Method of Computation
Method of Computation
FLC = 51.91 A
VD = 35.6 X 14.74 X 61 LM
= 9.14 Volts
1000 X 3.5 X 1 SET/S
%VD = 9.14 Volts
230 Volts
%VD = 3.98 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
VD = 35.6 X 14.35 X 61 LM
= 8.90 Volts
1000 X 3.5 X 1 SET/S
%VD = 8.90 Volts
230 Volts
%VD = 3.87 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
VD = 35.6 X 7.04 X 61 LM
= 4.37 Volts
1000 X 3.5 X 1 SET/S
%VD = 4.37 Volts
230 Volts
%VD = 1.90 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
VD = 35.6 X 7.30 X 61 LM
= 4.53 Volts
1000 X 3.5 X 1 SET/S
%VD = 4.53 Volts
230 Volts
%VD = 1.97 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
VD = 35.6 X 6.26 X 61 LM
= 3.88 Volts
1000 X 3.5 X 1 SET/S
%VD = 3.88 Volts
230 Volts
%VD = 1.69 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN