Eaton DC Power Solutions

The Eaton® DU-X Electronic Once partnered with high


Distribution (e-Fuse) is the ideal efficiency rectifiers and fitted
solution for next generation 5G into a small 1U high system
wireless networks, fibre-based shelf, operators have available
deployments and other low to them one of the most
power telecommunications compact and innovative small
applications requiring compact, systems on the market,
efficient and flexible DC power providing up to 2000Watt of
supplies. power.
Each load and battery system e-Fuse-based load protection
connection is controlled and offers benefits such as: rapid
protected using a semi- late point definition of
conductor device allowing for protection outputs, reduced
precise control of overcurrent lead-times, energy metering,
trip, fault currents and and remote reset preventing
connection. All terminations are costly truck rolls.
made via the front of the unit to
ensure ease of use in space
constrained installations. Include providing secure power
The DU-X distribution embeds a for
full featured system controller
Shown fitted into an RM3 magazine  Radio Base Stations
with a front access 100BaseT
Ethernet port. This provides  Fibre networks
access for easy system setup
and outbound network  Customer premises
communications. Also available equipment
from the front are digital and  Roadside cabinets
analogue inputs, and digital
outputs.  Converged VoIP/data
networks, PoE, and IP
routers.

 Super compact design


 Local or remote setting of load and battery protection
 Full current output at chosen setting, no derating
 Full front connection
 Rapid late point definition to reduce lead-times
 Embedded system controller
 On-board secure web server
 SNMP agent
 Energy metering function
 Setup via web, keypad or configuration file
 Compatible with Eaton’s Energy Saver (ES) rectifier
Input Mechanical
DC Input Voltage 37 – 59.5V Dimensions 42mm [1.65”], 3U: 133mm [5.25”],
Range H,W,D 266mm [10.45”] overall
Weight 1kg
Output
DC Output 43 – 57.5V Software
Voltage Range DU-X-GUI Configuration file software.
DC Output Nominal: 2.0kW 48V DC, 42Amp (APR48-ES)
Power * System
LVD†: 1.72kW 41V DC, 42Amp (APR48-ES) Compatible RM3-440-0120
Systems - 1x DU-X, space for 2x APR48-ES rectifiers
* Assumes two rectifiers fitted with one used for -
*3
335mm deep , 19” mounting, 1U high
redundancy and battery recharge.
- 2 x AC blunt cords (no plug)
† Low Voltage Disconnect point (example voltage)
- CE and UL compliant
System
RM3-440-0620
Load Load Outputs: 6
*1 - 1x DU-X, space for 2x APR48-ES rectifiers
e-Fuse rating: 5-25Amp each (1Amp steps) *3
- 335mm deep , 19” mounting, 1U high
*1 - 2 x IEC320 AC sockets
300Amp max fault, 10kA thermal inline fuse
- CE and UL compliant
Each pair of output leads must be less than 3m
long or 4uH in inductance. RM3-340-0120
- 1x DU-X, space for 2x APR48-ES rectifiers
Maximum non-current limited load capacitance that any *4
300mm deep , 19” mounting, 1U high
output will start into is 10uF with a minimum ESR of - 2 x AC blunt cords (no plug)
50mR at the end of 0.5m 2.5mm2 leads.
- CE compliant
Battery Battery Inputs: 2
*2
e-Fuse rating: 10-50Amp each (1Amp steps) *3
Additional rear space is required for exhaust air.
*4
Additional vertical space is required for exhaust air.
*2
550Amp max fault, 10kA thermal inline fuse

Maximum 200AH string per connection Certifications


All products comply with International Standards.
Battery connection leads shall be less than 3m long or
4uH in inductance North America UL Recognised (Canada, USA), FCC
Battery/Load LVD and PLD Europe CE
Disconnect Australia and New Zealand C-Tick

Communication In the interests of continual product improvement all specifications are


Physical 100BaseT Ethernet subject to change without notice.
Communications TCP/IP, https, SNMP, and on board web server
System Inputs Temperature (battery)
User Display 128*32 Dot matrix display
Indicators General: Power on, no alarms. Active alarm
Load/Battery: On, Pending, Tripped
Keypad 5-way navigation control

Input / Output
Digital Inputs 5 x TTL level compatible inputs, all common return.

2 x inputs can be configured as 0 to +10V analogue


input, or 0 to -60VDC for battery midpoint.
3 x inputs can be configured as digital input /output.
Digital Outputs 5 x relays (2 x isolated commons), all normally open

Datalogging
Event Log 10,000 lines
Data Log 10,000 lines
Energy Log 10,000 lines

Environmental
Operating Rated: -10°C to +65°C [14°F to +149°F]
Temperature Extended*: -25°C to +70°C [-13°F to +158°F]
Range
*Output current from the rectifiers is derated above 50°C

Eaton, SiteSure, DCTools and


PowerManager are trade names,
trademarks, and/or service marks of
Eaton Corporation or its subsidiaries and
affiliates. All other trademarks are
property of their respective owners.