Machines
Machines
Machines
Electrical Machines
Electrical Machines
Chapter–1 Transformers....................................................................................................................................................... 2
Solutions ..................................................................................................................................................................................15
Solutions ..................................................................................................................................................................................60
Chapter 1 – Transformers
01. The relative current directions through the Primary (P) 05. Two transformers of different kVA ratings working in
and Secondary (S) of a single phase transformer connected parallel share the load in proportion to their ratings when
to a resistive load on the secondary side, are indicated in their [1992]
the various cross-sectional views given in figure. Which of (a) Per unit leakage impedances on the same kVA base are
these are correct representations [1991] the same
(b) Per unit leakage impedances on their respective ratings
are equal
(c) Ohmic values of the leakage impedances are inversely
proportional to their ratings
(a) (b) (d) Ohmic values of the magnetizing reactances are the
same
10. When started by means of an auto-transformer with 18. A 3-phase transformer bank consists of three identical
50% tapping, supply current at start of an induction motor 2300/230V, 15 kVA single-phase transformers connect in
is reduced to ______________ of that when started by means delta/delta. The bank supplies a 20 kVA, unity p.f. 3-phase
of a star-delta starter. [1995] load. If one of the single-phase transformer develops a
fault, and is removed, the load carried by each of the two
11. The percentage impedance of a 100 kVA, 11 kV/400V, transformers now operating in open delta will be… kVA.
delta/wye, 50Hz transformer is 4.5%. For the circulation of [1997]
half the full load current during short circuit test, with low 19. Given figure shows a magnetic circuit formed by an
voltage terminals shorted, the applied voltage on the high ideal core material. Determine the magnetic flux density in
voltage side will be ________. [1995] the air gap. [1997]
38. An ideal transformer has a linear B-H characteristic with 500. The leakage reactance of the high and low voltage
a finite slope and a turns ratio 1:1. The primary of the windings are 1.0 and 0.012 respectively. Neglect the
transformer is energized with an ideal current source, winding resistance and core losses of the transformer. The
producing the signal I as shown in figure. Sketch the shape Thevenin voltage of system A is 3300V while that of system
(neglecting the scale factor) of the following signals, B is 400 V, the short circuit reactance of systems A and B
labeling the time axis clearly: [2001] are 0.5 and 0.010 respectively. If no power is
transferred between A and B, so that the two system
voltages are in phase, find the magnetizing ampere turns of
the transformer. [2002]
(a) The core flux oc with the secondary of the transformer
open 42. A single phase transformer has a maximum efficiency
(b) The open-circuited secondary terminal voltage V2(t) of 90% at full load and unity power factor. Efficiency at half
(c) The short-circuited secondary current i2(t), and load at the same power factor is [2003]
(d) The core flux sc with the secondary of the transformer (a) 86.7% (b) 88.26%
short-circuited. (c) 88.9% (d) 87.8%
39. A 1 kVA, 230V/100V, single phase, 50 Hz transformer 43. Figure shows an ideal single-phase transformer. The
having negligible winding resistance and leakage primary and secondary coils are wound on the core as
inductance is operating under saturation, while 250 V, 50 N1
Hz sinusoidal supply is connected to the high voltage shown. Turns ratio
= 2 . The correct phasors of
winding. A resistive load is connected to the low voltage N2
winding which draws rated current. Which one of the voltages E1 ,E2 currents I1 ,I2 and core flux are as shown
following quantities will not be sinusoidal? [2002] in [2003]
(a) Voltage induced across the low voltage winding
(b) Core flux
(c) Load current
(d) Current drawn from the source
53. The iron loss (pi) and copper loss (pC) in kW, under full
load operation are [2006]
(a) pc = 4.12, pi = 8.51 (b) pc = 6.59, pi = 9.21
The transformer connection will be represented by [2008]
(c) pc = 8.51, pi = 4.12 (d) pc = 12.72, pi = 3.07
(a) Yd0 (b) Yd1
(c) Yd6 (d) Yd11
54. What is the maximum efficiency (in %) at unity pf load?
(a) 95.1 (b) 96.2 [2006] 59. The core of a two-winding transformer is subjected to a
(c) 96.4 (d) 98.1 magnetic flux variation as indicated in the figure. [2008]
57. In the figure, transformer T1, has two secondary, all function of time will be of the form
three windings having the same number of tums and with
polarities as indicated. One secondary is shorted by a 10
resistor R, and the other by a 15 µF capacitor. The switch
SW is opened (t = 0) when the capacitor is charged to 5V
with the left plate as positive. At t=0+ the voltage Vp and
current IR are [2007]
(a) 25 V, 0.0 A
(b) Very large voltage, very large current
(c) 5.0 V, 0.5 A
(d) –5.0V, -0.5 A
62. With both S1 and S2 open, the core flux waveform will
be [2009]
(a) A sinusoid at fundamental frequency
(b) Flat-topped with third harmonic
(c) Peaky with third-harmonic
(d) None of these
66. The coils are to be connected to obtain a single phase,
63. With S2 closed and S1 open, the current waveform in 400/1000 V, auto-transformer to drive a load of 10kVA.
the delta winding will be [2009]
Which of the options given should be exercised to realize
(a) A sinusoid at fundamental frequency
(b) Flat-topped with third harmonic the required auto-transformer? [2009]
(c) Only third-harmonic (a) Connect A and D; Common B
(d) None of these (b) Connect B and D; Common C
(c) Connect A and C; Common B
Common Data for Questions 64 and 65:
(d) Connect A and C; Common D
(b) 2 A
(c) 2.24 A
(d) 3 A
75. The core loss of a single phase, 230/115 V, 50Hz power 79. An open circuit test is performed on 50Hz transformer,
transformer is measured from 230V side by feeding the using variable frequency source and keeping V/f ratio
primary (230V side) from a variable voltage frequency constant, to separate its eddy current and hysteresis losses.
source while keeping the secondary open circuited. The The variation of core loss/frequency as function of
core loss is measured to be 1050 W for 230V, 50Hz input. frequency is shown in the figure The hysteresis and eddy
The core loss is again measured to be 500W for 138V, 30Hz current losses of the transformer at 25Hz respectively are
input. The hysteresis and eddy current losses of the [2014-03]
transformer for 230V, 50Hz input are respectively, [2014-
01]
(a) 508W and 542W (b) 468W and 582W
(c) 498W and 552W (d) 488W and 562W
( )
(a) 2sin t , 4
(c) 1sin ( t ) ,2 Assuming the transformer to be ideal, the value of the
reactance X to improve the input power factor to unity is
(d) 2sin ( t ) ,0.5
________________. [2014-03]
81. The parameters measured for a 220V/110V, 50Hz, 86. Find the transformer ratios a and b such that the
single-phase transformer are: impedance ( Zin ) is resistive and equals 2.5 when the
Self inductance of primary winding = 45mH
network is excited with a sine wave voltage of angular
Self inductance of secondary winding = 30mH
frequency of 5000 rad/s. [2015-02]
Mutual inductance between primary and secondary
windings = 20mH
using the above parameters, the leakage (Ll1 ,Ll2 ) and
89. Two three-phase transformers are realized using single- 92. A single-phase 400V, 50Hz transformer has an iron loss
phase transformers as shown in the figure. of 5000W at the rated condition. When operated at 200V,
25Hz, the iron loss is 2000W. When operated at 416V,
52Hz, the value of the hysteresis loss divided by the eddy
current loss is _____________. [2016-01]
99. A single-phase 100kVA, 1000V/100 V. 50 Hz 104. A single-phase, 4 kVA, 200 V/100 V, 50 ~Hz
transformer has a voltage drop of 5% across its series transformer with laminated CRGO steel core has rated no-
impedance at fall load. Of this, 3% is due to resistance. The load loss of 450 W. When the high-voltage winding is
percentage regulation of the transformer at full load with excited with 160 V, 40 Hz sinusoidal AC supply, the no-load
0.8 lagging power factor is [2018] losses are found to be 320 W. When the high-voltage
winding of the same transformer is supplied from a 100 V,
(a) 4.8 (b) 6.8
25 Hz sinusoidal AC source, the no-load losses will be
(c) 8.8 (d) 10.8
…………… W (rounded off to 2 decimal places). [2020]
100. A 3-phase 900kVA, 3kV 3kV ( Y ) , 50Hz 105. Windings 'A', 'B' and 'C' have 20 turns each and are
transformer has primary (high voltage side) resistance per wound on the same iron core as shown, along with winding
phase of 0.3 and secondary (low voltage side) resistance 'X which has 2 turns. The figure shows the sense
(clockwise/anti-clockwise) of each of the windings only and
per phase of 0.02 . Iron loss of the transformer is 10kW.
does not reflect the exact number of turns, If windings 'A',
The full load % efficiency of the transformer operated at 'B' and 'C' are supplied with balanced 3 -phase voltages at
unity power factor is ______ (up to 2 decimal places). 50 Hz and there is no core saturation, the no-load RMS
[2018] voltage (in V, rounded off to 2 decimal places) across
winding ' X is ____________ [2020]
101. A 5 kVA, 50 V/100 V, single-phase transformer has a
secondary terminal voltage of 95 V when loaded. The
regulation of the transformer is. [2019]
(a) 1 % (b) 4.5 %
(c) 9 % (d) 5 %
Solutions
01. Ans: (a), (b)
Solution:
In a transformer the flux produced by the secondary current must oppose the primary flux to satisfy Lenz’s law.
We can use right hand grip rule to check in which connection the fluxes oppose each other.
M.M.F 100
(iii) = = = 0.007mWb
Rnet 1.44 107
N2 10 4 10 4 0
(iv) L = = = = 0.69mH
Reac tance R ag 1.44 107
1
L ( I ) = 0.5 0.69 = 0.345mJ
2
(v) E =
2
Since voltage applied is same, the eddy current loss will remain the same. However, because of reduction in frequency, the
hysteresis loss will increase.
Magnetic Circuit symmetry ensures that reluctance faced by each phase is equal and so the flux and emf would be
balanced in each of the three phases.
Now since, voltage rating of transformer is not mentioned we will assume that turns ratio of transformer is 1:1 without loss
of generality.
Based on options given we assume the line or the phase voltage on primary side to be 230V as shown in the figure above.
Since, the voltage across A Phase on primary is 230V so, the voltage across a phase on secondary will also be 230V.
But due to line opening on primary this 230V gets equally divided in the other two phases as shown below.
Hence, the voltage across each of the other two phases would be 115V assuming the impedance of winding of all phases
is equal.
11. Ans:
Solution:
Given 100 kVA, 11 kV/400 V ( – Y) 50Hz Transformer
Per unit impedance = 0.045
When the load terminals are shorted and rated current flows, the equivalent circuit is shown below,
Rated Current in pu = 1 pu
Actual Current = 0.5 Irated
Current in pu = 0.5 pu
By KVL,
Induced EMF, E = IZ = 0.0225pu
Since, pu voltage is same on both sides of transformer.
So, voltage on HV side = 0.0225 pu
HV side voltage = 0.0225 11kV = 247.5V
V 4000
Z= = =200 850Ω
I 0 2 − 850
For open- connection with banks of ideal transformers, maximum kVA that the rest two transformers can supply is,
1
(Rated capacity of bank)
3
1
( 3 15 ) 26kVA
3
Both Transformers in open delta connection share equal load but still KVA rating is not twice of individual capacity due to
different phase of apparent power output of both transformers.
20
Therefore, each transformer will share a load of = 10kVA
2
( )
2
Hysteresis loss ,. Ph f Bm .
V2 = 0.9V1
f1 = 45Hz = 0.9 (50Hz ) = 0.9 f1
V2 V1
=
f2 f1
So flux density is constant.
Therefore, Ph f
Ph1 f1 1
= =
Ph2 f2 0.9
Ph2 = 0.9Ph1
Pe V 2
Pe2 ( 0.9 ) V1
2 2
= = 0.81
Pe1 V12
Pe2 = 0.81Pe1
Pcore1
Initially, Pe1 = Ph1 = [ Pcore1 → Total core loss]
2
Now,
Pcore2 = Pe2 + Ph2 = 0.81Pe1 + 0.9Ph1
Pcore2 = 0.855Pcore1
0.855Pcore1 − Pcore1
% change = 100 = −14.5%
Pcore1
Therefore, reduction of 14.5% takes place.
sin m sin m
kd = 2 2
( sin
for small values of ‘ ’)
msin
m 2 2
2 2
For 1-phase alternator,
m = (Phase spread)
kd =
( 2) = 2
sin
2
2
E (induced EMF) = (2T) = 1.273T Volts
x=
(P ) = 500 = 0.913
i fl
(P ) 600
cu fl
3V1
So voltage ratio becomes and rating as Q.
3V2
Note: If the windings are connected in parallel then voltage rating remains same but current rating becomes thrice so the
KVA rating will remain same.
Hence, none of the option matches.
(MVA )
(MVA ) Short −circuit
= rated
%Z or Z (p.u)
So, Isc =
(I) rated
%Z
10 kVA 10 103
( I )rated = 400 = 400 = 25A
25
Isc = = 250A
10%
LV
Where, K =
HV
10
(kVA ) new
=
400
= 50 kVA
1−
500
(V) − ( V )full−load
So, V.R . = no −load
= 0.8 + 5 0.6 = 3.8%
(V) no −load
E−V
Or, = 3.8%
E
Since, V = 415 V (L − L )
3.8
E (L − L ) = E (L − L ) + 415
100
415 100
E (L − L ) = = 431.33V
96.2
431.33
Induced EMF per phase = = 249.06V
1.732
In Delta, phase voltage is same as line voltage so Phase Voltage on primary is 6000 V.
E1 6000
So, turns ratio = = 24.08 24
E2 249.06
(
So primary p.f. = cos 53.13 = 0.6
0
)
Here, we have neglected no-load current and assumed that secondary side is open-circuited so that there is no
component of secondary current reflected in primary.
(
Switching say we have an AC circuit with cos or sine input as Vm sin t + )
Then total current i(t) at any instant is given as:
−V
I (t) = m
R2 + X2
.sin − tan−1 L
R ( )
−Rt
.e L +
Vm
R 2 + XL2
sin t + − tan−1 L
( )
R
L
For transient part to be zero
= tan−1 L ( R ) , generally in Transformer
(X L
R )
So, = 900
So, phase difference between voltage current should be 900 .
So from curve we can see that if we switch the circuit at voltage-maximum current is zero at the instant .So heavy inrush
can easily be avoided but if we switch at voltage min at 00 ,then current is maximum which will increase inrush current.
3 ( Vbase ) 3 ( 33kV )
2 2
( Zb ) = Sbase
=
20MVA
3 ( 33)
2
12
( Z )actual = ( Z )base ( Z )pu = 20
100
= 19.6
d
()
(b) V2 t = −N
dt
We cannot exactly determine the polarity of induced emf as dot polarity on the winding is not mentioned.
(d) Flux wave from will remain same, in short circuit condition also, as secondary flux will be compensated by additional
primary flux.
XL2 0.012
XL2
= = = 0.8167
k2 ( 0.1212)
2
V2 400
V2 = = = 3300V
k 0.1212
3300 1.49
Im1 = = 4.7012 A
(500 || 1.49 ) + 0.6 501.49
3300 0.6
Im2 = = 1.8931A
(500 || 0.6 ) + 1.49 500.6
Im = 6.5943A
Magnetizing Ampere Turns, Fm = 99 6.5943 = 652.83AT
Pi = (1 ) .PCu,FL = 0.055s
2
( )
2
3VL2 3 11 10
3
Z e (base ) = = = 3630
Sbase 105
Z e ( ) = 0.02 + j0.07 3630 = ( 72.6 + j254.1 )
50 + Ploss = 50
0.95
Ploss = 2.6315kW
When it is reconfigured as an auto transformer
LV 500 2
k= = =
HV 750 3
Rating of 2 Winding 50
Rating of auto transformer = = = 150KVA
( 3)
(1 − k ) 1− 2
Efficiency , =
(kVA ) cos 100%
(kVA ) cos + P
loss
Since, turns ratio = 1.1. Current and voltages remain same on both sides
Vp = − Vc = −5V
VP −5
IR = = = −0.5A
R 10
1<t<2
d
=0 ers = 0
dt
2<t<2.5
d 0.12
= = −0.24
dt 0.5
ers = −200 0.24 = − 48V
M2 ( area)2 M 1
= 2 =
M1 ( area) M1 2
1
400 di
Peak voltage = mH
dt max
400 800
Vp = 10 −3 2000 = V
6000
VS = 400 = 600V
4000
VP = 400V VS = 600V
To obtain 400V/1000V auto transformer primary must be coil 1 and additive polarity must be used.
This is shown in figure below:
So, A and D are connected together and B serves as common terminal between primary and secondary.
400I1 = 600I2
I1 = 1.5I2
Only option (d) satisfies this condition.
Also, current in both coils should be less than rated which is 25 A.
I = 1 − 90 A
Total primary current
IP = 20 + 1 − 90 = 2.236 − 26.56 A
Zs Zs 12
Zp = 2
= 2
= 2
=1Ω
Ns Vph,s
220
Np Vph,P 110
3
Zp =1+j0 Ω
Since, primary is star connected.
So load impedance will also be star connected.
( )
2
Voltage rating area dimention
( dimention)
2 2
V2 2
= 2
=
V1 1
( dimention)
1
1
V2 = 2V1
V2 = 2KV
No load current dimension
I 2 dim2
=
I dim
1 1
( )
3
Cross loss core volume = dimension
3
Pc2 dim2
( 2)
3
= =
Pc1 dim1
Pc2 = 55 2 2 = 155.6W
( 0.9I )
2
fl
R = 81
I fl R = 100
2
Pi 64
For maximum efficiency, x = = = 0.8
Pcu,FL 100
Maximum efficiency occurs at 80% of rated current.
r1
It is given that, r2 =
2
2
N2
= 4
N1
N
Hence, 2 = 2
N1
So, number of turns become double.
Hence, Bm = constant
2
Therefore, Ph f & Pe f
For V = 230 V, f = 50 Hz
Ph + Pe = 1050W …………..(i)
For V = 138 V, f = 30 Hz
Ph' + Pe' = 500W ………....(ii)
Ph' 30 P' 30
2
= = 0.6 ; e = = 0.36
Ph 50 Pe 50
Substituting in (ii),
0.6 Ph + 0.36 Pe = 500 ..……..(iii)
Solving (i) & (iii)
Ph = 508 W , Pe = 542 W
1 1
KVA rating = (KVA rating of 2-winding transformer) = 50 = 550 KVA
1 −K 1 − 1000
1100
V
Bm
f
V
Since is constant, Bm = Constant
f
So, Ph=K'hf ; Pe=K'ef 2
K'e =
( 10 )
15 −
=
1
W / Hz2
50 10
Ph
= 10
f
Ph =10 × 25 = 250 W
1 125
Similarly, Pe= 252 = W = 62.5W
10 2
Since, voltage phase angle is assumed to be zero at secondary and hence primary emf will also have zero phase angle.
E1 = 2VL = 2200V
2200 220
I2 = = − 900 A
jXL XL
For unity pf, I must not have any imaginary part & I2 is purely imaginary.
( )
Hence, I2 = − Im I1 = 9.3148A
220
XL = = 23.618
I2
L = L1 − 2M = 45 − 2 20 = 5mH
1
N1
Magnetizing inductance = M = 2M = 2 × 20 = 40mH
N2
Lb = M = 480mH
L eq = L a + (Lb || L c )
Leq = 320 +
( 480 120 ) = 416 mH
600
2 2 2
N V 200
Alternatively, Z in = s RL = s RL = 12 = 1.33
N V
P P 600
100
Per-phase current on delta connected secondary side = 30A
3
Vph,p 230 3 2
Turns ratio of primary to secondary = = =
Vph,s 115 3
Iph,s Vph,p 2
= =
Iph,p Vph,s 3
3 100
Iph,p = 30 = 5030A
2 3
89. Ans: 30
Solution:
The first transformer is a Dd0 connection, so phase difference between primary and secondary will be 0.
The second transformer is Dy11 connection, so secondary leads primary by 30.
Therefore, phase difference between V1 & V2 is −30 as V2 leads V1 by 30 but in this case only magnitude of phase
difference will be specified as answer.
91. Ans:
Solution:
For negative sequence on star side, voltage in phase leads line voltage by 30
VAB
VAN = 30
3
From the connection, the winding AN is parallel to ab
N N V
Vab = S VAN = S AB 30
NP NP 3
Hence, Vab leads VAB by 30°
VAB lags Vab by 30 .
Alternatively, phasor diagram can be drawn to derive this relation.
93. Ans:
Solution:
Since, the output voltage is sum of two voltages
So, auto – transformer is connected in additive polarity.
There are two configurations possible 220/2420
Low voltage 220 1
K= = =
High voltage 2420 11
22 22 22 11
(KVA ) auto
= =
1 −K 1 − 1
=
10
= 24.2 KVA
11
Second configuration 2200/2420
Low voltage 2200 10
K= = =
High voltage 2420 11
22
(KVA ) = = 242KVA
1 − 10
auto
11
Hence, maximum KVA is achieved in second configuration and it is equal to 242 kVA.
94. Ans: 10
Solution:
Referring the circuit to primary,
2
N 80 103
RP = P R S = = 8
NS 10 4
2
N 40 103
XP = P XS = = 4
NS 10 4
Equivalent circuit
V 1000
I= = = 10 − 36.870 A
Z eq 1036.87
95. Ans: 6
Solution:
The two possible configuration assuming additive polarity are 100 / 300 and 200 / 300
Low voltage
K=
high voltage
K1 = 100 =1
300 3
K 2 = 200 =2
300 3
(KVA )
(KVA ) auto
=
2−dg
1 −k
2
(KVA ) = = 3 KVA
1
1− 1
3
2
(KVA ) = = 6 KVA
2
1− 2
3
S = 3VL IL
1190.955
IL = = 625.089A
3 1.1
s 25 125
IL = = = = 37.878 A
3 VL 3.3 3.3
3
5 3
Impedance = 5% = 0.05 pu
Resistance = 3% = 0.03 pu
VR (0.8pf log) = Rcos + Xsin = 0.03 0.8 + 0.04 0.6 = 0.048 pu = 4.8%
Vline ( Y ) = 3 kV
900
IPh ( ) = = 100A
3 3 kV
( )
Copper loss = 3Iph pri RP + 3Iph sec R sec
2 2
( )
Pcu = 3 1002 0.3 + 3 3002 0.02 = 3 10000 0.48 = 14400 W = 14.4 kW
Core loss = 10 kW
900
= 100 = 97.36%
900 + 24.4
(
= 12 tan cos−1 0.6 =16KVAr )
For transformer rating, S= 25KVA
S2 = P2 + Q2
Since additional load has unity pf, so it consumes only P
(P + 12)
2
+ 162 = 252
P= 7.21kW
R core =
0 r A
=0 ( r
= )
0.2 10 −2 2 10 −3
R gap = =
0 A 0 A
2 10 −3
R1 = R core + R gap =
0 A
Final resistance,
R core = core 40 10 −2 4 10 −4
= =
0 r A 0 1000 A 0 A
2 10 −3
R gap =
0 A
R2 = Rcore + Rgap =
2.4 10−3
0 A
If I = constant, MMF = constant
Then,
1
R
2 B2 R1
= =
1 B1 R2
2.0
B2 = 1 = 0.83T
2.4
105. Ans: *
Solution:
[Data given in question is ambiguous leading to dead short-circuit of supply, marks to all was awarded for this question].
106. Ans: *
Solution:
Wi1 = 2500 W at 440 V1 50Hz
W12 = 850 W at 220 V1 ,25Hz
Wi3 = Re + Ph at 440 V, 50Hz
3 3
v
Re = ?, Ph = ?, = constant
3
f
3
2500 = Af + Bf2
400 220
= = Constant
50 25
2500
Or = A + Bf
f
2500
= A + B(50)
Or 50 …….. (i)
850
= A +B
And 25 …………….(ii)
Solving (i) & (ii), we get
2500 850 2500 − 1700
25B = − =
50 25 50
800
= = 16
50
16
B=
25
16
And from (i), A = 50 − 50 = 50 − 32 = 18
25
So at 50 Hz,
Ph = Af = 18 50 = 900 W
Pe = Bf 2
16
= (50) = 1600 W
2
25
Solution:
5
Peak voltage across resistor = = 2.5V
2
V̂ 2.5
Peak current = r = A
R 22
Assume iP = Im sin ωt
V̂s = MIm
7.3
2
(
= 2 105 M )2.5
22
M = 51.12H
Chapter 2 – DC Machine
01. Level compounded D.C generator is used for which of 07. A separately excited d.c. motor has an armature
the following applications? [1991] resistance of 0.5 ohm. It runs off a 250V d.c. supply drawing
(a) Electric Arc Welding (b) Electric Traction an armature current of 20A at 1500 rpm. The torque
(c) Battery Charging (d) Lighting developed for an armature current of 10A will be
_________________ for the same field current. [1992]
02. A separately excited d.c. motor has to be run at 125%
of rated speed when delivering 50% torque. The excitation 08. A cumulative compounded long shunt motor is driving
will be _______________. [1991] a load at rated torque and rated speed. If the series field in
shunted by a resistance equal to the resistance of the series
03. Match the windings of a large D.C series motor and
field, keeping the torque constant [1993]
their functions: [1991]
Windings Function
(A) series field winding (P) to avoid field
distortion under the pole
(B) shunt field winding (Q) to avoid sparking
(C) commutating pole (R) to generate working
winding flux
(a) The armature current increases
(D) compensating (S) to avoid runway
winding speeds on no-load (b) The motor speed increases
(c) The armature current decreases
04. A 10 kW, 6 pole, D.C generator develops an EMF of (d) The motor speed decreases
200V at 1500 rpm. The armature has a lap l connected
winding. The average flux density over a pole pitch is 0.9 09. A differentially compounded d.c. motor with inter poles
Tesla. The length and diameter of the armature are 0.25m and with brushes on the neutral axis is to be driven as a
generator in the same direction with the same polarity of
and 0.2m respectively. Calculate [1991]
the terminal voltage. It will then [1995]
(a) The flux per pole
(a) Be a cumulatively compound generator but the coil
(b) The total number of active conductors in the armature connections are to be reversed
and (b) Be a cumulatively compounded generator without
(c) The torque developed by the machine when the reversing the inter pole coil connections
armature supplies a current of 50A. (c) Be a differentially compounded generator without
reversing the inter pole coil connections
(d) Be a differentially compounded generator but the inter
05. Neglecting all losses, the developed torque (T) of a d.c.
pole coil connections are to be reversed.
separately excited motor, operating under constant
terminal voltage, is related to its output power (P) as under 10. A 220V, 1.5 kW, 859 rpm, separately excited dc motor
[1992] has armature resistance of 2.5 ohms and it draws a current
(a) T P (b) T P of 8A at rated-load condition. If the field current and the
(c) T P
2 3
(d) T independent of P armature voltage are fixed at the value of rated speed at
rated load, what will be the no-load speed of the motor?
06. The developed electromagnetic force and/or torque in Assume losses remain constant between no-load and full
electro-mechanical energy conversion systems act in a load operation. [1995]
direction that tends [1992]
(a) To increase the stored energy at constant mmf 11. A 4 pole generator with 16 coil has a two layer lap
(b) To decrease the stored energy at constant flux winding. The pole pitch is [1996]
(c) To decrease the co-energy at constant mmf (a) 32 (b) 16
(c) 8 (d) 4
(d) To decrease the stored energy at constant mmf
12. A 4 pole dynamo with wave wound armature has 51 19. A DC shunt generator delivers 60KW at 240V and 360
slots containing 20 conductors in each slot. The induced rom. The armature and field resistances are 0.015Ω and
EMF is 357 volts and the speed is 800 rpm. The flux per 60Ω respectively. Calculate the speed of the machine
pole will be [1996] running as a shunt motor and taking 60KW input at 240V.
(a) 3.5 mWb (b) 1.2 mWb Allow 1 volt per brush for contact drop. [1998]
(c) 14 mWb (d) 21 mWb
20. A 4-pole lap-wound DC generator has a developed
13. Out of the following factors for a dc machine, [1996] power of P watts and voltage of E volts. Two adjacent
(i) Inter pole (ii) Armature resistance brushes of the machine are removed as they are worn out.
(iii) Armature current (iv) Reduction in field current If the machine operates with the remaining brushes, the
The factors that are responsible for decrease in the terminal developed voltage and power that can be obtained from
voltage of a shunt generator are the machine are [1999]
(a) i, ii and iv (b) ii, iii and iv E P
(c) ii, iv and iv (d) ii, iv and iv (a) E, P (b) ,
2 2
P P
14 A 5kW, 200V DC shunt motor has an armature (c) E, (d) E,
resistance of 1 ohm and shunt field resistance of 100 ohms. 2 2
At no-load, the motor draws 6A from a 200V supply and
runs at 1000rpm. The rotational loss of the machine is… W 21. A DC shunt motor is running at 1200 rpm, when excited
and the no load torque is… N-m [1997] with 220V DC. Neglecting the losses and saturation, the
speed of the motor when connected to a 175V DC supply
15. A 200V, 10kW lap-wound DC generator has 10 poles is: [1999]
and 500 conductors on its armature. If the pole face covers (a) 750 RPM (b) 900 RPM
80% of the pole pitch, the pole face conductors required to (c) 1050 RPM (d) 1200 RPM
fully compensate for armature reaction will be….
conductors/pole. [1997] 22. A separately excited DC shunt motor is driving a fan
load whose torque is proportional to the square of the
16. The field coil of a two-pole DC series motor is made up speed. When 100V are applied to the motor, the current
taken by the motor is 8A, with the speed being 500 rpm. At
of two identical sections. In one case (i) of two sections of
what applied voltage does the speed reach 750 rpm and
the field coil are connected in series, and in another case
then what is the current drawn by the armature? Assume
(ii) the two sections are connected in parallel. If the motor the armature circuit resistance to be 1 Ω. Neglect brush
takes the rated current in both the cases, then torque (i): and mechanical losses [1999]
torque (ii) is ….. and speed (i) : speed (ii) is ….. (Neglect the
effect of magnetic saturation) [1997] 23. The compensating winding in a dc machine [2000]
(a) Is located in armature slots for compensation of the
armature reaction
17. At 50% of full load, the armature current drawn by a DC
(b) Is located on commutating poles for improving the
shunt motor is 40A when connected to a 200V DC mains.
commutation
By decreasing the field flux, its speed is raised by 20% this (c) Is located on pole shoes for avoiding the flashover at
also causes a 10% increase in load torque. Calculate the the commutator surface
percentage change in field current. The armature resistance (d) Is located on poles shoes to avoid the sparking at the
including the brushes is 1 Ohm. Neglect saturation and brushes.
armature reaction. [1997]
24. A permanent magnet dc commutator motor has a no
load speed of 6000 rpm when connected to a 120V dc
18. A 240 V DC shunt motor with an armature resistance of supply. The armature resistance is 2.5 ohms and other
0.5Ω has a full load current of 40A. Find the ratio of the losses may be neglected. The speed of the motor with
stalling torque to the full load torque when a resistance of supply voltage of 60V developing a torque 0.5 Nm, is:
1Ω is connected in series with the armature? [1998] [2000]
(a) 4 (b) 12 (a) 3000 rpm (b) 2673 rpm
(c) 2836 rpm (d) 5346 rpm
(c) 6 (d) none of the above
25. A belt driven dc shunt generator runs at 1500 rpm 30. A 200 V, 2000 rpm, 10A, separately excited dc motor
delivering 10kW, at 220V bus bars. The belt breaks,
has an armature resistance of 2Ω. Rated dc voltage is
following which the machine operates as a motor drawing
2kW power. What will be its speed as a motor? The applied to both the armature and field winding of the
armature and field resistances are 0.25 ohms and 55 ohms
motor. If the armature draws 5A from the source, the
respectively. Ignore armature reaction and assume the
contact drop at each brush to be 1V. [2000] torque developed by the motor is [2002]
Group I Group II
P Field Control 1 Below base speed
Q Armature Control 2 Above base speed
3 Above base torque
4 Below base torque
(a) P – 1; Q – 3 (b) P – 2; Q – 1
(c) P – 2; Q – 3 (d) P – 1; Q – 4
29 A dc series motor fed from rated supply voltage is 33. To conduct load test on a dc shunt motor, it is coupled
overloaded and its magnetic circuit is saturated. The to a generator which is identical to the motor. The field of
torque-speed characteristic of this motor will be the generator is also connected to the same supply source
approximately represented by which curve of Figure?
as the motor. The armature of the generator is connected
[2002]
to a load resistance. The armature resistance is 0.02 p.u.
(a) Curve A
armature reaction and mechanical losses can be neglected.
(b) Curve B With rated voltage across the motor, the load resistance
across the generator is adjusted to obtain rated armature
(c) Curve C current in both motor and generator. The p.u. value of this
load resistance is [2003]
(d) Curve D
(a) 1.0 (b) 0.98
(c) 0.96 (d) 0.94
34. When Stator and Rotor windings of a 2-pole rotating 37. For a linear electromagnetic circuit, the following
electrical machine are excited, each would produce a statement is true. [2004]
sinusoidal MMF distribution in the air gap with peak values (a) Field energy is equal to the co-energy
(b) Field energy is greater than the co-energy
FS and Fr respectively. The rotor MMF lags stator MMF by a
(c) Field energy is lesser than the co-energy
space angle at any instant as shown in Figure. Thus, half (d) Co-energy is zero
of stator and rotor surfaces will form one pole with the
other half forming the second pole. Further, the direction 38. The armature resistance of a permanent magnet dc
motor is 0.8. At no load, the motor draws 1.5 A from a
of torque acting on the rotor can be clockwise or counter-
supply voltage of 25 V and runs at 1500 rpm. The efficiency
clockwise. of the motor while it is operating on load at 1400 rpm
drawing a current of 3.5 A form the same source will be
[2004]
(a) 48.0% (b) 57.1%
(c) 59.2% (d) 88.8%
42. In relation to DC machines, match the following and 46. The net voltage across the armature resistance at the
choose the correct combination. [2005] time of plugging will be [2008]
(a) 6V (b) 234 V
Group –1 Group – 2
(c) 240 V (d) 474 V
Performance Proportional to
Variables
47. The external resistance to be added in the armature
(P) Armature emf (E) (1) Flux ( ), speed () and
circuit to limit the armature current to 125% of its rated
(Q) Developed armature current ( I a ) value is [2008]
torque (T)
(2) and only (a) 31.1 (b) 31.9
(R) Developed
(3) and I a only (c) 15.1 (d) 15.9
power (P)
(4) I a and only
48. Figure shows the extended view of a 2 pole dc machine
(5) I a only with 10 armature conductors. Normal brush positions are
shown by A and B, placed at the inter-polar axis. If the
brushes are now shifted, in the direction of rotation, to A'
(a) P − 3 Q − 3 R − 1 (b) P − 2 Q − 5 R − 4
(c) P − 3 Q − 5 R − 4 (d) P − 2 Q − 3 R − 1 and B' as shown, the voltage waveform VAB will resemble
[2009]
43. In a DC machine, which of the following statements is
true? [2006]
(a) Compensating winding is used for neutralizing armature
reaction while inter pole winding is used for producing
residual flux
(b) Compensating winding is used for neutralizing armature
reaction while inter pole winding is used for improving
commutation
(c) Compensating winding is used for improving
commutation while inter pole winding is used for
neutralizing armature reaction
(d) Compensating winding is used for improving
commutation while inter pole winding is used for
producing residual flux
Common Data for Questions 49 and 50: the motor draws a line current of 70A. Neglect armature
A separately excited DC motor runs at 1500 rpm under no- reaction. The full load speed of the motor in rpm
load with 200 V applied to the armature. The field voltage is_____________. [2014-01]
is maintained at its rated value. The speed of the motor
when its delivers a torque of 5Nm is 1400rpm as shown in 55. A 250V dc shunt machine has armature circuit
the figure. The rotational losses and armature reaction are resistance of 0.6 and field circuit resistance of 125 .
neglected. The machine is connected to 250V supply mains. The
motor is operated as a generator and then as a motor
separately. The line current of the machine in both the
cases is 50A. The ratio of the speed as a generator to the
speed as a motor is_____________. [2014-02]
(a) 34.2 A (b) 30 A 75. A 280 V, separately excited DC motor with armature
(c) 22 A (d) 4.84 A resistance of 1 Ω and constant field excitation drives a load.
The load torque is proportional to the speed. The motor
70. A separately excited dc motor has an armature draws a current of 30A when running at a speed of 1000
resistance Ra = 0.05 . The field excitation is kept rpm. Neglect frictional losses in the motor. The speed, in
rpm, at which the motor will run, if an additional resistance
constant. At an armature voltage of 100V, the motor
of value 10 Ω is connected in series with the armature, is
produces a torque of 500 Nm at zero speed. Neglecting all ___________. (round off the nearest integer). [2022]
mechanical losses, the no-load speed of the motor (in
radian/s) for an armature voltage of 150 V is _______ (up to 76. The four stator conductors (𝐴, 𝐴′ , 𝐵 and 𝐵′ ) of a
2 decimal places). [2018] rotating machine are carrying 𝐷𝐶 currents of the same
value, the directions of which are shown in the figure (i).
71. A 200V DC series motor, when operating from rated The rotor coils 𝑎 - 𝑎 ' and 𝑏 - 𝑏 ' are formed by connecting
voltage while driving a certain load, draws 10 A current and the back ends of conductors ' 𝑎 ' and ' 𝑎 ' and ' 𝑏 ' and ' 𝑏 ',
runs at 1000r.p.m. The total series resistance is 1 Q. The respectively, as shown in figure (ii). The e.m.f. induced in
magnetic circuit is assumed to be linear. At the same coil 𝑎 - 𝑎 ' and coil 𝑏 - 𝑏 ′ are denoted by 𝐸𝑎−𝑎′ and 𝐸𝑏−𝑏′ ,
supply voltage, the load torque is increased by 44%. The respectively. If the rotor is rotated at uniform angular speed
speed of the motor in r.p.m. (rounded to the nearest 𝜔rad/s in the clockwise direction then which of the
following correctly describes the 𝐸𝑎−𝑎′ and 𝐸𝑏−𝑏′ ? [2023]
integer) is ________ [2018]
Solutions
01.Ans: (d)
Solution:
A level compounded generator has almost constant
terminal voltage with increase in load.
So it can be used for lighting purpose where, with
increase in load, constant terminal voltage is required.
03.Ans: (A-R,B-S,C-Q,D-P)
Solution:
• Compensating winding is connected in series with the armature winding to compensate armature reaction under the
pole arc region.
• Interpole winding/Commutating pole winding is used to improve commutation i.e. to avoid sparking by neutralizing
the reaction voltage in the winding undergoing commutation.
• In the DC Series Motor, the series field is used to generate the working flux.
• In case of No-Load in Series Motor, the armature current is small due to which series flux is small and the speed of
motor can increase without bound so the series motor is converted to Compound Machine so that shunt winding can
provide the flux under no-load condition.
04.Ans: (0.02355,340,63.69)
Solution:
Given, 10kW, 6 pole lap wound DC generator
E=200V, N=1500rpm, B = 0.9T
L=0.25; D=0.2m [ D → Diameter of rotor, L → Length of rotor]
A=6 (In a lap wound DC machine, A=P)
a) Total flux = P
P = BA
A = D L
05.Ans: (b)
Solution:
If supply voltage in a separately excited DC motor is constant, then input power
P Ia ........ (1 ) ( P = Vt .Ia )
T Ia ......... ( 2 )
T P
06.Ans: (b)
Solution:
In an electromechanical energy conversion device, total energy supplied= (Electric energy Mechanical energy + Field
energy)
For small load change or virtual displacement ‘dx’ of rotor
1
dWelec = 0 = i.d = 0
2
(E )
b 1500rpm
= Vt − ( Ia )1500rpm (R a ) = 250 − 20 0.5 = 240V
Eb Ia 240x20
T1500rpm = = = 30.56N − m
2
1500
60
T1 Ia1
= (since flux is constant)
T2 Ia2
I 10
T2 = a2 T1 = 30.56 = 15.28N − m
I
a1 20
08.Ans: (a)
Solution:
If the series field is shunted by a resistance, then current through series field will reduce & hence, series flux ( se ) will
reduce. Hence net flux (net = se + sh ) will reduce.
Since, T=K Ia ,to keep the torque constant, the armature current will increase.
09.Ans: (b)
Solution:
• In a compound machine, we have series as well as Shunt Winding. The current is Shunt winding remains in same
direction until the terminal voltage connection is reversed. So, the field poles polarity remains the same when the
motor is run as generator.
• Since, the direction of rotation also remains the same so the emf has the same polarity and hence to reverse the
power flow the armature current should be reversed.
• Interpoles in Generator have same polarity as that on next pole in direction of rotation and that of previous pole in
case of motor so polarity of interpoles must be reversed. But since, interpoles are connected in series with armature,
their polarity reverses when the armature current reverses so there is no need to interchange the interpole connection.
• In differentially compounded machine, the shunt and series flux oppose each other but when it is run as generator the
armature current reverses which reverses the series field flux but shunt field flux remains in same direction.
• Hence, the two fluxes are in same direction and get added up and machine acts as compound machine without
reversing the interpole connections.
NPZ
E=
60A
E 60A 357 60 2
= = = 1.23 mWb
NPZ 8500 4 51 20
13. Ans: B
Solution:
(i) Inter-pole is used to reduce armature reaction, so it increases air-gap flux, hence induced EMF and hence terminal
voltage should increase.
(ii) Armature resistance reduces terminal voltage from no-load to full-load due to IaRa drop
(V = E − I R ) a a
(iii) Armature current also drops terminal voltage, as it also causes drop in no-load voltage or induced EMF as it increases.
( )
(iv) Reduction in field current reduces field flux and hence induced emf and since, V = E − IaR a , the terminal voltage also
V 200
If = = = 2A
R f 100
Ia=6-2=4A
Eg = 200 − 4 1 = 196V
Protational loss = EgIa = 196 4 = 784W
Protational 784
nl = = = 7.486N − m
( ) nl
104.72
15. Ans: 4
Solution: Given, 200V, 10kW, lap wound DC-generator
P=10, Z=500
Pole Arc
Since, = 0.8 or 80%
Pole − pitch
Z
Compensating conductors required per pole is given as: = ( 0.8 )
AP
500
Compensating Conductors = 0.8 4
10 10
17. Ans: 28
Solution:
Ia1 = 40A
Induced EMF E1 = 200 − 40 1 = 160V = k..
Now, let reduction in flux be by ‘x’ times (x<1)
2
Thus means =x
1
So, due to this torque increases by 10%
So, T2 = 1.1T1 2 = x1
T2 2 .Ia2 x.Ia2
Or, = =
T1 1 .Ia1 40
Ia2
Or, x = 1.1
40
40 1.1
Or, Ia2 =
x
So, new induced EMF
40 1.1
E = 200 − Ia2 1 = 200 − …………. (1)
x
Since reduction of flux causes 20% increase in speed.
2
= 1.2
Modified EMF, E = k. ( x. ) . (1.2) …………(2)
40 1.1 40 1.1
200 − = 1.2x k200
=− = 1.2x 160
x x
192x2 + 44 − 200x = 0
Solving we get x=0.315
And x 0.72
For x=0.315
40 1.1
Ia2 = = 139.68 Amps
0.315
Which is very large, it will damage the machine
For x=0.72
40 1.1
Ia2 = 61A is a permissible value
0.72
As If for linear region of BH curve
So % change of reduction is field current or field flux is
1 − 2
100
1
1 − 0.721
100 = 28%
1
Egen = Kgen
Egen = K ' Ngen
Now, when it works as motor, voltage across field winding is same as in case of generator. Therefore, field current and
hence, flux will remain the same.
(I )
a m
= 250 − 4 = 246A
Emot = 240 − 246 0.015 − 2 = 234.31V
Emot = K' Nmot
234.31=K’ Nmot ……………………….(2)
After removal of two brushes, induced EMF across the brushes remains the same(since they are in parallel)=E But, the
1
current becomes th
4
Ia P
So, P = E. =
4 4
If
Vt
Eb
Speed =
k
Since, both & Eb are proportional to
terminal voltage, speed will remain constant for a lossless machine.
14.056
k = = 5.13 10−3 N − m − sec2 rad2
(52.36 )
2
2
2 = 750rpm = 78.54 rad sec
60
T2 = k 22 = 5.13 10 −3 ( 78.54 )
2
T2 = 31.64 N − m = k1 .Ia2
31.64
Ia2 = 18A
1.757
Eb2 = k12 = 1.757 78.54 138 V
Vt2 = Eb2 + Ia2Ra = 138 + 18 = 156V
New Terminal Voltage, Vt2 = 156V
E1 = 120V = k. 2 ( 60
6000 )
V − sec
k = 0.191
rad
0.5
I a for, T = 0.5N − m is given as Ia = = 2.617A
0.191
Now when the terminal voltage is reduced to 60V.
Modified EMF, E2 = 60 − 2.617 2.5 = 53.45V
E2 53.45
2 = = = 279.87rad sec
k 0.191
60
N2 = N2
2
279.87 60
Or, N2 = 2673rpm
6.28
220
Field Current, I f = = 4A
55
Since, the machine is Shunt Connected, Ia = IL + If = 4 + 45.45 = 49.45A
Generated EMF, Eg = 220 + 49.45 0.25 + 2 = 234.36V
1500
Nm = = 1387.11rpm
1.081
200
Hence, k e = = 5 10 −5
( 2000 )
2
V − I a (R a + R f )
Also, = E = E = E =
k kk k1 k1
T
V− (R + R f ) (R + R ) V
k1 a
From (1), = = − a 2 f .T +
k1 k1 k1
Ra V
=− .T + → y = mx + c
k12 k1
So graph would look like as shown,
m → Slope → Negative
From speed-torque characteristics we can see that, there will be linear decrement in speed with increase in torque.
Proportionality Constant,
180
k = = 6.875 V − sec rad
2 250
60
Armature control:
It provides constant torque drive. By keeping
the field current at maximum value, full-load
torque can be obtained at full-load armature
current at all speeds.
This control provides speed below base speed.
(E ) = V − I R = 1 − 1 0.02 = 0.98pu
b m m
(P ) = E I = 0.98 1 = 0.98pu
output motor b m
This output power of motor is fed to generator so input power and developed power of generator is 0.98 pu.
Vg 0.96
RL = = = 0.96pu
Ig 1
Inside a magnetic material flux flows from South Pole to North pole & from North Pole to South Pole in the air gap.
So, FS will indicate flux from NS to SS and Fr will indicate from Sr to Nr
ABC → Stator surface → N pole
CDA → Stator surface → S pole
abc → Rotor surface → S pole
cda → Rotor surface → N pole
Torque will be in anti-clockwise direction as rotor M.M.F lags stator M.M.F and as only rotor can move so rotor poles will
try align themselves along stator poles.
Let (R a
+ R sc = R )
E = V − IR
E = kmN
V − IR
N=
k m
In series motor I
So at constant power load T = Constant
If ' ' is decreased by 1/4th of its rated value, then torque will increases by 4 times to maintain constant power.
Since, in series motor T I
2
(E ) b no −load
= Vt − IaNLR a = 25 − 1.5 0.8 = 23.8V
(P )
output no −load
= 28.8 1.5 = 35.7W → Rotational losses
At loaded condition,
Input power = 25 3.5 = 87.5W
The direction of magnetic field will be from North pole to South Pole i.e. from right to left.
The conductors of coil C2 rotate in same or opposite direction of magnetic field so cross product for induced emf will be
zero.
The velocity of conductors will be perpendicular to the magnetic field so cross product will be maximum and hence
maximum emf will be induced in C1.
The direction of induced emf can be determined by Right Hand Thumb Rule and so direction of emf will be outwards in C1
and inwards for C1’.
2
Since, =1
1 2
1
P2 = 50kW = 25kW
2
So, power becomes half at half the rated speed.
P = (k) .Ia
P Ia
Hence, P → 2,Q → 3,R → 1
Since E N
E2 2 N2
=
E1 1 N1
N2 2 E2
=
N1 1 E1
N2 1 196
=
N1 1.11 204
N2
= 0.873
N1
474
R a + R ex = = 31.6
15
Rex = 31.6 − 0.5 = 31.1
Assuming that the commutator is stationery and brushes are rotating in opposite direction then when the brushes arrive at
AB after rotation then maximum emf would be collected.
So, waveform shifted looks like as shown below,
200 12000
K m = E = = = 1.273
1500 3000
2
60
Since, field voltage is unchanged.
Km = Constant
Torque = (K ) I
m a
5 = 1.273 Ia
Ia = 3.927A
Under loaded condition, N = 1400 rpm
2
E = 1.273 1400 = 186.63V
60
Vt − Ea
Armature resistance, R a =
Ia
200 − 186.63
Ra = = 3.4
3.927
Torque ( flux )( Ia )
Since torque = constant
1
Ia
flux
Initially, Ra = 1 , Ia = 10A
Ea = Vt − IaRa = 220 − 10 1 = 210V
Ea
Ea 2 2
= = 0.9
Ea 1 1
Ia2 = 10 = 11.11A
0.9
Now, Vt = Ea 2 + Ia 2R 2
65.8
Ea = 220 − = 203.55V
4
Under loaded condition
IL = 52.8A
If = 1.8A
Ia = IL − If = 52.8 − 1.8 = 51A
By KVL,
220 = Ea + 51 0.25
Ea = 207.25V
Since Ea N
E1 1 N
= . 1
E2 2
N2
203.55 1 1000
=
207.25 2 1600
2 1000 207.25
= = 0.6363
1 1600 203.55
2 = 63.63% of 1
(Eb ) NL
= V − IaR a = 230 − 4 0.4 = 228.4V
Under full load, IL = 70A
Field current will remain constant as terminal voltage is constant
Ia = 70 − 1 = 69A
(Eb ) FL
= V − IaR a = 230 − 69 0.4 = 202.4V
We know, Eb =K m
Since, flux is constant,
(Eb ) FL
=
NFL
(Eb ) NL
NNL
NFL 202.4
=
1400 228.4
NFL = 1240.63 rpm
Eb Vt 230
K' = = = = 1.568
2
1400
60
Torque = = KIa = K'Ia = 1.568 8 = 12.55N − m
Eg2 2N2
=
Eg1 1N1
59. Ans: 8
Solution:
Under no load, Ia = 0
VT = Eb
Ia
Vt = E b2 +IaR a = Eb3 + R
2 a
Ia
100 + IaR a = 104 + R
2 a
Ia
4= R
2 a
8
Ia = = 8A
Ra
Therefore, full load armature current = 8A
Vt − Eb 230 − 222
Armature Current, Ia = = = 29.9625A
Ra 0.267
Developed Power = EbIa = 6651.685W
Shaft power = Developed power – Rotational loss
Shaft power = 6651.685 – 600= 6051.685W
Psh 6051.685
Tsh = = = 57.789N − m
2
1000
60
TL = 2.78r
Under steady state neglecting rotational losses, both torques must be equal
= 200 − 0.04 2.78
= 179.985 rad / sec
Elap 1
=
Ewave 2
Elap = 115V
In lap connected since number of parallel paths are now doubled, so current rating is doubled.
Ilap = 2.I wave
1
Elap = Ewave
2
P = E.I = Cons tant
So, power rating = 5 kW
After one pole pitch, conductor changes the pole so current in conductor reverses so half cycle of current takes 25 m sec.
So, the armature current waveform looks like:
Vt 220
If = = = 5A
Rf 44
By KCL, Ia = IL + If = 45 + 5 = 50A
By KVL,
Eg = Vt + IaRa = 220 + 50 0.01 = 220.5V
Developed power = EgIa = 220.5 50 = 11025W
Mechanical input = Pdev + Pr ot = 11025 + 375 = 11400W
Electrical output = 220 45 = 9900W
P 9900
Efficiency, = e 100% = 100 = 86.84%
Pm 11400
2
T2 N2
= = 0.25
T1 N1
Ia2
= 0.5
Ia1
Ia2 = 15A
EMF, E N IaN
E2 I N
= a2 2
E1 Ia1 N1
E2 = 205 0.5 0.5 = 51.25V
V − E2 220 − 51.25
R2 = = = 11.25
I2 15
Rext = 11.25 − 0.5 = 10.75
km
2
(30) − 220km + 1.4 = 0
km = 2.3278
70
Ia = = 30.07 A
km
Since T = kIa
500 1
k = =
2000 4
Since motor is separately excited k = constant
At no load, if mechanical losses are ignored
Ia = 0
Vt = E = 150
150 = km
150
m = = 600 rad sec
1
4
188 10
N2 = 1000 = 824.56 rpm
190 12
Since, the speed should be rounded off to nearest integer the speed will be 825rpm
220
Field current I f = = 1A
220
At full load,
Line current, IL = 25A
Line current, IL = 3A
E speed
E2 N2
=
E1 N1
219
N2 = 1500 = 1579.32 rpm
208
No load current 5 A
= 247.5 Volts
Ebload = 250 − 47.5(0.2) − 1 2
= 238.5 volts
N2 Eb2 1
=
N1 Eb1 2
N2 238.5 1
=
1200 247.5 0.951
N2 = 1217.22rpm
100 103
IL = = 500 A
200
200
Ish = = 4A
50
Ia = 504 A
Eq = V + Ia Ra + Brush drop
=214.6 V
In motoring case: VI = 10 kW, V = 200 V
10000
I = = 50A
200
Field current, If = 4 A, Ia = IL - If
= 46 A
Eb = V – Ia Ra – Brush Drop
= 200 – 46 (0.025) – 2
= 196.85 V
Nm Eb
=
Ng Eg
Eb
Nm = Ng
Eg
196.85
Nm = 300 = 275.18rpm
214.6
Rext = 10Ω
T ∝ φIa
∴ Flux constant,
T∝
T2 Ia2
=
T1 Ia 1 I
a
Given, T ∝ ,
T2 N2
=
T1 N1 N
Ia2 N2
=
Ia1 N1
30
Ia2 = (N )
1000 2
Ia2 = 0.03N2
Ef
N
280 − 0.33N2
=
250
N2 = 482.76 rpm
The poles formed on stator based on direction of magnetic field are also shown.
Number of poles = 4
p
e = : = 2 / pe
2 m m
If θe = 90°, θm = 45°
Geometry Neutral Axis (GNA) lies at 90° electrical to pole axis ie. at 45° mechanical to poles axis. GNA is shown in figure
below.
Since the coils a-a’ & b-b’ lie along GNA, emf induced in each of them is 0.
01. Damper winding is provided in a poly-phase 06. A three phase alternator has negligible stator
synchronous motor in order to [1991] resistance. A short circuit test is conducted on this
(a) Damp out the noise of the machine alternator. At a particular speed a field current of I f1 is
(b) Prevent hunting required to drive the rated armature current. If the speed of
(c) Provide starting torque the alternator is reduced to half, the field current required
(d) Provide a cylindrical structure to reduce wind friction to maintain rated armature current [1993]
(a) Would be equal to I f1
02. A 500 MVA, 11 KV synchronous generator has 0.2 p.u.
synchronous reactance. The p.u. synchronous reactance on (b) Would be equal to 2If1
the base values of 100 MVA and 22 KV is: [1991] (c) Would be equal to If1 / 2
(a) 0.16 (b) 0.01 (d) Cannot be predicted due to insufficient data
(c) 4.0 (d) 0.25
07. A synchronous motor operates at 0.8 p.f. lagging. If the
03. A 10 kVA, 380V, 4-pole, 50 Hz, star-connected field current of the motor is continuously increased [1993]
cyclindrical rotor alternator has a stator resistance and (a) The power factor decreases upto a certain value of field
synchronous reactance of 1 ohm and 15 ohms respectively. current and thereafter it increases
It supplies a load of 8 kW at rated voltage and 0.8 power (b) The armature current increases upto a certain value of
factor lagging. [1991] field current and thereafter it decreases
(a) Draw a phasor diagram of operation (c) The power factor increases upto a certain value of field
(b) Express the resistance and synchronous reactance in per current and thereafter it decreases
unit values with the machine rating as the base (d) The armature current decreases upto a certain value of
(c) Calculate the percentage regulation field current and thereafter it increases.
(d) What is the terminal voltage if the load is suddenly
removed (with the speed and excitation unaltered)? 08. Match the items on the right hand side with those on
04. The torque angle of a synchronous machine operating left hand side [1994]
from a constant voltage bus, is usually defined as the space (a) Commutation (P) Resistive load
angle between [1992] (b) V-curves (Q) Inductive load
(a) Rotor mmf wave and stator mmf wave (c) Freewheeling diode (R) Capacitive load
(b) Rotor mmf wave and resultant flux density wave (d) Overlap (S) Inter pole
(c) Stator mmf wave and resultant flux density wave (T) Source Inductance
(d) Stator mmf wave and resultant mmf wave (U) Synchronous motor
05. Figure depicts the load characteristics of an isolated 09. A synchronous motor on load draws a current at a
three-phase alternator, running at constant speed. Match
leading power factor angle . If the internal power factor
the following sets of operating conditions with the given
characteristics. Disregard the effects of saliency, saturation angle- which is the phase angle between the excitation
and stator resistance. [1992] e.m.f. and current in the time phasor diagram is then
the air gap excitation m.m.f lags the armature m.m.f by
(a) (b) + [1995]
2
(c) − (d) +
2
(a) Constant excitation and non-zero leading power-factor
(b) Constant excitation and zero power-factor leading 10. The distribution factor for a 36 slot stator with three-
(c) Constant terminal voltage and zero power-factor phase, 8-pole winding, having 120° phase spread, is
leading _____________ [1995]
(d) Constant terminal voltage and non-zero leading power-
factor
11. A three-phase, 50 Hz, 415V, synchronous machine 18. A three phase alternator is wound with a 60 degree
operates at rated voltage and at a leading power factor of phase-spread armature windings and develops 300 kVA. If
0.8. Shaft power is 15 kW and excitation emf is 400V. If per the armature is reconnected utilizing all the coils for single
phase resistance is 0.5 ohm, find the synchronous phase operation with a phase spread of 180 degrees, the
reactance. Neglect mechanical losses of the system. [1995] new rating of the machine is [1999]
(a) 100 kVA (b) 200 kVA
12. A cylindrical rotor synchronous motor is switched on (c) 250 kVA (d) 300 kVA
the supply with its field winding shorted on themselves. It
will [1996] 19. A 5 MVA, 11 kV, 3-phase star connected alternator is
(a) Not start synchronized to the bus bars and is operating with an
(b) Start but not run at synchronous speed induced EMF of 125% of the rated voltage. If the load
(c) Start as an induction motor and then run as current is 500A, what is the power factor of operation? The
synchronous motor machine has a synchronous reactance of 5Ω and negligible
(d) Start and run as a synchronous motor resistance per phase. [1999]
13. In figure the characteristic that corresponds to the 20. The phase sequence of a three-phase alternator will
variation of synchronous reactance of a synchronous motor reverse if [2000]
with field current is [1996] (a) The field current is reversed keeping the direction of
rotation same
(a) Curve I (b) The field current remains the same but the direction of
rotation is reversed
(b) Curve II (c) The field current is reversed and the number of poles is
doubled
(c) Curve III (d) The number of poles is doubled without reversing the
field current
(d) Curve IV
21. A 240V dc series motor takes 40A when giving its rated
output at 1500 rpm. Its resistance is 0.3 ohms. The value of
14. During hunting of synchronous motor [1996] resistance which must be added to obtain rated torque at
(a) Negative phase sequence currents are generated 1000 rpm is: [2000]
(b) Harmonics are developed in the armature circuit (a) 6 ohms (b) 5.7 ohms
(c) Damper bar develops torque (c) 2.2 ohms (d) 1.9 ohms
(d) Field excitation increases
22. A single-phase, 2000V alternator has armature
15. A single-phase alternator has a synchronous reactance resistance and reactance of 0.8 ohms and 4.94 ohms
of 2 ohms and negligible resistance. If it supplies 10A to a respectively. The voltage regulation of the alternator at
purely capacitive load at 200V, then generated e.m.f will 100A load at 0.8 leading power-factor is: [2000]
be… V and the regulation will be…% [1997] (a) 7% (b) -8.9%
(c) 14% (d) 0%
16. A synchronous generator connected to an infinite bus
is overexcited. Considering only the reactive power, from 23. A 2300V, 3-phase synchronous motor driving a pump is
the point of view of the system, the machine acts as [1998] provided with a line ammeter and a field rheostat. When
(a) a capacitor the rheostat is adjusted such that the ac line current is
(b) an inductor minimum, the armature reads 8.8A. What is the power
(c) a resistor being delivered to the pump, neglecting losses?
How should the rheostat be adjusted so that the motor
(d) none of the above
operates at 0.8 leading power factor? How many KVARs is
the motor supply to the system at this new power factor?
17. Higher synchronous reactance is preferred in the
[2000]
present day alternators, because one can have [1999]
(a) Reduced sub-transient currents
24. It is desirable to eliminate 5th harmonic voltage from
(b) Reduced harmonic currents
the phase voltage of an alternator. The coils should be
(c) Reduced transient currents
short-pitched by an electrical angle of [2001]
(d) Higher voltage regulation with load
(a) 30 o (b) 36 o 29. The flux per pole in a synchronous motor with the field
(c) 72 o (d) 18 o circuit ON and the stator disconnected from the supply is
found to be 25mWb. When the stator is connected to the
25. Figure shows the magnetization curves of an alternator
rated supply with the field excitation unchanged, the flux
at rated armature current, unity power factor and also at no
per pole in the machine is found to be 20mWb while the
load. The magnetization curve for rated armature current,
0.8 power factor leading is given by [2001] motor is running on no load. [2002]
Assuming no load losses to be zero, the no load current
down by the motor from the supply
(a) Lags the supply voltage
(b)Leads the supply voltage
(c) Is in phase with the supply voltage
(d) Is zero
(a) Synchronous reactance 39. In relation to the synchronous machines, which one of
(b) Magnetizing reactance the following statements is false? [2005]
(c) Potier reactance (a) In salient pole machines, the direct-axis synchronous
(d) Leakage reactance
reactance is greater than the quadrature-axis synchronous
reactance
33. A 4-pole, 3-phase, double layer winding is housed in a
36-slot stator for an ac machine with 60° phase spread. Coil (b) The damper bars help the synchronous motor self-start
span is 7 slot pitches. Number of slots in which top and (c) Short circuit ratio is the ratio of the field current
bottom layers belong to different phases is [2003] required to produce the rated voltage on open circuit to
(a) 24 (b) 18 the rated armature current
(c) 12 (d) 0 (d) The V-curve of a synchronous motor represents the
variation in the armature current with field excitation, at a
34. The synchronous speed for the seventh space harmonic
mmf wave of a 3-phase, 8 pole, 50 Hz induction machine is given output power
[2004]
(a) 107.14 rpm in forward direction Statement for Linked Answer Questions 40(A) & 40(B):
(b) 107.14 rpm in reverse direction A 1000 kVA, 6.6 kV, 3-phase star connected cylindrical pole
(c) 5250 rpm in forward direction synchronous generator has a synchronous reactance of 20
(d) 5250 rpm in reverse direction . Neglect the armature resistance and consider operation
at full load and unity power factor. [2005]
35. Two 3-phases, Y-connected alternators are to be (A) The induced emf (line-to-line) is close to
paralleled to a set of common bus bars. The armature has a (a) 5.5 kV (b) 7.2 kV
per phase synchronous reactance of 1.7 and negligible (c) 9.6 kV (d) 12.5 kV
armature resistance. The line voltage of the first machines (B) The power (or torque) angle is close to
is adjusted to 3300 V and that of the second machine is (a) 13.9° (b) 18.3°
adjusted to 3200 V. the machine voltages are in phase at (c) 24.6° (d) 33.0°
the instant they are paralleled. Under this condition, the
synchronizing current per phase will be [2004] 41. A synchronous generator is feeding a zero power factor
(a) 16.98 A (b) 29.41 A (lagging) load at rated current. The armature reaction is
(c) 33.96 A (d) 58.82 A [2006]
(a) Magnetizing (b) Demagnetizing
36. A 400V, 50 kVA, 0.8 pf leading -connected, 50 Hz (c) Cross-magnetizing (d) Ineffective
synchronous machine has a synchronous reactance of 2Ω
and negligible armature resistance. The friction and 42. A 3 phase, 400 V, 5 kW, star connected synchronous
windage losses are 2kW and the core loss is 0.8 kW. The motor having an internal reactance of 10 is operating at
shaft is supplying 9kW load at a power factor of 0.8 50% load, unit pf. Now, the excitation is increased by 1%.
leading. The line current drawn is [2004] What will be the new load in percent, if the power factor is
(a) 12.29 A (b) 16.24 A to be kept same? Neglect all losses and consider linear
(c) 21.29 A (d) 36.88 A magnetic circuit. [2006]
(a) 67.9% (b) 56.9%
37. A 500 MW 3-phase Y-connected synchronous (c) 51% (d) 50%
generator has a rated voltage of 21.5 kV at 0.85 pf. The line
current when operating at full load rated conditions will be Common Data for Questions 43, 44 , 45:
[2004] A 4 pole, 50 Hz synchronous generator has 48 slots in
(a) 13.43 kA (b) 15.79 kA which a double layer winding is housed. Each coil has 10
(c) 23.25 kA (d) 27.36 kA turns and is short pitched by an angle to 36o electrical. The
fundamental flux per pole is 0.025Wb.
38. A hydraulic turbine having rated speed of 250 rpm is
connected to a synchronous generator. In order to produce
power at 50 Hz, the number of poles required in the 43. The line-to-line induced EMF (in volts). For a three
generator are [2004] phase star connection is approximately [2006]
(a) 6 (b) 12 (a) 808 (b) 888
(c) 16 (d) 24 (c) 1400 (d) 1538
44. The line-to-line induced EMF (in volts), for a two phase 50. The excitation voltage (E) and load angle () will
connection is approximately [2006] respectively be [2008]
(a) 1143 (b) 1332 (a) 0.8pu and 36.86o lag
(c) 1617 (d) 1791 (b) 0.8pu and 36.86o lead
(c) 1.17pu and 30.96o lead
45. The fifth harmonic component of phase emf (d) 1.17pu and 30.96o lag
(in volts), for a three phase star connection is [2006]
(a) 0 (b) 269 51. Keeping the excitation voltage same, the load on the
(c) 281 (d) 808 motor is increased such that the motor current increases by
20%. The operating power factor will become [2008]
46. A three-phase synchronous motor connected to ac (a) 0.995 lagging (b) 0.995 leading
mains is running at full load and unity power factor. If its (c) 0.791 lagging (d) 0.848 leading
shaft load is reduced by half, with field current held
constant, its new power factor will be [2007] 52. A field excitation of 20 A in a certain alternator results
(a) Unity in an armature current of 400 A in short Circuit and a
(b) Leading terminal voltage of 2000 V on open circuit. The magnitude
(c) Lagging of the internal voltage drop within the machine at a load
(d) Dependent on machine parameters current of 200 A is [2009]
(a) 1V (b) 10V
47. A 100 kVA, 415V (line), star-connected synchronous (c) 100V (d) 1000V
machine generates rated open circuit voltage of 415 V at a
field current of 15 A. The short circuit armature current at a 53. A three-phase, salient pole synchronous motor is
field current of 10A is equal to the rated armature current. connected to an infinite bus. It is operated at no load at
The per unit saturated synchronous reactance is [2007] normal excitation. The field excitation of the motor is first
(a) 1.731 (b) 1.5 reduced to zero and then increased in the reverse direction
(c) 0.666 (d) 0.577 gradually. Then the armature current [2011]
(a) Increase continuously
48. An isolated 50 Hz synchronous generator is rated at 15 (b) First increases and then decreases steeply
(c) First decreases and then increases steeply
MW which is also the maximum continuous power limit of
(d) Remains constant
its prime mover. It is equipped with a speed governor with
5% droop. Initially, the generator is feeding three loads of 4 54. The direct axis and quadrature axis reactance of a
MW each at 50 Hz. One of these loads is programmed to salient pole alternator are 1.2p.u. and 1.0 p.u. respectively.
trip permanently if the frequency falls below 48 Hz. If an The armature resistance is negligible. If this alternator is
additional load of 3.5 MW is connected then the frequency delivering rated kVA at upf and at rated voltage then its
will settle down to [2007] power angle is [2011]
49. Distributed winding and short chording employed in 55. A star connected 400V, 50Hz, 4 pole synchronous
AC machines will result in [2008] machine gave the following open circuit and short circuit
(a) Increase in emf and reduction in harmonics. test results: [2014-01]
(b) Reduction in emf and increase in harmonics. Open circuit Test: Voc = 400V (rms,line to line ) at field
(c) Increase in both emf and harmonics.
(d) Reduction in both emf and harmonics. current If = 2.3A
56. A three phase synchronous generator is to be Hz/MW. Total load in the system is 2.5MW. Assuming that
connected to the infinite bus. The lamps are connected as the generators are operating under their respective droop
shown in the figure for the synchronization. The phase characteristics, the frequency of the power system in Hz in
sequence of bus voltage is R-Y-B and that of incoming the steady state is__________. [2014-02]
generator voltage is R-Y-B.
60. In a synchronous machine, hunting is predominantly
damped by [2014-03]
(a) mechanical losses in the rotor
(b) iron losses in the rotor
(c) copper losses in the stator
(d) copper losses in the rotor
66. If a synchronous motor is running at a leading power 73. A three-phase cylindrical rotor synchronous generator
factor, its excitation induced voltage (Ef) is [2017-02]
has a synchronous reactance XS and a negligible armature
(a) Equal to terminal voltage Vt
(b) Higher than the terminal voltage Vt resistance. The magnitude of per phase terminal voltage is
(c) Less than terminal voltage Vt
VA and the magnitude of per phase induced emf is EA.
(d) Dependent upon supply voltage Vt
Considering the following two statements, P and Q,
67. Two generating units rated 300 MW and 400 MW have
P : For any three phase balanced leading load connected
governor speed regulation of 6% and 4% respectively from
no load to full load. Both the generating units are across the terminals of this synchronous generator, VA is
operating in parallel to share a load of 600 MW. Assuming
always more than EA
free governor action, the load shared by the larger unit is
___________ MW. [2017-02] Q : For any three-phase balanced lagging load connected
across the terminals of this synchronous generator, VA is
68. A 25 kVA, 400 V, –connected, 3-phase, cylindrical
rotor synchronous generator requires a field current of 5 A always less than EA
to maintain the rated armature current under short-circuit Which of the following options is correct? [2020]
condition. For the same field current, the open-circuit
voltage is 360 V. Neglecting the armature resistance and (a) P is false and Q is true. (b) P is true and Q is false.
magnetic saturation, its voltage regulation (in % with (c) P is false and Q is false. (d) P is true and Q is true.
respect to terminal voltage), when the generator delivers
the rated load at 0.8 pf leading, at rated terminal voltage is
___________. [2017-02] 74. A single 50 Hz synchronous generator on droop control
was delivering 100 MW power to a system. Due to increase
69. A 3-phase, 2-pole, 50 Hz, synchronous generator has a in load, generator power had to be increased by 10 MW, as
rating of 250 MVA. 0.8 pf lagging. The kinetic energy of the a result of which, system frequency dropped to 49.75 Hz.
machine at synchronous speed is 1000 MJ. The machine is
Further increase in load in the system resulted in a
running steadily at synchronous speed and delivering 60
frequency of 49.25 Hz. At this condition, the power in MW
MW power at a power angle of 10 electrical degrees. If the
load is suddenly removed, assuming the acceleration is supplied by the generator is __________ (rounded off to 2
constant for 10 cycles, the value of the power angle after 5 decimal pages). [2020]
cycles is ___________ electrical degrees. [2017-02]
75. The figure below shows the per-phase Open Circuit
70. In a salient pole synchronous motor, the developed Characteristics (measured in V) and Short Circuit
reluctance torque attains the maximum value when the Characteristics (measured in A) of a 14 kVA, 400~V. 50~Hz,
load angle in electrical degrees is [2018] 4-pole, 3-phase, delta connected alternator, driven at 1500
(a) 0 (b) 45 rpm. The field current, If is measured in A. Readings taken
(c) 60 (d) 90 are marked as respective (x, y) coordinates in the figure.
Ratio of the unsaturated and saturated synchronous
71. A Three-phase synchronous motor draws 200 A from impedances (Zs(unsat) / Zs(sat)) of the alternator is closest to
the line at unity power factor at rated load. Considering the [2020]
same line voltage and load, the line current at a power
factor of 0.5 leading is. [2019]
(a) 300 A (b) 400 A
(c) 100 A (d) 200 A
76. A cylindrical rotor synchronous generator with constant 79. A star-connected 3-phase, 400 V, 50 kVA, 50 Hz
real power output and constant terminal voltage is synchronous motor has a synchronous reactance of 1 ohm
supplying 100 A current to a 0.9 lagging power factor load. per phase with negligible armature resistance. The shaft
An ideal reactor is now connected in parallel with the load,
load on the motor is 10 kW while the power factor is 0.8
as a result of which the total lagging reactive power
leading. The loss in the motor is 2 kW. The magnitude of
requirement of the load is twice the previous value while
the real power remains unchanged. The armature current is the per phase excitation emf of the motor, in volts, is
now _________ A (Rounded off to 2 decimal places). [2020] ___________ (round off to nearest integer). [2022]
77. A cylindrical rotor synchronous generator has steady 80. A three-phase synchronous motor with synchronous
state synchronous reactance of 0.7 pu and subtransient impedance of 0.1+j0.3 per unit per phase has a static
stability limit of 2.5 per unit. The corresponding excitation
reactance of 0.2 pu. It is operating at (1 + j0) pu terminal
voltage in per unit is (Round off to 2 decimal places).
voltage with an internal emf of (1 + j0.7) pu. Following a
[2023]
three-phase solid short circuit fault at the terminal of the
generator, the magnitude of the subtransient internal emf
(rounded off to 2 decimal places) is _____________ pu. [2020]
Solutions
01. Ans: (c)
Solution:
Synchronous motor is not a self-starting motor. This is because the rotor is unable to rotate quickly because of large
mechanical time constant or inertia of rotor (net torque is zero and rotor is unable to get locked to stator poles)
The damper winding acts as a short circuited winding like in squirrel cage induction motor. When supply is given to stator
and excitation is off, the rotor starts like squirrel cage induction motor and gains speed near to synchronous speed, such
that when excitation is switched on, the rotor poles can catch the stator poles easily and get locked [Effect of rotor inertia
is cancelled out].
The damper bars also help to damp out oscillations in synchronous state (known as Hunting)
(MVA ) (kV )
2
(E cos V )
f t
OP = Ef cos
OQ = Vt
OP OQ → (Overexcited)
( V ) = (380 ) = 14.44
2 2
(Z) = base
(S ) 10 10
base 3
base
R () 1
R (pu) =
s
= = 0.06925 pu
s
Z 14.44 base
Xs ( ) 15
X s (p.u) = = = 1.03878 pu
Zbase 14.44
(c) P= 3 VLILcos
8000= 3 x380 x IL x 0.8
IL= 15.2 A
→
IL =15.2 (-36.870)
→ → → →
Ef = Vt + Ia Z s
380
Ef =
3
( )
00 + 15.2 −36.870 x (1 + j15 )
Ef = 407.07525.190 Volts
Ef − Vt
%Vreg= x100
Vt
380
407.075 −
%Vreg= 3 x100 = 85.54%
380
3
Vt (L − L ) = 705.07V
The electric space angle ' ' between rotor and stator M.M.F is called ‘Torque angle’ and the electric space angle between
either stator or rotor M.M.F and resultant is called ‘Load angle’ → sor r
(b) In case of zero power factor leading, armature reaction is completely magnetizing.
So, terminal voltage rises at a faster rate.
(c) For constant terminal voltage and ZPF leading current, if the load current increases, then to maintain constant terminal
voltage we have to reduce the excitation voltage due to increasing magnetizing effect of armature reaction.
(d) In case of non-zero leading power factor load, to maintain constant terminal voltage, excitation must be reduced for
increase in load current upto a certain value. But beyond rated current the cross magnetizing effect of armature reaction is
dominant. Hence, ‘ Ef ’ must be increased.
k1f k1
(I )
a rated
=
k 2f
=
k2
So, if the flux remains constant, rated armature current can be maintained by given field current, even if speed is changed.
As can be seen the angle between the excitation emf and armature current (or mmf) is ‘’ and since the angle between
excitation emf and field mmf is 900. So, the angle between armature and field mmf is 90 − ψ
( V cos + I R ) + ( V sin − I X )
2 2
Ef = t a a t a s
So, at high values of field current the voltage will saturate but current will keep on increasing and hence their ratio i.e.
Synchronous Reactance will decrease.
(
Ef = 200 + 10900 2900 )( )
Ef = 200 − 20 = 180V
Ef − Vt 180 − 200
Voltage regulation= = = −10%
Vt 200
16. Ans: (a)
Solution:
An over excited synchronous generator delivers lagging VARs to the infinite bus (or takes leading VARs from the bus) and
hence it acts like a capacitor from system’s point of view.
k d2 =
sin ( 2) = 2
( 2 )
Since armature conductors are same, the current carrying capability will be the same.
(kVA ) rating
E kd
3
(kVA ) 1
=
300
= =
3
(kVA ) 2
(kVA )2 2
2
(kVA ) 2
= 200 kVA
(1 ) + ( 2 )
2 2
E = (I X )
2
2
f a s
+ Vt2 + 2Vt . Ia X S sin
11
Ef = 1.25 103 V
3
11
Vt = 103 V [Per phase value]
3
( I ) ( X ) = 500 5 = 2500 V
a s
2 2
11 11 11
103 = ( 2500 ) +
2
1.25 103 + 2 103 500 5 sin
3 3 3
sin = 0.5176
= 31.170
cos = 0.8556 lag
Now if field current is reversed, it will only reverse the pole as shown
Hence now phase ‘a’ will get maximum negative peak EMF first then phase ‘b’ will get
maximum negative peak EMF and then ‘c’.
So phase sequence doesn’t change and it remains ABC.
Since, the torque remains at the rated value, the armature current ( I ) remains constant.
a
Ef − V 1822.316 − 2000
V.R = 100 = 8.884%
100 = −8.384%
V 2000
From, the V-curve of Synchronous Motor it can be observed that minimum line current occurs at upf load as shown below.
Otherwise, for a constant power input and terminal voltage
P = 3Vt Ia cos
Armature current will be minimum when power factor is maximum
i.e. unity power factor.
(i) Since losses are neglected, input power is same as
output power.
P = 3 Vt Ia cos00
P= 3 2300 8.8 1 = 35.056kW
(ii) For getting leading 0.8 p.f, motor has to be overexcited, now output load power remains same as load is not changed.
3 Vt Ia1 cos 1 = 3 Vt Ia2 cos 2
cos 1
8.8 1
Ia2 = Ia1 = = 11A
cos 2
0.8
So we should decrease field resistance using rheostat until line ammeter reads 11A
Since, the synchronous impedance consist of only reactance so, the impedance angle is 900.
= 113.180 − 900 = 23.180
cos = 0.92
(iii) With excitation armature, open-circuited, output driving motor supplies power corresponding to friction and windage
and the iron losses.
P = PFraction & Windage + Piron
Piron = 1800 − 800 = 1000W
To calculate the efficiency at half load, the output will be 50% of the rated power and Copper Losses will become 1/4 th of
the original value.
(P ) = 1700
cu
4
= 425W
50 0.5 103
So, = = 91.82%
50 0.5 103 + 1000 + 425 + 800
( V cos + I R ) + ( V sin + I aX s )
2 2
Initially, EA = EB = a a
( V cos ) + ( V sin + I aX s )
2 2
So, 1.532 =
Or, Ia = 0.883p.u
(b) When, load is increased the power factor also changes but excitation remains constant. For lagging power factor,
excitation emf is given by
( V cos + I R ) + ( Vt sin + I aX s )
2 2
Ef = t a a
( V cos ) + ( V sin − I X )
2 2
Ef = t t a s
3 3
sin = 0.175
= 10.090
Since, Φ comes out to be positive. So, our assumption is correct that the pf is lagging. This can also be derived from
phasor diagram that as the load increases the pf becomes lagging.
cos = 0.9845lag
Output Power = Input Power as the machine is given to be lossless.
P = 3 Vt Ia cos = 3 415 50 0.9845 = 35.38kW
By looking into second row, we can see out of 9 slots 3 have coils of same phase & 6 have coils of different phase.
36
In 36 slots, 6 = 24 slots have coils of different phase.
9
NS
Synchronous Speed of 7th order space harmonic =
7
120 50
Speed of Fundamental RMF, Ns = ( ) 8
= 750rpm
750
(N )
s 7th Harmonic
=
7
= 107.14rpm
Also, (3k + 1) order harmonics are positive sequence and (3k-1) harmonics are negative sequence and so 7th order
harmonic magnetic field rotates in forward direction.
• Synchronous Motor is not self-starting as the rotor is not able to catch up with the rotating magnetic field rotating at
synchronous speed sue to which pulsating torque is produced and motor cannot rotate in one direction. Damper Bars
help the synchronous motor to self-start as an Induction Motor.
• Short circuit ratio is the ratio of the field current required to produce the rated voltage on open circuit to the field
current required to produce rated armature current on short circuit. It is reciprocal of per unit synchronous reactance.
So, third statement is false.
• The V-curve of a synchronous motor represents the variation in the armature current with field excitation, at a given
output power.
(V) L −L
= 6.6kV
Rated Armature Current, I = S 1000
a
= = 87.477A
3 VL −L 3 6.6
As alternator is Y-connected
VL −L 6.6
Per-phase terminal voltage Vt = = = 3.81kV
3 3
Vt = 3.8100 kV
Ia = 87.47700 A [Unity power factor]
( V cos + I R ) + ( V sin + I aX s )
2 2
E = a a
( )
2 2
E = V + I2a R 2a + X 2s + 2IaX s sin + 2 I aR a cos
at unity pf cos = 1,sin = 0
Also Ra = 0, Xs = 10
2
400
( 236.0774 )
2
+ Ia 10
2 2
=
3
Ia = 4.8981A
5000
Rated current at upf = = 7.2168A
3 400 1
4.8981
New current in percent = 100% = 67.9%
7.2168
K w = 0.91
sin m
2
Distribution factor, K d =
msin
2
Kd =
(
sin 6 15 )
2 = 0.9028
6sin 15( 2)
Kp = 0.951
480
Number of turns per phase = = 240
2
Induced emf per phase, Eph = 4.44fNphK w
When Ef is constant and P is reduced. decreases, the phasor diagram of synchronous motor is shown below.
Δf=0.083Hz
f=fi +Δf=50.083 Hz
Ra = 0
1
Ef = V 2 cos2 + V 2 sin2 + I2a X 2s − 2Ia X s V sin 2
Ia = 1.2(Ia )(initial) = 1.2 0.6 = 0.72
−1.44sin = −0.1495
sin = 0.1038
= 5.960
pf= cos = 0.995 lag
If P=0 = 0 or 180
Assume initially =0
The phasor diagram looks like as shown below
Now here Iq = 0 and
Vt − Ef = Ia Xd increases
And armature current increases.
When we increase excitation in reverse direction
Ef becomes negative or we can say = 180
0
10 2.3
ISC = = 15.33A
If =2.3 1.5
Voc 400
Synchronous Reactance, XS = = = 15.06
3 ISC 3 15.33
56. Ans: (a)
Solution:
L a corresponds to phase R
L b corresponds to phase Y
L c corresponds to phase B
A lamp goes off when voltage of generator &
infinite bus corresponding to that
phase has same magnitude & phase.
If both had the same phase sequence, all lamps would have gone off at the same instant (when all phases would have
coincided) . Since that is not the case, incoming generator & infinite bus have opposite phase sequence.
If frequency is same then both phases will get locked to each other and no lamp will go off. Since that is not the case, the
frequency is different.
If frequency of bus is more, magnetic flux of bus rotates with respect to generator flux and after R phase, B phase will
overlap (120 ° rotation anticlockwise). So lamp C will go off, which is incorrect as after La ,Lb goes off.
If frequency of generator is more, then generator field moves anti-clockwise with respect to bus field and after R phase, Y
phase will overlap & L b goes off. Hence, option (A) is correct.
57. Ans: 2
Solution:
1800 1800
Slot angle, = = = 200
number of slots/pole 180 / 20
For a single phase connection,
number of slots 180
m= = =9
number of poles number of phases 1 20
m 9 20
sin sin
Distribution factor, Kd = 2 = 2 = 0.6398
20
m sin 9 sin
2 2
Number of conductors in each slot 180 6
Number of turns = Number of slots × = = 540
2 2
For a three phase connection,
= 20°
m= Number of slots 180 = 3
=
Number of poles Number of phases 3 20
m 20
sin sin 3
Distribution factor, Kd = 2 = 2 = 0.9597
20
m sin 3 sin
2 2
Number of conductors in each slot 1
Nph = Number of slots × = 180
2 Number of phases
E = 4.44 Kd fNph
E1− V1 4.44 0.6398 f 540 = 2
= =
E3− V2 4.44 0.9597 f 180
59. Ans: 50
Solution:
Given, P + P = 2.5MW ………(i)
1 2
The droop characteristics of the two
generators are shown on the right,
Droop,
(51.5 − f ) = 1
P1
f = (51.5 − P1) ………(ii)
Similarly for generator- 2 having same droop as 1
f = (51 – P2 ) ………(iii)
From (ii) & (iii)
51.5 - P1 = 51 - P2
P1-P2 = 0.5 MW ………….(iv)
( )
Ef = Vt0 − jIa (cos − jsin ) X s = Vt − IaXs sin − jIaXs cos
2
( 8082.9 )2 − 11000 = (120)2 (50)2 − 2 120
11000
50 sin
3 3
sin = 0.1443
= 8.298
11000 = −47.26
Ef = Vt0 − jIaXs = − j (120 − 8.298 ) 50 = 8082.97 − 47.26 V
3
= 0.8383125MW = 838.31kW
Xs 30 30
300 (f − f ) 400 (f − f )
+ = 600
0.06 f 0.04 f
50 (f − f) + 100 (f − f ) = 6f
144
144f = 150 f ; f = f
150
Load shared by larger machine i.e. machine 2
144
f − f
150 6 16
P2 = 400 = 400 = = 400 MW
0.04 f 150 0.04 0.04
H d2
= Pm − Pe
180f dt2
Initially, Pm = Pe = 60MW
60
Pm = Pe = pu
250
Kinetic energy = GH = 1000 MJ
1000
H= = 4MJ / MUA
250
If load is suddenly removed, Pe =0
4 d2 60
=
180 f dt2 250
d2 60
Acceleration = = 180 50 = 540 elect − deg/ sec2
dt 2
250 4
1 2
By equation of motion = 0 + t
2
5
t = 5 cycles = = 0.1 sec
50
1
= 10 + 540 0.01 = 12.7 elect deg
2
3Vt 12
1
T= − sin2
2s X q X d
1 1
(
E = 101.6166 − 2.5 ) + (76.2124 + 25) = ( 99.1166 ) + (101.2124 )
2 2 2 2 2 2
= 141.6617V
Line to line voltage= 245.38V
7. Ans: A
Solution:
• For leading of near unity. VR 0 & hence VA < EA For most leading of loads, VR < 0 & VA > EA but not for all
leading of loads.
• For all lagging of loads, VR > 0 & hence VA < EA
∴ first statement is false & second statement is True.
Change in load = 10 MW
f
Slope of droop characteristics = = −0.025Hz / MW
P
When frequency becomes 49.25 Hz
f = 49.25 – 50 = – 0.75 Hz
f
P = = 30MW
slope
P = 100 + 30 = 130 MW
At 400 V, If = 8 A
So, air gap line equation will be like,
y=mx+C
y = 100 x + 10 …………………(i)
At If = 8 A
Unsaturated voltage =100 × 8 + 10 = 810
810 81
Zsunsat = =
20 2 ……..(ii)
400 40
Zsaturated = =
And 20 2 …….(iii)
From equation (ii) and (iii)
Zunsaturated 81 / 2
= = 2.025
Zsaturated 40 / 2
cos 1 = 0.9
Q
tan 1 = 0.484 =
P
2Q
= 0.9686 = tan 2
P
cos 2 = 0.7182
100 0.9 = Ia2 0.7182
Ia2 = 125.29 A
At 400 V, If = 8 A
So, air gap line equation will be like,
y=mx+C
y = 100 x + 10 …………………(i)
At If = 8 A
Unsaturated voltage =100 × 8 + 10 = 810
810 81
Zsunsat = =
20 2 ……..(ii)
400 40
Zsaturated = =
And 20 2 …….(iii)
From equation (ii) and (iii)
Zunsaturated 81 / 2
= = 2.025
Zsaturated 40 / 2
cos 1 = 0.9
Q
tan 1 = 0.484 =
P
2Q
= 0.9686 = tan 2
P
cos 2 = 0.7182
100 0.9 = Ia2 0.7182
Ia2 = 125.29 A
Solution:
Pre-fault condition
Ea − Vt (1 + j0.7) − 1
Ia = = = 1 pu
jxs j0.7
During fault
Connect – Vt at terminals
Use sub transient reactance
1
If = = − j 5pu
j0.2
f0 − f f0 − f
P1 = 250 P = 400
f − 0.94f 2 f − 0.936f
0 0 0 0
P1 + P2 = 500
250 400
(f0 − f) + = 500
0.06f0 0.064f0
f = 0.9542 f0
∴ P1 = 190.833 mW
( V cos − I R ) + ( V sin I X )
2 2
Eb = a a a s
( V cos − I R ) + ( V sin + I X )
2 2
Eb = a a a s
Ef = 1.5811 pu
01. In a poly-phase squirrel-cage induction motor, 08. In a variable frequency induction motor drive, the
increased starting torque can be obtained by [1991] voltage must be varied _____________ to the frequency.
(a) Increasing the frequency of operation [1994]
(b) Using deep-bar rotors
(c) Increasing the number of poles 09. An induction motor is fed from a balanced three phase
(d) Using a double-cage rotor supply at rated voltage and frequency through a bank of
three single phase transformers connected in delta-delta.
02. A prime mover drives a 6 pole, 3-phase induction
One unit of the bank develops fault and is removed. Then,
frequency converter. The converter is connected to 60 Hz,
[1995]
3-phase supply on the primary. If the prime mover speed is
3000 rpm, the frequencies of the possible outputs from the (a) Single phasing will occur and the machine fails to start
converter are [1991] (b) Single phasing will not occur but the motor terminal
(a) 120 Hz, 60 Hz (b) 90 Hz, 210 Hz voltages will become unbalanced and the machine can be
(c) 186 Hz, 86 Hz (d) 180 Hz, 210 Hz loaded to the extent of 57.7% of its rating.
(c) The machine can be loaded to the extent of 57.7% of its
03.. A 5 kW, 400 V, 50 Hz, 4 pole, delta connected three- rating with balanced supply at its terminals.
phase induction motor is supplied by a cable of negligible
2
inductance. On starting the motor using a star-delta starter, (d) The machine can be loaded to the extent of 66 % with
it is found that the starting torque is the same on star as 3
well as delta connection, due to the voltage drop in the balanced supply at its terminals.
feeder resistance. The equivalent circuit parameters of the
motor are as follows: 10. An induction motor runs stably under constant torque
load at 1250 rpm off a 50Hz supply. Its number of poles is
r1 = 1 ohm , x1 = 4.5ohms , r2 = 1.4ohms and
_______________ [1995]
x2 = 4.50ohms
Determine the feeder resistance. [1991] 11. Motor characteristics [1995]
04. A three phase slip ring induction motor is fed from the
rotor side with stator winding short circuited. The
frequency of the currents flowing in the short circuited
stator is [1993]
(a) Slip frequency
(b) Supply frequency
(c) Frequency corresponding to rotor speed
(d) Zero
15. An induction motor having full load torque of 60Nm 21. A 50kVA, 400V, 3-phase, 50Hz squirrel cage induction
when delta-connected develops a starting torque of motor has full load slip of 5%. Its standstill impedance is
120Nm. For the same supply voltage, if the motor is 0.866 ohms/phase. It is started using a tapped
changed to star-connection, the starting torque developed autotransformer. It the maximum allowable supply current
will be [1996] at the time of starting is 100A, then calculate the tap
(a) 40Nm (b) 60Nm position and the ratio of starting torque to full load torque
(c) 90Nm (d) 120Nm [1997]
16. In case of a split phase motor, the phase shift between 22. A 3 phase squirrel cage induction motor has a full load
currents in the two windings is around [1996] efficiency of 0.8 and a maximum efficiency of 0.9. it is
(a) 30 degrees (b) 70 degrees operated at a slip of 0.6 by applying a reduced voltage. The
(c) 90 degrees (d) 120 degrees efficiency of the motor at this operating point is: [1998]
(a) less than 0.4
17. In an induction motor, if the air gap is increased (b) greater than 0.6
[1996] (c) in the range of 0.8±0.1
(a) Speed will reduce (d) none of the above
(b) Efficiency will improve
(c) Power factor will be lowered 23. Match the column [1998]
(d) Breakdown torque will reduce Test Machine
(A) No load and (P) Transformer
18. Out of the several characteristics shown in figure blocked rotor test
identify the appropriate ones to match the (B) Sumpner’s test (Q) Induction machine
following for a 3-phase induction motor. [1996] (C) Swinburne’s test (R) Synchronous machine
(S) DC machine
25. Starting torque can be obtained in the case of a single 31. A 230V, 20 hp, 60 Hz, 6-pole, 3-phase induction motor
phase induction motor with identical main and auxiliary driving a constant torque load at rated frequency, rated
windings by connecting [1999] voltage and rated horse-power, has a speed of 1175 rpm
and an efficiency of 92.1%. Determine the new operating
(a) A capacitor across the mains
speed if a system disturbance causes 10% drop in voltage
(b) A capacitor in series with the machine
and 6% drop in frequency. Assume that friction, windage
(c) A capacitor in series with the auxiliary winding and stray power losses remain constant. [2000]
(d) The main and the auxiliary windings in series
32. If a 400V, 50 Hz, star connected, 3 phase squirrel cage
26. The following starting method for an induction motor is induction motor is operated from a 400 V, 75 Hz supply,
inferior view of the poor starting torque per ampere of the the torque that the motor can now provide while drawing
rated current from the supply? [2002]
line current drawn: [1999]
(a) Reduces
(a) Direct line starting (b) Increases
(b) Auto transformer method of starting (c) Remains the same
(c) Series inductor method of starting (d) Increase or reduces depending upon the rotor
(d) Star-Delta method of starting resistance
33. The rotor of a three phase, 5 kW, 400V, 50 Hz, slip ring
27. A 3 kW, 400V/200V, Delta/Star, 50Hz, three phase, 6-
induction motor is wound for 6 poles while its stator is
pole induction motor is found to draw a line current of 25A
wound for 4 poles. The approximate average no load
at a power factor of 0.4, when a blocked rotor test is
steady state speed when this motor is connected to 400V,
conducted at the rated voltage. Determine the stator and
50 Hz supply is [2002]
rotor winding resistances in ohms per phase, if the torque
(a) 1500 rpm (b) 500 rpm
developed by the motor under the above conditions is 25
(c) 0 rpm (d) 1000 rpm
N-m [1999]
34. A 440 V, 50 Hz, 6 poles and 960 rpm star connected
28. A 3-phase, 4-pole squirrel cage induction motor has 36 induction machine has the following per phase parameters
stator and 28 rotor slots. The number of phases in the rotor referred to the stator:
is: [2000] RS = 0.6,Rr = 0.3, Xs = 1
(a) 3 (b) 9 The magnetizing reactance is very high and is neglected.
(c) 7 (d) 8 The machine is connected to the 440V, 50 Hz supply and a
certain mechanical load is coupled to it. It is found that the
29. The power input to a 415V, 50 Hz, 6 pole, 3-phase magnitude of the stator current is equal to the rated
induction motor running at 975 rpm is 40 kW. The stator current of the machine but the machine is running at a
losses are 1 kW and friction and windage losses total 2kW. speed higher than its rated speed. Find the speed at which
The efficiency of the motor is [2000] the machine is running. Also find the torque developed by
(a) 92.5% (b) 90% the machine. [2002]
(c) 91% (d) 88%
30. A three phase, wound rotor induction motor is to be 35. An ac induction motor is used for a speed control
operated with slip energy recovery in the constant torque application. It is driven from an inverter with a constant V/f
mode, when it delivers an output power P0 at slip s. Then control. The motor nameplate details are as follows
V: 415 V Ph: 3 f: 50Hz N: 2850 rpm
theoretically, the maximum power that is available for
recovery at the rotor terminals, is equal to [2000]
The motor is run with the inverter output frequency set at
(a) P0 (b) P0s
40 Hz, and with half the rated slip. The running speed of
P0 P0 .s the motor is [2003]
(c) (d)
(1 − s ) (1 − s ) (a) 2400 rpm (b) 2280 rpm
(c) 2340 rpm (d) 2790 rpm
36. No-load test on a 3-phase induction motor was (a) Rotor current is zero
conducted at different supply voltages and a plot of input (b) Rotor current is non-zero and is at slip frequency
power versus voltage was drawn. This curve was (c) Forward and backward rotating fields are equal
extrapolated to intersect the y-axis. This intersection point (d) Forward rotating field is more than the backward
yields [2003] rotating field
(a) Core loss
(b) Stator copper loss 40. The type of single-phase induction motor having the
(c) Stray load loss highest power factor at full load is [2004]
(d) Friction and windage loss (a) Shaded pole type (b) Split-phase type
(c) Capacitor-start type (d) Capacitor-run type
37. Following are some of the properties of rotating
electrical machines [2003] 41. The direction of rotation of a 3-phase induction motor
P Stator winding current is dc, rotor-winding is clockwise when it is supplied with 3-phase sinusoidal
current is ac voltage having phase sequence A-B-C. For counter
Q Stator winding current is ac, rotor-winding clockwise rotation of the motor, the phase sequence of the
current is dc power supply should be [2004]
R Stator winding current is ac, rotor-winding (a) B-C-A (b) C-A-B
current is ac (c) A-C-B (d) B-C-A or C-A-B
S Stator has salient poles and rotor has
commutator 42. A single-phase, 230 V, 50 Hz, 4 pole, capacitor-start
T Rotor has salient poles and slip rings and stator is induction motor has the following stand still impedances
cylindrical Main winding Zm =6.0 + j4.0
U Both stator and rotor have poly-phase windings
Auxiliary winding Z a = 8.0 + j6.0
DC machines, Synchronous machines and Induction The value of the starting capacitor required to produce 90°
machines exhibit some of the above properties as given in phase difference between the currents in the main and
the following table. Indicate the correct combination from auxiliary windings will be [2004]
this table (a) 176.84 µF (b) 187.24µF
DC Synchronous Induction (c) 256.26µF (d) 280.86µF
machines machines machines
P.S Q.T R.U 43. A 400V, 15 kW, 4 poles, 50 Hz, Y-connected induction
Q.U P.T R.S motor has full load slip of 4%. The output torque of the
P.S R.U Q.T machine at full load is [2004]
R.S Q.U P.T (a) 1.66 Nm (b) 95.50 Nm
(c) 99.47 Nm (d) 624.73 Nm
38. A 3-phase Inductor Motor is driving a constant torque
44. On the torque/speed curve of induction motor shown
load at rated voltage and frequency. If both voltage and
frequency are halved, following statements relate to the in Figure, four points of operation are market as W, X, Y
new condition if stator resistance, leakage reactance and and Z. Which one of them represents the operation at a slip
core loss are ignored. greater than 1? [2005]
P The difference between synchronous speed and actual
speed remains same (a) W
Q The air-gap flux remains same (b) X
R The stator current remains same
S The p.u. slip remains same (c) Y
Among the above, correct statements are [2003] (d) Z
(a) All (b) P, Q and R
(c) Q, R and S (d) P and S
45. For an induction motor, operating at a slip s, the ratio
39. A single phase induction motor with only the main of gross power output to air gap power is equal to: [2005]
winding excited would exhibit the following response at (a) (1 – s)2 (b) (1 – s)
synchronous speed [2003] (c) (1 − s ) (
(d) 1 − s )
46. Under no load condition, if the applied voltage to an the machine constant in the constant torque region by
induction motor is reduced from the rated voltage to half
controlling the terminal voltage as the frequency changes.
the rated value, [2005]
(a) The speed decreases and the stator current increases The inverter output voltage vs frequency characteristics
(b) Both the speed and the stator current decrease
should be [2006]
(c) The speed and the stator current remain practically
constant
(d) There is negligible change in the speed but the stator
current decreases
55. The electromagnetic torque Te of a drive, and its 60. A 230V. 50 Hz, 4-pole, single-phase induction motor is
rotating in the clockwise (forward) direction at a speed of
connected load torque TL are as shown below. Out of the
1425 rpm. If the rotor resistance at standstill is 7.8, then
operating points A, B, C and D, the stable ones are [2007] the effective rotor resistance in the backward branch of the
equivalent circuit will be [2008]
(a) 2 (b) 4
(c) 78 (d) 156
63. The speed of rotation of stator magnetic field with (a) rotates clockwise
respect to rotor structure will be [2008] (b) rotates anticlockwise
(a) 90 rpm in the direction of rotation (c) does not rotate
(b) 90 rpm in the opposite direction of rotation (d) rotates momentarily and comes to a halt
(c) 1500 rpm in the direction of rotation
(d) 1500 rpm in the opposite direction of rotation 67. A balanced three-phase voltage is applied to a star-
connected induction motor, the phase to neutral voltage
64. Neglecting all losses of both the machines, the dc being V. The stator resistance, rotor resistance referred to
generator power output and the current through resistance the stator. Stator leakage reactance, rotor leakage
(R ) will respectively be
ex [2008]
reactance referred to the stator and the magnetizing
reactance are denoted by rs − rr − xs − xr and Xm
(a) 96 W, 3.10 A (b) 120 W, 3.46 A
respectively. The magnitude of the starting current of the
(c) 1504 W, 12.26 A (d) 1880W, 13.71 A
motor is given by: [2010]
66. A 220V, 50 Hz, single-phase induction motor has the (a) Both machines act as generators.
following connection diagram and winding orientations (b) The dc machine act as generators, and the induction
shown. MM’ is the axis of the main stator winding (M1M2) machine acts as a motor
and AA' is that of the auxiliary winding (A1, A2). Directions (c) The dc machine act as motor, and the induction
of the winding axes indicate direction of .flux when currents machine acts as a generator
in the windings are in the directions shown. Parameters of (d) Both machines act as motors.
each winding are indicated. When switch S is closed, the
motor. [2009] 69. A three-phase 440V, 6pole, 50Hz, squirrel cage
induction motor is running at a slip of 5%. The speed of
stator magnetic field with respect to rotor magnetic field
and speed of rotor with respect to state magnetic field are
[2011]
(a) zero, -5rpm (b) zero, 955rpm
(c) 1000rpm, -5rpm (d) 1000rpm, 955rpm
71. A two-phase load draws the following phase currents: (a) f1, f2 > 50Hz and f1 > f2
i1 ( t ) = Im sin ( t − 1 ) , i2 ( t ) = Im cos ( t − 2 ) . These (b) f1 < 50Hz and f2 > 50 Hz
currents are balanced if 1 is equal to [2012] (c) f1, f2 < 50Hz and f2 > f1
(a) −2 (b) 2 (d) f1 > 50Hz and f2 > 50 Hz
(c) ( / 2 − )
2 (d) ( / 2 + )2
78. In a constant V/f control of induction motor, the ratio
V/f is maintained constant from 0 to base frequency, where
72. The blocked rotor current in a 3-phase, star connected V is the voltage applied to the motor at fundamental
15kW, 4-pole, 230V, 50Hz induction motor at rated frequency f. Which of the following statements relating to
conditions is 50A. Neglecting losses and magnetizing low frequency operating of the motor is TRUE? [2014-02]
current, the approximate blocked rotor line current drawn (a) At low frequency, the stator flux increases from its rated
when the motor is connected to a 236V, 57Hz supply is value.
[2012] (b) At low frequency, the stator flux decreases from its
(a) 58.5A (b) 45.0A rated value.
(c) 42.7A (d) 55.6A (c) At low frequency, the motor saturates.
(d) At low frequency, the stator flux remains unchanged at
73. Leakage flux in an induction motor is [2013] its rated value.
(a) Flux that leaks through the machine
(b) Flux that links both stator and rotor windings 79. A three-phase slip-ring induction motor, provided with
a commutator winding, is shown in the figure. The motor
(c) Flux that links none of the windings
rotates in clockwise direction when the rotor windings are
(d) Flux that links the stator winding or the rotor winding closed. [2014-02]
but not both
(b)
(c) Synchronous motor is a source and induction generator 93. The equivalent circuit of a single phase induction motor
and synchronous generator are sinks of reactive power. is shown in the figure, where the parameters are
(d) All are sources of reactive power. R1 = R2 = Xl1 = Xl2 = 12 XM = 240 and S is the slip. At
no-load, the motor speed can be approximated to be the
87. The direction of rotation of a single-phase capacitor run
synchronous speed. The no-load lagging power factor of
induction motor is reversed by [2016-02]
the motor is ________ (up to 3 decimal places). [2018]
(a) interchanging the terminals of the AC supply
(b) interchanging the terminals of the capacitor.
(c) interchanging the terminals of the auxiliary winding
(d) interchanging the terminals of both the windings.
92. A star-connected, 12.5kW, 208 V (line), 3-phase, 60 Hz 97. Consider the table given:
squirrel cage induction motor has following equivalent
circuit parameters per phase referred to the stator: Constructional Machine type Mitigation
R1 = 0.3 , R2 = 0.3 , X1 = 0.41 , X2 = 0.41 . Neglect feature
shunt branch in the equivalent circuit. The starting current (P) Damper bars (S) Induction (X) Hunting
(in Ampere) for this motor motor
(Q) Skewed rotor (T) Transformer (Y) Magnetic
when connected to an 80 V (line), 20 Hz, 3-phase AC source slots locking
is ___________. [2017-02] (R) Compensating (U) Synchronous (Z) Armature
winding machine reaction
(V) DC machine
The correct combination that relates the constructional 103. A 3-phase, 415 V, 50 Hz induction motor draws 5
feature, machine type and mitigation is [2021] times the rated current at rated voltage at starting. It is
(a) P-V-X, Q-U-Z, R-T-Y required to bring down the starting current from the supply
(b) P-U-X, Q-S-Y, R-V-Z to 2 times of the rated current using a 3-phase
(c) P-T-Y, Q-V-Z, R-S-X autotransformer. If the magnetizing impedance of the
(d) P-U-X, Q-V-Y, R-T-Z induction motor and no load current of the
autotransformer is neglected, then the transformation ratio
98. The power input to a 500 V, 50 Hz, 6-pole. 3-phase of the autotransformer is given by ……………….. (round off to
induction motor running at 975 RPM is 40 kW. The total two decimal places). [2022]
stator losses are 1 kW. If the total friction and windage
losses are 2.025 kW. then the efficiency is __________ %. 104. The following columns present various modes of
[2021] induction machine operation and the ranges of slip
(A)
99. An 8-pole, 50 Hz. three-phase, slip-ring induction Mode of Operation
motor has an effective rotor resistance of 0.08 Ω per phase. (a) Running in generator mode
Its speed at maximum torque is 650 RPM. The additional (b) Running in motor mode
resistance per phase that must be inserted in the rotor to (c) Plugging in motor mode
achieve maximum torque at start is …………… Ω. (Round off (B)
to 2 decimal places.) Range of Slip
Neglect magnetizing current and stator leakage (p) From 0.0 to 1.0
impedance. Consider equivalent circuit parameters referred (q) From 1.0 to 2.0
to stator. [2021] (r) From –1.0 to 0.0
The correct matching between the elements in column A
100. The type of single-phase induction motor, expected to with those of column B is [2023]
have the maximum power factor during steady state (a) a-r, b-p, and c-q
running condition, is (b) a-r, b-q, and c-p
(a) split phase (resistance start) (c) a-p, b-r, and c-q
(b) shaded pole. (d) a-q, b-p, and c-r
(c) capacitor start.
(d) capacitor start, capacitor run. [2022] 105. A 10-pole, 50 Hz, 240 V, single phase induction motor
runs at 540RPM while driving rated load. The frequency of
101. The frequencies of the stator and rotor currents induced rotor currents due to backward field is [2023]
flowing in a three-phase 8-pole induction motor are 40 Hz (a) 100 Hz (b) 95 Hz
and 1 Hz, respectively. The motor speed, in rpm, is _________ (c) 10 Hz (d) 5 Hz
(round off to nearest integer). [2022]
106. A three phase 415 V, 50 Hz, 6-pole, 960 RPM, 4 HP
102. A 4-pole induction motor with inertia of 0.1 kgm2 squirrel cage induction motor drives a constant torque load
drives a constant load torque of 2 Nm. The speed of the at rated speed operating from rated supply and delivering
motor is increased linearly from 1000 rpm to 1500 rpm in 4 rated output. If the supply voltage and frequency are
seconds as shown in the figure below. Neglect losses in the reduced by 20%, the resultant speed of the motor in RPM
motor. The energy, in joules, consumed by the motor (neglecting the stator leakage impedance and rotational
during the speed change is ……… (round off to nearest losses) is (Round off to the nearest integer). [2023]
integer). [2022]
Solutions
01. Ans: (b, d)
Solution:
Deep-bar rotor: During starting, frequency of induced current in rotor is very high. As a result, the deep bars offer great
opposition to flow of current and hence the rotor current is forced to flow in the outer bars. So, effective cross-sectional
area reduces and hence, resistance of rotor increases resulting in a higher starting torque. As the rotor speeds up, the
frequency of induced current keeps on decreasing and rotor current eventually spreads out uniformly throughout the rotor
making sure resistance during running condition is less.
In a double cage rotor, we have an inner cage and an outer cage. During starting, due to high frequency of induced
current, reactance of inner cage will be high.
So at starting, current flows through high resistance outer-cage increasing the starting torque and during running
condition when the rotor speeds up, the frequency decreases and reactance of inner cage becomes less and current flows
through it resulting in a higher efficiency.
In order to choose one out of the two options D should be preferred.
Case-2
If both fields rotate opposite to rotor then, speed of rotor field with respect to stationary air-gap
( N) − 3000 =Stator field speed in air gap= 1200rpm
rotor field
(N) rotor field
= 4200rpm (Breaking operation, s>1)
Δ-Y
Conversion
400
3
( )
So, I2
Y
=
2
2.4
RC + +9
3
This is the line current in equivalent star of delta connection. So, per phase current would be
( I2 )Y = I
2
3
400 1
400
3 3 3
I2 = =
2 2
2.4 2.4
RC + +9 RC + +9
3 3
400 400
As derived earlier, I2 = I2 ; 3 = 3
(R + 2.4 ) + 81
2 2
2.4
RC + +9
C
3
2
2.4
− (R C + 2.4 ) = 54
2
3 RC +
3
2R2C = 57.84 ; RC = 5.377
→ Skew angle
Induced EMF within the span AOB can be eliminated using the given skew angle.
Given Nr = 1400rpm
Nr NS
Slip s<0 → negative
So, induction machine is working in generating mode.
V
f
10. Ans: 4
Solution:
Speed of Induction motor (Nr) = 1250 rpm.
Input supply frequency = 50 Hz
120 f 6000
Synchronous speed, Ns = =
P P
The nearest synchronous speed to the rotor speed with even number of poles is 1500rpm which is obtained with 4 poles.
Hence, P = 4
11. Ans: a – R, b – U, c – P, d – S, e – Q
Solution:
(a) Speed-Torque Characteristics of Induction Motor is the inverse of Torque-Speed Characteristics and it is depicted in
Curve-R.
(b) In DC series Motor, T I 2a at low values of armature current and for high values the machine saturates so the torque
varies linearly with current T I a . Curve, U is the closest approximation to this behavior.
(c) Under No-Load, the current drawn by the motor is magnetizing and core loss current. With increase in voltage and
constant frequency the flux increases linearly with voltage and thus the magnetizing as well as core loss current increases.
But magnetizing current dominates over core loss component so power factor reduces. Curve-P is most appropriate.
(d) When DC voltage is applied, the mmf produced is stationery in space and it cuts the rotor conductors and induces emf
and produces braking torque. At zero relative speed, the emf induces is zero and there is zero braking torque. Hence,
curve-S depicts the variation.
(e) Curve-Q is a standard Variation of Speed vs Torque in a DC Series Motor.
Presence of co-phasal component (i.e. zero sequence component) depends on presence of return path also, so it may not
be present necessarily, but negative sequence component will always be there.
Tst ( Ist )
2
(T )
st Y 1
=
2
(T )
st 3
1
(T )
st Y
=
3
120 = 40N − m
(b) With decrease in speed the slip increases which reduces the effective rotor impedance,
2
R
Zr = 2 + X 22
s
Due to increase in rotor impedance the rotor current would reduce.
At high speed, i.e. at low slip I = V = V
sV
Zr 2
R2 R2
+ X2
2
s
So, current is less at low slip.
Hence, current would increase with decrease in speed. Curve-1 correctly depicts this behavior.
1500 − 1400 1
Slip, s1 = =
1500 15
Now, torque produced in any machine I [ → Air gap flux]
T I & = Constant
Therefore, current will remain the same for torque to be same.
3 2 R2 3 2 R2
I = I
s1 2 s1 s2 2 s2
120 30 8
N2 = Ns2 (1 − s2 ) =
4 9
N2 = 800rpm
V V
100 = x ( xISC )
3 3
100 100
x2 = = = 0.2165
ISC 461.89
x 0.4652
2
Tst I 461.9
= x2 . SC .sfl = ( 0.4652 )
2
Now 0.05 = 0.4432
Tfl Ifl 72.17
(I )
2 fl
= 40A , (Pcu )
rotor
= 300W , (P )mech = 1200W
120 50
NS = = 1000rpm
6
NS − Nr 1000 − 960
s= = = 0.04
NS 1000
Pd = Pg ( )
− (Pcu )rotor = Pg − sPg = 1 − s Pg [ Pg → air-gap power, Pd → Developed power]
Now,
PShaft = 50 746 = 37.3kW
Pd = Pshaft + Pmech = 37.3 + 1.2 = 38.5kW
38500 38500
Pg = =
(1 − 0.04 ) 0.96
Prcu = sPg = 3I22R 2 + 300
38500
0.04 = 3I22R 2 + 300
0.96
1304.167
R2 = = 0.27 / phase
3 ( 40 )
2
( )
2
R2 = a2R 2 = 2 3 R 2 = 12R 2
X2 = a2 X2 = 12X2
The Induction Motor Circuit referred to Stator is shown below,
Req = R1 + 12R2
X eq = X1 + 12X 2
Since, the current drawn has a pf of 0.4
X
tan cos−1 ( 0.4 ) = eq
R eq
X 2eq = 5.25 R eq
2
............. (1 )
400
Input impedance, Z =
25 / 3
( 27.71)
2
= R 2eq + X eq
2
From (1),
27.712
R 2eq = = 122.85
6.25
R eq = R1 + 12R 2 = 11.084 ............ ( 2 )
Torque Developed can be computed as Air-Gap Power divided by the Synchronous Speed.
T = 25N − m
3
( Is ) 12R 2 = 25
2
s
2
3 25
.12R 2 = 25
104.67 3
R 2 = 0.3489
From (2) R1 = 6.8972
1000 − 975
s= = 0.025
1000
Power Output or Developed Power by motor = (1 − s )P [ P → Air-gap power]
g g
Pg (1 − s ) = P0
P0
Air Gap Power, Pg =
1−s
Rotor Copper Losses can be recovered at the slip ring terminals and can be used to drive another Induction Motor in
cascade.
sP0
Pcu = sPg =
1−s
3 sVph
2
T dev =
s R 2
Synchronous Speed, s f
Hence, 6% drop in frequency causes 6% drop in synchronous speed.
s2 f2
= = 0.94
s1 f1
Due to 10% drop in voltage
V2
= 0.90
V1
Since, T 2 = T1
3 s2 V2 3 s1 V1
2 2
=
s2 R 2 s1 R 2
2 2
V 1 1
Hence, s2 = s1 s2 1 = 0.94 = 0.0242
s1 V2 48 0.9
New Synchronous Speed, Ns2 = 0.94Ns1 = 0.94 1200 = 1128 rpm
So, T v
f
So, T 1 for constant supply voltage
f
So, for 75Hz 400V supply torque developed will be less compared to 50Hz, 400V supply
120 50
Ns = = 1000rpm
6
1000 − 960
s= = 0.04
1000
440
Stator Current, Ir =
2
R
3 R1 + 1 + ( x1 + x2 )
2
s
440
Ir = = 30.447A
2
0.3
3 0.6 + +2
2
0.04
Developed Torque,
180 R 180 0.3
( Ir ) 2 = ( 30.47 )
2 2
T=
2 Ns s 2 1000 0.04
T = 199.48N − m
If the machine is running above rated speed with same stator current, then its is working as Induction Generator with
negative slip of same magnitude.
s = −0.04
N = 1000 (1 + 0.04 ) = 1040rpm
Developed torque by induction machine when it is running at a speed higher than its rated speed:-
440
Ir ' = = 35.361 A
2
0.3
3 0.6 − +2
2
0.04
180 0.3
( 35.361 )
2
Developed torque T = = 268.66 N-m
2 1000 0.04
35. Ans: (c)
Solution:
Rated Synchronous Speed should be nearest to rated speed = 3000 rpm
3000 − 2850
Rated Slip of the Motor is, sfl = = 0.05
3000
sfl
At half the rated slip, s = = 0.025
2
40
At 40Hz frequency the synchronous speed will be, Ns = 3000 = 2400 rpm
50
Speed of Induction Motor,
40
Nr = Ns (1 − s ) = 2400 (1 − 0.025 ) = 2400 0.975 = = 2340 rpm
50
Hence, s2 = s2 V1 = 1 4 = 2
2
s1 s1 V22 2
s2 = 2s1
Ns2 − Nr2 N − Nr1
= 2 s1
Ns2 Ns1
Ns2 1
Ns2 − Nr2 = 2 (Ns1 − Nr1 ) = 2 (Ns1 − Nr1 ) = (Ns1 − Nr1 )
Ns1 2
Hence, difference between synchronous and actual speed remains same.
Torque produced in any motor is given as
T I2
Now as load torque is constant and flux is constant . So, I 2 has to be constant
So reflected component of I 2 in stator will remain same → I1
Ns − Nr
Forward Slip, sf = =s
Ns
At Nr = Ns , rotor is stationary w.r.t forward field
So, forward slip is 0.
Ns + Nr Ns − ( −Nr ) 2Ns − (Ns − Nr )
Backward Slip, sb = = =
Ns Ns Ns
sb = 2 − s
At s = 0,sb = 2
So rotor current is produced at slip frequency w.r.t backward field.
Due to series capacitor auxiliary circuit is capacitive and leading pf whereas due to inductor main winding circuit is lagging
pf.
Zm = ( 6 + j4 )
V 23000
Im = = = 81.89 − 33.70 Amp
Zm 6 + j4
Now starting capacitor should be connected in series with auxiliary winding, so net impedance produces 90 0 phase
difference. So, the phase of auxiliary current should be 90 − 33.7 = 56.30
Z a = 8 + j6 − j
C
1 − 6
tan−1 C = 56.3
8
C = 176.84F
Ns + Nr
(s)braking
=
Ns
1
fraction.
But slip ‘s’ for the IM at no-load is nearly 0
So even if current reduces, there won’t be much noticeable change in speed as it is operating at no-load. Hence, we can
say unless frequency changes at no-load the speed will not change.
= st .sfl
(T) full−load
I
fl
In the above expression rotor current is replaced by stator current as ratio of rotor current and stator currents will be same.
I
Given, st = 6
I fl
(T) starting
= 36 0.04 = 1.44
(T) full−load
Hence both assertion & reason are true and [r] is the correct reason of [a].
120 50
Ns = = 1500rpm
4
2
s = 1500 = 50 rad sec
60
2
400
3 0.5
3
T=
50 1 + 0.5 2 + 1.2 + 1.2 2
( ) ( )
T = 63.6N − m
( 15 )
2
Armature Cu loss at full load= 20 762
Pcu,FL = 1354.67W
Core loss at rated voltage= 1002 W
Total losses= 2356.67 W
Pout
= 100%
Pout + PLoss
10000
= 100% 81%
10000 + 2356.67
So D is stable
T 2
=
Tmax s sm,T
+
sm,T s
At starting T = Tst ,s = 1
Tst 2
=
Tmax 1 + sm,T
sm,T
0.15 2s
= 2 m,T
0.30 sm,T + 1
sm,T
2
− 4sm,T + 1 = 0
x 2 = 30
49
x = 0.78246 = 78.25%
Ns − Nr 1500 − 1425 1
slip = = =
Ns 1500 20
R2
Resistance in backward branch =
2
(2 − s)
7.8
2 7.8 20
Rb = = × = 2
1 2 39
2 −
20
Hence, speed of stator magnetic with respect to rotor= speed of rotor magnetic field wrt rotor
Speed of rotor magnetic field with respect to rotor = Ns = 1500rpm
In case of inverted IM, rotor moves opposite to magnetic field.
2 50 10
L a = − tan−1 1000 = −89.9427
Phase = −a = − tan−1 = − tan−1
Ra 1
Current in main winding
V0 V
Im = = − m
Zmm Zm
2 50 0.1
L m = − tan−1 100 = −89.427
Phase = −m = − tan−1 = − tan−1
Rm 0.1
Ns − Nr
s=
Ns
It depends on shaft torque as shaft torque is a function of mechanical power output which depends on slip.
Slip is independent of core – loss component.
Currents are balanced when there is a phase shift of 90 between both currents.
Phase shift
−1 − ( 90 − 2 ) = 90
1 = 2 − 90 90
Either 1 = 2 or 1 = 2 − 180
1500 + 1440
Slip = = 1.96
1500
Slip frequency = s f = 1.96 50 = 98 Hz
1
Rotor frequency = s × Stator frequency = 50 = 3.33 Hz
15
If the switch does not disconnect the starting capacitor then it remains permanently connected and acts as Run Capacitor.
dTL dTe
At S, . So, S is an unstable operating point
dn dn
Note: These are speed-torque curves instead of Torque-speed curves so slope must be taken carefully.
R
sm,T = 2
X2
0.03
0.15 =
X2
X2 = 0.2
For maximum torque to occur at starting,
sm,T = 1
R 2 + R ext
=1
X2
sm,T 1
f
Synchronous Speed Ns =
120f
P
Ns f 1
sm,T
Ns
So, Slip for maximum torque is inversely proportional to synchronous speed.
12.50
X − 12.75
a = tan−1 c
24.50
X c − 12.75 90 − 51.56
Hence, = tan = 0.3486
24.50 2
Xc = 21.29
1 1
C= = = 149.5F
X c 2 50 21.29
Xf
f 20 x
x = x= x=
f 60 3
0.41
x1 = x2 =
3
80
Ist = 3 = 70.0533 A
2
0.82
0.6 +
2
3
Z eq = 12 + j132 +
( −720 + j360 )(3 − j126 )
15885
Z eq = 12 + j132 +
( 43200 + j91800 )
(15885)
Zeq = 12 + j132 + 2.7195 + j5.779
Zeq = 14.7195 + j137.779
137.779
= tan−1 = 83.9
14.7195
pf = cos = 0.1062
95. Ans: 14 to 16
Solution:
R2
At starting s = 1, = R2
s
At 10Hz
10 X
X = X =
50 5
Since motor is delta connected V = 100V
100
Ist =
16.44
(
5.39 + 5.72 + j )
5
100 100
Ist = = A
270.2736 11.586
123.43 +
25
100
Line current = 3 = 14.95A
11.586
96. Ans:
Solution:
4 pole, 50 Hz. . has no load slip 1 %
4 pole, 50 Hz I.M has full load slip 5 %
NS=1500 rpm
N0=Ns(1-s)=1500(1-0.01)=1485
N=Ns(1-s)=1500(1-0.01)=1425
Speed regulation is
N0 − N
% S.R. = 100
N
1485 − 1425
= 100 = 4.21%
1425
97. Ans: B
Solution:
(1) Damper Bars are used in Synchronous Machines to prevent Hunting.
(2) Skewed rotor slots are used in Induction Machines to prevent Magnetic Locking.
(3) Compensating winding is used in DC Machines to reduce the effect of armature reaction.
98. Ans: 90
Solution:
Pi/p = 40 kW, stator loss = 1 kW, F and W = 2.025 kW
Stator O/P = 40 – 1= 39 kW
1000 − 975
Slip = = 0.025
1000
Rotor o/p= Rotor i/p × (1-s)
=39(1-0.025)=38.025 kW
Motor o/p=38.025-2.025=36 kW
Motor output
=
Motor input
36
= 100 = 90%
40
R2 0.08
x2 = = = 0.601
sm 0.133
R2 = 0.08, X2 = 0.601
Condition for maximum Tst
R2 = X2
R2 + Rext = X2
Rext = 0.601 − 0.08 = 0.521
Or dE = Jd + TL dt
Or E = J d + TL dt
21500
2 2 8
E = J
60
NdN + TL
60 4
Ndt
Or
1000
2 1500
2 N2 2 8
60 4
= J + 2 (125t + 500)dt
60 2 1000
2 8
2 15002 − 10002 2 125x2
= 0.1 + 2 + 500t
60 2 60 2 4
=685.389+1047.197
= 1732.5865 J
2If
= x2
ISC
1 2
x2 = 2 x = = 0.63
5 5
Torque
Braking Generating
mode mode
S>1 S<1
Motoring Speed
mode
0<S<1
01. The torque speed characteristic of a repulsion motor 07. For a 1.8°, 2-phase bipolar stepper motor, the stepping
resembles which of the following dc motor characteristic? rate is 100steps/second. The rotational speed of the motor
[1996] in rpm is [2004]
(a) Separately excited (b) Shunt (a) 15 (b) 30
(c) Series (d) Compound (c) 60 (d) 90
02. Which type of motor is most suitable for computer 08. A three-phase, three-stack, variable reluctance step
printer drive? [1996] motor has 20 poles on each rotor and stator stack. The step
(a) Reluctance motor (b) Hysteresis motor angle of this step motor is [2007]
(c) Shaded pole motor (d) Stepper motor (a) 3o (b) 6 o
(c) 9 o (d) 18 o
03. A 1.8° step, 4-pole stepper motor has a total of 40
teeth on 8 poles of stator. The number of rotor teeth for 09. In a stepper motor, the detent torque means [2008]
this motor will be [2000] (a) Minimum of the static torque with the phase winding
(a) 40 (b) 50 excited.
(c) 100 (d) 80 (b) Maximum of the static torque with the phase winding
excited.
04. Group I lists different applications and Group II lists the (c) Minimum of the static torque with the phase winding
motors for these applications. Match the application with unexcited.
the most suitable motor and choose the right combination (d) Maximum of the static torque with the phase winding
among the choices given thereafter [2003] unexcited.
Group I Group II
P Food mixer 1 Permanent magnet dc
motor
Q Cassette tape 2 Single phase induction
recorder motor
R Domestic water 3 Universal motor
pump
S Escalator 4 Three phase induction
motor
5 DC series motor
6 Stepper motor
(a) P – 3 Q – 6 R – 4 S – 5
(b) P – 1 Q – 3 R – 2 S – 4
(c) P – 3 Q – 1 R – 2 S – 4
(d) P – 3 Q – 2 R – 1 S – 4
05. For a given stepper motor, the following torque has the
highest numerical value. [2004]
(a) Detent torque (b) Pull-in torque
(c) Pull-out torque (d) Holding torque
Solutions
01. Ans: (c)
Solution:
Speed-torque characteristics of a repulsion motor is similar to the the speed torque characteristics of a DC-series motor.
3600
Number or rotor teeth = = 50
4 1.80
Pull-out-Torque:
It is the maximum torque that the motor can generate while running, beyond which the motor will fall back. Hence highest
value is that of pull-out torque.
So, if inductance is independent of rotor position, that means; reluctance is also not varying with rotor position. So that
means the machine is a cylindrical rotor synchronous machine which has uniform reluctance and air-gap. Hence the
reluctance torque should be zero.
Reluctance torque is produced in non-uniform air gap when the rotor mmf tries to align itself along the path of minimum
reluctance.