STS Digital Energy TM

STS
Static Transfer Switches

Static Transfer Switches (STS) are designed to transfer


the supply between 2 independent AC power sources.
Unlike traditional automatic transfer switches (ATS), a
static transfer switch provides a fast load transfer (typi-
cally 1/4 of a cycle), which ensures uninterrupted opera-
tion of sensitive electronic equipment. Load retransfer to
the preferred input source is virtually instantaneous
(typically 0.1 ms). The basic applications of STS are in
automatic systems in the power industry, power supply
systems for petrochemical industry, computer and tele-
communication centers, automatic and security systems
of 'intelligent' buildings as well as other equipment which
is sensitive to interruptions in the supply. The excellent
overload capability and transfer algorithm enables fast
fuse clearance in the event of a short-circuit. In conse-
quence the voltage immediately returns to normal to
supply the other loads. The built-in transient voltage surge
suppression system for SCR switches provides additional
protection against damage to the supplied equipment.

The static transfer switch consists of two (for each phase)


bidirectional thyristor switches equipped with a control and
protection system. The 4 pole types have an additional
neutral line switch. After failure of the preferred source,
the STS checks the state of the alternate power source
and transfers the load to the source that provides power
within selectable limits. This transfer can be triggered by:
disturbance in the preferred source voltage, overcurrent in
the source, manual or remote change of the preferred source.

With both sources in limits and synchronized (phase error within the acceptable range), manual or
remote transfer is performed in less than 200 µs. Transfers initiated by fault conditions in the pre-
ferred source depend on the status of the alternate source. For synchronized power sources with
phase error within the limits, switching to an alternate source is obtained within 6 ms delay. Lack of
synchronization causes delay before transfer. It is possible to set the delay with dipswitches.

Through their complete life cycle, all GE Power Quality systems are fully supported by service teams
which provide world-class, 24x7 preventive and corrective services, training and application expertise.

FEATURES & BENEFITS

● Selectable voltage limits for full flexibility to protect ● Blocked transfer in case of short circuit preventing
equipment against sags, swells and interruptions to jeopardize other user.
● Three redundant power supplies providing maximum ● Manual bypass for no-break operation of the load
reliability during maintenance
● Fail-Safe CMOS logic for fast and reliable control ● Dry contacts to provide status and alarm
of the STS information to other control systems
● Easy to install and to operate ● Rackmounted models for easy integration into
● Redundant cooling providing full functionality, other systems
even in case of a fan failure ● Userfriendly control panel for easy operation
● Surge protection to prevent damage to the STS ● Neutral dimensioned for 200% of nominal current
and the supplied equipment to handle imbalanced loads

UPS Product Technology - www.gedigitalenergy.com ENGLISH


TECHNICAL SPECIFICATIONS
Nominal Current Rating 25A 40A 63A 100A 150A 250A 400A 630A
Enclosures
3 pole, floorstanding cabinet * A B C F
3 pole, 19 inch rackmounted * E -
4 pole, floorstanding cabinet * A B C F D
4 pole, 19 inch rackmount * E -
Weight (kg), preliminary 60 68 72 195 195 195 280 280
Color RAL 7032
Input characteristics
Nominal input voltage 3 x 400V ph-ph
Input voltage window -25% / +20%
Nominal frequency 50Hz
Frequency window -9% / +6%
Output characteristics
Efficiency >99% at cos phi 0.8
Crestfactor acceptance 3.5
Powerfactor (max. Cos phi) 0.5 - 1.0 (leading/lagging)
Overload behavior 125/400/800/1000/1500% 1 hour, 5sec, 400ms, 200ms, 20ms
Short circuit current withstand (max 20ms) 3200A 8000A 15000A 25500A 39000A
Transfer time (manual triggering) < 0.1 ms
Transfer time (automatic transfer) < 6 ms, typical: 3 ms
Settings
Overvoltage level setting + 6/9/13/16/20%, selectable by dipswitch
Undervoltage level setting - 8/12/16/24%, selectable by dipswitch
Phase delay limit (for synchronized lines) 8/12/16/20/24 degrees, selectable by dipswitch
Transfer blocked after output current exceeding limit no blocking, 3/4.5/6/7.5/9 x nominal current, selectable by dipswitch
Transfer time (lines not synchronized) 13/17/25/50 ms , selectable by dipswitch
Delay for retransfer to preferred source 0.8/1/8/25 sec, selectable by dipswitch
Ambient conditions
Operating temperature 0-40 degr. Celcius
Humidity <95%, non condensing
Altitude 1000 m (above 1000m 5% derating per 500m ; max: 3000m)
Cooling redundant cooling fans
Audible noise < 55 dBA
EMC EN50022 level B, EN60555-23
Protection IP20 (floorstanding), IP00 (for rackmounted models)
Alarm / Status Contacts
Dry contacts 300Vdc or 250Vac / 0.3A dc or 4A ac @220V
Status information manual transfer on, retransfer off, primary/secondary source OK, primary/secondary source on
Disturbance alarms primary/secondary source not healthy, sources not synchronized, manual control on
Failure alarms overload, overtemperature, fuse failure, internal STS failure

* Dimensions of cabinets h x w x d (mm) A:1100x800x400 B:1900x800x500 C:1900x1200x500 D:2300x1200x600 E:710x483x465 F:2100x1200x600

GE Consumer & Industrial


Via Cantonale 50
6595 Riazzino (Locarno)
Switzerland
+ 41 (0) 91 850 51 51

1 Oak Hill Center, Suite 301


Westmont, IL 60559, USA
+ 1 773 299-6600
866. GEDE:UPS
(866 433 3877)

www.gedigitalenergy.com
GEA D1018 CE © General Electric Company, USA All Rights Reserved (01/04) Reproduction only upon written consent by GE