Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Fire Norms Design Standards

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

FIRE NORMS

NBC 2016
Design standards
6 ARRANGEMENT OF EXIT
6.1 Exits from the upper floor should be so located that no point in
the floor is more than 22.5 m from the nearest exit, for the Type I,
Type II and Type III construction. NOTE - Type IV construction is not
allowed for construction of educational buildings.

6.2 Exits should be so arranged that at least two separate exits are
available in every floor area. Exits shall be as remote from each
other as practicable and so arranged that there are no pockets or
dead ends of appreciable size in which occupants may be trapped.

6.3 Every room with a capacity of 45 persons in area shall have at


least two doorways.

6.4 Elevators, lifts and escalators shall not be counted as exits.

6.5 Fire escapes constitute only means of the required exit and
should not be taken into account in calculating the evacuation time
of the building. Fire escapes shall always be kept in sound operating

7 CORRIDOR AND PASSAGE WAYS


7.1 Exit corridors and passage ways shall be of width not less than
the aggregate required width of exit doorways leading from them in
the direction of travel to the exterior.

7.2 Where stairways discharge through corridors and passageways, the


height of corridors and passageways shall be not less than 2.4 m.

7.3 All internal staircase, lift, lobbies and corridors should be


adequately ventilated and illuminated.

8 DOORWAYS
8.1 No exit doorway shall be less than 1 m in width except assembly
halls where door width should not be less than 2 m.

8.2 The height of door shall not be less than 2 m.

8.3 These shall be opening-outwardly.

8.4 Overhead or sliding door shall not be installed. NOTE - In case


of buildings where there is Central Corridor the door shall open
inwards to allow smooth flow of traffic in the corridor.

8.5 These shall be openable from inside and shall not be opening
immediately on flight.

9 STAIRCASE
9.1 Any building having area more than 500 m2 on each floor and 15 m
or more in height shall have minimum two staircases of enclosed type;
at least one of these shall be on external wall and shall directly

IS 14435 : 1997;pg.no:1,2
open to exterior, interior open space or to an open place of safety.
Further the provision or otherwise of alternative staircase shall be
subject to the requirements of travel distance being complied with.
9.2 Internal Staircases
9.2.1 Internal stairs shall be constructed of noncombustible
materials throughout. Hollow combustible construction shall not be
permitted.

9.2.2 Internal staircases shall be constructed as a self-contained


unit with an external wall constituting at least one ofits sides and
shall be completely enclosed.

9.2.3 Staircase shall not be arranged round a lift shaft.

9.2.4 No gas piping shall be laid in the stairway.

9.2.5 Notwithstanding, the detailed provision for exits in the


educational buildings, the width ofstaircase shall not be less than
1.5 m up to a height of 30 m. NOTE - Buildings above 30 m height are
not permitted.

9.2.6 Minimum width of treads shall not be less than 300 mm. The
treads should be constructed and maintained in a manner to prevent
slipping.

9.2.7 Maximum height of riser shall not be more than 150 mm and
number shall be limited to 15 per flight.

9.2.8 Height of railing shall be more than 1 m. Gap between verticles


should not exceed 200 mm. The gap should be reduced to 150 mm where
small children are likely to use the staircase.

9.2.9 The number of people in between floor landings in staircase


shall not be less than the population on each floor for the purpose
of design of staircase.
The other main parameters for the design of staircase are as given
below:
a) The minimum head room in a passage under the landing of a
staircase and under the staircase shall be 2.2 m.
b) For building 15 m in height or more, access to main staircase
shall be through a fire smoke check door or 1 h fire resistance
IS 14435 : 1997;pg.no: 2
rating. Fire resistance rating may be reduced to half an hour for
residential buildings.
c) No living space, store or other fire risk shall open directly into
the staircase or staircases.
d) External exit door of staircase enclosure at ground level shall-
open directly to the open spaces or through a draught lobby, if
necessary.
e) The main staircase and external staircase shall be continuous from
ground floor to the terrace level.
f) No electrical shafts/AC ducts or gas pipe, etc, shall pass through
the staircases. Lift shall not open in staircase.
g) No combustible material shall be used for decoration/ wall
panelling in the staircase.
h) Beams/columns and other building feature shall not reduce the head
room/width of the staircase.
i) The exit sign with arrow indicating the way to the escape route
shall be provided at a suitable height from the floor level on the
wall and shall be illuminated by electric light connected to corridor
circuits. All exit way marking signs shall be flush with the wall and
so designed that no mechanical damage shall occur to them due to
moving of furniture or other heavy equipments. Further, all landings
of floor shall have floor indicating boards prominently indicating
the number of floor as per bye-laws.
j) The floor indication board shall be placed on the wall immediately
facing the flight of stairs and nearest to the landing. It shall be
of size not less than 0.5 x 0.5 m.
k) Individual floors shall be prominently indicated on the wall
facing the staircases.
l) In case of single staircase it shall terminate at the ground floor
level and the access to the basement shall be by a separate
staircase. However, the second staircase may lead to basement levels
provided the same is separated at ground level by ventilated lobby
with discharge points to two different ends through enclosures.

IS 14435 : 1997;pg.no: 2
IS 14435 : 1997;pg.no: 2
IS 14435 : 1997;pg.no: 2
9.3 External Stairs
9.3.1 All external stairs shall be directly connected to the ground.

9.3.2 Entrance to the external staircases shall be separate and


remote from the internal staircase.

9.3.3 Care shall be taken to ensure that no wall opening or window


opens on to or close to a external staircase.

9.3.4 The route to the external stairs shall be free from


obstructions at all times.

9.3.5 ‘The external staircase shall beconstructed of non-combustible


materials, preferably of masonry and any doorway leading to it should
have the required fire resistance.

9.3.6 No external staircase, used as a fire escape, should be


inclined at an angle greater than 45’ to the horizontal. 9.3.7
External stairs shall have straight flight not less than 1 m wide
with 200 mm treads and risers not more than 190 mm. The number of
risers shall be limited to 15 per flight.

9.3.8 Hand rails shall be of a height not less than 1 m and not
exceeding 1.2 m.

9.4 In case the educational building has got a mixed occupancy such
as auditorium, etc, necessary recommendations for exits as per the
requirements as given in SP 7 : 1983 shall be followed.

10 AIR CONDITIONING
10.1 In some educational institutions, a part of it may be having air
conditioning arrangement. In case of room air conditioning, no extra
precautions than laid down are required. In cases, like auditorium
and laboratories having central air conditioning system, the measures
as laid down in IS 1642 should apply.

11 CHIMNEYS
11.1 Where chimneys are used, the requirements shall be as laid down
in IS 1642 and IS 164

IS 14435 : 1997;pg.no: 3
15 EMERGENCY AND ESCAPE LIGHTING
15.1 Emergency lighting shall be powered from a source independent of
that supplying normal Iighting.

15.2 The emergency lighting shall be provided to be put on within 5


second (preferably within 1 second) of the failure of the normal
lighting supply.

15.3 Emergency lighting luminaries and their fittings shall be non-


flammable.

15.4 It is essential that the wiring and installations of the


emergency lighting systems are of high qualityso as to ensure their
perfect serviceability at all times.

15.5 The emergency lighting system shall be capable of continuous


operation for a minimum duration of 1 h 30 min even for smallest
premises.

15.6 It shall be ensured that the emergency lighting system is well


maintained by periodical inspections and tests so as to ensure their
perfect serviceability at all times.

15.7 Escape lighting shall be capable of:


a) Indicating clearly and unambiguously the escape routes,
b) Providing adequate illumination along such routes to allow safe
movement ~of persons towards and through exit,
c) Ensuring that fire~alarm call point and lirefighting equipments
provided along the escape routes can be readily located.

15.8 Escape lighting luminaries shall be sited to cover the following


locations:
a) Near each intersection of corridors,
b) At each exit door
c) Near each change of direction in the escape route
d) Near each staircases so that each flight of stair receives direct
light
e) Near any other change of floor level,
f) Outside each final exit and close to it
g) Near each fire alarm call point
h) Near fire-fighting equipment
i) To illuminate exit and safety signs as required by the enforcing
authority.NOTE - For the purpose of this clause ‘near’ is
normally considered to be within 2 m measured horizontally.

IS 14435 : 1997;pg.no: 4

You might also like