R3G500-RA28-03 EC centrifugal fan - RadiCal

backward-curved, single-intake

ebm-papst Mulfingen GmbH & Co. KG


Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
info1@de.ebmpapst.com
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
Amtsgericht (court of registration) Stuttgart · HRA 590344

General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen


Amtsgericht (court of registration) Stuttgart · HRB 590142

Nominal data

Type R3G500-RA28-03
Motor M3G150-FF

Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Frequency Hz 50/60

Method of obtaining data ml


Status prelim.
Speed (rpm) min-1 1900
Power consumption W 3650
Current draw A 5.6
Min. ambient temperature °C -40
Max. ambient temperature °C 40
ml = Max. load · me = Max. efficiency · fa = Free air · cs = Customer specification · ce = Customer equipment
Subject to change

Data according to Commission Regulation (EU) 327/2011


Actual Req. 2015

01 Overall efficiency ηes % 63.1 57.4 09 Power consumption Ped kW 3.65


02 Measurement category A 09 Air flow qv m³/h 8095
03 Efficiency category Static 09 Pressure increase pfs Pa 983
04 Efficiency grade N 67.7 62 10 Speed (rpm) n min-1 1905
05 Variable speed drive Yes 11 Specific ratio* 1.01
*
Data obtained at optimum efficiency level. Specific ratio = 1 + pfs / 100 000 Pa LU-182081
The ErP data is determined using a motor-impeller combination in a standardized measurement setup.

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 1 / 7

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G500-RA28-03 EC centrifugal fan - RadiCal
backward-curved, single-intake

Technical description

Weight 21.9 kg
Size 500 mm
Motor size 150
Rotor surface Painted black
Electronics housing material Die-cast aluminum
Impeller material PP plastic
Number of blades 7
Direction of rotation Clockwise, viewed toward rotor
Degree of protection IP55
Insulation class "F"
Moisture (F) / Environmental (H) H1
protection class
Ambient temperature note Occasional start-up at temperatures between -40°C and -25°C is permitted. For
continuous operation at ambient temperatures below -25°C (such as refrigeration
applications), use must be made of a fan design with special low-temperature bearings.
Max. permitted ambient temp. +80 °C
for motor (transport/storage)
Min. permitted ambient temp. for -40 °C
motor (transport/storage)
Installation position Shaft horizontal or rotor on bottom; rotor on top on request
Condensation drainage holes On rotor side
Mode S1
Motor bearing Ball bearing
Technical features - Operation and alarm display with LED
- External 15-50 VDC input (parameterization)
- Alarm relay
- Integrated PI controller
- Configurable inputs/outputs (I/O)
- MODBUS V6
- Motor current limitation
- RFID - ISO 15693 compatible
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000 maximum
- Voltage output 3.3-24 VDC, Pmax = 800 mW
- Control interface with SELV potential safely disconnected from the mains
- Thermal overload protection for electronics/motor
- Line undervoltage / phase failure detection
Touch current according to IEC <= 3.5 mA
60990 (measuring circuit Fig. 4,
TN system)
Electrical hookup Terminal box
Motor protection Reverse polarity and locked-rotor protection
Protection class I (with customer connection of protective earth)
Conformity with standards EN 61800-5-1; CE
Approval CSA C22.2 No. 77 + CAN/CSA-E60730-1; EAC; UL 1004-7 + 60730

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 2 / 7

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G500-RA28-03 EC centrifugal fan - RadiCal
backward-curved, single-intake

Product drawing

1 Accessory part: inlet ring 50901-2-2943 not included in scope of delivery


2 Max. clearance for screw 20 mm
3 Cable diameter min. 4 mm, max. 10 mm, tightening torque 2 ± 0.3 Nm
4 Tightening torque 1.5 ± 0.2 Nm

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 3 / 7

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G500-RA28-03 EC centrifugal fan - RadiCal
backward-curved, single-intake

Accessory part

1 Accessory part: inlet ring 50901-2-2943

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 4 / 7

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G500-RA28-03 EC centrifugal fan - RadiCal
backward-curved, single-intake

Connection diagram

No. Conn. Designation Function/assignment


CON1 - L1, L2, L3 Supply connection, power supply, protection class 1
PE - PE Ground connection, PE connection
CON2 - RSA Bus connection RS485, RSA, MODBUS-RTU; SELV
CON2 - RSB Bus connection RS485, RSB, MODBUS-RTU; SELV
CON2 - GND GND reference ground for control interface, SELV
CON2 - IO1 IN2: Digital input - positive logic (factory setting: Enable)
function parameterizable, SELV
- normal: Pin open or applied voltage < 1.5 VDC
- inverse: applied voltage 3.5-50 VDC
CON2 - IO2 IN1: Analog input 0-10 V
0-10 V, Ri=100 K, parameterizable as set value or measured value (factory setting: set value)
characteristic curve parameterizable, SELV
CON2 - IO3 OUT1: Analog output 0-10 V
0-10 V, max 5 mA, function parameterizable (factory setting: modulation level)
max output frequency 300 Hz, SELV
CON2 - V out Voltage output 3.3-24 VDC +/-5%, Pmax=800 mW, voltage parameterizable (factory setting: 10 VDC)
short-circuit-proof, supply for external devices, SELV
alternatively: 15-50 VDC input for parameterization via Modbus without line voltage
CON2 - COM Status relay, floating status contact; common connection, nominal voltage 250 VAC; max 2 A (AC1): min
10 mA; Reinforced insulation in accordance with EN60335-1, EN61800-5-1, UL60730-1
CON2 - NC Status relay, floating status contact, break for failure

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 5 / 7

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
○ configurable option

For further information and additional functions see EC Control Software, Fan-Set-App,

D101 [...]
D147 [...]
D104 [...]
D12E [...]
D148 [...]
D16C [...]
D16A [...]
(selected directly
via IO mode)
(selected directly
D130 [0]
D130 [1]
D130 [2]
D130 [5]
D00C [1]
D130 [4]

via IO mode)
or MODBUS Parameter Specification V6.0
INPUT OUTPUT

inverse
R3G500-RA28-03

configurable IO
functions: normal /
Terminal/plug assignment

MODBUS
Register for IO
mode

source: set value


source: sensor value
switch: parameter set: #1 / #2
switch: control function: heating (pos.) /
switch: direction of rotation: cw / ccw

cooling (neg.)
signal: actual speed
signal: system modulation level %
signal: remote control output 0-10V
pulse input for auto-adressing
pulse output for auto-adressing

switch: set value source


switch: fan enable / disable
signal: tach out
signal: diagnostics out
signal: fan modulation level %
CON2 configurable IO mode electrical specification configuration
Din1 (active high): digital input not active: pin open or applied voltage < 1,5VDC D158 [0]
○ ○ ○ ○ ○ ○
active: applied voltage 3,5-50VDC, SELV
IO1 ○ Ain1 0-10V/PWM: analog input Ri=100K, characteristic curve parameterizable, fPWM=1k..10KHz, SELV D158 [2] ○ ○
○ Tach out (open collector output) Umax=50VDC, Imax=20mA, SELV D158 [5] ○
○ Diagnostics out (open collector output) Umax=50VDC, Imax=20mA, SELV D158 [6] ○
○ Din2 (active high): digital input not active: pin open or applied voltage < 1,5VDC D159 [0]
○ ○ ○ ○ ○
active: applied voltage 3,5-50VDC, SELV
IO2
Ain2 0-10V/PWM: analog input Ri=100K, characteristic curve parameterizable, fPWM=1k..10KHz, SELV D159 [2]
○ ○

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 6 / 7


○ Ain2 4-20mA: analog input Ri=125R, characteristic curve parameterizable, SELV D159 [3]
○ Din3 (active high): digital input not active: pin open or applied voltage < 1,5VDC D15A [0]
active: applied voltage 3,5-50VDC, SELV
○ Din3 (active low): digital input
○ ○ ○ ○ ○
active: pin open or applied voltage 3,5-50VDC D15A [1]
not active: applied voltage < 1,5VDC, SELV
○ PWMin3: digital input 40Hz - 10kHz, characteristics parameterizable D15A [7]
IO3
not active: pin open or applied voltage 3,5-50VDC ○
active: applied voltage < 1,5VDC, SELV
backward-curved, single-intake

Aout3 0-10V: analog output function parameterizable, max. 5mA, max output frequency 300Hz, SELV D15A [4] ○ ○ ○ ○ ○
○ Tacho out (pulses), analog output 0-10V max. 5mA, max output frequency 300Hz, SELV D15A [5] ○
○ Diagnostics out (pulses) 0-10V max. 5mA, max output frequency 300Hz, SELV D15A [6] ○
RSA RS485 bus connection, MODBUS RTU, specification V6.0, SELV
○ ○ ○ ○ ○ ○
RSB
voltage output voltage parameterizable 3,3...24VDC +/- 5,5%, Pmax=800mW, short-circuit-proof, D16E [...]
Vout
supply for external devices, SELV
EC centrifugal fan - RadiCal

alternatively: Input auxillary power supply for 15...50VDC


parameter-ization via RS485/MODBUS RTU without line
voltage

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
R3G500-RA28-03 EC centrifugal fan - RadiCal
backward-curved, single-intake

Curves: Air performance 50 Hz


in wg
Pa

ρ = 1.15 kg/m³ ± 2 %
Measurement: LU-182081-1
5

1200 4
Air performance measured according to ISO
5801 installation category A. For detailed
information on the measurement setup,
contact ebm-papst. Intake sound level:
3 Sound power level according to ISO 13347 /
4

8 sound pressure level measured at 1 m


distance from fan axis. The values given are
valid under the specified measuring
conditions and may vary due to conditions of
800 installation. For deviations from the standard
7 configuration, the parameters have to be
checked on the installed unit.
3

12
2
11
6
2

400 16
15 10
1

14

0 2000 4000
13 9 6000
5 cfm
1
Pfs

qv 2000 4000 6000 8000 10000 m³/h

Measured values
U f n Ped I LpAin LwAin LwAout qV pfs qV pfs
V Hz min-1 W A dB(A) dB(A) dB(A) m3/h Pa cfm in. wg
1 400 50 1900 2554 3.95 82 89 96 12965 0 7630 0.00
2 400 50 1900 3485 5.34 77 85 91 10495 600 6180 2.41
3 400 50 1900 3650 5.60 73 80 87 7880 1000 4635 4.01
4 400 50 1900 3248 4.98 77 84 89 5350 1200 3150 4.82
5 400 50 1700 1815 2.80 79 86 93 11570 0 6810 0.00
6 400 50 1700 2482 3.80 74 82 88 9375 481 5515 1.93
7 400 50 1700 2584 3.96 70 77 84 7035 800 4140 3.21
8 400 50 1700 2313 3.55 74 82 86 4780 960 2815 3.85
9 400 50 1400 1014 1.57 74 81 88 9530 0 5610 0.00
10 400 50 1400 1386 2.12 70 77 84 7720 326 4545 1.31
11 400 50 1400 1443 2.21 65 72 79 5790 543 3410 2.18
12 400 50 1400 1292 1.98 69 77 81 3935 651 2315 2.61
13 400 50 1100 492 0.76 68 75 82 7485 0 4405 0.00
14 400 50 1100 672 1.03 63 71 77 6065 202 3570 0.81
15 400 50 1100 700 1.07 59 66 73 4550 335 2680 1.34
16 400 50 1100 626 0.96 63 71 75 3090 402 1820 1.61
U = Voltage · f = Frequency · n = Speed (rpm) · Ped = Power consumption · I = Current draw · LpAin = Sound pressure level intake side · LwAin = Sound power level intake side
LwAout = Sound power level outlet side · qV = Air flow · pfs = Pressure increase

Item no. 55742-5-9980 · ENU · Change 98080 · Approved 2018-08-01 · Page 7 / 7