An Enhanced Intelligent Facts Device For Reduction
An Enhanced Intelligent Facts Device For Reduction
An Enhanced Intelligent Facts Device For Reduction
net/publication/361144170
CITATIONS READS
0 12
3 authors, including:
J.P. I. Iloh
Chukwuemeka Odumegwu Ojukwu University
30 PUBLICATIONS 22 CITATIONS
SEE PROFILE
All content following this page was uploaded by J.P. I. Iloh on 02 May 2023.
Authors’ contributions
This work was carried out in collaboration among all authors. All authors read and approved the final
manuscript.
Article Information
DOI: 10.9734/JERR/2022/v22i917561
ABSTRACT
In this research, an enhanced intelligent FACTS device for reduction of losses on power lines
using intelligent Static Synchronous Series Compensator (SSSC) devices for Nigerian 330kv
network has been presented. The findings showed total real power losses of 127.9131MW before
network compensation, with transmission lines accounting for 125.7MW and producing stations
accounting for 2.2131MW. After compensation using Static Synchronous Series Compensator
(SSSC), the total Real power losses were reduces to 104.53MW, while the total Reactive losses
(MVar) reduced to 26.87MVar. The research concludes that the injection of reactive power by
Static Synchronous Series Compensator (SSSC) devices compensates for the drop in voltage,
leading to improvement in voltage and reduces power losses for the network.
23
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Except for the slack bus, where V and 8 are where sis very small number.
defined, we assume the bus voltage magnitude
and phase angle for other load buses where P 3.2 52 Bus Test System
and Q are stated. We usually use a flat voltage
start, which means we set the expected bus In the 52 bus test system, load flow analysis is
voltage magnitude and phase angle (i.e., the real performed. Table 1 Appendix1 shows the output
and imaginary components e and / of the bus voltage magnitude and voltage angle values
voltages) to the slack bus quantities. from the Newton Raphson method for a 52 bus
system. All values are in per unit and angle is
We calculate the real and reactive components given in radian. Fig. 1 depicts a single-line
of power, i.e., Pi and Qi, for all buses I = 2, 3, diagram of Nigeria's enhanced 52-bus 330kV
4,..., n except the slack bus, by substituting transmission network.
these assumed bus voltages (i.e., e and f) (bus
no. 1). 3.3 Load Flow Input Data
Since Ptand Qi for any bus i is given,
i.e.,specified, the error in power will be The load flow data displaying load and
generation at the buses is one of the input data
……………. (1) for the power flow analysis. The flowchart for
Newton-Power Raphson's Flow Solution is
shown in Fig. 2.
where r is an iteration count.
4. RESULTS AND DISCUSSION
Here and are the power calculated with
the latest value of bus voltages at any iteration r. 4.1 Results
Then the elements of Jacobian matrix (J1,J2, J3 4.1.1 Result of load flow with and without
and J4) are determined with the latest bus facts
voltages and calculated power equations.
The first procedure was to run computation of
After this the linear set of equation (1) is solved
the case study program in software. Then, the
by iterative technique or by the method of
simulation was done with and without
elimination (normally by Gaussian elimination
incorporation of FACT devices.
method) to determine the voltage correction, i.e.,
24
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Fig. 1. One-line diagram of the improved 52-bus 330kv nigerian transmission network
25
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Table 2 in Appendix 2 shows the Line flow and The active power loss for the voltage with SSCS
Losses before compensating with FACTS is shown in Fig. 4.
devices.
4.2 Discussion
From the active power loss for the voltage
without SSSC as depicted in Fig. 3, there is a The acquired results based on the test case
clear indication that the power loss is higher as (Nigeria 330 kv integrated power system)
can be seen in the figure as against the active revealed that the voltage profile and power
power loss when an intelligent FACTS device transfer in the network had significantly
was incorporated as can been seen in fig 4. improved.
The overall Real power losses were reduced to According to the findings, transmission lines
104.53MW with SSSC compensation, while the account for around 125.7MW of the total real
total Reactive losses (MVar) were reduced to power losses of 127.9131MW before
26.87MVar. compensation from the network, while
generating stations account for 2.2131MW.
It can also be clearly deduced that the losses Furthermore, transmission lines account for
(MW) on buses 8 and 15 in the 52 bus 30.75MVar of the total reactive power losses
transmission line without compensation is higher created in the network, while generating stations
than the power losses on the same 8 and 15 account for 31.5424MVar.
buses on the 52 bus power network as seen in
Figs. 3 and 4 respectively. The overall Real power losses were reduced to
104.53MW with SSSC compensation, while the
Table 3 in Appendix 3 shows the Line flow and total Reactive losses (MVar) were reduced to
Losses after compensating with FACTS devices. 26.87MVar.
Fig. 3. The active power loss for the voltage without SSSC
26
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Fig. 4. The active power loss for the voltage with SSSC
27
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
28
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
LIST OF APPENDICES
Appendix 1
Table 1. Bus voltages and angles of the integrated 52 network using N-R algorithm
29
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Appendix 2
30
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
Appendix 3
Table 3. The line flow and losses of 52 bus system using SSCS
31
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
32
Anyanor et al.; JERR, 22(9): 22-33, 2022; Article no.JERR.86904
© 2022 Anyanor et al.; This is an Open Access article distributed under the terms of the Creative Commons Attribution License
(http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium,
provided the original work is properly cited.
Peer-review history:
The peer review history for this paper can be accessed here:
https://www.sdiarticle5.com/review-history/86904
33