2019 Summer Model Answer Paper (Msbte Study Resources)
2019 Summer Model Answer Paper (Msbte Study Resources)
2019 Summer Model Answer Paper (Msbte Study Resources)
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
1 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 Marks
2)Generator Reactor:
1 Mark
3)Feeder Reactor:
2 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
1 Mark
1 b) i) Fig. No. 1 shows single line diagram of three phase system.The percentage reactance
of each alternator is based on its own capacity. Find short circuit current that will flow
into a complete three phase short circuit at „A‟ „F‟.
3 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
Ans:
1 Mark
(NOTE: Since data regarding line voltage is not specified, Examiners are
requested to award the marks appropriately to the examinee who has attempted
to solve the problem. Here the line voltage is assumed as 11 kV and point ‘A’ is
not specified so fault at F is considered for the calculation of reactance as per
assumed base kVA)
Now assume base kVA = 5000 kVA
% Reactance related to base kVA
% X = (Base kVA / Rated kVA) x % Reactance on Rated kVA
XA = (5000/2000) x 10%
= 50 % 1 Mark
XB = (5000/5000) x 50%
= 50 % 1 Mark
For Fault at Bus
Total reactance ,
% X = XA || XB
= 50 || 50 1 Mark
% X = 25%
Rated current at base kVA = I = (5000 x 1000) / (√3 x 11 x 1000)
I = 262.431 amp 1 Mark
ISC = I x (100/% X) = 262.431 x (100/25)
ISC = 1049.724amp 1 Mark
1 b) ii) Draw the circuit diagram of biased differential protection of ∆/λ transformer.
Ans:
Biased Differential Protection of ∆/λ Transformer:
Labeled
diagram
6 Marks
Partially
Labeled
diagram
4 Marks
Un-Labeled
diagram
3 Marks
OR Equivalent Diagram
4 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 a) Define:
i) Arcing time
ii) Recovery time
iii) Arcing voltage
iv) Rate of rise of restriking voltage
Ans:
i) Arcing time: It is the time measured from the instant of occurrence of cut off (or
commencement of arc) to the instant at which arc is extinguished.
ii) Recovery time: The time required for piece of equipment to resume its usual 1 Mark for
condition following an action, such as the passage of a current through electrical each
equipment. definition
iii) Arcing Voltage: The voltage existing between the circuit breaker contacts during = 4 Marks
arcing is called as the arc voltage.
iv) Rate of Rise of Restriking Voltage: The RRRV (Rate of Rise of the Restriking
Voltage) is defined as the slope of the steepest tangent to the restriking voltage
curve. It is expressed in volts per micro-second.
Labeled
diagram
4 Marks
Partially
Labeled
diagram
3 Marks
Un-Labeled
diagram
2 Marks
2 c) Explain basic principle of lightning arrestor and enlist different types of lightning.
Ans:
Basic Principle of Lightning Arrestor:
1 Mark for
Diagram
5 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
Lightning arrestor (LA) consists of spark gap in series with a nonlinear resistor. The
line/equipment to be protected is connected to one end of LA and other end of LA is 2 Marks for
solidly grounded to earth. The length of spark gap is set such that normal working Explanation
voltage is not sufficient to break the gap. The nonlinear resistor provides very high
resistance for working voltage and offers very low resistance for high voltages.
Under normal working condition the gap does not break and nonlinear resistor offer
very high resistance so there is no path for current from line to ground. But when
lightning stroke/surge appears on the line/equipment then the spark gap breaks with the
nonlinear resistor offering very low resistance value. Thus ultimately the lightning
stroke is diverted to earth instead of entering the equipment and the equipment is
protected.
Types of lighting: 1 Mark for
1) Direct Lightning Stroke types
2) Indirect Lightning Stroke
2 d) Give any four differences between equipment earthing and neutral earthing.
Ans:
Difference between Equipment Earthing and Neutral Earthing:
Sr.
Equipment Earthing Neutral Earthing
No.
6 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
4 Marks
Consider the above circuit in which the current flowing through MCB is sum of load
current and fault current. If fault path resistance is less, the current flowing through the
MCB may exceeds the limit i.e rated value of 5 A and the MCB will trip.
Consider a second case where the earth fault is through highly resistive path. So the
fault current may be very less and total current flowing through MCB will be within
the limit. Hence, even under earth fault condition, the MCB will not trip.
7 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 f) List the difficulties experienced in differential relay in alternator protection. How are
they overcome?
Ans:
Difficulties Experienced in Differential Relay in Alternator Protection:
8 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
3 c) With a neat diagram explain the working of static over current relay.
Ans:
Static Over Current Relay:
2 Marks for
diagram
The current derived from the main CT is feed to the input transformer, which gives a
proportional output voltage. The input transformer has an air gap in the iron core to
give linearity in the current voltage relationship up to the highest value of current
expected and is provided with taping on its secondary to obtain different current
settings. The output voltage is then rectified and then filtered at a single stage to avoid
undesirable time delay in filtering so as to excurse high speed of operation. A zener 2 Marks for
diode is also incorporated in the circuit to limit the rectified voltage to safe value even Explanation
when the input current is very high under fault conditions.
A fixed portion of the rectified filtered voltage is compared against a preset pick-up
value by a level detector and if it exceeds the pick-up value, a signal through an
amplifier is given to the output device, which issues the trip signal.
9 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 Marks for
Diagram
The relay is located in the path of the oil from transformer tank to conservator. As
seen from diagram, the upper mercury switch operates the alarm circuit due to tilting of
the float by accumulation of gas evolved slowly in the transformer tank due to minor
faults, which may develop into major ones if the alarm is not investigated.
Further lower mercury switch operates the trip circuit to switch off the circuit breaker 2 Marks for
related to the transformer when there is a sudden flow or rush of oil from the Description
transformer tank to conservator. Such flow occurs when there is serious fault in the
transformer tank. Here the float (lower) is placed in such a manner that it senses the
sudden violent movement of oil from transformer tank to conservator.
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
4 a) i) Draw a neat labeled diagram of Merz Price protection scheme for an alternator.
Ans:
Merz Price Protection of Alternator:
Labeled
diagram
4 Marks
Partially
Labeled
diagram
3 Marks
Un-Labeled
diagram
2 Marks
2 Marks for
Diagram
When the line voltage is normal, the air gap assembly does not break down. When a
lighting stroke occurs the series spark gap breaks down providing the earth path for the
2 Marks for
surge current through the nonlinear resistors, which offer a low resistance to surge
Explanation
current and again regain back high value after the surge gets conducted to earth.
11 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 Marks for
Diagram
OR Equivalent Answer
4 a) iv) Explain time graded over current protection for ring main system of busbar.
Ans:
Time Graded Over Current Protection for Ring Main System of Bus Bar:
The ring main consists of various generating stations and substations interconnected by
alternate routes. When the fault occurs in any section of the ring, that section can be 2 Mark for
disconnected for repairs and power is supplied from both ends of ring, maintaining the Explanation
continuity of supply.
Figure represents the single line diagram of a typical ring main system, which consists
of a generator and four sub-stations S1, S2, S3, S4. As the power can flow in both the
directions under fault conditions, it is necessary to grade feeder protection in both
directions round the ring with directional relays.
12 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
In order to ensure selectivity, the circuit breakers at E & F should open to clear the
2 Marks for
diagram
fault, there by maintaining other section intact. Actually the power is fed to the fault
via two routes i.e. (i) From G around S1, S2 and (ii) from G around S4 and S3. The
relays at A, B, C and D as well as J, I, H and G do not trip. Therefore, only relays at E
and F operate before any other relay operates.
4 b) i) Explain what is single phasing of 3ϕ I.M? Draw a neat circuit diagram of single phase
preventer.
Ans:
Single Phasing of 3ϕ I.M :
When one of the supply lines of the three phase supply connection gets disconnected
then this situation is known as single phasing. Under this condition, motor continues to 3 Marks
operate on two-phase supply. If the motor is loaded to its rated full load, it will draw
excessive current on single phasing. Single phasing may cause extreme magnetic
unbalance, reduction in torque and over- heating due to negative phase sequence
current. This condition may cause damage to the motor. Hence protection against
single phasing is necessary.
Single Phase Preventer:
3 Marks
13 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
3 Marks for
Diagram
2 Marks for
Diagram
Working:
Under normal conditions, the fuse element is at a temperature below its melting point.
Therefore, it carries the normal current without overheating.
When a fault occurs, the current increases and the heat produced is sufficient to melt 1 Mark for
Working
14 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
these elements. Fuse element melts before the fault current reaches its first peak value.
Vaporized metal /fuse element chemically reacts with filling powder and results in the
formation of high resistance substance that helps in quenching the arc.
5 b) State methods for arc extinction and explain working of any one method with neat
circuit diagram.
Ans:
Methods for Arc Extinction:
There are two methods of arc extinction: 1 Mark for
i) High resistance extinction method two methods
ii) Low resistance or Zero current extinction method
High Resistance Arc Extinction Method:
In this method, the arc is so controlled that its effective resistance increases with time so
that the current reduces to a value insufficient to maintain the arc. The currents tends to
be in phase with the voltage so that at zero current instant, the restriking voltage
appearing across the contacts is relatively low and arc cannot struck again. Arc path
resistance is increased to reduce the current to low values while interrupting the arc.
Arc resistance = varc/iarc. The arc resistance mainly increased by: 3 Marks for
i) Lengthening of the arc by arc runners Explanation
ii) Splitting the arc by arc splitters: An appreciable voltage is absorbed at the contact with
surface so that if the arc can be split into a number of small arcs in series, the Diagram of
voltage available for the actual arc column is reduced. any one
iii) Arc cooling: The voltage required to maintain ionization increases with decrease of method
temperature of arc, so that cooling effectively increases the resistance.
iv) Constraining the arc: If the arc can be constrained into a very narrow channel, the
voltage necessary to maintain it is increased.
15 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
the arc vanishes for a brief moment. However the arc restrikes again with the rising
current waves.
In this method, at current zero instant, fresh unionized medium is introduced between
the spaces in between the contacts. Due to this medium deionization effect takes place.
The dielectric strength of the contact space increases to such an extent that the arc does
not continue after current zero.
5 c) With the help of neat sketch, explain principle of operation and working of induction
type overcurrent relay.
Ans:
Principle of Operation and Working of Induction Type Overcurrent Relay:
Figure represents the details of
induction type overcurrent relay. It
consists of two electromagnets, the 2 Marks for
upper magnet is of „E‟ shape & on Explanation
the central limb of which are placed
two windings. The upper winding
acts as primary winding and lower
winding acts as secondary winding.
The upper magnet produces flux ϕ1
when current flows through primary
winding. The alternating flux ϕ1 of
primary winding links to secondary
winding ultimately induces emf in the
secondary winding. The emf induced
in the lower winding produces current
to flow through the winding placed
on the lower „U‟ magnet. This 2 Marks for
secondary current produces flux ϕ2. The two fluxes ϕ1 and ϕ2 are sufficiently displaced Diagram
from each other and cause eddy currents in the disc, which will set up a torque on the
disc causing rotation of the disc. The tapings are connected to plug setting bridge for
giving desired current setting.
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 Marks for
Diagram
5 e) Draw neat sketch of induction type reverse power relay and explain its working.
Ans:
Induction Type Reverse Power Relay:
2 Marks for
Diagram
Figure shows the induction type directional relay used for the reverse power
protection. Here the shunt magnet coil and series magnet coil are exited from machine
17 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
6 a) Draw figure for restricted earth fault protection scheme for transformer. Labeled
Ans: diagram
4 Marks
Restricted Earth Fault Protection Scheme for Transformer:
Partially
Labeled
diagram
3 Marks
Un-Labeled
diagram
2 Marks
18 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
2 Marks for
Diagram
2 Marks for
Diagram
19 of 20
MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
(Autonomous)
(ISO/IEC-27001-2013 Certified)
Model Answers
Summer – 2019 Examinations
Subject & Code: Switchgear & Protection (17508)
6 e) Explain with neat sketch the operation of attracted armature type relay. State two
advantages.
Ans:
Operation of Attracted Armature Type Relay:
1 Mark for
Diagram
The coil is energized by the actuating quantity current or voltage proportional to the
system voltage or current as the case may be. The electromagnetic force on the 2 Marks for
armature is proportional to the square of the magnetic flux (the flux is proportional to Operation
the current in the coil) in the air gap between core and armature. As the armature is
attracted and its motion is linked to the trip contacts that operate to give the trip signal.
The force of attraction increases as the armature nears the core (or as the air gap
reduces). A restraining force in the form of a spring can be used to avoid unwanted
operation of the armature relay for normal currents in the current coil.
Advantages:
1. Simple construction.
2. Reliable operation. 1 Mark for
3. Unaffected by temperature changes. any 2
4. Long life. advantages
5. Robust construction.
20 of 20