Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Polaris 2000

User’s Manual

2018/11 Version : 2.5us


Polaris 2000 User’s Manual

Page 2
Polaris 2000 User’s Manual

Polaris 2000 User’s Manual, 2018, Nov.

Copyright
© 2018 DAE Instrument Corp. All rights reserved.

DAE Controls LLC.


3124 Chesapeake Dr. Sterling Heights, MI 48314, USA
Tel:+1-248-635-3708 Fax:+1-586-488-3601
e-mail:info@DAEcontrols.com

DAE Headquarters
5F, No. 157, Xinhu 1st Road, Neihu District, Taipei 11494, Taiwan, R.O.C.
Tel:+886-2-2793-6123 Fax:+886-2-2793-6150
e-mail:info@DAEinstrument.com

Page 3
Polaris 2000 User’s Manual

Safety Precautions

Please read these safety instructions before using this equipment.

For safety purposes, please observe the following when unwrapping and installing the
package:

1. When opening the package, check that the contents have not been damaged during
transit.
2. Check to make sure that the product model and the labeling on the outside of the
packaging are consistent.
3. This product is designed for and suitable for most electrical power panels.
4. Do not install this product at the openings of ventilation ducts or near heat sources.
5. Make sure that the actual wiring conforms to the wiring diagram designated in this
manual.
6. Guard against dust and water damage.
7. Make sure all power sources to be connected to the product have been shut off
before installing.
8. If the equipment is used in a manner not specified by manufacturer, the protection
provided by the equipment may be impaired.

This symbol means double insulation.

This symbol means to beware of electric shock, turn off all adjacent
sources of high voltage during installation.

This symbol means there is risk of danger.

The Polaris is a sensitive electrical equipment, care should be taken so that the
maximum benefit and performance can be derived from the device.

Before cleaning or performing any maintenance on the Polaris, disconnect the device
from its power source. The input voltage and current should be either turned off or
disconnected.

Page 4
Polaris 2000 User’s Manual

Cleaning
Use a dry cloth or dry brush to wipe away the dust, or use in conjunction with a
vacuum cleaner to suck the dust as it is being wiped away. Do not use any water or other
liquid cleaning agents.

Ventilation
Check to make sure that there is sufficient space around the periphery of the Polaris
to allow air to circulate. Reposition any extraneous wiring that is on the Polaris.

Maintenance
Check to make sure that the wiring contacts are tight and making good contact,
tighten any terminal screws that may have loosened over time from jarring or vibration.
Make sure that the wiring contact of each terminal is not touching or shorting adjacent
terminals.

Repair
Do not attempt to repair the product or modify the circuitry; contact the product
representative or a qualified electrical person if the product requires repair or servicing.

Page 5
Polaris 2000 User’s Manual

CONTENT
1 INTRODUCTION ................................................................................................... 7

1.1 GENERAL DESCRIPTION.......................................................................................... 7


1.2 FEATURES ......................................................................................................... 7
1.3 CERTIFICATIONS .................................................................................................. 7
1.4 SPECIFICATIONS .................................................................................................. 7
1.5 COMMUNICATION ................................................................................................. 8
1.6 PRODUCT INFORMATION ......................................................................................... 8

2 INSTALLATION .................................................................................................... 9

2.1 FRONT PANEL ................................................................................................... 10


2.2 TERMINALS ...................................................................................................... 11
2.3 MOUNTING PROCEDURE ....................................................................................... 13
2.4 BEFORE INSTALLATION ........................................................................................ 13
2.5 CONDUIT AND WIRE INGRESS ................................................................................ 14
2.6 METER INSTALLATION .......................................................................................... 15
2.7 CT INSTALLATION .............................................................................................. 15
2.8 WIRING DIAGRAM .............................................................................................. 17
2.9 MEASURING MULTIPLE LOADS WITH ONE METER .......................................................... 18
2.10 POWER SUPPLY ................................................................................................. 19
2.11 USING A REGULAR 5A OUTPUT CT .......................................................................... 19

3 DISPLAY, OPERATION AND SET UP .................................................................... 20

3.1 STARTUP DISPLAY .............................................................................................. 20


3.2 OPERATING BUTTON ........................................................................................... 21
3.3 LED DISPLAY PAGES........................................................................................... 22
3.4 OPERATION ...................................................................................................... 23
3.5 SET UP ........................................................................................................... 24

4 TROUBLESHOOTING ........................................................................................... 27

5 FREQUENTLY ASKED QUESTIONS ....................................................................... 28

6 WARRANTY AND RETURN POLICY ...................................................................... 30

6.1 WARRANTY ...................................................................................................... 30


6.2 RETURN POLICY................................................................................................. 30

7 SUPPLEMENTARY INFORMATION ....................................................................... 31

Page 6
Polaris 2000 User’s Manual

1 Introduction
1.1 General Description

The Polaris 2000 meter is an electronic kilowatt-hour (kWh) meter that is


designed for permanent connection to an electrical service. It is designed for three
phase applications.

The Polaris 2000 meter can be used in either 3 wire or 4 wire configurations.

1.2 Features
 Revenue-grade accuracy
 Non-volatile memory, the stored data is maintained through power outages
 Use with DAE’s dedicated split-core CTs (5~600A). Optional solid-core CTs
also available in 5, 50 & 200A.
 Parallel up to three sets of CTs for cumulative reading

1.3 Certifications
 UL/CUL Listed, California CTEP Approved. Certified by independent test lab
to exceed ANSI C12.1 national accuracy standards.

1.4 Specifications

Item Description
Frequency 50/60 Hz
Working Voltage Derived from A phase
Power Consumption 7VA
Measured Parameters kW, kWh (default), demand (optional)
Operating -20~50 (-4~122 )
Environment 0~95%RH (non-condensing)
Accuracy 1 0.5% from 1% to 100% of rated load
733g (regular terminal cover)
Weight
690g (special terminal cover 2)
W 5” x H 7.42” x D 2.24” wall-mount (regular terminal cover)
Dimensions 2
W 5” x H 6.5” x D 2.24” wall-mount (special terminal cover 2)

1
Based on DAE solid-core CT @ PF=1
2
Please see section 2.5 Conduit and Wire Ingress.

Page 7
Polaris 2000 User’s Manual

1.5 Communication

Item Description
Interface RS485
Protocol Modbus/RTU
1 to 254 (default is last 2 digits of serial number,
Address
01~99=1~99, 00=100)
Baud Rate 1200, 2400, 4800, 9600 bps (default 9600 bps)
Data Format 8/n/1 (8 data bits, no parity, 1 stop bit)

1.6 Product Information

Polaris 2000 meters model No.

No. Item Description


(1) Series P20 – Polaris 2000
(2) Configuration 2 – 3 phase, 3 wire, 480V
3 – 3 phase, 3 wire, 208~240V
4 – 3 phase, 4 wire, 120/208V
5 – 3 phase, 4 wire, 240/416V
6 – 3 phase, 4 wire, 277/480V
(3) CT Rating 005 – 5 amp 3
200 – 50~200 amp
depends on CT current range
400 – 400 amp
600 – 600 amp

3
Please see section 2.11 Using a Regular 5A Output CT.

Page 8
Polaris 2000 User’s Manual

Demand option

Demand is an optional feature, which needs to be specified when ordering.


The meter with demand function will be marked on the label on the left side of the
meter.

Current sensor information

Model No. CT Type Amp Compatible with


CT-5S 5A P20x-005
CT-50S / CT-50SB 50A
CT-100S / CT-100SB 100A P20x-200
1. Split-core
CT-200S / CT-200SB 200A
CT-400S 400A P20x-400
CT-600S 600A P20x-600
CT-5D3 5A P20x-005
CT-50D3 2. Solid-core 50A
P20x-200
CT-200D3 200A
Note : x = 2, 3, 4, 5 or 6

Current sensor requirement

Configuration CTs Required


3 phase, 3 wire 2 CTs
3 phase, 4 wire 3 CTs

2 Installation
The Polaris is a sophisticated energy meter with multiple capabilities and functions.
Before installation be sure to read and understand this section and the appropriate
wiring diagrams. Installation of this device must be performed by qualified personnel
according to these instructions and in conjunction with all applicable electrical codes.
DAE Instrument and its representatives assumes no responsibility for any damage or
injury resulting from the improper installation of this equipment.

WARNING: Please make sure to read the “Safety Precautions” at the beginning
of this manual before starting installation.

Page 9
Polaris 2000 User’s Manual

2.1 Front Panel

6-digit primary LCD display


LED display
for showing kWh and other parameters
TX, RX Reserved
A, B, C Phases A, B, C phase voltage inputs indicator
Watthour test constant indicator
P
Kt=1Wh (1000 imp/kWh)
Load Load status indicator
DI Digital input indicator
Terminal Cover To cover the terminals
Series Model series
Model No. This specific model ordering code
Meter Specification Phase/wire, voltage,
Markings max current and test current

Page 10
Polaris 2000 User’s Manual

2.2 Terminals

Terminal cover removed

Voltage input terminals


(19) VA Phase A voltage input
(20) VB Phase B voltage input
(21) VC Phase C voltage input
(22) VN Phase N voltage input

CT input terminals
(13) CT-A + Phase A CT + input
(14) CT-A - Phase A CT - input
(15) CT-B + Phase B CT + input
(16) CT-B - Phase B CT - input
(17) CT-C + Phase C CT + input
(18) CT-C - Phase C CT - input

Operating button input terminals


(3)
Operating button input
(4)

Other terminals (1~2, 5~12) are reserved.

Page 11
Polaris 2000 User’s Manual

Terminal detail

(1) Voltage input terminals

Use the proper size and wire type as per electrical regulations.

(2) Other terminals

Make sure that the wires are screwed tightly onto the terminals and
making good contact.

(3) Recommended wire size

Terminal type Wire range


Voltage input #10-18 AWG, screw torque 16 lb-inch
CT input #14-22 AWG, screw torque 5 lb-inch
Operating button input #14-22 AWG, screw torque 5 lb-inch

Note : It is important to make sure to consult your local electrical codes for proper
sizing requirements.

Page 12
Polaris 2000 User’s Manual

2.3 Mounting Procedure

(1) The Polaris is wall-mounted, drill the screw holes according to the diagram
below.
(2) Place the Polaris flat against the wall making sure that the mounting holes are
aligned with the screw holes.
(3) Secure the Polaris using the screws through the mount holes.

2.4 Before Installation

(1) Check that the ratings and specifications of the model to be installed is
suitable for its intended application.

(2) Verify that the dedicated CT being used is compatible with the type of Polaris.
Note that the Polaris cannot be directly used with non-DAE dedicated CTs.

(3) Verify that the current rating of the dedicated CT being used is suitable for its
intended load.

(4) Make sure to turn off all power sources to the Polaris and any adjacent power
sources before performing the installation.

Page 13
Polaris 2000 User’s Manual

2.5 Conduit and Wire Ingress

(1) Regular terminal cover

Each Polaris meter has two knockouts at the bottom. Both knockouts can
be cut open for either 1/2" or 3/4" conduit. For voltage and CT wirings, cut
open the knockout for 3/4" conduit. For the RS485 communication cable, cut
open the knockout for 1/2" conduit. Avoid placing both the communication and
power cables in the same conduit to avoid interference.

Note : Please use UL certified cables and conduits.

(2) Special terminal cover

An alternate terminal cover is also available (purchased separately) for


use when the meter is to be installed within an enclosure. The voltage and CT
wires will enter the meter through the rear opening of the terminal cover.

Page 14
Polaris 2000 User’s Manual

2.6 Meter Installation

(1) Attach the dedicated CTs to the CT terminal with their appropriate phases.

(2) Connect the phase A voltage terminal of the Polaris to the corresponding
power source with an intermediate fuse.

(3) Connect the voltage terminals of the Polaris to their corresponding phase
voltages. (* Use 10 to 18 AWG, 600V wire for the voltage terminals.)

(4) Assemble the CTs onto the corresponding conductors being measured
making sure that the direction and orientation of the CTs with wiring are
consistent. With solid core CTs, the wire must be threaded through the CT,
which would necessitate disconnecting the wire from the load. With split core
CTs and clamp type CTs, the CT can be opened and clipped or clamped onto
the conductor without the need to disconnect the wiring to the load.

2.7 CT Installation

The Polaris can only make use of the dedicated CTs provided by DAE. There are
two types of dedicated CTs as shown in the following descriptions.

(1) Split-core CT installation

Load side

Step 1. Open the split-core CT Step 2. Lay the load wire inside the
opening

Step 3. Snap close the split-core CT

Page 15
Polaris 2000 User’s Manual

Meter side

Connect the CT white wire to the CT+ terminal on the meter, and the CT
black wire to the CT– terminal on the meter. Please refer to section 2.2 on
Terminals.

(2) Solid-core CT installation

Load side

With solid core CTs, the wire must be threaded through the CT, which
would necessitate disconnecting the wire from the load.

Meter side

Connect the CT white wire to the CT+ terminal on the meter, and the CT
black wire to the CT– terminal on the meter. Please refer to section 2.2 on
Terminals.

Page 16
Polaris 2000 User’s Manual

2.8 Wiring Diagram

(1) 3 phase, 3 wire

Fuses

VAB, VBC, VCA = 120V or 208~240V or 480V

Note : Please install a fuse for each voltage input. (Except the phase N)

(2) 3 phase, 4 wire

Fuses

VAN, VBN, VCN = 120V or 240V or 277V

Note : Please install a fuse for each voltage input. (Except the phase N)

Page 17
Polaris 2000 User’s Manual

2.9 Measuring Multiple Loads with One Meter

(1) The loads must be the same configuration and come from the same power
source.

(2) Each meter can accept 3 loads at most, each load needs to have its own set
of CTs and each CT must be of the same rating.

(3) The load wires threaded through the CTs must be in the same direction. Each
of the CTs for the same phase on different loads must be connected to the
correct polarity (CT white wire to the CT+ terminal on the meter, and the CT
black wire to the CT– terminal on the meter)

e.g. 3 phase, 4 wire on 2 loads

Fuses

Page 18
Polaris 2000 User’s Manual

2.10 Power Supply

The power supply of the Polaris is derived from the phase A voltage. To provide
additional protection for the Polaris, a fuse should be placed between the Polaris
and the power source as shown in each of the electrical wiring diagrams.

2.11 Using a Regular 5A Output CT

For installations with pre-existing CTs already in place, or if a larger capacity


CT is required than is available, then the user should choose the dedicated 5A CT4
and connect the user provided CT to the dedicated 5A CT 5 as shown in the
diagram below.

When using regular 5A output CTs, the meter needs to have its CT ratio set. For
example, when using a 500A:5A regular CTs, the CT ratio should be set to 100.

4
Can be used on the P20x-005.
5
Dedicated 5A CTs are CT-5S (split-core) and CT-5D3 (solid-core).

Page 19
Polaris 2000 User’s Manual

3 Display, Operation and Set Up


The Polaris meter has several pages of displayable information, settings and
measurement parameters.

3.1 Startup Display


The power up sequence of the Polaris shows the following information on the
display:

Display
# Example Description Range
Shows

1 8.8.8.8.8.8. LED display test ---

2 A1-xxx Reserved ---

3 b1- xx Reserved ---

Firmware
4 r--xxx Varies
version
(1) 2000 = Polaris 2000
(2) a = d (with demand)
a = n/a (without demand)
Polaris type
5 2000ab (3) b = A (P20x-005)
and function
b = n/a (P20x-200)
b=4 (P20x-400)
b=6 (P20x-600)

6 8.8.8.8.8.8. LED display test ---

P.-05

7   Page 5
Energy (kWh)
0~99,999.9 kWh

xxxxx.x

Page 20
Polaris 2000 User’s Manual

3.2 Operating Button

The Polaris meter requires an external button to change the displayed


contents. Please follow the steps below to install the button.

(1) Operating button input terminals

(2) Install the operating button

Page 21
Polaris 2000 User’s Manual

3.3 LED Display Pages

(1) Basic operation

(2) LED display pages

Pages & display Description

LED display test

Polaris type and function


(see section 3.2)

Firmware version

CT ratio6

Energy (kWh)

Power (kW)

Peak Demand (kW)7

Demand (kW)7

6
Shown only on the P20x-005, P20x-400 and P20x-600.
7
Shown only on the Polaris meters with demand function.

Page 22
Polaris 2000 User’s Manual

3.4 Operation

Follow the steps below to change between “Manual Mode” and “Auto Mode”.

(1) Manual mode (default)

During manual mode, the display will remain fixed displaying one
parameter unless the button is pressed.

Each time the button is pressed, the display will go to the next parameter.
It will first display the parameter number then after a pause of one second it
will show the value for that parameter. If the button is not pressed after 3
seconds, the display will return to displaying the kWh.

When the last parameter is reached and the button is pressed, the display
will cycle back to the “888888” display test page, the operator may choose to
press and hold the button for 3 seconds if they want to change to auto cycling
mode.

(2) Cycle mode

During auto cycling mode, the display will automatically cycle among all
the parameters. The parameter number is first displayed, then after a pause
of one second it will show the value for that parameter, then after another
pause of 3 seconds, the next parameter number is displayed.

This process will continue until all parameters are shown in turn, after the
last parameter is shown, the display will cycle back to the “888888” display
test page, the operator may choose to press and hold the button for 3
seconds if they want to change to manual cycling mode.

If the operator wants to hurry the cycling process, they may press the
button to skip the pause and immediately go to the next parameter.

Page 23
Polaris 2000 User’s Manual

3.5 Set Up

(1) CT ratio

Step 1
Press the button and switch to P.-04, CT ratio.

Step 2
Press the button and hold for 3 seconds, and the first number of the CT
ratio starts to blink.

Blinking
Press the button to change the digit. Press the button and hold for 3
seconds to move to the next digit of the CT ratio.
The range of the CT ratio is 1~400.

Step 3
After setting up the CT ratio, press the button and hold for 3 seconds to
return to the kWh display page.

Note: Only the models P20x-005 can have their CT ratio set and their default is 1.
The CT ratio of P20x-400 is 2 and the CT ratio of P20x-600 is 3 both of which
are fixed and cannot be changed.

Page 24
Polaris 2000 User’s Manual

(2) Resetting the peak demand

Step 1
Press the button and switch to P.-07, peak demand.

Step 2
Press and hold the button until the peak demand value is reset to zero

The rolling demand start time is also reset.

Step 3
The display will return to the kWh page automatically.

Page 25
Polaris 2000 User’s Manual

(3) Rolling demand duration (default = 15 minutes)

Step 1
Press the button and switch to P.-08, demand.

Step 2
Press the button and hold for 3 seconds, and the display shows the rolling
demand duration, which is also blinking and changeable.

Blinking
Press the button to change the value. It can be set to 15 minutes, 30
minutes and 60 minutes.

Step 3
After setting up the rolling demand duration, press the button and hold for 3
seconds to return to the kWh display page.

Page 26
Polaris 2000 User’s Manual

4 Troubleshooting
The Polaris meters are fully calibrated and tested during production. The Polaris
meters should work normally if installed properly by correctly following our installation
guide. If the meter has any problem, please consider the following troubleshooting
procedures.

Problems or Symptoms Possible Causes and Solutions


The LED does not light up. (a) Check that the voltage input terminal wiring are
connected properly.

(b) Check that the fuse and circuit breaker are


neither blown nor tripped, respectively.

(c) Check to make sure that power is being supplied


from the power source to the voltage input.

(d) Check that the power source voltage is within the


rated power supply.

(e) Check to make sure that the enclosure or


terminals are not damaged.

kWh value is not incrementing. (a) Check that CT wiring to the terminals.

(b) Check to make sure that the measured circuit


corresponds to its phase.

(c) Check to make sure that the power is on for the


load circuit being measured.

(d) Check the fuse or circuit breaker.

(e) Check to make sure that only the L wire passes


through the CT. If the N wire is also passing
through then remove it from the CT.

(f) The CT may be damaged or defective, swap it


with another CT for a cross check. If defective or
damaged, replace the CT.

Page 27
Polaris 2000 User’s Manual

Problems or Symptoms Possible Causes and Solutions


Any Voltage input indicators do not (a) Check to make sure that the voltage input
light up. terminal wiring is connected properly.

(b) Check the voltage input terminals are not


damaged.

The accumulation of kWh does not (a) Check to make sure the voltage input is
match total consumption. continuously 24 hours/day.

(b) Check the CT wiring direction on load and


polarity on meters if parallel 2 or 3 CTs for any
phase. When parallel 2 or 3 CTs, the wiring
direction and polarity must be the same.

5 Frequently Asked Questions


Q. Why is the kWh value of a new Polaris meter not zero?
A. Each Polaris meter must proceed a loading test with a calibration exam before put
in stock. The kWh value exists to make sure this unit passes the calibration exam.

Q. What is the meaning of Kt = 1Wh?


A. It means 1000 pulses will be output for every kWh. Another way of saying it is that
1 pulse is output for every Watt. The P indicator will flash once for every Watt
consumed.

Q. Does the Polaris meters come with its own CTs? Can I make use of my own
CTs?
A. The Polaris meters are sold with the CTs included which cannot be used direct
connects. The Polaris 2000 meters use DAE’s dedicated CTs and can accept
neither regular 5A output CTs nor dedicated CTs from other suppliers. The CT
input of the Polaris can only accept milli-amps which matches DAE’s dedicated
CTs. Connecting a regular 5A output CT directly will thus damage the Polaris
meters.

Q. Can the CT lead wire be extended?


A. Yes, the CT lead wire can be extended up to 2000 feet. An example of a suitable
cable would be the 7958A or the 7957A from Belden cables. It is important to
make sure to consult your local electrical codes for proper sizing requirements.

Page 28
Polaris 2000 User’s Manual

Q. Can a single CT be used to monitor multiple circuits?


A. It is possible to do so if the different circuits share the same phase and power
source. The L wire for each circuit must go through the CT in the same direction,
and the current rating of the CT in must be higher than the total amperage for all
the circuits to be measured.

Q. Can a single Polaris be used to monitor two different sub panels?


A. It is possible if the two sub panels have the same power source. If the two sub
panels do not share the same power source, then two separate Polaris must be
used.

Q. What will happen if the polarities are reversed for each of the CT?
A. The Polaris only considers the absolute value of the current and disregards the
direction; thus, the current and energy values can only be positive. However, we
still recommended that the CTs be connected with the correct wiring orientation.

Q. What does Polaris message “cht-01” mean?

A. It means that the circuit currently being measured has a power factor that is less
than 0.5. This is not normal behavior and could be caused by having the phases
reversed (voltage and current phases are not properly matched), or there may be
some run-down equipment that are in need of repair or replacement. Check to
make sure that the voltage and current inputs are matched properly, if they are,
they check the condition of equipment on the circuit being measured.

Q. I have checked and followed all the troubleshooting guidelines but my


problem is still not resolved; what should I do?
A. Contact our technical support by phone or email before concluding that the unit is
faulty and removing it. Our technical support team will help to diagnose your
problem and provide advice on potential fixes. Please see Section 8,
Supplementary Information, for our contact info.

Page 29
Polaris 2000 User’s Manual

6 Warranty and Return Policy


6.1 Warranty

The warranty is effective for a period of five years from the date of shipment. The
buyer must inform DAE of the defect within 80 days after the defect is experienced or
found. DAE’s responsibility is limited to repair, replacement, or refund, any of which
may be selected by DAE in its sole discretion. DAE reserves the right to substitute
functionally equivalent new or serviceable used parts.

This warranty covers only defects from normal use and does not include the
damage due to improper installation, improper maintenance, misuse, neglect, water
damage, acts of nature, tornadoes, any alterations or repairs that are not DAE.

DAE's liability to the Customer from the sale of DAE's products, whether such
liability is asserted on the basis of contract, tort or otherwise, shall not exceed the
purchase price paid by Customer for the products claimed.

6.2 Return Policy

All returned material must be in good, “as new” and in salable condition. A 20%
restocking fee is charged on all RMA’s.

Products may not be returned if more than 80 days have elapsed since the
shipment date from DAE.

Buyer must notify DAE and request a Returned Material Authorization Number
(RMA Number) and state the specific reason for return. Unauthorized returns will not be
accepted. When requesting an RMA Number please supply the following information:

(1) Distributor name and address


(2) Model number of meter
(3) Original purchase order number
(4) Reason for return

All paperwork and boxes must be marked with an RMA number issued by DAE. All
authorized returned materials must be shipped freight prepaid to DAE. DAE is not
responsible for uninsured packages or packages lost by your carrier.

RMA's are only valid for 30 days. The buyer will be responsible for all return
shipping costs and customs duties.

Page 30
Polaris 2000 User’s Manual

7 Supplementary Information
Please add fuses to the voltage input to protect damage from a short circuit.

Our contact information

US Website: www.DAEcontrols.com
US Email: info@DAEcontrols.com
US Phone: +1-248-635-3708
International Website: www.DAEinstrument.com
International Email: info@DAEinstrument.com
International Phone: +886-2-2793-6123

Note : This document may change without notice, please check our website for
the latest version.

Page 31

You might also like