Schneider Electric - Altistart-22 - ATS22D62Q

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Product data sheet

Specifications

soft starter-ATS22-control 220V-


power 230V(15kW)/
400...440V(30kW)
ATS22D62Q

Main
Range Of Product Altistart 22

Product Or Component Type Soft starter

Product Destination Asynchronous motors

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Specific Application Pumps and fans

Component Name ATS22

Network Number Of Phases 3 phases

[Us] Rated Supply Voltage 230...440 V - 15...10 %

Motor Power Kw 15 kW 230 V


30 kW 400 V
30 kW 440 V

Factory Setting Current 57 A

Power Dissipation In W 59 W for standard applications

Utilisation Category AC-53A

Type Of Start Start with torque control (current limited to 3.5 In)

Icl Starter Rating 62 A for connection in the motor supply line for standard applications

Ip Degree Of Protection IP20

Complementary
Assembly Style With heat sink

Function Available Internal bypass

Supply Voltage Limits 195…484 V

Supply Frequency 50...60 Hz - 10...10 %

Network Frequency 45...66 Hz

Device Connection To the motor delta terminals


In the motor supply line

[Uc] Control Circuit Voltage 230 V - 15...10 % 50/60 Hz

Control Circuit Consumption 20 W

Discrete Output Number 2

Discrete Output Type Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/
O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/
O

Minimum Switching Current 100 mA at 12 V DC (relay outputs)

List Price displayed is VAT EXCLUSIVE.

Nov 21, 2023 1


Maximum Switching Current 5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs

Discrete Input Number 3

Discrete Input Type (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm

Discrete Input Voltage 24 V <= 30 V

Discrete Input Logic Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA

Output Current 0.4...1 Icl adjustable

Ptc Probe Input 750 Ohm

Communication Port Protocol Modbus

Connector Type 1 RJ45

Communication Data Link Serial

Physical Interface RS485 multidrop

Transmission Rate 4800, 9600 or 19200 bps

Installed Device 31

Protection Type Phase failure: line


Thermal protection: motor
Thermal protection: starter

Marking CE

Type Of Cooling Forced convection

Operating Position Vertical +/- 10 degree

Height 295 mm

Width 145 mm

Depth 207 mm

Net Weight 12 kg

Motor Power Range Ac-3 15…25 kW at 200…240 V 3 phases


30…50 kW at 380…440 V 3 phases

Motor Starter Type Soft starter

Environment
Electromagnetic Compatibility Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5

Standards EN/IEC 60947-4-2

Product Certifications C-Tick


CCC
UL
CSA
GOST

Vibration Resistance 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6


1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6

Shock Resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27

Noise Level 45 dB

Pollution Degree Level 2 conforming to IEC 60664-1

Relative Humidity 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

2 Nov 21, 2023


Ambient Air Temperature For -10…40 °C (without derating)
Operation 40…60 °C (with current derating 2.2 % per °C)

Ambient Air Temperature For -25…70 °C


Storage
Operating Altitude <= 1000 m without derating
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 31.0 cm

Package 1 Width 23.5 cm

Package 1 Length 36.0 cm

Package 1 Weight 8.262 kg

Unit Type Of Package 2 P06

Number Of Units In Package 2 6

Package 2 Height 73.5 cm

Package 2 Width 80.0 cm

Package 2 Length 60.0 cm

Package 2 Weight 64.0 kg

Contractual warranty
Warranty 18 months

Nov 21, 2023 3


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.

Learn more arrow2_right

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Declaration

China Rohs Regulation China RoHS declaration

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

4 Nov 21, 2023


Product data sheet ATS22D62Q
Dimensions Drawings

Frame Size B

Dimensions

Nov 21, 2023 5


Product data sheet ATS22D62Q
Mounting and Clearance

Precautions

Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH


ATS22 soft starters are open devices and must be mounted in a suitable enclosure.

Failure to follow these instructions will result in death or serious injury.

Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the
unit.

Overheating
To avoid the soft starter to overheat, respect the following recommendations:

• Mount the Altistart 22 Soft Starter within ± 10° of vertical.


Do not locate the Altistart 22 Soft Starter near heat radiating elements.
• Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the
• ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient
enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.
• If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat
generated from the bottom soft starter can adversely affect the ambient temperature around the top soft
starter.

6 Nov 21, 2023


Product data sheet ATS22D62Q

Mounting

Connection Between the Fan and the Altistart 22 Soft Starter

1 Altistart 22 Soft Starter

2 Fan

Nov 21, 2023 7


Product data sheet ATS22D62Q

Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection

Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.

Ventilation Grilles

Forced Ventilation Unit

8 Nov 21, 2023


Product data sheet ATS22D62Q
Connections and Schema

Power Terminal

Cage Style

1 Ground connection

Power connections, minimum and maximum wiring capabilities, tightening torque


IEC cable UL cable

min 4 mm (a) 10 AWG (a)


Size/gauge
max 50 mm 1/0 AWG

Power supply and output to motor min 8 N.m 70 lb.in


Tightening torque
max 8 N.m 70 lb.in

Strip length 15 mm 0.6 in.

Power connections, minimum required wiring section


IEC cable UL cable
mm² (Cu 70°C/158°F) (1) AWG (Cu 75°C/167°F) (1)

16 4

Nov 21, 2023 9


Product data sheet ATS22D62Q

230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control

With Line Contactor, Freewheel or Controlled Stop

10 Nov 21, 2023


Product data sheet ATS22D62Q

230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop

Nov 21, 2023 11


Product data sheet ATS22D62Q

Connection in the motor delta winding in series with each winding

Wiring
ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.
The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user
manual. Please contact Schneider Electric commercial organisation for further informations.

Example
A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each
winding is equal to 195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal
current (ICL) just above this current.

12 Nov 21, 2023


Product data sheet ATS22D62Q
Performance Curves

Motor Thermal Protection - Cold Curves

Curves

A Class 10

B Class 20

C Class 30

Trip time for a Standard Application (Class 10)

3.5 ln

32 s

Trip time for a Severe Application (Class 20)

Nov 21, 2023 13


Product data sheet ATS22D62Q

3.5 ln

63 s

Trip time for a Severe Application (Class 30)

3.5 ln

95 s

14 Nov 21, 2023


Product data sheet ATS22D62Q

Motor Thermal Protection - Warm Curves

Curves

A Class 10

B Class 20

C Class 30

Trip time for a Standard Application (Class 10)

3.5 ln

16 s

Trip time for a Severe Application (Class 20)

3.5 ln

Nov 21, 2023 15


Product data sheet ATS22D62Q

32 s

Trip time for a Severe Application (Class 30)

3.5 ln

48 s

16 Nov 21, 2023