Hybrid Inverter
User Manual
Contents
1. Safety Introductions ………………………………………………… 01
2. Product instructions ………………………………………………… 01-04
2.1 Product Overview
2.2 Product Size
2.3 Product Features
2.4 Basic System Architecture
3. Installation …………………………………………………………… 05-29
3.1 Parts list
3.2 Mounting instructions
3.3 Battery connection
3.4 Grid connection and backup load connection
3.5 PV Connection
3.6 CT Connection
3.6.1 Meter Connection
3.7 Earth Connection(mandatory)
3.8 WIFI Connection
3.9 Wiring System for Inverter
3.10 Typical application diagram of diesel generator
3.11 Single phase (230Vac) parallel connection diagram
3.12 Split phase (120/240Vac) parallel connection diagram
3.13 Parallel connection for 230/400 three phase
3.14 Pcs Parallel connection for 120/208 three phase
3.15 Parallel connection for 120/208 three phase
4. OPERATION …………………………………………………………… 30
4.1 Power ON/OFF
4.2 Operation and Display Panel
5. LCD Display Icons …………………………………………………… 31-43
5.1 Main Screen
5.2 Solar Power Curve
5.3 Curve Page-Solar & Load & Grid
5.4 System Setup Menu
5.5 Basic Setup Menu
5.6 Battery Setup Menu
5.7 System Work Mode Setup Menu
5.8 Grid Setup Menu
5.9 Generator Port Use Setup Menu
5.10 Advanced Function Setup Menu
6. Mode …………………………………………………………………… 43-45
7. Fault information and processing ………………………………… 45-48
8. Limitation of Liability ……………………………………………… 48
9. Datasheet ……………………………………………………………… 49-50
10. Appendix I …………………………………………………………… 51-52
11. Appendix II …………………………………………………………… 53
About This Manual
The manual mainly describes the product informa�on, guidelines for installa�on, opera�on and
maintenance. The manual cannot include complete informa�on about the photovoltaic (PV)
system.
1. Safety Introduc�ons
· This chapter contains important safety and opera�ng instruc�ons. Read and keep this manual
for future reference.
· Before using the inverter, please read the instruc�ons and warning signs of the ba�ery and
corresponding sec�ons in the instruc�on manual.
· Do not disassemble the inverter. If you need maintenance or repair, take it to a professional
service center.
· Improper reassembly may result in electric shock or fire.
· To reduce risk of electric shock, disconnect all wires before a�emp�ng any maintenance or
cleaning. Turning off the unit will not reduce this risk.
· Cau�on: Only qualified personnel can install this device with ba�ery.
· Never charge a frozen ba�ery.
· For op�mum opera�on of this inverter, please follow required specifica�on to select appropriate
cable size. It is very important to correctly operate this inverter.
· Be very cau�ous when working with metal tools on or around ba�eries. Dropping a tool may
cause a spark or short circuit in ba�eries or other electrical parts, even cause an explosion.
· Please strictly follow installa�on procedure when you want to disconnect AC or DC terminals.
Please refer to "Installa�on" sec�on of this manual for the details.
· Grounding instruc�ons - this inverter should be connected to a permanent grounded wiring
system. Be sure to comply with local requirements and regula�on to install this inverter.
· Never cause AC output and DC input short circuited. Do not connect to the mains when DC
input short circuits.
2. Product Introduc�on
This is a mul�func�onal inverter, combining func�ons of inverter, solar charger and ba�ery
charger to offer uninterrup�ble power support with portable size. Its comprehensive LCD display
offers user configurable and easy accessible bu�on opera�on such as ba�ery charging, AC/solar
charging, and acceptable input voltage based on different applica�ons.
- 01 -
2.1 Product Overview
1
2
3
4
6
5
7
8
9
10
11 16
12
13
14
15
- 02 -
2.2 Product Size
Inverter Size
- 03 -
2.3 Product Features
- Supports Split phase 120/240Vac, Three-phase 120/208Vac system.
- Self-consump�on and feed-in to the grid.
- Auto restart while AC is recovering.
- Programmable supply priority for ba�ery or grid.
- Programmable mul�ple opera�on modes: On grid, off grid and UPS.
- Configurable ba�ery charging current/voltage based on applica�ons by LCD se�ng.
- Configurable AC/Solar/Generator Charger priority by LCD se�ng.
- Compa�ble with mains voltage or generator power.
- Overload/over temperature/short circuit protec�on.
- Smart ba�ery charger design for op�mized ba�ery performance
- With limit func�on, prevent excess power overflow to the grid.
- Suppor�ng WIFI monitoring and build-in 2 strings of MPP trackers
- Smart se�able three stages MPPT charging for op�mized ba�ery performance.
- Time of use func�on.
- Smart Load Func�on.
AC cable DC cable
WiFI
GPRS
CT
- 04 -
3. Installa�on
3.1 Parts List
Check the equipment before installa�on. Please make sure nothing is damaged in the package.
You should have received the items in the following package:
User
manual
- 05 -
3.2 Moun�ng instruc�ons
Installa�on Precau�on
This Hybrid inverter is designed for outdoor use(IP65), Please make sure the installa�on site
meets below condi�ons:
· Not in direct sunlight
· Not in areas where highly flammable materials are stored.
· Not in poten�al explosive areas.
· Not in the cool air directly.
· Not near the television Antenna or antenna cable.
· Not higher than al�tude of about 2000 meters above sea level.
· Not in environment of precipita�on or humidity(>95%)
Please AVOID direct sunlight, rain exposure, snow laying up during installa�on and
opera�on. Before connec�ng all wires, please take off the metal cover by removing
screws as shown below:
- 06 -
≥500mm
≥500mm
For proper air circula�on to dissipate heat, allow a clearance of approx. 50cm to the side and
approx. 50cm above and below the unit. And 100cm to the front.
- 07 -
12 mm
1 2 3
( 0.47 in.)
82~90mm
[(3.23 in.)to(3.54 in.)]
For safe opera�on and compliance, a separate DC over-current protector or disconnect device is
required between the ba�ery and the inverter. In some applica�ons, switching devices may not
be required but over-current protectors are s�ll required. Refer to the typical amperage in the
table below for the required fuse or circuit breaker size.
- 08 -
All wiring must be performed by a professional person.
Connec�ng the ba�ery with a suitable cable is important for safe and efficient
opera�on of the system. To reduce the risk of injury, refer to Chart 3-2 for
recommended cables.
29.54
4. In case of children touch or insects go into the inverter, Please make sure the inverter
connector is fasten to waterproof posi�on by twist it clockwise.
- 09 -
3.3.2 Func�on port defini�on
Inverter
1 2 3 4 5 6 7 8 9 10 RS 485 CAN
- 10 -
3.3.3 Temperature sensor connec�on for lead-acid ba�ery
1 2
Temp. sensor
- 11 -
3.4 Grid connec�on and backup load connec�on
· Before connec�ng to grid, please install a separate AC breaker between inverter and grid. Also,
it is recommended that installs an AC breaker between backup load and inverter.This will ensure
the inverter can be securely disconnected during maintenance and fully protected from over
current. The recommended of AC breaker is 40A for 5kw and 63A for 8KW.
· There are three terminal blocks with "Grid" "Load"and "GEN" markings. Please do not misconnect
input and output connectors.
- 12 -
GRID
GEN PORT LOAD
(Region:EU)
L L L
N N N
(Region:US)
L1 L1 L1
N L2 N L2 N L2
GRID GEN PORT LOAD
- 13 -
Be sure that AC power source is disconnected before a�emp�ng to wire it to the
unit.
3. Then, insert AC output wires according to polari�es indicated on the terminal block and �ghten
terminal. Be sure to connect corresponding N wires and PE wires to related terminals as well.
4. Make sure the wires are securely connected.
5. Appliances such as air condi�oner are required at least 2-3 minutes to restart because it is
required to have enough �me to balance refrigerant gas inside of circuit. If a power shortage
occurs and recovers in short �me, it will cause damage to your connected appliances. To
prevent this kind of damage, please check manufacturer of air condi�oner if it is equipped with
�me-delay func�on before installa�on. Otherwise, this inverter will trigger overload fault and
cut off output to protect your appliance but some�mes it s�ll causes internal damage to the air
condi�oner
3.5 PV Connec�on
Before connec�ng to PV modules, please install a separately DC circuit breaker between
inverter and PV modules. It is very important for system safety and efficient opera�on to
use appropriate cable for PV module connec�on. To reduce risk of injury, please use the
proper recommended cable size as below.
2
Model Wire Size Cable(mm )
5/6/7.6/8KW 12AWG 4
To avoid any malfunc�on, do not connect any PV modules with possible current
leakage to the inverter. For example, grounded PV modules will cause current
leakage to the inverter. When using PV modules, please ensure the PV+ & PV- o
f solar panel is not connected to the system ground bar.
It is requested to use PV junc�on box with surge protec�on. Otherwise, it will
cause damage on inverter when lightning occurs on PV modules.
- 14 -
3.5.1 PV Module Selec�on:
When selec�ng proper PV modules, please be sure to consider below parameters:
1) Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of
inverter.
2) Open circuit Voltage (Voc) of PV modules should be higher than min. start voltage.
3) The PV modules used to connected to this inverter shall be Class A ra�ng cer�fied according
to lEC 61730.
Chart 3-5
- 15 -
3.6 CT Connec�on
N L N L N L
Inverter
N L
White wire Black wire
5 6
CT
5 CT
6 L
Arrow pointing
to inverter
N
Grid
The primary side of the CT
needs to be clamped on the
If the data read by the CT is wrong, you can try to point Grid live line.
the direction of the CT to the grid.
(Region:US)
Grid GEN Load
N L2 L1 N L2 L1 N L2 L1
Inverter
3
4
5
6 N L2 L1
White wire Black wire
3 4 5 6
CT2 CT
L2
Arrow pointing
CT1 to inverter
Grid
L1 The primary side of the CT
needs to be clamped on the
Grid live line.
If the data read by the CT is wrong, you can try to point
the direction of the CT to the grid.
N
- 16 -
3.6.1 Meter Connec�on
N L N L N L N L
Inverter
AC
Meter_CON Parallel_A Parallel_B Breaker
1 2 3 4
3 4
4
7 8
3
L N
DDSU666 DIN-RAIL METER
RS485A
230V 5(60) A 800imp/kWh
RS485B
1 2
5 6
N L N L N L N L
RS485
Inverter
AC
Meter_CON Parallel_A Parallel_B Breaker
2 4 5 6 7
1
230V/2T
230V/2T
Grid
L L
A B GND 5 6 7 8 9 10
N N
A B
3
GND 1+COM
4
2+
L N
5 6 7 8 9 10
A B GND 1+COM 2+
RS485A
3 4
RS485B
EASTRON SDM230 Pic 7.1 EASTRON meter
- 17 -
(Region:US)
Grid GEN Load
N L2 L1 N L2 L1 N L2 L1
N L2 L1
Inverter
AC
Breaker
Meter_CON Parallel_A Parallel_B
3 6 9 10
L1 RS485A
L2
Three-Phase Smart Meter
(1,4,7,10) L3 RS485B
(3,6,9,10)
SET ESC L1 L2
RS 485 3 6 9 10
24 25
1 4 7 10
SET ESC
24 25
1 4 7 10
L1
Grid L2
N
N L2 L1 N L2 L1 N L2 L1
N L2 L1
Inverter
AC
Breaker
Meter_CON Parallel_A Parallel_B
1 2 3 4 5 6 7 8
L1 RS485A
L2 L1
L2 L3
Eastron RS485B
L3 L2
L1
(1,2,3,4) (5,6,7,8) 8 7 6 5
B A G
5 6 7 8
RS 485
RS 485 B RS 485 A GND
Eastron
N
Grid L2
L1
- 18 -
Note:
When the inverter is in the off-grid state, the N line needs to be connected to the
earth.
Note:
In final installa�on,breaker cer�fied according to IEC 60947-1 and IEC 60947-2
shall be installed with the equipment.
- 19 -
3.9 Wiring System for Inverter (Region:EU)
AC Breaker
BMS L L
N N Load
PE PE
Battery Load
DC Breaker CT
Hybrid Inverter
AC Breaker AC Breaker
AC Breaker
L L
CT
N N Grid
Diesel
generator PE PE
Grid
E-BAR
E-BAR
L N PE
Home Loads
This diagram is an example for applica�on that Neutral connects together with
DC Breaker PE in distribu�on box.
Such as: Australia, New Zealand, South Africa, etc. (Please follow local wiring
PV regula�ons!)
AC Breaker
BMS L L
N N Load
PE or Do not connect this terminal PE
Battery Load
when the neutral wire and PE
wire are connected together.
DC Breaker CT
Hybrid Inverter
AC Breaker AC Breaker
AC Breaker
L L
CT
N N Grid
Diesel
PE PE
generator
Grid
N-BAR
E-N
Link
E-BAR
E-BAR
L N PE
Home Loads
- 20 -
PV
DC Breaker
(Region:US)
AC Breaker
BMS
L1 L1
L2 L2
N N Load
PE or PE
Battery
Load
DC Breaker
Hybrid Inverter CT AC Breaker AC Breaker
L1 L1
AC Breaker CT1
L2 L2
- 21 -
L1 CT2
L2 N N Grid
GEN
N PE PE
PORT PE Grid
E-N
LINK
E-BAR
E-BAR
L1 L2 N PE
Home Loads
3.10 Typical applica�on diagram of diesel generator
(Region:EU)
CAN L wire N wire PE wire
7 8
G S
Load
3
① DC Remotely control signal line
Breaker 2
Generator
Battery pack PE N L
L
N
PE
Backup Load
- 22 -
3.11 Single phase (230Vac) parallel connec�on diagram
(Region:EU) CAN L wire N wire PE wire
Inverter
No.3 Grid GEN Load
Parallel A Parallel B
(slave) N L N L N L
Ground
Inverter
④
① DC
Inverter Grid GEN Load
Breaker No.2 N L N L N L
⑤
(slave)
①②③ DC Breaker for battery
SUN 5K-SG-EU: 150A DC breaker
SUN 6K-SG-EU: 200A DC breaker
SUN 7.6K-SG-EU: 200A DC breaker
SUN 8K-SG-EU: 250A DC breaker
② DC ⑥
⑤⑦⑨ AC Breaker for grid port Breaker
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 40A AC breaker
SUN 8K-SG-EU: 63A AC breaker
④⑥⑧ AC Breaker for ⑦
backup load port
SUN 5K-SG-EU: 40A AC breaker
Inverter
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 63A AC breaker
No.1 Grid GEN Load
⑩ AC Breaker
Depends on Home Load
③ DC
Breaker ⑧
Battery pack ⑨
CT
⑩
The primary side of the CT
needs to be clamped on the Grid PE N L
Grid live line. L
Arrow pointing N
to inverter PE
Home Load
Master inverter Slave Inverter Slave Inverter Backup Load
Advanced Function Advanced Function Advanced Function
Parallel Modbus SN A Phase Parallel Modbus SN A Phase Parallel Modbus SN A Phase
- 23 -
3.12 Split phase (120/240Vac) parallel connec�on diagram
(Region:US) CAN L wire N wire PE wire
Ground
Inverter
① DC Inverter N L2 L1 N L2 L1 N L2 L1 ⑤ ④
Breaker No.2
Grid GEN Load
(slave)
①②③ DC Breaker for battery
SUN 5K-SG-EU: 150A DC breaker
SUN 6K-SG-EU: 200A DC breaker
SUN 7.6K-SG-EU: 200A DC breaker
SUN 8K-SG-EU: 250A DC breaker
② DC ⑥
⑤⑦⑨ AC Breaker for grid port Breaker
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 40A AC breaker
SUN 8K-SG-EU: 63A AC breaker
④⑥⑧ AC Breaker for ⑦
backup load port
SUN 5K-SG-EU: 40A AC breaker Inverter
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 63A AC breaker No.1 N L2 L1 N L2 L1 N L2 L1
SUN 8K-SG-EU: 63A AC breaker
(master)
⑩ AC Breaker Grid GEN Load
③ DC
Breaker ⑧
Battery pack
⑨
CT CT2
CT1
The primary side of the CT Grid ⑩ AC
needs to be clamped on the PE N L2 L1 Breaker
Grid live line.
L1
Arrow pointing L2
to inverter N
PE
Home Load
Master inverter Slave Inverter Slave Inverter Backup Load
Advanced Function Advanced Function Advanced Function
Parallel Modbus SN A Phase Parallel Modbus SN A Phase Parallel Modbus SN A Phase
- 24 -
(Region:EU) CAN L wire N wire PE wire
Inverter
No.3 Grid GEN Load
Parallel A Parallel B
(slave) N L N L N L
Ground
Inverter
④
① DC
Inverter Grid GEN Load
Breaker No.2 N L N L N L
⑤
(slave)
①②③ DC Breaker for battery
SUN 5K-SG-EU: 150A DC breaker
SUN 6K-SG-EU: 200A DC breaker
SUN 7.6K-SG-EU: 200A DC breaker
SUN 8K-SG-EU: 250A DC breaker
② DC ⑥
⑤⑦⑨ AC Breaker for GEN port Breaker
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 40A AC breaker
SUN 8K-SG-EU: 63A AC breaker
⑦
④⑥⑧ AC Breaker for
backup load port Inverter
SUN 5K-SG-EU: 40A AC breaker No.1 Grid GEN Load
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 63A AC breaker (master) N L N L N L
③ DC
Breaker ⑧
Battery pack ⑨
Generator
PE N L
L
N
PE
- 25 -
CAN L wire N wire PE wire
Parallel A Parallel B
⑥ AC Breaker
Grid GEN Load Grid GEN Load Grid GEN Load
CAN/RS 485
④ AC Breaker for backup load port
Ground
① DC ② DC ③ DC
Breaker Breaker Breaker
④ AC Breaker
L3
L2
Battery pack L1
N
PE
⑤ AC Breaker
- 26 -
Home load
⑥ AC Breaker
3.13 Parallel connec�on for 230/400 three phase
CT1
E-BAR
CT2 CT A Phase Master inverter B Phase Master inverter C Phase Master inverter
CT3 Advanced Function Advanced Function Advanced Function
L1
Parallel Modbus SN A Phase Parallel Modbus SN A Phase Parallel Modbus SN A Phase
L2
Master 01 B Phase Master 02 B Phase Master 03 B Phase
L3 Paral. Paral. Paral.
N Slave C Phase Set3 Slave C Phase Set3 Slave C Phase Set3
PE
Arrow pointing
to inverter
Grid
①② DC Breaker for battery
SUN 5K-SG-EU: 150A DC breaker
SUN 6K-SG-EU: 200A DC breaker
SUN 7.6K-SG-EU: 200A DC breaker
Parallel A Parallel B N L2 L1 N L2' L1' SUN 8K-SG-EU: 250A DC breaker
③ AC Breaker for backup load port
Inverter No.1(master) Inverter No.2(master) SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 63A AC breaker
SUN 8K-SG-EU: 63A AC breaker
Grid GEN Load Grid GEN Load ④ AC Breaker for grid port
SUN 5K-SG-EU: 40A AC breaker
SUN 6K-SG-EU: 40A AC breaker
SUN 7.6K-SG-EU: 40A AC breaker
SUN 8K-SG-EU: 63A AC breaker
⑤ AC Breaker
CAN/RS 485 Depends on Home Load
Ground
Parallel communication cable
① DC ② DC
Breaker Breaker
③ AC Breaker
Battery pack L1(L1)
L2(L1' L2)
L3(L2')
- 27 -
N
PE
④ AC Breaker
Home load
⑤ AC Breaker
3.14 pcs Parallel connec�on for 120/208 three phase
backup Load
CT1
N-BAR
CT2
CT3
E-BAR
L1(L1) CT
L2(L1' L2) A Phase Master inverter B Phase Master inverter
L3( L2') Advanced Function Advanced Function
N
PE Parallel Modbus SN A Phase Parallel Modbus SN A Phase
① DC ② DC ③ DC
Breaker Breaker Breaker
④ AC Breaker
Battery pack L1(L1 L2'')
L2(L1' L2 )
L3(L1'' L2')
- 28 -
N
PE
⑤ AC Breaker
Home load
3.15 Parallel connec�on for 120/208 three phase
⑥ AC Breaker
backup Load
CT1
N-BAR
CT2
CT3 E-BAR
L1(L1 L2'') *CT
L2(L1' L2 ) A Phase Master inverter B Phase Master inverter C Phase Master inverter
L3(L1'' L2') Advanced Function Advanced Function Advanced Function
N
PE Parallel Modbus SN A Phase Parallel Modbus SN A Phase Parallel Modbus SN A Phase
N L N L N L N L N L N L N L N L N L
CAN/RS 485
Ground
① DC ② DC ③ DC
Breaker Breaker Breaker
④ AC Breaker
L3
L2
Battery pack L1
N
- 29 -
PE
⑤ AC Breaker
E-BAR
A Phase Master inverter B Phase Master inverter C Phase Master inverter
Advanced Function Advanced Function Advanced Function
L1
Parallel Modbus SN A Phase Parallel Modbus SN A Phase Parallel Modbus SN A Phase
L2
Master 01 B Phase Master 02 B Phase Master 03 B Phase
L3 Paral. Paral. Paral.
N Slave C Phase Set3 Slave C Phase Set3 Slave C Phase Set3
PE
Generator
4. OPERATION
4.1 Power ON/OFF
Once the unit has been properly installed and the ba�eries are connected well, simply press
On/Off bu�on(located on the le� side of the case) to turn on the unit. When system without
ba�ery connected, but connect with either PV or grid, and ON/OFF bu�on is switched off, LCD
will s�ll light up(Display will show OFF), In this condi�on, when switch on ON/OFF bu�on and
select NO ba�ery,system can s�ll working.
Up To go to previous selec�on
- 30 -
5. LCD Display Icons
5.1 Main Screen
The LCD is touchscreen, below screen shows the overall informa�on of the inverter.
05/28/2019 15:34:40
0 8.30 12 0 -3.00 8
KW KW
ON
25%
0 -2.00
KW
8 0 3.00
KW
8
1.The icon in the center of the home screen indicates that the system is Normal opera�on. If it
turns into "comm./F01~F64" , it means the inverter has communica�on errors or other errors,
the error message will display under this icon(F01-F64 errors, detail error info can be viewed in
the System Alarms menu).
3.System Setup Icon, Press this set bu�on,you can enter into the system setup screen which
including Basic Setup, Ba�ery Setup, Grid Setup, System Work Mode, Generator port use,
Advanced func�on and Li-Ba� info.
4.The main screen showing the info including Solar, Grid, Load and Ba�ery. Its also displaying the
energy flow direc�on by arrow. When the power is approximate to high level, the color on the
panels will changing from green to red so system info showing vividly on the main screen.
- 31 -
5.1.1 LCD opera�on flow chart
Inverter Page
Main Screen
Battery Page BMS Page
Battery Setting
Grid Setting
System Setup
Gen Port Use
Basic Setting
Advanced Function
Device info
- 32 -
5.2 Solar Power Curve
Energy Press the “Energy “bu�on will enter into the power
curve page.
Energy
Energy Press the “Energy “ bu�on will enter into the power
curve page.
- 33 -
Li-BMS
U:50.50V
I:-58.02A
Li-BMS
Power: -2930W Volt Curr Temp SOC Energy Charge Fault
Volt Curr
1 50.38V 19.70A 30.6C 52.0% 26.0Ah 0.0V 0.0A 0|0|0
Temp:30.0C
Li-BMS
2 50.33V 19.10A 31.0C 51.0% 25.5Ah 53.2V 25.0A 0|0|0
3 50.30V 16.90A 30.2C 12.0% 6.0Ah 53.2V 25.0A 0|0|0
Sum
4 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
5 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
6 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
7 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
8 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
This is Ba�ery detail page. 9 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
10 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Details
11 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
if you use Lithium Ba�ery, you can enter BMS page. 12
13
0.00V
0.00V
0.00A
0.00A
0.0C
0.0C
0.0%
0.0%
0.0Ah
0.0Ah
0.0V
0.0V
0.0A
0.0A
0|0|0
0|0|0
14 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
15 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
CANCEL Day Month Year Total CANCEL Day Month Year Total
CANCEL Day Month Year Total CANCEL Day Month Year Total
Solar power curve for daily, monthly, yearly and total can be roughly checked on the LCD, for more
accuracy power genera�on, pls check on the monitoring system. Click the up and down arrow to
check power curve of different period.
- 34 -
5.4 System Setup Menu
System Setup
This is System Setup page.
Basic Advanced
Setting Function Device Info.
Basic Setting
Factory Reset: Reset all parameters of the inverter.
Time Syncs Beep Auto Dim Lock out all changes: Enable this menu for se�ng
Year Month Day Basic parameters that require locking and cannot be set up.
2019 03 17
Set Before performing a successful factory reset and locking
the systems, to keep all changes you need to type in a
Hour Minute password to enable the se�ng.
24-Hour 09 15 The password for factory se�ngs is 9999 and for lock
out is 7777.
Factory Reset Lock out all changes
PassWord
Factory Reset PassWork: 9999
X--X--X--X DEL
Lock out all changes PassWork: 7777
1 2 3
System selfchek: A�er �cking this item,
4 5 6 it needs input the password.
The default password is 1234
7 8 9
CANCEL 0 OK
- 35 -
5.6 Ba�ery Setup Menu
Battery Setting
Ba�ery capacity: it tells Deye hybrid inverter to know
Batt Mode your ba�ery bank size.
Lithium Batt Capacity 400Ah
Batt
Use Ba� V: Use Ba�ery Voltage for all the se�ngs (V).
Use Batt V Max A Charge 40A
Mode Use Ba� %: Use Ba�ery SOC for all the se�ngs (%).
Use Batt % Max A Discharge 40A Max. A charge/discharge: Max ba�ery charge/discharge
No Batt
current(0-115A for 5KW model, 0-90A for 3.6KW model).
Activate Battery
For AGM and Flooded, we recommend Ah ba�ery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah ba�ery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instruc�ons.
No Ba�: �ck this item if no ba�ery is connected
to the system.
Ac�ve ba�ery: This feature will help recover a
ba�ery that is over discharged by slowly charging
from the solar array or grid.
0 2.00 7 0 0.00 5
KW KW
ON
76% Signal
on
0 -1.39
KW
5 0 2.00
KW 5
- 36 -
Generator
This page tells generator output voltage, frequency,
Power: 1392W Today=0.0 KWH power. And, how much energy is used from generator.
Total =2.20 KWH
L1: 228V
Freq:50.0Hz
Battery Setting
Lithium Mode: This is BMS protocol.Please reference
the document(Approved Ba�ery).
Lithium Mode 00
Shutdown 10%: It indicates the inverter will shutdown
Batt
Shutdown 10% Set3 if the SOC below this value.
Low Ba� 20%: It indicates the inverter will alarm if the
Low Batt 20%
SOC below this value.
Restart 40% Restart 40%: Ba�ery voltage at 40% AC output will
resume.
- 37-
5.7 System Work Mode Setup Menu
System Work Mode Work Mode
Selling First: This Mode allows hybrid inverter to sell
Selling First 8000 Max Solar Power back any excess power produced by the solar panels to
Zero Export To Load Solar Sell
Work the grid. If �me of use is ac�ve, the ba�ery energy also
Mode1
can be sold into grid.
Zero Export To CT Solar Sell The PV energy will be used to power the load and charge
the ba�ery and then excess energy will flow to grid.
Max Sell Power 8000 Zero-export Power 20
Power source priority for the load is as follows:
Energy pattern BattFirst LoadFirst 1. Solar Panels.
Grid Peak Shaving 8000 Power 2. Grid.
3. Ba�eries (un�l programable % discharge is reached).
Zero Export To Load: Hybrid inverter will only provide power to the backup load connected. The hybrid
inverter will neither provide power to the home load nor sell power to grid. The built-in CT will detect
power flowing back to the grid and will reduce the power of the inverter only to supply the local load and
charge the ba�ery.
Battery
Zero Export To CT: Hybrid inverter will not only provide power to the backup load connected but also give
power to the home load connected. If PV power and ba�ery power is insufficient, it will take grid energy
as supplement. The hybrid inverter will not sell power to grid. In this mode, a CT is needed. The installa�on
method of the CT please refer to chapter 3.6 CT Connec�on. The external CT will detect power flowing back
to the grid and will reduce the power of the inverter only to supply the local load, charge ba�ery and home
load.
CT
Battery
- 38 -
Solar Sell: “Solar sell” is for Zero export to load or Zero export to CT: when this item is ac�ve, the surplus
energy can be sold back to grid. When it is ac�ve, PV Power source priority usage is as follows: load
consump�on and charge ba�ery and feed into grid.
Max. sell power: Allowed the maximum output power to flow to grid.
Zero-export Power: for zero-export mode, it tells the grid output power. Recommend to set it as 20-100W
to ensure the hybrid inverter won' t feed power to grid.
Energy Pa�ern: PV Power source priority.
Ba� First: PV power is firstly used to charge the ba�ery and then used to power the load. If PV power is
insufficient, grid will make supplement for ba�ery and load simultaneously.
Load First: PV power is firstly used to power the load and then used to charge the ba�ery. If PV power is
insufficient, grid will make supplement for ba�ery and load simultaneously.
Max Solar Power: allowed the maximum DC input power.
Grid Peak-shaving: when it is ac�ve, grid output power will be limited within the set value. If the load
power exceeds the allowed value, it will take PV energy and ba�ery as supplement. If s�ll can’t meet the
load requirement, grid power will increase to meet the load needs.
System Work Mode Time of use: it is used to program when to use grid or
Grid
generator to charge the ba�ery, and when to discharge
Time Of Use
Charge Gen
the ba�ery to power the load. Only �ck "Time Of Use"
Time Power Batt
Work then the follow items (Grid, charge, �me, power etc.)
01:00 5:00 8000 49.0V Mode2 will take effect.
05:00 9:00 8000 50.2V Note: when in selling first mode and click �me of use,
the ba�ery power can be sold into grid.
09:00 13:00 8000 50.9V Grid charge: u�lize grid to charge the ba�ery in a �me
13:00 17:00 8000 51.4V period.
17:00 21:00 8000 47.1V
Gen charge: u�lize diesel generator to charge the ba�ery
in a �me period.
21:00 01:00 8000 49.0V Time: real �me, range of 01:00-24:00.
Power: Max. discharge power of ba�ery allowed.
Ba�(V or SOC %): ba�ery SOC % or voltage at when the
ac�on is to happen.
For example:
System Work Mode
During 01:00-05:00, when ba�ery SOC is lower than 80%, it will
Grid Time Of Use
use grid to charge the ba�ery un�l ba�ery SOC reaches 80%.
Charge Gen Time Power Batt During 05:00-08:00 and 08:00-10:00, when ba�ery SOC is higher
Work
01:00 5:00 8000 80% Mode2
than 40%, hybrid inverter will discharge the ba�ery un�l the SOC
reaches 40%.
05:00 8:00 8000 40%
During 10:00-15:00, when ba�ery SOC is higher than 80%, hybrid
08:00 10:00 8000 40% inverter will discharge the ba�ery un�l the SOC reaches 80%.
10:00 15:00 8000 80% During 15:00-18:00, when ba�ery SOC is higher than 40%, hybrid
15:00 18:00 8000 40% inverter will discharge the ba�ery un�l the SOC reaches 40%.
18:00 01:00 8000 35% During 18:00-01:00, when ba�ery SOC is higher than 35%, hybrid
inverter will discharge the ba�ery un�l the SOC reaches 35%.
- 39 -
5.8 Grid Setup Menu
Grid Setting
Please select the correct Grid Mode in your local area.
Grid Mode General Standard
If you are not sure, please choose General Standard.
UL1741& IEEE1547
Grid
CPUC RULE21 Set1 Please select the correct Grid Type in your local area,
SRD-UL-1741 otherwise the machine will not work or be damaged.
Grid Type 220V Single Phase
120/240V Split Phase
120/208V 3 Phase
120V Single Phase
Grid Setting
For California only.
Q(V) FW VW
Grid Setting
For California only.
L/HVRT L/HFRT
- 40-
GEN PORT USE Generator input rated power: allowed Max. power from diesel
generator.
Mode AC couple on grid side
GEN connect to grid input: connect the diesel generator to the
Generator Input
AC couple on load side grid input port.
Rated Power PORT
Set1
Smart Load Output: This mode u�lizes the Gen input connec�on
8000W GEN connect to Grid input
as an output which only receives power when the ba�ery SOC
SmartLoad Output On Grid always on and PV power is above a user programmable threshold.
Power AC Couple Fre High e.g. Power=500W, ON: 100%, OFF=95%: When the PV power
500W 52.00Hz exceeds 500W, and ba�ery bank SOC reaches 100%, Smart Load
OFF 95%
Port will switch on automa�cally and power the load connected.
Micro Inv Input ON 100% When the ba�ery bank SOC < 95% or PV power < 500w, the
Smart Load Port will switch off automa�cally.
- 41 -
Advanced Function Solar Arc Fault ON: This is only for US.
Solar Arc Fault ON Backup Delay
System selfcheck: Disable. this is only for factory.
0ms
Gen Peak-shaving: Enable When the power of the
Clear Arc_Fault Func generator exceeds the rated value of it, the inverter will
Set1 provide the redundant part to ensure that the generator
System selfcheck Gen peak-shaving will not overload.
DRM: For AS4777 standard
DRM CT Ratio
Backup Delay: (0-300)S adjustable
Signal ISLAND MODE
2000:1
BMS_Err_Stop: When it is ac�ve, if the ba�ery BMS failed
to communicate with inverter, the inverter will stop
BMS_Err_Stop working and report fault.
Signal island mode: when the inverter connects grid,
the ATS port will output 230Vac and it is used to cuts off
Inverter Earth-Neutral(load port N line) bond via connect external
load port relay. When the inverter disconnects from the grid, ATS
shell port voltage will be 0 and the Earth-Neutral bond keeps
L N ATS on. More details, please refer to le� picture.
Ground cable
230V
external relay
coil
closed
contact
Advanced Function
Ex_Meter For CT: when in Three phase system with CHNT
Parallel Modbus SN
A Phase Three phase energy meter (DTSU666), click corresponding
Master 00 B Phase phase where hybrid inverter is connected. e.g. when the
Paral.
Slave C Phase Set3
hybrid inverter output connects to A phase, please click A
Phase.
Ex_Meter For CT
A Phase
B Phase
C Phase
- 42 -
5.9 Device Info Setup Menu
Li-BMS
Device Info.
Volt Inverter
Curr Temp SOCID: 1601012001
Energy Charge Flash
Fault
This page show Inverter ID, Inverter version and alarm
HMI: Ver0302 MAIN:VerVolt
0-5213-0717
Curr codes.
1 50.38V 19.70A 30.6C 52.0% 26.0Ah 0.0V 0.0A 0|0|0
Alarms Code31.0C 51.0% 25.5Ah
Occurred
2 50.33V 19.10A 53.2V 25.0A 0|0|0 Device
Sum
3 F64 Heatsink_HighTemp_Fault
50.30V 16.90A 30.2C 12.0% 6.0Ah2019-03-11 15:56
53.2V 25.0A 0|0|0
4 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
Info
Data
5 F64 Heatsink_HighTemp_Fault
0.0Ah2019-03-08
0.0A 10:46
0.00V
0.00V
6 F64
0.00A
0.00A
0.0C
0.0C
0.0%
0.0%
0.0V
0.0Ah2019-03-08
Heatsink_HighTemp_Fault 0.0V
0|0|0
0.0A 10:45
0|0|0 HMI: LCD version
7 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
8 0.00V 0.00A
9 0.00V 0.00A
0.0C
0.0C
0.0%
0.0%
0.0Ah
0.0Ah
0.0V
0.0V
0.0A 0|0|0
0.0A 0|0|0
MAIN: Control board FW version
10 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Details
11 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
12 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
13 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
14 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
15 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
6. Mode
Mode I:Basic
AC cable DC cable COM cable
Solar
CT
Battery
Grid
AC cable DC cable
Grid
CT
Battery
Generator
- 43 -
Mode III: With Smart-Load
AC cable DC cable
Grid
CT
Battery
Smart Load
CT Grid
Solar
Backup Load
Battery
On-Grid Inverter
Solar
Battery
CT
Smart Load Grid
- 44 -
On-Grid+AC couple AC cable DC cable
Backup Load
Solar
Battery
CT
Smart Load Grid
The 1st priority power of the system is always the PV power, then 2nd and
3rd priority power will be the ba�ery bank or grid according to the se�ngs.
The last power backup will be the Generator if it is available.
If any of the fault messages listed in Table 7-1 appear on your inverter and the
fault has not been removed a�er restar�ng, please contact your local dealer or
service center. You need to have the following informa�on ready.
- 45 -
Error code Description Solutions
1. When the grid type and frequency changed it will report F13;
2. When the battery mode was changed to “No battery” mode,
it will report F13;
3. For some old FW version, it will report F13 when the system
F13 Working mode change work mode changed;
4, Generally, it will disappear automatically when shows F13;
5. If still same, and turn off the DC switch and AC switch and
wait for one minute and then turn on the DC/AC switch;
6. Seek help from us, if can not go back to normal state.
AC side over current fault
1. Please check whether the backup load power and common
AC over current fault
F18 load power are within the range;
of hardware 2. Restart and check whether it is in normal;
3. Seek help from us, if can not go back to normal state.
DC side over current fault
1. Check PV module connect and battery connect;
2. When in the off-grid mode, the inverter startup with big power
F20 DC over current fault of load, it may report F20. Please reduce the load power connected;
the hardware 3. Turn off the DC switch and AC switch and then wait one
minute,then turn on the DC/AC switch again;
4. Seek help from us, if can not go back to normal state.
- 46 -
Error code Description Solutions
No Utility
1. Please confirm grid is lost or not;
F35 No AC grid 2. Check the grid connection is good or not;
3. Check the switch between inverter and grid is on or not;
4. Seek help from us, if can not go back to normal state.
1. Check the hybrid inverter working status. If there's 1 pcs
hybrid inverter is in OFF status, the other hybrid inverters
F41 Parallel system stop may report F41 fault in parallel system.
2. If the fault still exists, please contact us for help.
Grid voltage fault
1. Check the AC voltage is in the range of standard voltage in
specification;
F42 AC line low voltage
2. Check whether grid AC cables are firmly and correctly
connected;
3. Seek help from us, if can not go back to normal state.
- 47 -
Under the guidance of our company, customers return our products so that our company can
provide service of maintenance or replacement of products of the same value. Customers need to
pay the necessary freight and other related costs. Any replacement or repair of the product will
cover the remaining warranty period of the product. If any part of the product or product is
replaced by the company itself during the warranty period, all rights and interests of the
replacement product or component belong to the company.
Factory warranty does not include damage due to the following reasons:
· Damage during transporta�on of equipment;
· Damage caused by incorrect installa�on or commissioning;
· Damage caused by failure to comply with opera�on instruc�ons, installa�on instruc�ons or
maintenance instruc�ons;
· Damage caused by a�empts to modify, alter or repair products;
· Damage caused by incorrect use or opera�on;
· Damage caused by insufficient ven�la�on of equipment;
· Damage caused by failure to comply with applicable safety standards or regula�ons;
· Damage caused by natural disasters or force majeure (e.g. floods, lightning, overvoltage, storms,
fires, etc.)
In addi�on, normal wear or any other failure will not affect the basic opera�on of the product.
Any external scratches, stains or natural mechanical wear does not represent a defect in the
product.
8.Limita�on of Liability
In addi�on to the product warranty described above, the state and local laws and regula�ons
provide financial compensa�on for the product's power connec�on (including viola�on of implied
terms and warran�es). The company hereby declares that the terms and condi�ons of the
product and the policy cannot and can only legally exclude all liability within a limited scope.
- 48 -
9. Datasheet
Model SUN-5K-SG01LP1 SUN-6K-SG01LP1 SUN-7.6K-SG01LP1 SUN-8K-SG01LP1
-US -US -US/EU -US/EU
Battery Input Date
Ba�ery Type Lead-acid or Li-lon
Ba�ery Voltage Range(V) 40-60V
Max. Charging Current(A) 120A 135A 190A 190A
Max. Discharging Current(A) 120A 135A 190A 190A
Charging Curve 3 Stages / Equaliza�on
External Temperature Sensor yes
Charging Strategy for Li-lon Ba�ery Self-adap�on to BMS
PV String Input Data
Max. DC Input Power(W) 6500W 7800W 9880W 10400W
PV Input Voltage(V) 370V (125V~500V)
MPPT Range(V) 150~425V
Start-up Voltage(V) 125V
PV Input Current(A) 11A+11A 22A+11A 22A+22A 22A+22A
Max.PV Isc(A) 16.5A+16.5A 28A+16.5A 28A+28A 28A+28A
No. of MPPT Trackers 2
No. of Strings Per MPPT Tracker 1+1 2+1 2+2 2+2
AC Output Data
Rated AC Output and UPS Power(W) 5000 6000 7600 8000
Max. AC Output Power(W) 5500 6600 8360 8800
Peak Power(off grid) 2 �mes of rated power, 10 S
AC Output Rated Current(A) 20.8/24A 25/28.8A 31.6/36.5A 34.5 33.3/38.5A 36.4
Max. AC Current(A) 22.9/26.4A 27.5/31.7A 34.8/40.2A 38 36.7/42.3A 40
Max. Con�nuous AC Passthrough(A) 40A 40A 50A 50A
Power Factor 0.8 leading to 0.8 lagging
50 / 60Hz; 120 / 240Vac (split phase), 208Vac (2 / 3 phase),
Output Frequency and Voltage
220/230Vac (single phase)
Grid Type Split phase; 2 / 3 phase; Single Phase
Current Harmonic Distor�on THD<3% (Linear load<1.5%)
Efficiency
Max. Efficiency 97.60%
Euro Efficiency 97.00%
MPPT Efficiency >99%
Protection
PV Arc Fault Detec�on Integrated
PV Input Lightning Protec�on Integrated
An�-islanding Protec�on Integrated
PV String Input Reverse Polarity Protec�on Integrated
Insula�on Resistor Detec�on Integrated
Residual Current Monitoring Unit Integrated
Output Over Current Protec�on Integrated
Output Shorted Protec�on Integrated
Surge Protec�on DC Type II / AC Type III
- 49 -
Model SUN-5K-SG01LP1 SUN-6K-SG01LP1 SUN-7.6K-SG01LP1 SUN-8K-SG01LP1
-US -US -US/EU -US/EU
Certifications and Standards
CEI 0-21,VDE-AR-N 4105,NRS 097,IEC 62116,IEC 61727,G99,G98,
Grid Regula�on
VDE 0126-1-1,RD 1699,C10-11
IEC/EN 62109-1,IEC/EN 62109-2,IEC/EN 61000-6-1,
EMC / Safety Regula�on
IEC/EN 61000-6-2,IEC/EN 61000-6-3,IEC/EN 61000-6-4
General Data
Opera�ng Temperature Range(℃) -40~60℃, >45℃ Dera�ng
Cooling Smart cooling
Noise(dB) <30 dB
Communica�on with BMS RS485; CAN
Weight(kg) 30
Size(mm) 445W×708H×233D
Protec�on Degree IP65
Installa�on Style Wall-mounted
Warranty 5 years
- 50 -
10. Appendix I
Defini�on of RJ45 Port Pin for BMS
1 RS485 --
2 Meter_CON GND
3 GND --
4 CANH
321
87654
5 CANL
6 GND --
7 RS485A --
8 RS485B --
RS485 Port
CAN Port
- 51 -
Meter_CON port
This port is used to connect the energy meter.
Note: some hardware versions hybrid inverter don't support conenc�ng the energy meter
12345678
321
87654
RS232
No. WIFI/RS232
1
2 TX
3 RX
5 4 3 2 1
4 9 8 7 6
5 D-GND
6
7 WIFI/RS232
8
This RS232 port is used to connect the wifi datalogger
9 12Vdc
- 52 -
11. Appendix II
1. Split Core Current Transformer (CT) dimension: (mm)
2. Secondary output cable length is 4m.
Lead Outside