Introduction

1.3 Characteristics

Monitoring

Self-supervision of the device

Oscillographic fault recording

Phase sequence of busbar voltage

Voltage circuit of busbar and line

Communication and interface

PC front port for setting with DIGSI 4

System interface
• IEC 60870-5-103, redundant optional
• IEC 61850, Ethernet
• DNP 3.0
• Profibus-DP
• Modbus RTU
Service interface for DIGSI 4 (modem)

Time synchronization via IRIG B/DCF 77

1.3 Characteristics

General

• Fast transfer in accordance to ANSI C50.41-2012

• Fast transfer success increased - exclusive REAL-TIME FAST complied with C50.41-2012 using predictive
algorithm
• Engineering effort saving - typical connection diagram and default configuration suitable for most cases

• Cost saving - auto adapt line VT installation at transformer HV side, no matching VT required

• Cost saving - protection functions for tie-CB integrated

• Switching sequences optimized - FAULT starting condition classified into Type A and B, less bus dead time
under non-electric fault transfer

• Setting "free" - default transfer settings suitable for most cases

• Kinds of abnormal starting condition to cover power loss and in-advertent CB open, stabilized against fault
and motor starting

• Manual start remotely over protocol or locally by binary input, controlled by REMOTE/LOCAL key switch

• Function's on/off remotely over protocol or locally on device panel

• Support both mono-direction and bi-direction switching

• Performance enhanced - the high speed relay contact (approx. 1 ms) designed for CB closing

• Specially designed HSBT online test mode and powerful SIGRA help the functional test and settings'
verification

• Application extended to single busbar w. 3-CB besides single busbar w. 2-CB and sectionalized single
busbar w. 3-CB

16 SIPROTEC, 7VU683, User Manual


C53000-G1176-C369-4, Release Date 07.2016
Introduction
1.3 Characteristics

• Friendly HMI with large graphic LCD

• Smart LCD display of transfer data, e.g, dU, df, dj, Ures and Udiff/f

• Smart oscillographic record, e.g, differential voltage Udiff, residual voltage Ures

• Kinds of supervision function


• Kinds of international standard communication interface/protocol.

SIPROTEC, 7VU683, User Manual 17


C53000-G1176-C369-4, Release Date 07.2016
Introduction
1.3 Characteristics

18 SIPROTEC, 7VU683, User Manual


C53000-G1176-C369-4, Release Date 07.2016
Function 2
This chapter describes the individual functions available on the SIPROTEC 4 device 7VU683. It shows the
setting possibilities for each function in maximum configuration. Guidelines for establishing setting values, and
formula are given where required.

Additionally, on the basis of the following information, it may be defined which functions are to be used.

2.1 General 20

2.2 HSBT 23

2.3 Protection for Tie-CB 112

2.4 Monitor Function 121

SIPROTEC, 7VU683, User Manual 19


C53000-G1176-C369-4, Release Date 07.2016
Function
2.1 General

2.1 General

This chapter describes the analogue inputs' connection between HSBT and voltage, current circuit.

2.1.1 VT Installation

Line voltage and bus voltage are necessary for criterions. During the transfer, device makes decisions based
on the measuring and computing results derived from voltages across the alternative source CB. Figure 2-1
shows the voltage connection example.

Figure 2-1 Voltage Connection Illustration


Only 1-ph voltage is required for line side. Either phase-earth voltage or phase-phase voltage can be used.
And, this must be parameterized under Power System Data 1, for example, 0213 VT connection of Line 1 = Uab.

3-ph voltage is required for bus side. It's essential for voltage phase sequence check, fault detection, etc.

In some case, line voltage can only be taken from high voltage side of in-feeding transformer. 7VU683 supports
this application. It will auto-adapt the voltage amplitude and angle difference by two parameters, for example,
0283 Voltage balancing factor of Line 1 and 0284 Voltage angle adjustment of Line 1. No matching VT is required.
Figure 2-2 shows the application.

20 SIPROTEC, 7VU683, User Manual


C53000-G1176-C369-4, Release Date 07.2016