6.2
! WARNING and high speed rotating fan blades. Can cause injury or death. Risk of electric shock
Disconnect all local and remote electric power supplies and verify that fan blades have stopped rotating before working within.
! WARNING modules dropping downward suddenly. Can cause injury or death. Risk of very heavy fan
Support fan modules before removing mounting hardware. Use caution to keep body parts out of the fan modules pathway during repositioning. Only properly trained and qualified personnel should work on this equipment. Fan modules weigh in excess of 100 lbs (45.4kg) each. NOTE The Liebert DS unit should be used with the fans either in their original raised position or with the fans in their fully lowered position. Suspension of fans in an intermediate position will directly affect product performance and is not recommended. 1. Remove the middle and bottom panels from the front of the unit. 2. For ease of fan removal, Emerson recommends removing the infrared humidifier using the approved infrared humidifier removal procedure. 3. If the fan to be removed has been lowered into the floor stand, position the factory supplied jack and jack support under the fan module so it is safely supported before removing any hardware. NOTE A properly positioned jack will be centered between the first and second set of tabs on the jack support. The jack will be biased toward the front of the unit. If the fan module is fully raised, proceed to Step 6. 4. Remove any securing hardware used to retain the fan in the lowered position. Retain hardware for fan module reinstallation. 5. Use the jack to raise the fan module slowly out of the floor stand and into the unit, ensuring that the fan motor clears the front frame channel.
NOTICE
Risk of equipment snagging cables and wiring. Can cause unit damage. Monitor the position of the fan harnesses and other parts while raising the fan to be sure that they are not caught or pinched while the fan is being raised.
47
B
Raise Jack to Support Fan Position Jack to Support Fan Position Jack to Support Fan
A
Floor Stand Partially Hidden
Tabs
Detail A
Jack Location
Remove and retain any hardware used to secure the lowered fan
SECTION B-B
Remove and retain any hardware used to secure the lowered fan DPN001695 Page 1, Rev. 5
6. Insert a field-supplied fan removal device under the fan module. The fan removal device should rest securely on the front and rear frame channels. 7. Disconnect high-voltage and low-voltage fan motor wiring from the fan motor electric component inside the electric panel. Carefully cut cable ties as needed. 8. Using the removal device, slide the fan module out through the front of the unit. 9. To reinstall the fan module, reverse the steps above. Remove the field-supplied fan removal device before resuming unit operation. NOTE Refer to the units electrical schematic for specific wire attachment points.
48
Raise Fan Module With Jack Disconnect Hign- and Low-Voltage Wiring
49
7.0
! WARNING from high-pressure refrigerant. Can cause injury or death. Risk of explosive discharge
This unit contains fluids and/or gases under high pressure. Relieve pressure before working with piping, compressors or other internal components.
! WARNING falling over. Improper handling can cause equipment damage, injury, Risk of top heavy unit
or death. Read all instructions before attempting to move or lift unit. Installation and service of this equipment should be done only by properly trained and qualified personnel who have been specially trained in the installation of air conditioning equipment.
! CAUTIONand heavy parts. Can cause personal injury. Risk of sharp edges
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
! CAUTION and lengthy parts. Can cause personal injury and equipment damage. Risk of handling heavy
Cabinet panels can exceed 5ft. (1.5m) in length and weigh more than 35lb. (15.9kg). Follow relevant OSHA lifting recommendations and consider using a two-person lift for safe and comfortable removal and installation of cabinet panels. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves and shoes should attempt to remove or install cabinet panels.
NOTICE
Risk of improper disassembly. Can cause equipment damage. Disassembling this unit requires substantial work, including reclaiming refrigerant and charging the unit, cutting and brazing refrigerant lines, cutting and brazing water lines, disconnecting and reconnecting electrical lines and moving heavy, bulky equipment. One member of the crew disassembling the unit must be qualified in wiring, brazing and refrigeration. Improperly disassembling or reassembling the Liebert DS may affect warranty.
7.1
Required Equipment
Piano jacks Stepladder for downflow units Refrigeration tools
50
7.2
DisassemblyDownflow Units
For detailed views of downflow units, see Figures 43 through 51. 1. Remove the unit from its shipping skid before beginning (refer to 5.2 - Unpacking the Unit). 2. Remove all panels except the top front accent. 3. Remove all filters. This allows access to the screws for metal plate blocking off the top coil and removal of the filter plate. 4. All wires are hot-stamped and all circuit board connectors are lettered to ease connection. Some cable ties must be cut and replaced. Refer to the units wiring schematic on the units deadfront panel for details.
NOTICE
5. 6. 7. 8. 9. 10. Do not lay the compressor section on its side. It must remain upright. The coil section also must remain upright. Label the three quick-connect plugs from the compressor compartment and disconnect them. Disconnect the compressor wire harness, including the crankcase heater wires, if present, from the contactor in the electric box. Pull the conduit and wires into the compressor compartment. Disconnect the fan motor wire harness from the bottom of the contactor in the electric box. Pull the conduit and wires into the bottom section of the Liebert DS. ReheatOptional Component a. Disconnect the reheat wire harness from the bottom of the contactor in the electric box. b. Unplug the low-voltage quick connect for the reheat safety wires. c. Pull the conduit and wires into the units blower and coil assembly section. HumidifierOptional Component a. Disconnect the humidifier wire harness from the bottom of the contactor in the electric box. b. For infrared humidifiers: Remove the quick-connect plugs from the following low-voltage connections: 35-5 and 35-6 (safety under pan), 35-3 and 35-4 (humidifier make-up valve), and 8-5 and 8-7 (high water alarm). For steam generating humidifiers: Remove the quick-connect plugs from the following low-voltage connections: 35-1, H-24H and H-24G, and 35-7 and HAR-24H. c. Disconnect 35-3 and 35-4 from the control board. d. Pull the conduit and wires into the units blower and coil assembly section. Condensate PumpOptional Component a. Disconnect the condensate pumps high-voltage wiring harness. b. Remove the low-volt wires from terminal strips #24 and #55. c. Pull the conduit and wires into the units blower and coil assembly section. GLYCOOL/Dual-CoolOptional Component a. On units with an actuator, unplug the valve actuator harness at the actuator and pull the wire harness into the electric box. b. Disconnect the glycol sensor from the control board and pull it into the units blower and coil assembly section. Disconnect the air sail switch wires and pull them into the electric box. Smoke DetectorOptional Component a. Remove the smoke detector cover. b. Remove the plug connector from the smoke detector and pull it into electric box. c. Remove the wires from terminal strips #91, 92, 93 and route them into the smoke detector box. d. Remove the sensing tube from top of the smoke detector. The wand and tube will remain attached to filter and electric box assembly. Close the electric box cover and the accent panel. Remove the pull bar that supports the accent panel from the left end of unit, otherwise it will fall out when the compressor section is removed.
11.
12.
13.
14. 15.
16. 17.
51
18. Evacuate and recover all refrigerant from the Liebert DS. Air-cooled units are shipped with a nitrogen holding charge. Water, glycol and GLYCOOL units are factory-charged with refrigerant. Refer to 9.0 - Piping for piping guidelines and to the ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
NOTICE
Risk of compressor oil contamination with moisture. Can cause equipment damage. Emerson recommends front-seating the compressor service valves. Front-seating the valves keeps the nitrogen or refrigerant charge in the compressor and prevents moisture from contaminating the compressor oil. This is particularly important with units using R-407C refrigerant. 19. Cut the insulation and pull it back from the piping. 20. Cut the refrigerant piping with a tubing cutter; if there is no Schrader fitting, let the nitrogen bleed out before cutting all the way through the pipe. NOTE Emerson does not recommend unsweating refrigerant connections. 21. Unsweat or cut all copper water pipes that interconnect unit sections. 22. Immediately cap and seal all piping that has been cut, including the suction and liquid lines, as well as the fluid piping on GLYCOOL and dual-cool units.
7.2.1
NOTICE
The compressor section is top-heavy and has a small base. It must remain upright. Do not lay the compressor section on its side during or after removing it from the Liebert DS. Do not remove shipping blocks from semi-hermetic compressors until the Liebert DS is fully reassembled and ready for installation. NOTE Emerson recommends using piano jacks when moving this section.
52
7.2.2
NOTICE
Risk of improper handling. The filter and electric box section should be moved forward and set on the floor. Make sure to lift the coil plate over the Schrader fittings on the headers. Emerson recommends using four people to remove this section. Special care is required when moving this section because the legs are not designed to withstand strong shocks. The blower and coil assembly must remain upright. The coil is not secured to the blower and coil assembly. Secure the coil to the bottom section with straps or a similar method before moving the section. 7. Move each section of the Liebert DS to the installation location.
7.3
ReassemblyDownflow Units
1. Replace the top section. Make sure to clear the Schrader valves on the coil header. 2. Reconnect the filter and electric box assembly to the blower and coil assembly using threadcutting bolts. Torque the bolts to 225 in-lb. (25Nm) 3. Reattach the evaporator top cover plate; there are eight screws on each side. 4. Reattach the filter support plate to the filter and electric box assembly; there is one screw on each side. 5. Reattach the tags to the Schrader fittings on top of the coil headers. 6. Replace the compressor section. Insert all compressor thread-cutting bolts before tightening any of the bolts. 7. Reinstall the pull bar to support the accent panel. 8. Reattach the low-voltage plugs in the compressor section. 9. Reconnect the wiring for the compressor, fan motor, reheat, humidifier, condensate pump, smoke detector and air sail switch. 10. Reattach the sensing tube to the top of the smoke detector. 11. On GLYCOOL and dual-cool units, reattach the plug connection at the actuator and reroute the sensor wire back through the electric box and onto the control board.
53
7.3.1
7.4
Reassembly Checklist
___ 1. Thread-cutting bolts reconnected and torqued to 225 in-lb. (25Nm) ___ 2. Top cover plate attached to coil ___ 3. Filter plate attached ___ 4. High-voltage wires connected to proper contactors: ___ a. Compressor ___ b. Fan motor ___ c. ___ e. Reheat, if applicable Condensate pump, if applicable ___ d. Humidifier, if applicable ___ 5. Low-voltage wires connected ___ a. Actuator ___ b. Terminal strip ___ c. Plug connections ___ d. Smoke detector, if applicable ___ 6. Coil access plates on right and left replaced ___ 7. Water lines brazed ___ 8. Suction and liquid refrigerant lines brazed ___ 9. Unit recharged ___ 10. Filters replaced ___ 11. Panels replaced
54
Figure 43 Component dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Filter & Electric Box Assembly
39" (991mm)
Compressor Assembly
76" (1930mm)
60-3/16" (1529mm)
37" (940mm)
33" (838mm)
26" (660mm)
Table 29
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
55
Figure 44 Component dimensionsdownflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Filter & Electric Box Assembly
39" (991mm)
Compressor Assembly
76" (1930mm)
60-3/16" (1529mm)
37" (940mm)
33" (838mm)
13" (330mm)
Table 30
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
56
Figure 45 Component dimensionsdownflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Filter & Electric Box Assembly
39" (991mm)
Compressor Assembly
76" (1930mm)
60-3/16" (1529mm)
37" (940mm)
33" (838mm)
Table 31
26" (660mm)
DPN000899 Rev. 1
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
57
Figure 46 Component dimensionsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Filter & Electric Box Assembly
39" (991mm)
76" (1930mm)
59-7/16" (1509mm)
37" (940mm)
33" (838mm)
26" (660mm)
DPN000926 Rev. 3
Table 32
Component weightsdownflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic; forward-curved and EC fan
Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled 970 (441) 250 (114) 1230 (560) Dual-Cool 970 (441) 250 (114) 1410 (641)
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
58
Figure 47 Component dimensionsdownflow air-cooled, 53-77kW (15-22 ton), scroll/digital scroll compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
39" (991mm)
76" (1930mm)
59-7/16" (1509mm) 37" (940mm)
33" (838mm)
Table 33
15" (381mm)
DPN000927 Rev. 3
Component weightsdownflow, air-cooled, 53-77kW (15-22 ton), scroll/digital scroll; forward-curved and EC fan
Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled 540 (246) 250 (114) 1230 (560) Dual-Cool 540 (246) 250 (114) 1410 (641)
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
59
Figure 48 Component dimensionsdownflow water/glycol, GLYCOOL, 53-77kW (15-22 ton), all compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
Filter & Electric Box Assembly
39" (991mm)
Compressor Assembly
76" (1930mm)
33" (838mm)
26" (660mm)
DPN000932 Rev. 2
Table 34
Liebert DS Section Compressor Assembly Filter and Electric Box Assembly Blower & Coil Assembly
60
Figure 49 Component dimensionsdownflow, air-cooled, 105kW (30 ton), semi-hermetic compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
Filter and Electric Box Assembly
76" (1930mm)
33" (838mm)
26" (660mm)
Table 35
Component weightsdownflow, air-cooled, 105kW (30 ton), semi-hermetic compressors; forward-curved and EC fan
Dry Weight, lb (kg) Approximate (Includes Panels) Forward Curved Fans Component Air-Cooled 950 (432) 270 (123) 1820 (827) Dual Cool 950 (432) 270 (123) 2180 (991) EC Fans Air-Cooled 950 (432) 270 (123) 1560 (708) Dual Cool 950 (432) 270 (123) 1915 (870)
Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
61
Figure 50 Component dimensionsdownflow, air-cooled, 105kW (30 ton), scroll compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
Filter & Electric Box Assembly
76" (1930mm)
33" (838mm)
26" (660mm)
DPN001058 Rev. 1
Table 36
Component weightsdownflow, air-cooled, 105kW (30 ton), scroll compressor models; forward-curved and EC fan
Dry Weight, lb (kg) Approximate (Includes Panels) Forward Curved Fans EC Fans Air-Cooled 830 (377) 270 (123) 1560 (708) Dual Cool 830 (377) 270 (123) 1915 (870)
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly
62
Figure 51 Component dimensionsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), forward-curved and EC fan, all compressor models; forward-curved and EC fan
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
Filter & Electric Box Assembly
76" (1930mm)
33" (838mm)
26" (660mm)
Table 37
Component weightsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models; forward-curved and EC fan
Dry Weight, Approximate, Including Panels, lb (kg) Semi-Hermetic Compressor Scroll Compressor Water/Glycol 1200 (545) 270 (123) 1820 (827) / 1560 (708) GLYCOOL/Dual-Cool 1200 (545) 270 (123) 2180 (991) /
Component Compressor Assembly Filter & Electric Box Assembly Blower & Coil Assembly, Forward-Curve Fan / EC Fan)
1915 (870)
1915 (870)
63
7.5
DisassemblyUpflow Units
For detailed views of upflow units, see Figures 52 through 60. 1. Remove the unit from its skid. 2. Remove all panels except top front accent. 3. Remove all filters on front return units. This allows easier access to items located in the filter and coil assembly. 4. All wires are hot stamped and all circuit board connectors are lettered for easy replacement. Cable ties will need to be cut and replaced as necessary. Reference unit wiring schematic on deadfront panel for details. 5. Label the (3) quick connect plugs from the compressor compartment, and disconnect them. 6. Disconnect compressor wire harness, including crankcase heater wires, if applicable, from contactor in electric box. Pull conduit and wires into compressor compartment. 7. Reheat (optional component): Disconnect reheat wire harness from bottom of contactor in electric box. Unplug low-voltage quick connect for reheat safety wires. Pull conduit and wires into filter and coil assembly section of unit. 8. Humidifier (optional component): a. Disconnect the humidifier wire harness from the bottom of the contactor in the electric box. For infrared humidifiers: Remove the quick-connect plugs from these low-voltage connections: 35-5 and 35-6 (safety under pan), 35-3 and 35-4 (humidifier make-up valve) and 8-5 and 8-7 (high water alarm). For steam generating humidifiers: Remove the quick-connect plugs from the following low-voltage connections: 35-1, H-24H and H-24G, and 35-7 and HAR-24H. b. Disconnect 35-3 and 35-4 from the control board. c. Pull the conduit and wires into the units filter and coil assembly section. 9. Condensate pump (optional component): Disconnect condensate pump high-voltage wire harness. Remove low volt wires from terminal strip #24 and #55. Pull conduit and wires into filter and coil assembly section of unit. 10. Glycool/Dual-Cool (optional component): On units with actuator, unplug valve actuator harness at actuator and pull wire harness into electric box. Disconnect glycol sensor from control board and pull into filter and coil assembly section of unit. 11. Smoke detector (optional component): For units with smoke detector, remove cover on smoke detector. Remove plug connector from smoke detector and pull into electric box. Remove wires from terminal strip #91, 92, 93 and route the wires to the smoke detector box. Remove the sensing tube from the bottom of the plastic elbow. 12. Filter Clog Switch: Disconnect both tubes from the filter clog switch. Pull both of the tubes into the electric box. 13. Close the electric box cover and the accent panel. 14. Remove the pull bar that supports the accent panel from left end of unit, otherwise it will fall out when the compressor section is removed. 15. Evacuate and recover all refrigerant from the unit. Air-cooled units contain a nitrogen holding charge. Water, glycol and GLYCOOL units are factory charged with refrigerant. Refer to 9.0 - Piping for piping guidelines and to the ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
NOTICE
Risk of compressor oil contamination with moisture. Can cause equipment damage. Emerson recommends front-seating the compressor service valves. Front-seating the valves keeps the nitrogen or refrigerant charge in the compressor and prevents moisture from contaminating the compressor oil. This is particularly important with units using R-407C refrigerant. 16. Cut and pull back insulation from piping.
64
17. Cut the refrigerant piping with a tubing cutter; if there is no Schrader fitting, let the nitrogen bleed out before cutting all the way through the pipe. NOTE Emerson does not recommend unsweating refrigerant connections. 18. Unsweat or cut all copper water pipes that interconnect unit sections. 19. Immediately cap off and seal all piping that has been cut, including the suction and liquid lines, the humidifier supply line and the condensate discharge line (if applicable), as well as fluid piping on GLYCOOL and dual-cool units.
7.5.1
NOTICE
The compressor section is top-heavy and has a small base. It must remain upright. Do not lay the compressor section on its side during or after removing it from the Liebert DS. Do not remove the shipping blocks from the semi-hermetic compressors until the Liebert DS is fully reassembled and ready for installation. NOTE Emerson recommends using piano jacks when moving this section.
7.5.2
NOTICE
Risk of improper handling. May cause damage to the Liebert DS. The blower and electric box assembly should be moved forward and set on the floor. Emerson recommends using four people to remove this section. The motor end will be significantly heavier than the other end. The filter and coil assembly must remain upright. The coil is not secured to the filter and coil assembly. Secure the coil to the bottom section with straps or a similar means before moving the section. 4. Move each section of the Liebert DS to the installation location.
65
7.6
ReassemblyUpflow Unit
1. Reattach the top section using thread-cutting bolts; there are four on each side. Torque the bolts to 225 in-lb (25Nm). 2. Reinstall the motor access plate. Do not replace the left end coil access plates until brazing is finished. 3. Reattach the compressor section. Insert all compressor thread-cutting bolts before tightening them all down. 4. Reinstall the pull bar to support the accent panel. 5. Reinstall the low-voltage plugs in the compressor section. 6. Rewire the compressor, reheat, humidifier, condensate pump and smoke detector, if applicable. 7. Reattach the sensing tube to the blower inlet. 8. Reattach the plug connection at the actuator and reroute the sensor back through electric box and onto control board, on GLYCOOL and dual-cool units. 9. Piping must be reassembled in accordance with local codes. 10. Move the insulation and plastic bushings away from the brazing area. 11. Wrap the piping with wet cloths. Use copper fittings where required. 12. Refer to 9.0 - Piping for piping guidelines and to the ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping. 13. Open service valves on compressor. 14. Reinsert plastic bushings. 15. Charge the Liebert DS with refrigerant; see the units nameplate for the proper charge. 16. Replace the galvanized panels on the left side of the coil. 17. Replace the filters. 18. Replace the panels.
7.7
Reassembly Checklist
___ 1. Thread-cutting bolts reconnected at a torque specification of 225 in-lb (25Nm). ___ 2. High-voltage wires connected to proper contactors: ___ a. compressor ___ b. reheat, if applicable ___ c. humidifier, if applicable ___ d. condensate pump, if applicable ___ 3. Low-voltage wires connected: ___ a. actuator ___ b. terminal strip ___ c. plug connections ___ d. smoke detector, if applicable ___ 4. Coil access plates on left side replaced ___ 5. Motor access plate on right side replaced ___ 6. Water lines brazed ___ 7. Suction and liquid refrigerant lines brazed ___ 8. Unit recharged ___ 9. Filters replaced ___ 10. Panels replaced
66
Figure 52 Component dimensionsupflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
31-1/4" (794mm)
45-13/16" (1163mm)
33" (838mm)
26" (660mm)
DPN001171 Rev. 0
Table 38
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
67
Figure 53 Component dimensionsupflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Blower & Electric Box Assembly
31-1/4" (794mm)
33" (838mm)
13" (330mm)
DPN001172 Rev. 0
Table 39
Component weightsupflow, air-cooled, 28-42kW (8-12 ton), scroll/digital scroll compressor models
Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled 490 (223) 510 (231) 520 (236) Dual-Cool 490 (223) 510 (231) 670 (304)
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
68
Figure 54 Component dimensionsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
31-1/4" (794mm)
Compressor Assembly
45-13/16" (1163mm)
33" (838mm)
26" (660mm)
DPN001173 Rev. 0
Table 40
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
69
Figure 55 Component dimensionsupflow, air-cooled, 53-77kw (15-22 ton), semi-hermetic compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
31-1/4" (794mm)
33" (838mm)
26" (660mm)
DPN001209 Rev. 0
Table 41
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
70
Figure 56 Component dimensionsupflow, air-cooled, 53-77kw (15-22 ton), scroll/digital scroll compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual.
31-1/4" (794mm)
45-13/16" (1163mm)
33" (838mm)
15" (381mm)
DPN001210 Rev. 0
Table 42
Component weightsupflow, air-cooled, 53-77kw (15-22 ton), scroll /digital scroll compressor models
Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled 540 (246) 770 (349) 760 (345) Dual-Cool 540 (246) 770 (349) 940 (426)
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
71
Figure 57 Component dimensionsupflow water/glycol/GLYCOOL 53-77kw (15-22 ton), all compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Blower & Electric Box Assembly
31-1/4" (794mm)
45-13/16" (1163mm)
33" (838mm)
26" (660mm)
DPN001211 Rev. 0
Table 43
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
72
Figure 58 Component dimensionsupflow, air-cooled, 105kW (30 ton), semi-hermetic compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Blower & Electric Box Assembly
31-1/4" (794mm)
Compressor Assembly
33" (838mm)
26" (660mm)
DPN001254 REV 0
Table 44
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
73
Figure 59 Component dimensionsupflow, air-cooled, 105kW (30 ton), scroll/digital scroll compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Blower & Electric Box Assembly
31-1/4" (794mm)
Compressor Assembly
45-13/16" (1164mm)
33" (838mm)
26" (660mm)
DPN001255 REV 0
Table 45
Component weightsupflow, air-cooled, 105kW (30 ton), scroll/digital scroll compressor models
Dry Weight, Approximate, Including Panels, lb (kg) Air-Cooled 830 (376) 1080 (490) 970 (440) Dual-Cool 830 (376) 1080 (490) 1300 (590)
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
74
Figure 60 Component dimensionsupflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models
Drawing views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. Blower & Electric Box Assembly
31-1/4" (794mm)
Compressor Assembly
33" (838mm)
26" (660mm)
105" (2667mm)
DPN001256 REV 0
Table 46
Component Compressor Assembly Blower & Electric Box Assembly Filter & Coil Assembly
75
Electrical Connections
8.0
ELECTRICAL CONNECTIONS
Three-phase electrical service is required for all models. Electrical service must conform to national and local electrical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic when making connections. Refer to Figure 61 for electrical service entrances into unit. A manual electrical disconnect switch should be installed in accordance with local codes and distribution system. Consult local codes for external disconnect requirements.
! WARNING
Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage, injury or death. Installation and service of this equipment should be done only by qualified personnel who have been specially trained in the installation of air conditioning equipment. NOTE Seal openings around piping and electrical connection to prevent air leakage. Failure to do so could reduce the units cooling performance.
NOTICE
Risk of improper electrical connection of three-phase input power. Can cause unit damage. Service technicians should use a gauge set on the Liebert DS system during the initial startup to verify that the three-phase power is connected properly. The EC fans are not a reliable indicator of proper connection. The blowers will rotate the same direction, regardless of the three-phase power input.
NOTICE
Risk of backward compressor rotation. Can cause equipment damage. Three-phase power must be connected to the unit line voltage terminals in the proper sequence so that scroll compressors rotate in the proper direction.
NOTICE
Risk of improper electrical supply connection. Can cause equipment damage. See transformer label for primary tap connections. Installer will need to change transformer primary taps if applied unit voltage is other than pre-wired tap voltage.
NOTICE
Risk of overheated terminals. Can cause wiring and component damage. Use copper wiring only. Make sure that all connections are tight.
76
Electrical Connections
A
5 14
B D
C
OVERCURRENT PROTECTION DEVICES
P64 P67
CONTACTORS
6 60 Hz 12
CONTACTORS & RELAYS AND OVERLOAD PROTECTORS Note: Typical orientation of components shown. Component location varies by option and unit size. 16 17 10 21 15 18 9
6 50 Hz
Downflow 3
UPFLOW
82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78
A
23 22 20 7
B
8 11 19
CAUTION: Risk of broken or shorted low-voltage wiring. Field-installed low-voltage wiring must be routed with loop as shown to allow electric box to swing.
58 59 84 85
37C38C37B38B 37 38 24 50 51 55 56 70 71 72 73
C
Refer to Table 47 on page 78 for keys to numbered items.
77
Electrical Connections
Table 47
OPTIONAL ELECTRICAL CONNECTIONS 12.Factory-installed disconnect switch. 13.Secondary disconnect switch and earth ground. STANDARD ELECTRICAL CONNECTIONS 14.Three-phase electrical service - Terminals are on top of disconnect 1. Primary high voltage entrance - 2.50" switch. Three-phase service not by Emerson. (64mm); 1.75" (44mm); 1.375" (35mm) diameter concentric knockouts in bottom of box. 15.Smoke sensor alarm - Factory-wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 2. Secondary high voltage entrance - 2.50" & 81, open on sensor trouble indication. This smoke sensor is not (64mm); 1.75" (44mm); 1.375" (35mm) intended to function as, or replace, any room smoke detection diameter concentric knockouts in top of box. system that may be required by local or national codes. 1A, 24VAC 3. Primary low voltage entrance - Quantity (3) max load. Use field-supplied Class 1 wiring. 1.125" (28mm) diameter knockouts in bottom of 16.Reheat and humidifier lockout - Remote 24VAC required at unit. Terminals 82 & 83 for lockout of reheat and humidifier. 4. Secondary low voltage entrance - Quantity 17.Condensate alarm (with condensate pump option) - On pump (3) 1.125" (28mm) diameter knockouts in top of high water indication, normally open dry contact is closed across box. Terminals 88 & 89 for remote indication. 1A, 24VAC max load. Use 5. Three-phase electrical service - Terminals field-supplied Class 1 wiring. are on high voltage terminal block (disregard if 18.Analog inputs - Terminals for up to two customer-supplied analog unit has optional disconnect switch). inputs. Device 1 wires to 41(-) and 42(+). Device 2 wires to 43(-) and Three-phase service not by Emerson. 44(+). 6. Earth ground - Terminal for field-supplied earth grounding wire. Earth grounding required for all 19.Remote humidifier - On any call for humidification, normally open dry contact is closed across Terminals 11 & 12 to signal field-supplied units. remote humidifier. 1A, 24VAC max load. Use field-supplied Class 1 7. Remote unit shutdown - Replace existing wiring. jumper between Terminals 37 & 38 with field20.Auxiliary cool contact - On any call for Econ-O-Coil operation, supplied normally closed switch having a normally open dry contact is closed across Terminals 72 & 73 on minimum 75VA, 24VAC rating. Use Dual-Cool units only. 1A, 24VAC max load. Use field-supplied field-supplied Class 1 wiring. Class 1 wiring. 8. Customer alarm inputs - Terminals for field-supplied, normally open contacts, having a OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS 21.Remote unit shutdown - Two additional contact pairs available for minimum 75VA, 24VAC rating, between unit shutdown (labeled as 37B & 38B, 37C & 38C). Replace jumpers Terminals 24 & 50, 51, 55, 56. Use with field-supplied normally closed switch having a minimum 75VA, field-supplied Class 1 wiring. Terminal 24VAC rating. Use field-supplied Class 1 wiring. availability varies by unit options. 9. Liebert SiteScan - Terminals 77(-) & 78(+) for 22.Common alarm - On any alarm, two additional normally open dry contacts are closed across Terminals 94 & 95 and 96 & 97 for remote a 2-wire, twisted-pair, communication cable indication. 1A, 24VAC max load. Use Class 1 field-supplied wiring. (available from Emerson) to optional Liebert 23.Main fan auxiliary switch - On closure of main fan contactor, SiteScan. The communication cable must be normally open dry contact is closed across Terminals 84 & 85 for shielded on units with VFD or EC fans. remote indication. 1A, 24VAC max load. Use field-supplied Class 1 10.Common alarm - On any alarm, normally open wiring. dry contact is closed across Terminals 75 & 76 for remote indication. 1A, 24VAC max load. Use 24.Liebert Liqui-tect shutdown and dry contact - On Liebert Liqui-tect activation, normally open dry contact is closed across field-supplied Class 1 wiring. Terminals 58 & 59 for remote indication (Liebert Liqui-tect sensor 11.Heat rejection interlock - On any call for ordered separately). 1AMP, 24VAC max load. Use field-supplied compressor operation, normally open dry Class 1 wiring. contact is closed across Terminals 70 & 71 to DPN000807 heat rejection equipment. 1A, 24VAC max load. Rev. 2 Use field-supplied Class 1 wiring. Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size.
78
Electrical Connections
8.1
! WARNING from leakage current. Can cause injury or death. Risk of electric shock
Reconnect earth ground if servicing or replacing the variable speed drive (VSD). An optional Variable Speed Drive (VSD) is available on some Liebert DS models. The VSD reduces power consumption by reducing the blower speed to match the units load. This packaged unit is factory-set and should not require field-adjustment.
! WARNING Risk of contact with nearby high speed moving parts. Can cause injury or death.
Do not attempt to adjust or view variable frequency drive settings at the display on the face of the VSD. Instead, use a remote display (Liebert service item part number 196632P1) and connect to the VSD remote cable in the extra low voltage electric panel.
NOTICE
Risk of improper program adjustment. Can cause equipment damage and loss of warranty. The VSD is factory-programmed for proper operation. Altering the VSD program without authorization from the factory may void the warranty. NOTE Emerson requires the Liebert DS to have a grounded supply. The VSD may be damaged if it is operated on an ungrounded supply.
8.1.1
NOTICE
Risk of mismatched input power supply and VSD requirements. May cause equipment damage and failure. The EMC filter must be removed from the VSD if the power supply is Delta-connected.
8.1.2
Winding A Winding B
Neutral
79
Electrical Connections
8.1.3
Winding C-A
Winding A-B
Table 48
Motor hp 3hp 5hp 7.5hp 10hp
Inverter type
Unit Electrical Requirements, Voltage, Phase, Hz 208-3-60 Size C Size D Size 2 N/A 230-3-60 Size C Size D Size 2 Size 2 380-3-60 Size C Size C Size D Size 2 460-3-60 Size C Size C Size D Size D 575-3-60 N/A N/A N/A N/A 200-3-50 N/A N/A N/A N/A 380/415-3-50 Size C Size C Size D Size 2
Disconnect EMC Filter for Delta-Connected Power for Size C & D Inverters
The EMC filter on the VSD must be disconnected if the Liebert VSD control DS unit will be operated with Delta-connected power. 1. Disconnect the power supply before working on the unit. 2. Locate the VSD (refer to Figure 1 for the drives location on downflow units; see Figure 2 for the location on upflow units). 3. Remove electrical junction box cover. 4. Using Figure 64, locate the small black plastic tab immediately to the right of the wiring connection block of the VFD control. 5. Pull the tab to fully extend it, disconnecting the EMC filter from the circuit. 6. Reinstall the electrical junction box cover.
80
Electrical Connections
Figure 64 Disconnecting EMC filter for operation with Delta-connected power size C & D inverters
B
Internal EMC filter
DPN001946 Rev. 0
4 1 2
3 DPN001947 Rev. 0
81
Piping
9.0
PIPING
All fluid and refrigeration connections to the unit, with the exception of the condensate drain, are sweat copper. Factory-installed piping brackets must not be removed. Field-installed piping must be installed in accordance with local codes and must be properly assembled, supported, isolated and insulated. Avoid piping runs through noise-sensitive areas, such as office walls and conference rooms. Refer to specific text and detailed diagrams in this manual for other unit-specific piping requirements. All piping below the elevated floor must be located so that it offers the least resistance to air flow. Careful planning of the piping layout under the raised floor is required to prevent the air flow from being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be run parallel to the air flow.
9.1
Fluid Connections
NOTICE
Risk of clogged or leaking drain lines. Can cause equipment and building damage. This unit requires a water drain connection. Drain lines must be inspected regularly and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson recommends installing leak detection equipment for unit and supply lines. NOTE Seal openings around piping and electrical connection to prevent air leakage. Failure to do so could reduce the units cooling performance.
9.1.1
Condensate PipingField-Installed
Do not reduce drain lines Do not expose drain line to freezing temperatures Drain line may contain boiling water. Use copper or other suitable material Drain line must comply with local building codes Emerson recommends installing under-floor leak detection equipment
NOTICE
The drain line must not be trapped outside the unit or water may back up in the drain pan.
82
Piping
DOWNFLOW DS UNIT
INTERNAL DRAIN UNIT
UPFLOW DS UNIT
EXTERNAL DRAIN INTERNAL DRAIN UNIT
CORRECT
INTERNAL DRAIN
CORRECT
INTERNAL DRAIN UNIT EXTERNAL DRAIN
UNIT
EXTERNAL DRAIN
INCORRECT
INTERNAL DRAIN UNIT
INCORRECT
EXTERNAL DRAIN INTERNAL DRAIN UNIT
EXTERNAL DRAIN
THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH UNINTENTIONAL. LINES MUST BE RIGID ENOUGH NOT TO BOW OVER TOP OF OTHER OBJECTS. THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH UNINTENTIONAL. LINES MUST BE RIGID ENOUGH NOT TO BOW OVER TOP OF OTHER OBJECTS.
INCORRECT
Condensate Pump
INCORRECT
DPN001556 Rev. 0
1/2" copper sweat connection is provided on units with optional factory-installed condensate pump Condensate Pump (60Hz): Condensate pump is rated for approximately 400 gph at 10 feet total head Condensate Pump (50Hz): Condensate pump is rated for approximately 315 gph at 10 feet total head Size piping based on available condensate head
83
Piping
9.1.2
9.1.3
9.1.4
General Guidelines
Equipment damage and personal injury can result from improper piping installation, leak checking, fluid chemistry and fluid maintenance. Follow local piping codes, safety codes. Qualified personnel must install and inspect system piping. Contact a local water consultant regarding water quality, corrosion protection and freeze protection requirements. Install manual shutoff valves at the supply and return line to each indoor unit and drycooler to permit routine service and emergency isolation of the unit.
NOTICE
Risk of frozen fluids. Can cause equipment damage and building damage. Freezing system fluids can rupture piping. Complete system drain-down cannot be ensured. When the field piping or unit may be exposed to freezing temperatures, charge the system with the proper percentage of glycol and water for the coldest design ambient. Automotive antifreeze is unacceptable and must NOT be used in any glycol fluid system.
NOTICE
Risk of corrosion. Can cause equipment damage. Read and follow individual unit installation instructions for precautions regarding fluid system design, material selection and use of field-provided devices. Liebert systems contain iron and copper alloys that require appropriate corrosion protection. Contact a water consultant about water quality, corrosion and freeze protection requirements. Water chemistry varies greatly by location, as do the required additives, called inhibitors, that reduce the corrosive effect of the fluids on the piping systems and components. The chemistry of the water used must be considered, because water from some sources may contain corrosive elements that reduce the effectiveness of the inhibited formulation. Preferably, surface waters that are classified as soft and are low in chloride and sulfate ion content should be employed. Proper inhibitor maintenance must be performed to prevent corrosion of system components. Consult glycol manufacturer for testing and maintenance of inhibitors. Commercial ethylene glycol (Union Carbide Ucartherm, Dow Chemical Dowtherm SR-1 and Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive to the common metals of construction than water itself. It will, however, assume the corrosivity of the water from which it is prepared and may become increasingly corrosive with use if not properly inhibited.
NOTICE
Risk of fluid leaks from tubing and piping corrosion. Can cause serious equipment and building damage. Idle fluid allows the collection of sediment that prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched ON and system pump operating.
84
Piping
9.2
Refrigeration Piping
! WARNING from high-pressure refrigerant. Can cause injury or death. Risk of explosive discharge
This unit contains fluids and/or gases under high pressure. Relieve pressure before working with piping.
! WARNING rupture or explosion from over pressurization. Can cause Risk of refrigerant system
equipment damage, injury or death. For systems requiring EU CE-compliance (50Hz), the system installer must provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and the field installed relief valve. The pressure relief valve must be CE-certified to the EU Pressure Equipment Directive by an EU Notified Body. NOTE The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp condensers. Consult local building codes to determine whether the Liebert Fan Speed Control and VFD condensers will require field provided pressure relief devices.
NOTICE
Risk of oil contamination with water. Can cause equipment damage. Some Liebert DS Systems require the use of POE (polyolester) oil. See 13.10.1 - Compressor Oil for requirements. POE oil absorbs water at a much faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage. Refrigerant charge must be weighed into scroll and digital scroll compressors before they are started. Starting scroll and digital scroll compressors without proper refrigerant charging can cause the compressors to operate at less than 5F (-15C) evaporator temperature and at less than 20psig (138kPa). Operation for extended periods at less than 20psig (138kPa) can cause premature compressor failure.
85
Piping
9.2.1
Standard Scroll Models (Non-Digital Scroll) Hot Hot Hot Hot Hot Hot Hot Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line 50 ft (15m) 100 ft (30m) 150 ft (45 m) Model 7/8 7/8 7/8 1/2 5/8 5/8 028 7/8 7/8 7/8 1/2 5/8 5/8 035 7/8 7/8 7/8 042 1/2 5/8 5/8 7/8 1-1/8 1-1/8 053 5/8 7/8 7/8 1-1/8 1-1/8 1-1/8 070 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 7/8 7/8 1-3/8 1-3/8 7/8 7/8
4-Step Semi-Hermetic and Digital Scroll Models 077 Hot Hot Hot Hot Hot Hot Hot Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line 50 ft (15m) 100 ft (30m) 150 ft (45 m) 3/4 3/4 7/8 1/2 5/8 5/8 3/4 7/8 7/8 1/2 5/8 5/8 7/8 7/8 1-1/8* 5/8 5/8 5/8 7/8 1-1/8* 1-1/8 7/8 7/8 7/8 1-1/8* 1-1/8 1-1/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 7/8 7/8 1-3/8 1-3/8 7/8 7/8
1-3/8 1-1/8
Table 50
System Type
Air-Cooled
Water, Glycol/GLYCOOL
86
Piping
Table 51
Line Size, O.D., in. 1/2 5/8 3/4 7/8 1-1/8 1-3/8
Table 52
Standard Condenser Models 165 205 251 308 415 510 143 214 286 409 572
FSC or VFD 5 (2.3) 7 (3.2) 10 (4.6) 11 (5.0) 25 (11.3) 30 (13.6) N/A N/A N/A N/A N/A
Lee-Temp (includes receiver) 27 (12.3) 56 (25.3) 38 (17.2) 58 (26.3) 107 (48.4) 149 (67.6) 64 (29.0) 81 (36.7) 125 (56.7) 129 (58.5) 196 (88.9)
87
Piping
9.2.2
60lb (27.2kg)
80lb (36.3kg)
100lb (45.4kg)
120lb (54.4kg)
140lb (63.5kg)
160lb (72.6kg)
180lb (81.6kg)
200lb (90.7kg)
Additional Oil Required Per Circuit - Ounces (Grams) 0 7.5 (213) 5 (142) 4 (113) 15.5 (439) 13 (369) 7 (198) 23.5 (666) 21 (595) 10 (283) 31.5 (893) 29 (822) 13 (369) 39.5 (1120) 37 (1049) 16 (454) 47.5 (1347) 45 (1276) 20 (567) 55.5 (1573) 53 (1502) 23 (652) 63.5 (1800) 61 (1729) 26 (737) 71.5 (2027) 69 (1956)
For system charges over 200lb (90.7kg), consult your Emerson representative.
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage. Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty. See Table 64 for compressor oil types. Do not mix polyolester (POE) and mineral-based oils. Do not mix oils of different viscosities. Consult Emerson or the compressor manufacturer if questions arise.
88
Piping
9.3
9.3.1
89
Piping
Due to control processing time, the pumpdown pressure at compressor shutoff will be approximately 20psiG (138kPa) / 35psiA (241 kPa) even though the setpoint is 35 psiG (241 kPa) / 50 psiA (344kPa).
6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound (2.2kg) of refrigerant. NOTE A digital scroll compressor will have a clear sight glass only when operating at 100% capacity. When operating below 100%, the sight glass may show bubbles with each 15-second unloading cycle. 7. As head pressure builds, the variable fan speed controlled condenser fan begins rotating. The fan will run at full speed when sufficient head pressure is developedfan starts to rotate at 190 psig (1310 kPA) and is full speed at 250 psig (1724 kPA).
90
Piping
9.3.2
Air-Cooled Condenser with Liebert Lee-Temp Flooded Condenser Head Pressure Control System
The Liebert Lee-Temp system consists of a modulating type head pressure control valve and insulated receivers with heater pads to ensure operation at ambient temperatures as low as -30F (-34.4C). The Liebert Lee-Temp system can be used with any Liebert DS compressor choice.
91
Piping
7. After completion of leak testing, release the test pressure (per local code) and pull an initial deep vacuum on the system with a suitable pump. 8. After four hours, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen. Pull a second (R-407C and R-22) and third (R407C only) vacuum to 250 microns or less. Recheck the pressure after two hours. After completing this step, proceed to Variable Fan Speed Charging on page 90. 9. Remove the jumper hose installed previously from between the service valve fitting and the condenser. After completing this step, proceed to Lee-Temp Charging.
Lee-Temp Charging
1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending on refrigerant type. 2. Refrigerant charging requires unit operation. Refer to 11.0 - Checklist for Completed Installation. 3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line charge data in Tables 50, 51 and 52. 4. Weigh in as much of the system charge as possible before starting the unit.
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage. Refrigerant R407C is a blend of three components and must be introduced and charged from the cylinder only as a liquid. When adding liquid refrigerant to an operating system, it may be necessary to add the refrigerant through the compressor suction service valve. Care must be exercised to avoid damage to the compressor. Emerson recommends connecting a sight glass between the charging hose and the compressor suction service valve. This will permit adjustment of the cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the compressor. 5. Turn on unit disconnect switch. Operate the unit for 30 minutes using the charging function for System # 1 and System # 2 in the diagnostic section of the Liebert iCOM control. The charging function operates the compressor at full capacity and energizes the blower motor and liquid line solenoid valve. The reheat and humidifier are disabled. A minimum 20psig (138kPa) must established and maintained for the compressor to operate. The charging function can be reset as many times as required to complete unit charging. Table 55 Lee-Temp suction pressure transducer settings
R-22 Function Pump-Down Cutout Pump-Down Reset Minimum to Start-Cooling Low-Pressure Cutout (DX only) Freeze Protection (DX w/Econ-O-Coil) Gauge (Sea Level) psiG (kPa) 35 (241) 65 (448) 50 (345) 20 (138) 48 (331) Absolute psiA (kPa) 50 (344) 80 (552) 65 (448) 35 (241) 63 (434) R-407C Gauge (Sea Level) psiG (kPa) 35 (241) 65 (448) 50 (345) 20 (138) 52 (358) Absolute psiA (kPa) 50 (344) 80 (552) 65 (448) 35 (241) 67 (461)
Due to control processing time, the pumpdown pressure at compressor shut off will be approximately 20psiG (138kPa) / 35psiA (241kPa) even though the setpoint is 35psiG (241kPa) / 50psiA (344kPa).
6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound (2.2 kg) of refrigerant. NOTE A digital scroll compressor will have a clear sight glass only when operating at 100% capacity. When operating below 100%, the sight glass may show bubbles with each 15-second unloading cycle.
92
Piping
9.3.3
Due to control processing time, the pumpdown pressure at compressor shut off will be approximately 20 psiG (138 kPa) / 35 psiA (241 kPa) even though the set point is 35 psiG (241 kPa) / 50 psiA (344kPa).
93
Piping Schematics
LIQUID RETURN
Inverted Trap on discharge & liquid lines to extend above base of coil by a minimum of 7-1/2" (190mm)
LIEBERT LEE-TEMP
LIQUID EVAPORATOR COIL * For rises over 25ft. (7.6m), trap every 20ft. (6m) or at evenly spaced points
Service Valve
Cylinder Unloader(s)
External Equilizer
Field installed relief valve(s) required for 50Hz EU CE units rated maximum 480 PSIG (33 Bar). *Isolation Valve
**Muffler
Sight Glass
Filter Drier
NOTES: Schematic representation shown. Do not use for specific connection locations. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. REFRIGERANT PIPING FIELD PIPING SERVICE / SCHRADER (ACCESS) CONNECTION, NO VALVE CORE SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
*Isolation * Trap at base Valve of risers longer * Components are not supplied than 5ft. (1.5m) by Emerson but are recommended for proper circuit operation and maintenance ** Components supplied by Emerson and must be field-installed (70kW, 77kW & 105kW models only)
LIQUID RETURN
DPN000797 REV 5
94
Piping Schematics
FAN SPEED/VFD (Liebert Lee-Temp or VFD condenser is required with digital scroll) LIQUID
28-42kW Digital Solenoid Valve 53-70kW Digital Solenoid Valve Service Valve Check Valve Service COMPRESSOR Valve External Equalizer Sensing Bulb SUCTION
LIEBERT LEE-TEMP (Liebert Lee-Temp or VFD condenser is required with digital scroll)
* For rises over 25ft. (7.6m), trap every 20ft. (6m) or at evenly spaced points
EVAPORATOR COIL
Field-installed relief valve(s) required for 50Hz EU CE units rated maximum 480 PSIG (33 Bar). *Isolation Valve HOT GAS DISCHARGE
Sight Glass
Filter Drier
LIQUID RETURN
NOTES: Schematic representation shown. Do not use for specific connection locations. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. REFRIGERANT PIPING FIELD PIPING SERVICE / SCHRADER (ACCESS) CONNECTION, NO VALVE CORE
* Trap at base of risers longer than 5ft. (1.5m) * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance
*Isolation Valve
DPN000798 REV 5
95
Piping Schematics
Drycooler (Glycol )
Pressure Port *
Check Valves * (on Dual Pump Systems only) Gate Valves * Air Vents (typical) *** Pressure Port * Flow Switch Supplied with Dual Pump Systems Flow-Regulating Valve
Shutoff Valve *
Return Supply
Supply Supply
Shutoff Valve *
Liebert DS Unit
(and associated piping)
Return
Optional 3-Way Regulating Valve Shutoff Valve * Hose Bib *
Liquid
Service Valve
Cylinder Unloader (s) Sensing Bulb Suction
Evaporator Coil
Hose Bib *
Compressor
Muffler
Discharge
Paradenser Condenser
Expansion Valve Sight Glass Relief valve(s) supplied with 50Hz EU CE units rated maximum 480 PSIG (33 Bar). Sensor To Second Refrigeration Circuit
Bypass Valve
Factory Piping Field Piping Optional Factory Piping Service/Schrader (Access) Connection No Valve Core Service/Schrader (Access) Connection With Valve Core Note: Schematic representation shown This schematic does not imply or define elevations . and component location unless specifically noted .. Two refrigeration circuits provided Single refrigeration circuit shown for clarity . .
DPN00895 Rev. 2
96
Piping Schematics
EXPANSION TANK**
Optional Dual Pump System shown GLYCOL PUMPS Check Valves* (on Dual Pump Systems only) Gate Valves*
DRYCOOLER (Glycol)
Pressure Port*
Shutoff Valve*
RETURN SUPPLY
Shutoff Valve*
RETURN
SUPPLY
EVAPORATOR COIL
External Equalizer
PARADENSER CONDENSER
Expansion Valve Solenoid Valve Sight Glass Filter Dryer Sensor Relief valve(s) supplied with 50Hz EU CE units rated maximum 480 PSIG (33 Bar) TO SECOND REFRIGERATION CIRCUIT
Bypass Valve
Factory Piping Field Piping Optional Factory Piping Service/Schrader (Access) Connection No Valve Core Service/Schrader (Access) Connections With Valve Core Note: Schematic representation shown. This schematic does not imply or define elevations and component location unless specifically noted. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance ** Field-installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points DPN000896 REV 3
97
Piping Schematics
EXPANSION TANK**
GLYCOL PUMPS
Pressure Port* Check Valves* (on Dual Pump Systems only) Gate Valves*
Shutoff Valve*
Flow-Regulating Valve*
RETURN
SUPPLY
ECON-O-COIL
3-Way Chilled Glycol Valve
RETURN
Shutoff Valve*
SUPPLY
Shutoff Valve*
EVAPORATOR COIL
Thermistor
Hose Bib*
Hose Bib*
Muffler
COMPRESSOR
Service Valve
External Equalizer
Sensor
Factory Piping Field Piping Service/Schrader (Access) Connection No Valve Core Service/Schrader (Access) Connections With Valve Core Notes: Schematic representation shown. This schematic does not imply or define elevations and component location unless specifically noted.
Two refrigeration circuits provided. Single refrigeration circuit shown for clarity
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance ** Field-installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points
DPN000897 Rev. 02
98
Piping Schematics
EXPANSION TANK**
Pressure Port*
Gate Valves*
Shutoff Valve*
Pressure Port*
Flow Switch Supplied with Dual Pump Systems
Shutoff Valve*
EVAPORATOR COIL
Hose Bib*
Service Check Valve COMPRESSOR Valve External Equalizer DISCHARGE Paradenser Condenser Expansion Solenoid Sight Valve Valve Glass Filter Dryer Sensor 3-Way Regulating Valve
Relief valve(s) supplied with 50 Hz EU CE units rated To Second maximum 480 PSIG (33 Bar). Refrigeration Circuit NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. FIELD PIPING FACTORY PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE NOTE: Schematic representation shown. This schematic does not imply or define elevations and component location, unless specifically noted.
* Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance ** Field installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points DPN000898 REV 3
99
Piping Schematics
EXPANSION TANK**
Pressure Port*
Gate Valves*
RETURN SUPPLY
Shut-Off Valve*
HOT GAS REHEAT Optional 3-Way Motorized Ball Valve EVAPORATOR COIL
Hot Gas Reheat Valve External Equalizer Check Valve 2-Way Motorized Ball Valve
PARADENSER CONDENSER Expansion Solenoid Sight Filter Drier Valve Valve Pressure Glass Relief valve(s) supplied Transducer with 50 Hz EU CE units rated maximum 480 PSIG (33 Bar). To iCOM Control TO SECOND REFRIGERATION CIRCUIT
NOTE: TWO REFRIGERATION CIRCUITS PROVIDED SINGLE REFRIGERATION CIRCUIT SHOWN FOR CLARITY. FACTORY PIPING FIELD PIPING OPTIONAL FACTORY PIPING SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance ** Field installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points DPN001430 Rev. 0
NOTE: SCHEMATIC REPRESENTATION SHOWN. THIS SCHEMATIC DOES NOT IMPLY OR DEFINE ELEVATIONS AND COMPONENT LOCATION, UNLESS SPECIFICALLY NOTED.
100
Piping Schematics
EXPANSION TANK**
Optional Dual Pump System shown GLYCOL PUMPS Check Valves* (on Dual Pimp Systems only) Gate Valves*
Pressure Port*
Shut-Off Valve*
Pressure Port*
Flow Switch Supplied with Dual Pump Systems Shut-Off Valve* RETURN Flow-Regulating Valve* SUPPLY SUPPLY Shut-Off Valve*
EVAPORATOR COIL
Hose Bib*
External Equalizer
PARADENSER CONDENSER Expansion Solenoid Sight Filter Drier Valve Valve Pressure Glass Relief valve(s) supplied Transducer with 50 Hz EU CE units rated maximum 480 PSIG (33 Bar). To iCOM Control TO SECOND REFRIGERATION CIRCUIT
NOTE: TWO REFRIGERATION CIRCUITS PROVIDED SINGLE REFRIGERATION CIRCUIT SHOWN FOR CLARITY. FACTORY PIPING FIELD PIPING SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance ** Field installed at highest point in system on return line to pumps *** Locate at tops of all risers and any intermediate system high points
NOTE: SCHEMATIC REPRESENTATION SHOWN. THIS SCHEMATIC DOES NOT IMPLY OR DEFINE ELEVATIONS AND COMPONENT LOCATION, UNLESS SPECIFICALLY NOTED.
DPN001432 Rev. 0
101
Piping Schematics
Return Supply
Thermistor *
Return Supply
Thermistor *
Actuator
Actuator
Return
Return
Supply
Econ-O-Coil
Supply
Econ-O-Coil
Factory Piping * Supplied with 10 feet (3m) extra thermistor wire for installation on field supply line . Field Piping
Note: 1. Place thermistor in location where flow is always present DPN000805 . 2. Thermistor must be located out of the supply air stream Rev. 1 .
102
Piping Schematics
Figure 76 Primary connection locationsdownflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
BLOWER OUTLET
L1 L2 G1 G2
16-1/16" (408mm) B
R 35" (889mm)
FRONT OF UNIT
86" (2184mm)
DPN000803 Rev. 3
Y inches (mm) 13-13/16 (351) 16-3/4 (425) 16-3/4 (425) 16-3/4 (425) 16-3/4 (425) 29-1/2 (749) 29-1/2 (749) 29-1/2 (749) 29 (737) 22-9/16 (573) 30-3/4 (781) 31-1/4 (794) 31-1/4 (794) 27 (686) 29 (737) 31 (787) 18-1/16 (459) Connection Size / Opening inches (mm) 16-7/16 x 4 (418 x 102) 1/2 Cu Sweat 1/2 Cu Sweat 5/8 Cu Sweat 5/8 Cu Sweat 3/4 FPT 1-1/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 1-5/8 Cu Sweat 1-5/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8 18-3/4 x 16-1/16 (476 x 408)
Point R L1 L2 G1 G2
Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain* (infrared humidifier or no humidifier)*
X inches (mm) 63 (1600) 79-3/16 (2011) 76-1/2 (1943) 73-7/8 (1876) 70-1/8 (1780) 46 (1168) 46 (1168) 46 (1168) 53-1/2 (1359) 54-7/8 (1394) 49-3/8 (1254) 55-1/2 (1410) 52-7/16 (1332) 2-1/4 (57) 2-1/4 (57) 2-1/4 (57) 21-15/16 (558)
CD
Condensate Drain* (steam generating humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Connection (High Volt) Electrical Connection (High Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Blower Outlet
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
103
Piping Schematics
Figure 77 Primary connection locationsdownflow, air-Cooled, 28-42kW (8-12 ton) with scroll compressor models
NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
BLOWER OUTLET R
L1 L2 G1 G2
16-1/16" (408mm) B
35" (889mm)
FRONT OF UNIT
73" (1854mm)
DPN000804 Rev. 3
Point R L1 L2 G1 G2
Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain* (infrared humidifier or no humidifier)
X inches (mm) 59-5/16 (1507) 69-15/16 (1776) 67-5/8 (1718) 65-1/2 (1664) 62-7/16 (1586) 46 (1168) 46 (1168) 46 (1168) 53-1/2 (1359) 54-7/8 (1394) 49-3/8 (1254) 55-1/2 (1410) 52-7/16 (1332) 2-1/4 (57) 2-1/4 (57) 2-1/4 (57) 21-15/16 (557)
Y inches (mm) 14-3/4 (375) 16-13/16 (411) 16-13/16 (411) 16-13/16 (411) 16-13/16 (411) 29-1/2 (749) 29-1/2 (749) 29-1/2 (749) 29 (737) 22-9/16 (573) 30-3/4 (781) 31-1/4 (794) 31-1/4 (794) 27 (686) 29 (737) 31 (787) 18-1/16 (459)
Connection Size / Opening inches (mm) 11-3/16 x 4 (284 x 102) 1/2 Cu Sweat 1/2 Cu Sweat 5/8 Cu Sweat 5/8 Cu Sweat 3/4 FPT 1-1/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 1-5/8 Cu Sweat 1-5/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8 18-3/4 x 16-1/16 (476 x 408)
CD
Condensate Drain* (steam generating humidifier) W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Connection (High Volt) Electrical Connection (High Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Electrical Connection (Low Volt) Blower Outlet
Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
104
Piping Schematics
Figure 78 Primary connection locationsdownflow water/glycol/GLYCOOL 28-42kW (8-12 ton), all compressor models
NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
A
FRONT VIEW SECTION A-A
W 8" (203mm) WS WR
BLOWER OUTLET
16-1/16" (408mm) B
35" (889mm)
3-1/2" (89mm)
FRONT OF UNIT
86" (2184mm) DPN000900 Rev. 3
Point W WS WR
Description Water/Glycol/GLYCOOL Access Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Drain (infrared humidifier or no humidifier) *
X in. (mm) 79-15/16 (2030) 82-15/16 (2107) 82-15/16 (2107) 46 (1168) 46 (1168) 46 (1168) 53-1/2 (1359) 54-7/8 (1394) 49-13/16 (1265) 55-1/2 (1410) 52-7/16 (1332) 2-1/4 (57) 2-1/4 (57) 2-1/4 (57) 21-15/16 (557)
Y in. (mm) 9-1/16 (230) 10-15/16 (278) 14-1/16 (357) 29-1/2 (749) 29-1/2 (749) 29-1/2 (749) 29 (737) 22-9/16 (573) 28-1/2 (724) 31-1/4 (794) 31-1/4 (794) 27 (686) 29 (737) 31 (787) 18-1/16 (459)
Connection Size / Opening in. (mm) 3-1/2 x 8 (89 x 203) 1-5/8" Cu Sweat 1-5/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 1-5/8" Cu Sweat 1-5/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 18-3/4 x 16-1/16 (476 x 408)
CD
Condensate Drain (steam generating humidifier) * W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
105
Piping Schematics
Figure 79 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
All dimensions from rear corner of unit including panels
A NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
A
X O
R
R
BLOWER OUTLET
16-1/16" (408mm) B2
BLOWER OUTLET
Y
4" (102mm)
L1 L2
G1 G2
B1
16-7/16" (418mm)
35" (889mm)
DPN00928 Rev. 4
Connection Size / Opening in. (mm)
16-7/16 x 4 (418 x 102)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
Point
R
Description
Refrigerant Access
X in. (mm)
82-3/4 (2102)
Y in. (mm)
13-7/8 (352)
L1 L2 G1 G2
Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (infrared humidifier or no humidifier) *
97 (2464) 93-5/16 (2370) 90-5/8 (2302) 88 (2235) 69-1/4 (1759) 69-1/4 (1759) 69-1/4 (1759) 76-1/2 (1943) 78-5/8 (1997) 72 (1829) 78-1/2 (1994) 75-3/8 (1915) 1-7/8 (48) 1-7/8 (48) 1-7/8 (48) 23-1/8 (587) 27-3/4 (705) 50-3/8 (1280) 54-3/8 (1381)
16-7/8 (428) 16-7/8 (428) 16-5/8 (422) 16-5/8 (422) 30 (762) 30 (762) 30 (762) 29 (736) 22-1/4 (565) 29 (737) 31-1/8 (790) 31-1/8 (790) 28-1/2 (724) 30-1/4 (768) 32 (813) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459)
1/2" / 5/8" Cu Sweat 1/2" / 5/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 2-1/8" Cu Sweat 2-1/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408) 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408)
CD
Condensate Drain (steam generating humidifier)* W/ Optional Pump Humidifier Supply Line
HUM
ECS** Econ-O-Coil Supply ECR** Econ-O-Coil Return E1 E2 LV1 LV2 LV3 B1 B2 Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet (15 x 15) Blower Outlet (15 x 11) Blower Outlet (15 x 15) Blower Outlet (15 x 11)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (4 pipe system)
106
Piping Schematics
Figure 80 Primary connection locations downflow air cooled 53-77kW (15-22 tons) semi-hermetic compressor models, with EC fan
All dimensions from rear corner of unit including panels
A Note: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
4" (102mm)
L1 L2 G1 G2
FRONT OF UNIT
109" (2769mm)
DPN002179 Rev. 0
Point R L1 L2 G1 G2 CD HUM ECS** ECR** HS HR E1 E2 LV1 LV2 LV3 Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (infrared humidifier or no humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Hot Water Reheat Supply Hot Water Reheat Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) 78-1/2 (1994) 75-3/8 (1915) 2 (51) 2 (51) 2 (51) X in. (mm) 82-3/4 (2102) 97 (2464) 93-5/16 (2370) 90-5/8 (2302) 88 (2235) 68-3/8 (1737) 68-3/8 (1737) 76-1/2 (1943) 78-5/8 (1997) 73-15/16 (1862) Y in. (mm) 13-7/8 (352) 16-7/8 (428) 16-7/8 (428) 16-5/8 (422) 16-5/8 (422) 31-3/8 (797) 31-3/8 (797) 29 (736) 22-1/4 (565) 26-9/16 (675) CONSULT FACTORY CONSULT FACTORY 31-1/8 (790) 31-1/8 (790) 29 (737) 30-7/8 (784) 32 (813) 2-1/2" 2-1/ " 7/8" 7/8" 7/8" Connection Size / Opening in. (mm) 16-7/16 x 4 (4181 x 102mm) 53kW (15 Tons)/70 & 77kW (20 & 22 Tons) 1/2" / 5/8" Cu Sweat 1/2" / 5/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 3/4" FPT 1/2" Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (four-pipe system)
107
Piping Schematics
Figure 81 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton) with scroll compressor models
All dimensions from rear corner of unit including panels
A NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
A
FRONT VIEW SECTION A-A
X O
BLOWER OUTLET
16-1/16" (408mm)
BLOWER OUTLET B1
4" (102mm)
L1 L2 G1 G2
35" (889mm)
DPN00929 Rev. 4
Connection Size / Opening in. (mm) 12-3/16 x 4 (310 x 102) 53kW (15 tons) / 70 &77kW (20 &22 tons) 1/2" / 5/8" Cu Sweat 1/2" / 5/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 7/8" / 1-1/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 2-1/8" Cu Sweat 2-1/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408) 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408)
Point R L1 L2 G1 G2
Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1
X in. (mm) 81-3/4 (2076) 94-11/16 (2405) 91-7/8 (2334) 88-3/4 (2254) 85-9/16 (2173) 69-1/4 (1759) 69-1/4 (1759) 69-1/4 (1759) 76-1/2 (1943) 78-5/8 (1997) 72 (1829) 78-1/2 (1994) 75-3/8 (1915) 1-7/8 (48) 1-7/8 (48) 1-7/8 (48) 23-1/8 (587) 27-3/4 (705) 50-3/8 (1280) 54-3/8 (1381)
Y in. (mm) 14-3/4 (374) 16-3/4 (425) 16-3/4 (425) 16-3/8 (416) 16-3/8 (416) 30 (762) 30 (762) 30 (762) 29 (736) 22-1/4 (565) 29 (737) 31-1/8 (790) 31-1/8 (790) 28-1/2 (724) 30-1/4 (768) 32 (813) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459)
Hot Gas Discharge 2 Condensate Drain (infrared humidifier or no humidifier)* CD Condensate Drain (steam generating humidifier)* W/ Optional Pump HUM Humidifier Supply Line ECS** Econ-O-Coil Supply ECR** Econ-O-Coil Return E1 Electrical Conn. (High Volt) E2 Electrical Conn. (High Volt) LV1 Electrical Conn. (Low Volt) LV2 Electrical Conn. (Low Volt) LV3 Electrical Conn. (Low Volt) Blower Outlet (15 x 15) B1 Blower Outlet (15 x 11) Blower Outlet (15 x 15) B2 Blower Outlet (15 x 11)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (4 pipe system)
108
Piping Schematics
Figure 82 Primary connection locationsdownflow, air-Cooled, 53-77kW (15-22 ton) with scroll compressor models, with EC fan
All dimensions from rear corner of unit including panels Note: Drawing not to scale. A Tolerance on all piping dimensions is 1/2" (13mm).
A
FRONT VIEW SECTION A-A
X O
4" (102mm)
L1 L2 G1 G2
BLOWER OUTLET
35" (889mm)
FRONT OF UNIT
98" (2489mm)
DPN002182 Rev. 0
Point R L1 L2 G1 G2 CD HUM ECS** ECR** HS HR E1 E2 LV1 LV2 LV3 B1 Description Refrigerant Access Liquid Line System Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (Infrared Humidifier or No Humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Hot Water Reheat Supply Hot Water Reheat Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet 78-1/2 (1994) 75-3/8 (1915) 2 (51) 2 (51) 2 (51) 4-1/2 (114) X in. (mm) 81-3/4 (2076) 94-11/16 (2405) 91-7/8 (2334) 88-3/4 (2254) 85-9/16 (2173) 68-3/8 (1737) 68-3/8 (1737) 76-1/2 (1943) 78-5/8 (1997) 73-15/16 (1862) Y in. (mm) 14-3/4 (374) 16-3/4 (425) 16-3/4 (425) 16-3/8 (416) 16-3/8 (416) 31-3/8 (797) 31-3/8 (797) 29 (736) 22-1/4 (565) 26-9/16 (675) Connection Size / Opening in. (mm) 12-3/16 (310) X 4" (102) 53kW (15 Tons) / 70 & 77kW (20 & 22 Tons) 1/2 / 5/8" Cu Sweat 1/2 / 5/8" Cu Sweat 7/8 / 1-1/8" Cu Sweat 7/8 / 1-1/8" Cu Sweat 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat
CONSULT FACTORY CONSULT FACTORY 31-1/8 (790) 31-1/8 (790) 29 (737) 30-7/8 (784) 32 (813) 33 (838) 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 58-3/8 x 30 (1483x762)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (four-pipe system)
109
Piping Schematics
Figure 83 Primary connection locationsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
NOTE: Drawing not to scale. A Tolerance on all piping dimensions is 1/2" (13mm).
8" (203mm)
W WS WR
3-1/2" (89mm)
BLOWER OUTLET
16-1/16" (408mm) B2
BLOWER OUTLET
Y
B1
35" (889mm)
DPN00933 Rev. 4
Y in. (mm) 9 (229) 11 (279) 15 (381) 30 (762) 30 (762) 30 (762) 29 (736) 22-1/4 (565) 29 (737) 31-1/8 (790) 31-1/8 (790) 28-1/2 (724) 30-1/4 (768) 32 (813) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) 18-1/16 (459) Connection Size / Opening in. (mm) 3-1/2 x 8 (89 x 203) 2-1/8" Cu Sweat 2-1/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 2-1/8" Cu Sweat 2-1/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408) 18-3/4 x 16-1/16 (476 x 408) 14-3/4 x 16-1/16 (375 x 408)
Point W WS WR
Description Water/Glycol/GLYCOOL Access Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Drain (infrared humidifier or no humidifier)*
X in. (mm) 103 (2616) 104-3/4 (2661) 104-3/4 (2661) 69-1/4 (1759) 69-1/4 (1759) 69-1/4 (1759) 76-1/2 (1943) 78-5/8 (1997) 72 (1829) 78-1/2 (1994) 75-3/8 (1915) 1-7/8 (48) 1-7/8 (48) 1-7/8 (48) 23-1/8 (587) 27-3/4 (705) 50-3/8 (1280) 54-3/8 (1381)
CD
Condensate Drain (steam generating humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet (15 x 15) Blower Outlet (15 x 11) Blower Outlet (15 x 15) Blower Outlet (15 x 11)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (4 pipe system)
110
Piping Schematics
Figure 84 Primary connection locationsdownflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models, with EC fan
A Note: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
B1 LV2
LV3
FRONT OF UNIT
109" (2769mm)
DPN002183 Rev. 0
Point W WS WR CD HUM ECS** ECR** HS HR E1 E2 LV1 LV2 LV3 B1 Description Water/Glycol/GLYCOOL Access Water/Glycol/GLYCOOLSupply Water/Glycol/GLYCOOL Return Condensate Drain (Infrared Humidifier or No Humidifier)* W/Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Hot Water Reheat Supply Hot Water Reheat Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet 78-1/2 (1994) 75-3/8 (1915) 2 (51) 2 (51) 2 (51) 4-1/2 (114) X in. (mm) 103 (2616) 104-3/4 (2661) 104-3/4 (2661) 68-3/8 (1737) 68-3/8 (1737mm) " 76-1/2 (1943) 78-5/8 (1997) 73-15/16 (1862) Y in. (mm) 9 (229) 11 (279) 15 (381) 31-3/8 (797) 31-3/8 (797) 29 (736) 22-1/4 (565) 26-9/16 (675) CONSULT FACTORY CONSULT FACTORY 31-1/8 (790) 31-1/8 (790) 29 (737) 30-7/8 (784) 32 (813) 33 (838) 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 58-3/8 x 30 (1483 x 762) Connection Size / Opening in. (mm) 3-1/2 x 8 (89 x 203) 2-1/8 Cu Sweat 2-1/8 Cu Sweat 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (four- pipe system)
111
Piping Schematics
Figure 85 Primary connection locationsdownflow, air-cooled, 105kW (30 ton), all compressor models
A
NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
15-11/16" (398mm)
BLOWER OUTLET B3
BLOWER OUTLET B2
BLOWER OUTLET B1
Y 35" (889mm)
ECS
ECR CD
HUM E1
E2
FRONT OF UNIT
131" (3327mm)
DPN001014 Rev. 3
Point R L1 L2 G1 G2
Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (infrared humidifier or no humidifier)*
X in. (mm) 109 (2769) 121-3/4 (3092) 118-1/8 (3000) 118-1/4 (3004) 115-5/8 (2937) 83-13/16 (2129) 83-13/16 (2129) 83-13/16 (2129) 102-3/4 (2610) 101-7/8 (2588) 94-9/16 (2402) 98-1/8 (2492) 91 (2311) 2 (51) 2 (51) 2 (51) 27-7/8 (708) 52-1/16 (1322) 76-1/4 (1937)
Y in. (mm) 15-3/4 (400) 16-3/4 (425) 16-3/4 (425) 14-1/4 (362) 14-1/4 (362) 30 (762) 30 (762) 30 (762) 31-3/4 (806) 29 (737) 29 (737) 31-1/4 (794) 31-1/4 (794) 28-1/4 (718) 30-1/4 (768) 32 (813) 18 (457) 18 (457) 18 (457)
Connection Size / Opening in. (mm) 16-7/16" x 4 (418 x 102) 5/8" Cu Sweat 5/8" Cu Sweat 1-1/8" Cu Sweat 1-1/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 2-5/8" Cu Sweat 2-5/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 14-1/2 x 15-11/16 (368 x 398) 14-1/2 x 15-11/16 (368 x 398) 14-1/2 x 15-11/16 (368 x 398)
CD
Condensate Drain (steam generating humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet Blower Outlet Blower Outlet
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (4 pipe system)
112
Piping Schematics
Figure 86 Primary connection locationsdownflow, air-cooled, 105kW (30 ton), all compressor models, with EC fan
A Note: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
Y G1G2 R 4" (102mm) L1 L2 ECS ECR 16-7/16" (418mm) E1 E2 CD HUM B1 BLOWER OUTLET 35" (889mm)
FRONT OF UNIT
132" (3353mm)
DPN002154 Rev. 0
Point R L1 L2 G1 G2 CD HUM ECS ** ECR ** HS HR E1 E2 LV1 LV2 LV3 B1
*
Description Refrigerant Access Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Condensate Drain (Infrared Humidifier Or No Humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Hot Water Reheat Supply Hot Water Reheat Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet
X in. (mm) 109 (2769) 121-3/4 (3092) 118-1/8 (3000) 118-1/4 (3004) 115-5/8 (2937) 87-3/8 (2220) 83-13/16 (2129) 85-5/16 (2167) 101-7/8 (2588) 94-9/16 (2402)
Y in. (mm) 15-3/4 (400) 16-3/4 (425) 16-3/4 (425) 14-1/4 (362) 14-1/4 (362) 31 (787) 30 (762) 32-1/2 (825) 29 (737) 29 (737)
Connection Size / Opening in. (mm) 16-7/16 (418) x 4 (102) 5/8 Cu Sweat 5/8 Cu Sweat 1-1/8 Cu Sweat 1-1/8 Cu Sweat 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-5/8 Cu Sweat 2-5/8 Cu Sweat
CONSULT FACTORY CONSULT FACTORY 98-1/8 (2492) 91 (2311) 2 (51) 2 (51) 2 (51) 4-1/2 (114) 31 (788) 31 (788) 29 (737) 30-7/8 (784) 32 (813) 33 (838) 2-1/2 2-1/2 7/8 7/8 7/8 77-3/8 x 30 (1965 x 762)
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only (four-pipe system)
113
Piping Schematics
Figure 87 Primary connection locationsdownflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models
A
NOTE: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
8" (203mm)
W WS WR
BLOWER OUTLET B3
BLOWER OUTLET B2
BLOWER OUTLET B1
Y
35" (889mm)
HUM E1
E2
FRONT OF UNIT
131" (3327mm)
DPN001015 Rev. 3
Point W WS WR
Description Water/Glycol/GLYCOOL Access Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Drain (infrared humidifier or no humidifier)*
X in. (mm) 125-15/16 (3199) 127-7/8 (3248) 127-7/8 (3248) 83-13/16 (2129) 83-13/16 (2129) 83-13/16 (2129) 102-3/4 (2610) 101-7/8 (2588) 94-9/16 (2402) 98-1/4 (2496) 88-7/16 (2246) 2 (51) 2 (51) 2 (51) 28-1/4 (718) 52 (1321) 75-11/16 (1922)
Y in. (mm) 9 (229) 10-1/16 (256) 13-1/4 (337) 30 (762) 30 (762) 30 (762) 31-3/4 (806) 29 (737) 29 (737) 30 (762) 30 (762) 27-1/2 (796) 30-1/4 (768) 32 (813) 18 (457) 18 (457) 18 (457)
Connection Size / Opening in. (mm) 3-1/2 x 8 (89 x 203) 2-1/8" Cu Sweat 2-1/8" Cu Sweat 3/4" FPT 1-1/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 2-5/8" Cu Sweat 2-5/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 14-1/2 x 15-7/8 (368 x 403) 14-1/2 x 15-7/8 (368 x 403) 14-1/2 x 15-7/8 (368 x 403)
CD
Condensate Drain (steam generating humidifier)* W/ Optional Pump Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet Blower Outlet Blower Outlet
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling systems only (4 piping system).
114
Piping Schematics
Figure 88 Primary connection locations downflow water/glycol/GLYCOOL 105kW (30 tons) all compressor models, with EC fan
A Note: Drawing not to scale. Tolerance on all piping dimensions is 1/2" (13mm).
FRONT VIEW
All dimensions from rear corner of unit including panels X
SECTION A-A
W WS WR
8" (203mm)
BLOWER OUTLET
35" (889mm)
LV1 LV2 LV3
B1
E1
E2
FRONT OF UNIT
132" (3353mm)
DPN002153 Rev. 0
Point W WS WR CD Description Water/Glycol/GLYCOOL Access Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Drain (Infrared Humidifier or No Humidifier)* W/Optional Pump HUM Humidifier Supply Line ECS HS HR E1 E2 LV1 LV2 LV3 B1 Econ-O-Coil Supply Hot Water Reheat Supply Hot Water Reheat Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Blower Outlet 98-1/8 (2492) 91 (2311) 2 (51) 2 (51) 2 (51) 4-1/2 (114) ECR Econ-O-Coil Return X in. (mm) 125-15/16 (3199) 127-7/8 (3248) 127-7/8 (3248) 87-3/8 (2220) 83-13/16 (2129) " 85-5/16 (2167) 101-7/8 (2588) 94-9/16 (2402) Y in. (mm) 9 (229) 10-1/16 (256) 13-1/4 (337) 31 (787) 30 (762) 32-1/2 (825) 29 (737) 29 (737) CONSULT FACTORY CONSULT FACTORY 31 (788) 31 (788) 29 (737) 30-7/8 (784) 32 (813) 33 (838) 2-1/2" 2-1/2" 7/8" 7/8" 7/8" 77-3/8 x 30 (1965 x 762) Connection Size / Opening in. (mm) 3-1/2 (89) X 8" (203) 2-1/8 Cu Sweat 2-1/8 Cu Sweat 3/4 FPT" 1/2 Cu Sweat 1/4" Cu Sweat 2-5/8" Cu Sweat 2-5/8" Cu Sweat
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling systems only (4 piping system).
115
Piping Schematics
Figure 89 Primary connection locationsupflow, air-cooled, 28-42kw (8-12 ton), semi-hermetic compressor models
NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is 1/2" (13mm). 15-3/16" Field-routed alternatives for refrigerant 35" (386mm) gas and liquid line connection points. (889mm) See submittal page DPN001120 for 4" blower outlet and deck dimensional data. (102mm) 22-1/2" (572mm) All dimensions from rear corner of unit including panels Blower Outlet
16-7/16" (418mm)
86" (2184mm) Top View 6" (152mm) 17-3/16" (437mm) 14-1/4" (362mm) 15-7/8" (403mm) Left Side Section View 20-1/16" (509mm) Front of Unit
3-7/8" (98mm)
Factory Location Front Section View (Left Front Panel Not Shown) DPN001114 Rev. 02
Point R1 R2 L1 L2 G1 G2 R3
3
Description Refrigerant Access (Top) Refrigerant Access (Bottom) Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Refrigerant Access (Side) Condensate Gravity Drain Condensate Pump Discharge (Opt) Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Connection (High Voltage) Electrical Connection (High Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage)
X inches (mm) 60-11/16 (1542) 63 (1600) 79-3/16 (2011) 76-1/2 (1943) 73-7/8 (1876) 70-1/8 (1780) 56-1/4 (1429) 56-1/4 (1429) 56 (1423) 56 (1423) 52-3/8 (1330) 46-7/8 (1191) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
Y inches (mm) 1-7/8 (48) 13-13/16 (351) 16-3/4 (425) 16-3/4 (425) 16-3/4 (425) 16-3/4 (425) 11-1/8 (283) 9-1/8 (233) 7-5/16 (186) 4-1/2 (114) 30 (762) 30 (762) 29-1/16 (738) 30-1/2 (775) 31-15/16 (811)
Connection Size / Opening inches (mm) 22-1/2 x 15-3/16 (572 x 386) 16-7/16 x 4 (418 x 102) 1/2 Cu Sweat 1/2 Cu Sweat 5/8 Cu Sweat 5/8 Cu Sweat 6 x 17-3/16 (152 x 437) 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 1-5/8 Cu Sweat 1-5/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8
3 3
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (4-pipe system)
116
Piping Schematics
Figure 90 Primary connection locationsupflow, air-Cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is 1/2" (13mm). 3 Field routed alternatives for refrigerant gas and liquid line connection points. 4 See submittal page DPN001120 for blower outlet and deck dimensional data.
10-1/8" (257mm) 4-1/8" (105mm) 3. R1
ECR ECS HUM CPD
BL OWER OU T TLE 4. Y
R2 4" (102mm)
L1 L2 G1 G2
35" (889mm)
3.
LV 1 LV 2 LV 3
6" (152mm)
TOP VIEW
R3 3.
Front of Unit
17-3/16" (437mm)
CGD*
3-7/8" (98mm) 14-1/4" (362mm) 15-7/8" (403mm)
17-1/16" (434mm)
L1L2G1 G2
CGD*
Factory Location
FRONT SECTION
(Left Front Panel Not Shown)
DPN001119 Rev. 2
Point R1 R2 L1 L2 G1 G2 R3
3 3 3
Description Refrigerant Access (Top) Refrigerant Access (Bottom) Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Refrigerant Access (Side) Condensate Gravity Drain Condensate Pump Discharge (Opt) Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt)
X in. (mm) 60-1/2 (1537) 59-3/8" (1508mm) 70" (1778mm) 67-5/8" (1718mm) 65-3/8" (1661mm) 63" (1600mm) 56-1/4 (1429) 56-1/4 (1429) 56 (1423) 56 (1423) 52-3/8 (1330) 46-7/8 (1191) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
Y in. (mm) 1-7/8" (48mm) 14-3/4" (375mm) 16-3/4 (425) 16-3/4 (425) 16-5/8 (422) 16-5/8 (422) 11-1/8 (283) 9-1/8 (233) 7-5/16 (186) 4-1/2 (114) 30 (762) 30 (762) 29-1/16 (738) 30-1/2 (775) 31-15/16 (811)
Connection Size / Opening in. (mm) 10-1/8 x 4-1/8 (257 x 105) 11-1/8 x 4 (283 x 102) 1/2" Cu Sweat 1/2" Cu Sweat 5/8" Cu Sweat 5/8" Cu Sweat 6 x 17-3/16 (152 x 437) 3/4" FPT 1/2" Cu Sweat 1/4" Cu Sweat 1-5/8" Cu Sweat 1-5/8" Cu Sweat 2-1/2" 2-1/2" 7/8" 7/8" 7/8"
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual Cooling Systems only
117
Piping Schematics
Figure 91 Primary connection locationsupflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is 1/2" (13mm). 3. Field-routed alternatives for water/glycol connections. 4. See submittal page DPN001120 for blower outlet and deck dimensional data. W1,W2 8" 35" (203mm) (889mm) 3 2-7/8" (73mm) 3-1/2" (89mm)
E1 E2
All dimensions from rear corner of unit including X panels ECS ECR HUM CPD Blower Outlet 4
Front
15-7/8" (403mm)
Left Side Section View
CGD*
DPN001179 Rev. 2
Description Water/Glycol/GLYCOOL Access (Bottom) Water/Glycol/GLYCOOL Access (Top) Water/Glycol/GLYCOOL Access (Side) Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Gravity Drain Condensate Pump Discharge (Opt) Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Connection (High Voltage) Electrical Connection (High Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage)
X in. (mm) 79-15/16 (2030) 79-15/16 (2030) 56-1/4 (1429) 56-1/4 (1429) 56 (1423) 56 (1423) 52-3/8 (1330) 46-7/8 (1191) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
Y in. (mm) 9 (229) 9 (229) 11-1/8 (282) 9-1/8 (232) 7-5/16 (186) 4-1/2 (114) 30 (762) 30 (762) 29-1/16 (738) 30-1/2 (775) 31-15/16 (811)
Connection Size / Opening in. (mm) 3-1/2 x 8 (89 x 203) 3-1/2 x 8 (89 x 203) 6 x 17-3/16 (152 x 437) 1-5/8 Cu Sweat 1-5/8 Cu Sweat 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 1-5/8 Cu Sweat 1-5/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8
CGD
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (4-pipe system)
118
Piping Schematics
Figure 92 Primary connection locationsupflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models
22-1/2" (572mm) All dimensions from rear corner of unit including panels Blower Outlet Blower Outlet X
NOTES: 15-3/16" 1. Drawing not to scale. 35" (386mm) 2. Tolerance on all piping dimensions (889mm) is 1/2" (13mm). 4" 3. Field routed alternatives for refrigerant (102mm) gas and liquid line connection points. 4. See submittal page DPN001191 for blower outlet and deck dimensional data.
16-7/16" (418mm)
Front of Unit
17-3/16" (437mm)
14-1/4" (362mm) 15-7/8" (403mm)
20-1/16" (509mm)
3-7/8" (98mm)
Factory Location
* Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. DPN001212 ** Supplied on Dual Cooling Systems only
Rev. 2
Point R1 R2 L1 L2 G1 G2 R3
3 3 3
Description Refrigerant Access (Top) Refrigerant Access (Bottom) Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Refrigerant Access (Side) Condensate Pump Discharge (Opt) Humidifier Supply Line
X inches (mm) 83-3/4 (2127) 86 (2184) 97 (2464) 93-5/16 (2370) 90-5/8 (2302) 88 (2235) 79-5/16 (2015) 79-5-16 (2015) 78-5/8 (1998) 78-5/8 (1998) 75-3/8 (1915) 69-7/8 (1775) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
Y inches (mm) 1-7/8 (48) 13-7/8 (352) 16-3/4 (425) 16-3/4 (425) 16-5/8 (422) 16-5/8 (422) 11-7/8 (302) 9-7/8 (251) 7-7/8 (200) 4-5/8 (117) 30 (762) 30 (762) 29-1/16 (738) 30-1/2 (775) 31-15/16 (811)
Connection Size / Opening inches (mm) 22-1/2 x 15-3/16 (572 x 386) 16-7/16 x 4 (418 x 102)
53kW (15 ton)/ 70 & 77kW (20 & 22 ton) 1/2 / 5/8 Cu Sweat 1/2 / 5/8 Cu Sweat 7/8 / 1-1/8 Cu Sweat 7/8 / 1-1/8 Cu Sweat 6 x 17-3/16 (152 x 437) 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8
ECS** Econ-O-Coil Supply ECR** Econ-O-Coil Return E1 E2 LV1 LV2 LV3 Electrical Connection (High Voltage) Electrical Connection (High Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage)
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (4-pipe system)
119
Piping Schematics
Figure 93 Primary connection locationsupflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models
All dimensions from rear corner of unit including panels NOTE 4" 1. Drawing not to scale. (102mm) 2. Tolerance on all piping dimensions 35" is 1/2" (13mm). 4" (102mm) 3. Field-routed alternatives for refrigerant (889mm) gas and liquid line connection points. 12-13/16" 4. See submittal page DPN001191 for (325mm) blower outlet and deck dimensional data. Blower Outlet
4
Blower Outlet
4
Y
Lv1 LV2 LV3
98" (2489mm)
Front
Top View
6" (152mm)
CGD*
17-1/16" (433mm)
DPN001213 Rev. 1
Connection Size / Opening inches (mm) 12 x 4 (305 x 102) 12-3/16 x 4 (310 x 102) 53kW (15 tons )/ 70 & 77kW (20 & 22 ton)
L1 L2 G1 G2 R3
3
Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Refrigerant Access (Side) Condensate Gravity Drain Condensate Pump Discharge (Opt) Humidifier Supply Line
94-11/16 (2405) 91-7/8 (2334) 88-3/4 (2254) 85-9/16 (2173) 79-5/16 (2015) 79-5/16 (2015) 78-5/8 (1998) 78-5/8 (1998) 75-3/8 (1915) 69-7/8 (1775) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
16-3/4 (425) 16-3/4 (425) 16-3/8 (416) 16-3/8 (416) 11-7/8 (302) 9-7/8 (251) 7-7/8 (200) 4-5/8 (117) 30 (762) 30 (762) 29-1/16 (738) 30-1/2 (775) 31-15/16 (811)
1/2 / 5/8 Cu Sweat 1/2 / 5/8 Cu Sweat 7/8 / 1-1/8 Cu Sweat 7/8 / 1-1/8 Cu Sweat 6 x 17-3/16 (152 x 437) 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8
ECS** Econ-O-Coil Supply ECR** Econ-O-Coil Return E1 E2 LV1 LV2 LV3 Electrical Connection (High Voltage) Electrical Connection (High Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage)
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (four-pipe system)
120
Piping Schematics
Figure 94 Primary connection locationsupflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
All dimensions from rear corner of unit including panels Blower Outlet Blower Outlet
NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions 8" is 1/2" (13mm). (203mm) 3. Field routed alternatives for water/glycol 35" connections. (889mm) 2-7/8" (73mm) 4. See submittal page DPN001191 for 3-1/2" blower outlet and deck dimensional data.
(89mm)
Front of Unit
DPN001214 Rev. 1
Description Water/Glycol/GLYCOOL Access (Bottom) Water/Glycol/GLYCOOL Access (Top) Water/Glycol/GLYCOOL Access (Side) Water/Glycol/GLYCOOL Supply Water/Glycol/GLYCOOL Return Condensate Gravity Drain Condensate Pump Discharge (Option) Humidifier Supply Line
Connection Size / Opening inches (mm) 3-1/2 x 8 (89 x 203) 3-1/2 x 8 (89 x 203) 6 x 17-3/16 (152 x 437) 2-1/8 Cu Sweat 2-1/8 Cu Sweat 3/4 FPT 1/2 Cu Sweat 1/4 Cu Sweat 2-1/8 Cu Sweat 2-1/8 Cu Sweat 2-1/2 2-1/2 7/8 7/8 7/8
102-15/16 (2615) 102-15/16 (2615) 79-5/16 (2015) 79-5/16 (2015) 78-5/8 (1998) 78-5/8 (1998) 75-3/8 (1915) 69-7/8 (1775) 19-1/2 (495) 19-1/2 (495) 19-1/2 (495)
CGD*
Electrical Connection (High Voltage) Electrical Connection (High Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage) Electrical Connection (Low Voltage)
Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. ** Supplied on Dual-Cool systems only (four-pipe system)
121
Piping Schematics
All dimensions from rear corner of unit including panels Blower Outlet Blower Outlet Blower Outlet
R2
35" (889mm)
4" (102mm) NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is 1/2" (13mm). 3. Field routed alternatives for refrigerant gas and liquid line connection points. 4. See submittal page DPN001192 for blower outlet and deck dimensional data. 6" (152mm) R3 17-3/16" (437mm) 3-7/8" (98mm) 14-1/4" (362mm) 15-7/8" (403mm) 20-1/16" (509mm) CGD*
16-7/16" (418mm)
E1 E2
Front Of Unit
G1 G2 L1 L2
DPN001257 Rev. 0
Description Refrigerant Access (Top) Refrigerant Access (Bottom) Liquid Line System 1 Liquid Line System 2 Hot Gas Discharge 1 Hot Gas Discharge 2 Refrigerant Access (Side) Condensate Gravity Drain Condensate Pump Discharge (Opt) Humidifier Supply Line Econ-O-Coil Supply Econ-O-Coil Return Electrical Conn. (High Volt) Electrical Conn. (High Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt) Electrical Conn. (Low Volt)
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
122
Piping Schematics
35" (889mm)
8" (203mm)
NOTES: 1. Drawing not to scale. 2. Tolerance on all piping dimensions is 1/2" (13mm). 3. Field routed alternatives for water/glycol connections. 4. See submittal page DPN001192 for blower outlet and deck dimensional data. 6" (152mm)
Front Of Unit
W3 WS WR CGD* CGD*
DPN001258 Rev. 0
CGD*
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
123
11.2
Electrical
___ 1. Supply voltage and phase matches equipment nameplate. ___ 2. Wiring connections completed between disconnect switch, evaporator unit and heat rejection equipment. ___ 3. Power line circuit breakers or fuses have proper ratings for equipment installed. ___ 4. Control wiring connections completed between indoor evaporator and heat rejection equipment. ___ 5. All internal and external high- and low-voltage wiring connections are tight. ___ 6. Confirm that unit is properly grounded to an earth ground. ___ 7. Control transformer setting matches incoming power. ___ 8. Electrical service conforms to national and local codes. ___ 9. Check blowers and compressors (scroll only) for proper rotation. ___ 10. Upflow units only: Field installed low volt wiring routed with loop to allow electric box to swing. ___ 11. For units with variable speed drive (VSD) operating on Delta-connected power, ensure that the EMC filter has been disconnected; see 8.1 - Variable Speed Drive for details. ___ 12. Check for loose electrical connections on steam generating humidifier. Confirm that electrode plugs are pressed firmly onto the electrode pins.
11.3
Piping
___ 1. Piping completed to refrigerant or coolant loop (if required). ___ 2. Piping has been leak-checked, evacuated and charged (if required). ___ 3. Additional oil has been added for system charges over 40 pounds (18.1kg) per circuit (see 9.2.2 - Scroll and Digital ScrollAdditional Oil Requirements. ___ 4. Piping is properly sized, sloped and trapped as shown in the piping schematics ___ 5. Check piping inside and outside of equipment for proper supportand adequate spacing to prevent rub-through. ___ 6. Ensure TXV equalizer lines and sensing bulb lines have sufficient clearance and do not rub against other refrigerant lines. ___ 7. Ensure that factory clamps have been reinstalled. ___ 8. Drain line connected and pitched per local code. ___ 9. Water supply line connected to humidifier.
124
11.4
Other
___ 1. Ducting complete (if required), maintain access to filters. ___ 2. Filters installed. ___ 3. Check fasteners that secure compressors, reheats, humidifier and motorssome may have become loose during shipment. ___ 4. Verify water detection is properly installed around all units (recommended). ___ 5. Control panel DIP switches are set based on user requirements. ___ 6. Blower drive system rotates freely and belts are properly aligned and tensioned. ___ 7. Compressor shipping blocks removed and springs adjusted (see 5.3 - Semi-Hermetic Compressor Spring Isolation System). ___ 8. Remove rubber band from float in optional infrared humidifier. ___ 9. Seal openings around piping and electrical connections. ___ 10. Installation materials and tools have been removed from equipment (literature, shipping materials, construction materials, tools, etc.). ___ 11. Locate blank startup sheet, ready for completion by installer or startup technician.
125
12.0 INITIAL STARTUP CHECKS AND COMMISSIONING PROCEDURE FOR WARRANTY INSPECTION
! WARNING piping, moving, lifting and/or handling. Can cause equipment Risk of improper wiring,
damage, injury or death. Only qualified service personnel should move, install or service this equipment. Read all installation, operating and safety instructions before proceeding. Read and follow all warnings in this manual.
! WARNING and alarm system activation. Can cause injury during building Risk of fire suppression
evacuation and mobilization of emergency fire and rescue services. Startup operation of optional electric reheat elements may activate facility alarm and fire suppression system. Prepare and take appropriate steps to manage this possibility. Activating reheat during initial startup may burn off particulates from electric reheat elements. Check the steam generating humidifier electrode plugs to ensure that they are pressed firmly onto the pins. Loose connections will cause the cylinder and plugs to overheat. Before beginning initial startup checks, make certain that unit was installed according to the instructions in this manual. All exterior panels must be in place.
NOTICE
Risk of improper electrical connection of three-phase input power. Can cause unit damage. Service technicians should use a gauge set on the Liebert DS system during the initial startup to verify that the three-phase power is connected properly. The EC fans are not a reliable indicator of proper connection. The blowers will rotate the same direction, regardless of the three-phase power input. Confirm that all items on 11.0 - Checklist for Completed Installation have been done. Locate Liebert DS Warranty Inspection Check Sheet in unit electric panel. (Document number SAFM-8542-29) Complete Liebert DS Warranty Inspection Check Sheet during startup. (Document number SAFM-8542-29). Forward the completed Liebert DS Warranty Inspection Check Sheet to your local Emerson sales office. This information must be completed and forwarded to Emerson to validate warranty. Contact your local Emerson sales representative or Liebert Air Product Support if you have any questions or problems during unit startup and commissioning. Local Emerson Sales offices and Liebert Air Product Support contacts can be found at www.liebert.com or by calling 1-800-LIEBERT.
Liebert DS warranty startup procedures includes the following steps. These steps must be completed to validate warranty.
126
12.1
12.2
127
12.3
Startup
1. Turn On the Main Disconnect. 2. Check voltage at disconnect and record. L1-L2 _________________ L2-L3 _________________ L1-L3 _________________ 3. Check control voltage transformers for proper output. Secondary voltage(s) should not exceed 27VAC under load. Change tap if necessary. T1 __________ Volts. 4. Check fan rotation for proper direction. Change wiring at contactor if necessary. 5. Service technicians should use a gauge set on the Liebert DS system during the initial startup to verify that the three-phase power is connected properly. The rotation direction of EC blowers is not a reliable indicator of proper connection. The blowers will rotate the same direction, regardless of the three-phase power input. 6. Check Main Fan amps and record. L1 _____________ L2 _____________ L3 _____________ Fuse _____________ 7. Increase temperature setpoint to energize reheats. Check and record amperage. #1 _____________ #2 _____________ #3 _____________ Fuse _____________ 8. Increase humidity setpoint to energize humidifier. Check and record amperage L1-L2 _________________ L2-L3 _________________ L1-L3 _________________ 9. Infrared: Check water level and adjust high limit float for proper operation. 10. If condensate pump has been supplied, check for proper operation. 11. Chilled water and Econ-O-Coil (GLYCOOL) only: a. Decrease temperature setpoint to energize valve motor. Check for full valve travel in cooling mode. b. Adjust controls out of cooling mode. Check for valve closure. 12. Decrease humidity setpoint to call for dehumidification. Check for valve travel in dehumidification mode. 13. Decrease temperature setpoint to energize compressor(s). Check and record compressor amps. #1 L1 _____________ L2 _____________ L3 _____________ Fuse _____________ #2 L1 _____________ L2 _____________ L3 _____________ 14. Check compressor operating pressure and record. (Check digital compressors fully loaded position.) Suction Pressure 1 ___________________ 2 ___________________ Discharge Pressure 1 ___________________ 2 ___________________ 15. Sight Glass clear? 1 ___________________ 2 ___________________ some flashing may occur with system fluctuations and/or R-407c blend refrigerants 16. Sight Glass dry? 1 ___________________ 2 ___________________ 17. Check compressor oil sight glass , should be 1/2 to 3/4 full while running. Adjust accordingly. 18. Check superheat on each circuit. Should be approximately 10-25. Circuit 1 _____________ Circuit 2 _____________ 19. Check low pressure settings. Low pressure cutout 1 _____________ 2 _____________ Low pressure cut in 1 _____________ 2 _____________ 20. Winter Control System (air-cooled only) Liebert Lee-Temp liquid level correct ___________________ Record voltage to heater pads _______________Volts 21. If the head pressures recorded above equal 105F condensing temperature, no adjustment of the glycol/water regulating valves is required If the system has balancing valves in it, these valves also should be adjusted. After the condensing temperature has been set up properly, the system should be allowed to run for 10 to 15 minutes to obtain stable conditions. Entering condenser water/glycol temperature ____________________ Leaving condenser water/glycol temperature _____________________
128
12.4
NOTICE
Risk of improper operation. Can cause damage to equipment. Do not change Advanced Menu parameter settings in the Liebert iCom without first getting permission from Emerson Network Power Liebert Services. Lowering this parameter to less than 100% will cause the coil to freeze on DX units, will overheat the reheat components on any unit and cause condensation problems on any unit equipped with a humidifier. 8. 9. 10. 11. 12. 13. 14. Turn Off the unit with the On/Off button. Remove power from main unit disconnect and main breaker and check with a meter. Replace all fuses removed in Step 2. Restore power to the unit. Turn On the main unit disconnect switch. Press the On button. Check and record the current draw on all line voltage components and match with serial tag. NOTE Electric Reheat. See Warning on page 126. Activate for a minimum of five (5) minutes. 15. Check for unusual noises and vibration. Note observations on the warranty inspection forms comments section. 16. Check all refrigerant and water lines for leaks. Note observations on warranty inspection form. 17. Record all of the following on the warranty inspection form: All component voltages and current draws All air / water temperatures indoor and outdoor All refrigerant and water / glycol pressures, All levels of refrigerant and oil in sight glasses Record refrigerant pressure switch settings and operating pressures Record superheat and subcooling. NOTE Unit superheat should be in the range of 10 to 20F (-12 to -6C). 18. Test all control sequences and functions of your unit for proper operation. Use Liebert iCOM user manual as a guide to system control operations. 19. Complete the warranty inspection form with sign-off data.
129
Maintenance
13.0 MAINTENANCE
! WARNING piping, moving, lifting and handling. Can cause equipment damage, Risk of improper wiring,
injury or death. Only qualified service personnel should work on this equipment. Read all installation, operating and safety instructions before proceeding. Read and follow all warnings in this manual
NOTICE
Risk of improper operation. Can cause damage to equipment. Do not change Advanced Menu parameter settings in the Liebert iCom without first getting permission from Emerson Network Power Liebert Service. Lowering this parameter to less than 100% will cause the coil to freeze on DX units, will overheat the reheat components on any unit and cause condensation problems on any unit equipped with a humidifier. The Liebert DS product is a single component in the facility heat removal system. The system includes air distribution (raised floors, duct systems), outdoor heat rejection (condensers, pumps, drycoolers, cooling towers, piping, heat rejection fluid, ambient temperature, etc.) and indoor cooling and humidity loads (equipment load, location, outside air infiltration). Proper application and maintenance of the entire system is critical to the life and reliability of the Liebert DS. Good maintenance practices are essential to minimizing operation costs and maximizing product life. Read and follow monthly and semi-annual maintenance schedules included in this manual. These MINIMUM maintenance intervals may need to be more frequent based on site-specific conditions. See the Liebert iCOM user manual, SL-18835, for instructions on how to utilize the unit controller to predict some service maintenance intervals. Emerson recommends the use of trained and authorized service personnel, extended service contracts and factory-specified replacement parts. Contact your local Emerson representative.
130
Maintenance
13.1
Filters
NOTICE
Risk of improper filter installation and filter collapse. Can cause equipment damage. Pleat direction is non-standard. Use only short-pleat filters (see Figure 97). Long-pleat filters are subject to collapse at high airflows. To maximize the performance and reliability of Liebert DS equipment, use only Liebert filters. Contact your local Emerson representative to order replacement filters. Table 59 Filter quantities, downflow units
Filter Quantities Unit Size DS 028, 035, 042 DS 053, 070, 077 DS 105 16 x 25 Filter Size Width x Length 4" Filter Option Merv 8 or Merv 11 5 7 9 2" Primary / 2" Pre-Filter Option Merv 11 Primary Filter / Merv 7 Pre-Filter 5/5 7/7 9/9
Table 60
131
Maintenance
Do Not Use
25" (635mm)
13.2
! WARNINGpinching action from spring-loaded motor base. Can cause serious injury Risk of crushing and
to hands and fingers. Improper drive belt removal may cause the motor base to slam down suddenly. Read the directions in this manual and on the unit instruction labels before servicing the belts, motors or pulleys. Follow all directions when servicing the unit.
132
Maintenance
Deadfront Low Voltage Electric Box Screws Lateral Support DPN001221 Rev. 0
Screws
133
Maintenance
Spring Housing
Adjustment Nut
DPN000995 Rev. 0
134
Maintenance
Blower Motor
Inspect motor at regular intervals. Keep motor clean and ventilation openings clear of dust, dirt and other debris.
Blower Wheel
Check to see if wheel(s) are tightly mounted on fan shaft. Rotate wheel(s) and make sure they do not rub against fan housing. The wheel(s) should be periodically cleaned of dirt and debris.
13.3
135
Maintenance
! CAUTION lifting and handling. Can cause equipment damage or injury. Risk of improper moving,
Only properly trained and qualified personnel should work on this equipment. Fan modules weigh in excess of 100lb. (45kg) each. Take precautions to avoid back injury and dropping during removal.
NOTICE
Risk of improper installation. Can cause equipment damage. Only a properly trained and qualified technician should install or open this motor. Use 60/75C copper wire only. Use Class 1 wires only.
13.4
HumidifierInfrared
During normal humidifier operation, deposits of mineral solids will collect in humidifier pan and on the float switch. These must be cleaned periodically to ensure proper operation. Frequency of cleaning must be locally established since it is dependant on humidifier usage and local water quality. A spare pan is recommended to reduce maintenance time at unit. The Liebert autoflush system can greatly increase the time between cleanings, but does not eliminate the need for periodic checks and maintenance (see Liebert iCOM user manual SL-18835 for autoflush setup). To help reduce excessive scaling in locations with difficult water quality, the use of Vapure is recommended (contact your local Emerson representative).
136
Maintenance
137
Maintenance
13.5
HumidifierSteam Generating
The humidifier drains and refills to maintain a current setpoint and alert the operator when the humidifier canister needs to be replaced.
! WARNING piping, moving, lifting and handling. Can cause equipment damage, Risk of improper wiring,
injury or death. Only properly trained and qualified service personnel should work on this equipment. Read all installation, operating and safety instructions before proceeding. Read and follow all warnings in this manual.
138
Maintenance
The steam cylinder is disposable and must be replaced at the end of the cylinders life. Cylinder life will vary according to water supply conditions and humidifier usage.
! WARNING meltdown, smoke and fire. Can cause fire suppression system Risk of humidifier canister
activation, fire and smoke alarm activation, serious equipment and building damage, injury and death. Using a humidifier canister that has reached the end of its service life can be extremely hazardous. If the canister cannot be replaced immediately at the end of life condition, turn Off the power and water supply to the humidifier and remove the canister until a replacement canister can be installed.
Table 61
Unit Model DS 028-042 DS 053-105
139
Maintenance
Actuator Plunger Spring Sleeve Male Slip-On Connection Tabs Holding Coil
140
Maintenance
3O Cylinder Pin
Cylinder Pin
! WARNING meltdown, smoke and fire. Can cause fire suppression system Risk of humidifier canister
activation, fire and smoke alarm activation, equipment or serious building damage, injury and death. Check steam generating humidifier electrode plugs to ensure that they are pressed firmly onto pins. Loose connections will cause overheating of cylinder and plugs..
141
Maintenance
Table 62
Yellow
On
On
Off
Off
Off
Excess current. Operating amperage exceeded 130% of rated amps. Water is drained from the cylinder (drain valve on for 10 min.).
Off
Off
Off
Table 63
Unit in call for humidification, humidifier will not operate Humidifier Contactor pulled in, but no water enters canister
Excessive arcing in canister Insufficient drain rate Excessive mineral content in water
Maintenance
To configure the PCB to the proper voltage, the jumpers should be set as follows: (* = Factory setting; do not adjust)
200V/208V: 230V: 380V/415V: 460V: 575V: J6, J9, J15*, J17*, J19*, J10*, J23*, P11 pin (2-3)* J5, J9, J15*, J17*, J19*, J10*, J23*, P11 pin (2-3)* J3, J8, J15*, J17*, J19*, J10*, J23*, P11 pin (2-3)* J2, J8, J15*, J17*, J19*, J10*, J23*, P11 pin (2-3)* J1, J8, J15*, J17*, J19*, J10*, J23*, P11 pin (2-3)*
J8 J9
Current Transformer
HW Sensor Jumpers J9: Low Voltage 200-240V J8: High Voltage 380-600V P11
J24
P12 1
Capacity adjust (Default at 100%) Sealed, do not adjust CURRENT TRANSFORMER For MES-L 10, loop current-sensing wire twice through current-sensing coil.
1
J1 J2 J3 J4 J5 J6 J7 J18 J17 J16 J15 J14 J13 J12 J11
J25
J26
Mains Voltage Select Jumpers J6: 200-208 J5: 230V J3: 380-415 J2: 460V J1: 575V
J10
Green LED For MES-L 20, loop current-sensing wire once Yellow through current-sensing coil. LED
J23
13.6
143
Maintenance
13.7
13.8
13.9
144
Maintenance
13.10 Compressor
13.10.1Compressor Oil
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage. Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty. See oil types specified in Table 64. Do NOT mix polyolester (POE) and mineral-based oils. Do NOT mix oils of different viscosities. Consult Emerson or the compressor manufacturer if you have questions. Table 64 Compressor oil types
Refrigerant Type Compressor Type Carlyle Semi-Hermetic Copeland Scroll and Digital Scroll R-22 Mineral Oil 1 R-407c POE Oil - ISO 68 Viscosity 2
1. Use Carlyle Mineral Oil Totaline P903-2001, Witco Suniso 3GS or other Carlyle-approved oils. 2. Use Carlyle POE Oil Totaline P903-1001, Castrol SW68 or other Carlyle-approved oils. 3. Use Copeland POE Oil ULTRA 32-3MAF or other Copeland-approved oils.
13.10.2Semi-Hermetic Compressors
Oil level can be viewed at the sight glass on semi-hermetic compressors. Normal operating oil level is 1/4 to 3/4 up the sight glass. After a compressor has been idle for an extended length of time, foaming will usually be present when compressor first starts. Wait until compressor has been operating for at least five minutes before viewing the oil level. If oil level is low, the cause must be corrected and oil level returned to its proper level.
145
Maintenance
NOTICE
Risk of improper component reinstallation. Can cause equipment damage. Identify and mark location of suction pressure transducer and discharge pressure switch. These devices look similar and they must be reinstalled in their original location.
146
Maintenance
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure gauge indicates the desired setting. To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired setting is obtained. Consult the factory if your unit is equipped with valves from other manufacturers.
147
Maintenance
Location
The water regulating valves are located in the condenser fluid supply line.
Control
The valve actuator operates on 24VAC power and is controlled by a 2-10VDC proportional control signal. The valve full open to full close time is 60 seconds. At 2VDC the valve is closed; at 10VDC the valve is fully open. There is a 20-second delay to position the motorized ball valve before starting the compressor.
Control Method
The control utilizes an upper and lower pressure threshold with a 35 PSI (241 kPa) deadband to reduce valve movement. If the liquid pressure is between the upper and lower threshold the valve remains at the current position. If the liquid pressure exceeds the upper threshold the valve opens, and if the pressure falls below the lower threshold the valve closes. There are multiple adjustment bands to ease discharge pressure back into control range.
Adjustment
Both pressure thresholds can be shifted simultaneously over a 50 PSI (345 kPa) range (the 35 PSI [241 kPa] differential remains constant). The ball valve setpoint offset parameter in the Service menu can be adjusted from 0 to 50 PSI (345 kPa) to raise or lower the control band similar to the pressure adjustment on a water regulating valve. Changing the setpoint offset will adjust the pressure thresholds for both circuits. Units are factory set at a 30 PSI (207 kPa) setpoint offset (30 PSI [207 kPa] above minimum). This results in a 220 PSIA (1517 kPa) lower threshold and a 255 PSIA (1758 kPa) upper threshold pressure.
Startup
The setpoint offset is adjusted to the minimum value during startup, then transitions to the set value once the compressor reaches normal operating pressures. Due to the control dead band it is possible for each circuit to stabilize at different pressures within the dead band. Additionally changes in fluid temperature could cause pressure changes that do not result in valve movement within the dead band. Fan cycling stats should be set to prevent continuous fluid temperature swings greater than 10oF (5.6oC) (see 13.14.3 - Drycooler Settings).
Location
The motorized ball valves are located in the condenser fluid return line. Three-way valves are piped in a mixing arrangement with the common port at the valve outlet.
Manual Control
The valve can be manually set by disconnecting AC power, depressing the manual override button on the valve actuator, and adjusting the valve position with the handle. You also have the option to control the MBVs through the Service menu using manual mode to override the normal control.
148
Maintenance
13.14.3Drycooler Settings
Applications with the Optional Stat Setting require field piping to be insulated to prevent condensation. Table 66 shows acceptable applications where stats must be adjusted to Optional Setting. Aquastats must be field-adjusted to Optional Setting for: GLYCOOL/Dual Cool applications Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all Liebert DS units with digital compressors). These units have a D or G in the seventh character: DS/VS/xxxxD or DS/VS/xxxxG. Table 66 Water/glycol system conditions requiring optional settings for aquastats
Glycool MBV 1 Optional Yes Multiple Optional Yes 1 Optional Yes WRV Multiple Optional Yes 1 Optional Yes MBV Multiple Factory No 1 Factory No Glycol WRV Multiple Factory No Cooling Type Flow Control Drycoolers in Loop Stat Setting* Insulate Field Piping
Table 67
Fans F1 F2 & F3 F4
Table 68
Table 69
NOTE 1. All drycoolers are shipped at Factory Setting. 2. Factory Setting is used for all glycol applications, except single drycooler loops with motor ball valve controls. 3. Stats must be field-adjusted to Optional Setting for GLYCOOL/Dual Cool applications and all single drycooler loops using motor ball valve flow controls.
149
Filters
___ 1. Check/replace filters ___ 2. Grille area unrestricted ___ 3. Wipe section clean ___ 4. Coil clean
Blower Section
___ 1. Blower wheels free of debris ___ 2. Check belt tension and condition (replace if needed) ___ 3. Check/lube bearings ___ 4. Check sheave/pulley (replace if worn) ___ 5. Check motor mount ___ 6. Motor amp draw L1__________________ L2 __________________ L3______________ ____ Compare to nameplate amps
Reheat
___ 1. Inspect elements ___ 2. Check wire connections (inside reheat box) ___ 3. Reheat amp draw ___ a. #1 ___ a. #2 ___ a. #3
Infrared Humidifier
___ 1. Check drain lines and trap for clogs ___ 2. Check/clean pan for mineral deposits ___ 3. Clean reflector ___ 4. Check water make-up valve for leaks ___ 5. Check humidifier lamps (replace if burnt out) ___ 6. Check wire connections (inside humidifier box) ___ 7. Humidifier amp draw L1 ______________ L2 _______________L3 __________________
150
Condensate Pump
___ 1. Check for debris in sump ___ 2. Check operation of float(s) (free movement)
Refrigeration Piping
___ 1. Check refrigerant lines (clamps secure/no rubbing/no leaks) ___ 2. Check for moisture (sight glass)
Water-Cooled Condensers
___ 1. Check water regulating valve operation ___ 2. Cap tubes (not rubbing) ___ 3. Check for water/glycol leaks ___ 4. Entering water temperature ______________ ___ 5. Leaving water
Drain Piping
___ 1. Check for free running drain system ___ 2. Clear out obstructions and material buildup on tubing walls ___ 3. Check for leaks ___ 4. Check for tubing kinks or damage
Compressor Section
___ 1. Check oil level ___ 2. Check for oil leaks ___ 3. Check compressor mounts (springs/bushings) ___ 4. Cap tubes (not rubbing) ___ 5. Check wire connections (inside compressor box) ___ 6. Compressor operation (vibration/noise) ___ 7. Suction Pressure ___ 9. Superheat ___ 11. Low pressure cut in ___ 12. High pressure cut out ___ 13. Amp draw ____ Circuit #1 ___ a. L1 L2 L3 ____ Circuit #2 ___ a. L1 L2 L3 Circuit #1 __________________ Circuit #2 ______________________ Circuit #1 __________________ Circuit #2 ______________________ Circuit #1 ______________Circuit #2__________________ Circuit #1 ______________Circuit #2__________________ Circuit #1 ______________Circuit #2__________________ ___ 8. Discharge Pressure Circuit #1 __________________ Circuit #2 ______________________ ___ 10. Low pressure switch cut out
Electrical Panel
___ 1. Check fuses ___ 2. Check contactors for pitting ___ 3. Check wire connections
151
Controls
___ 1. Check/Verify Control Operation (Sequence) ___ 2. Check humidifier high water alarm operation ___ 3. Check operation of the air safety switch ___ 4. Check setting/operation of the filter clog switch ___ 5. Check/test changeover device(s) ___ 6. Check/test water detection device(s)
Glycol Pump
___ 1. Check pump rotation ___ 2. Check for glycol leaks ___ 3. Pump pressures
#1 #2 Suction Suction Discharge Discharge
152
Maintenance Notes___________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ Signature ___________________________________________________________________________________ Company ____________________________________________________________________________________ Make photocopies for your records. Compare readings / information to previous maintenance worksheet. To locate your local Emerson representative for Liebert-engineered parts, check the Liebert Web site: www.liebert.com or call 1-800-LIEBERT.
153
NOTES
154
155
156
Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 USA
IlProduttoredichiarache,semunitodimarchioCE,ilprodottoconformealledirettivedell'Unione europea: TheManufacturerherebydeclaresthatthisproduct,whenbearingtheCEmark,conformstothe EuropeanUniondirectives: DerHerstellererklrthiermit,dassdasvorliegendeProdukt,sollteesdieCEKennzeichnungtragen,den folgendenRichtlinienderEuropischenUnionentspricht: Lefabricantdclareparlaprsentequeceproduit,portantlamarqueCE,estconformeauxdirectives del'Unioneuropenne: ElfabricantedeclaraporlapresentequesiesteproductollevaelmarcadoCEesconformeconlas directivasdelaUninEuropea: Ofabricantedeclaraporestemeioqueesteproduto,quandoostentaamarcaCE,estem conformidadecomasdirectivasdaUnioEuropeia: Tillverkarentillknnagerhrmedattdenhrprodukten,nrdenrCEmrkt,verensstmmermed EU:sdirektiv: Defabrikantverklaarthierbijdatditproduct,indienhetvandeCEmarkeringisvoorzien,conformde EUrichtlijnenis: Valmistajavakuuttaatten,ettmiklituotteessaonCEmerkint,setyttseuraavienEUdirektiivien vaatimukset: Produsentenerklrerhervedatdetteproduktet,nrdeterCEmerket,erisamsvarmedEUdirektiver: Producentenerklrerhermed,atdetteproduktoverholderEU'sdirektiver,nrdetbrerCEmrket: ,CE, ..:
2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Locations
United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-18825_REV11_02-11
Emerson Network Power. The global leader in enabling Business-Critical Continuity AC Power Connectivity DC Power Embedded Computing Embedded Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. 2008 Emerson Electric Co.