Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Time Lag Switch

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PRODUCT DATA AND INSTALLATION SHEET

490-194 AND 279-8614 DESCRIPTION AND OPERATION


ELECTRONIC TIME LAG SWITCHES These time lag switches are a quick and effective way to reduce energy
consumption for lighting applications. Pressing the button brings the lights
on; the lights will then switch off automatically after a preset time period
has elapsed.

These units do not require a neutral connection, therefore they can be


used to replace an existing light switch. The duration of the time delay is
set by a thumbwheel on the reverse of the unit.

The switches comes with extra terminals to allow slave switches to be


connected to the system to trigger the timer.

The 279-8614 product has an illuminated push button to allow the unit to
be located in the dark.

Time lag switches can be used in two way and intermediate switching
arrangements without any extra wiring.

WIRING INSTALLATION
Conventional Wiring Warning. This device works at mains potential. Be sure to take care when
working with electricity.
Wire the units as in diagram 1. When using multiple switch posi-
1. Make sure the load is connected and in working order.
tions see diagram 2.
2. Isolate the mains supply to the circuit at the main consumer unit.
3. Connect the controller via the terminal block. Live supply to the L
For two way and intermediate switching follow the diagrams over-
terminal and the load to the LIVE OUT terminal.
leaf. Note that as long as each switch position has a Live feed
4. Connect the slave switches if using.
and a Live Out connection to the load then the switch will be
5. Set the timing range using the thumbwheel. Turn clockwise to
properly wired.
increase timing.
6. Screw the unit to the wall and switch the mains supply back on at
Using Slave Switches
the distribution board.
7. Wait 20 seconds before pushing the button
Where slave switches are used follow diagram 3. Limit the cable
8. Push the button and the lights will come on
run between the slave switches and the timer to 25m.
9. Wait for the time period and the lights will turn off again.
Note that the slave switch must connect directly to the terminals.
Putting Live, Neutral or Earth on the terminals will damage the
unit.

Slave switches with integral neons will only work if the neons are
supplied separately with a Live and Neutral connection.

Diagram 1 Diagram 3
Conventional Slave switches
wiring

Diagram 2
Multiple switch
locations

Ref %WD049 Issue 2


FAULT FINDING SPECIFICATION
LIGHTS DO NOT COME ON LOAD

Check to see if the live supply to the circuit is 10 Amp incandescent lighting
good. Strap across the L and LIVE OUT termi- 6 Amp fluorescent lighting
nal to turn the load on. 3 Amp compact fluorescent lighting
3 Amp low energy lighting
LIGHTS DO NOT GO OFF 3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
Ensure that you have waited for the time out Most fluorescent fittings have power factor correction capacitors fitted. If they are not present
period. the unit may fail to turn off properly or flicker. In this case fit one capacitor per circuit with a mini-
mum value of 1 F for every timer installed. The capacitor should be fitted across switched live
If the lights still do not go off then it is likely the and neutral. Note that it is not necessary to fit a capacitor on every fitting. This also applies to
unit was not given the 20 seconds start up pe- fittings controlled with high frequency ballasts and maintained emergency fittings.
riod on installation. Follow this procedure:
1. Isolate the mains supply to the circuit at For fluorescent lighting total power factor correction capacitance must not exceed 40 F.
the main consumer unit and unscrew
the unit from the wall. Not suitable for switching contactors
2. Turn the lights off by tapping the relay Not suitable for SON lighting
on the rear of the unit with the handle of Not suitable for heating or ventilation loads.
a screwdriver until the contact opens. Please contact our sales department for a suitable alternative product.
3. Reapply the mains and wait for 20 sec-
onds. SUPPLY VOLTAGE 220-240 Volts AC 50 Hz
4. Push the button for operation. TIME OUT PERIOD 20 seconds to 20 minutes (approximate)
FIXING METHOD Surface fixing 25mm deep plastic surface mount moulded box.
LIGHTS FLICKER Flush fixing 25mm steel wall box or 32mm deep cavity wall box.
TERMINAL CAPACITY 1.5mm2
Ensure that there are sufficient power factor MATERIAL Flame retardant ABS
correction capacitors fitted. TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-89/336/EEC
LVD-73/23/EEC

PART NUMBERS
490-194 Electronic time lag switch
279-8614 Electronic time lag switch with neon locator

IMPORTANT NOTICE! Due to our policy of continual


product i mprovement CP
This device should be installed by a qualified electrician Electronics reserves the right to
in accordance with the latest edition of the IEE wiring alter the specification of this
regulations. product without prior notice.

Ref %WD049 Issue 2

You might also like