0 PUMPING SYSTEM
8.1 Providing, fixing, testing and commissioning of Vertical in line type pump set
with SS casing, SS impeller and SS shaft suitable for operation on 400/440
volts, 3 phase 2900 RPM, TEFC electric motor mounted on a common
channel base plate with coupling guard, 150mm dia pressure gauge, GM
isolation cock and cement concrete foundation with plaster complete as
required.
c) 1 No. Variable speed drive Electric control panel with controller relays,
sequence timer for alternate operation of pumps, electrical wiring, cabling
from panel to pumps, level controller complete with all accessories as per
manufacturer specifications.
8.4 Providing, fixing and commissioning non clog type stainless Steel mono
block submersible drainage pumps suitable for handling solids of 12 mm
size with totally water and dust proof motor.
a) Capacity 300 lpm & Head 15m (In chilled water plant & basement) Each 4
b) Capacity 500 lpm & Head 15m (In pumproom) Each 2
8.6 Providing, fixing, testing and commissioning of Digital 5 Stage Water level
Indicators/ controllers with low voltage Relays and Magnetic Analog
Stainless Steel Probe operated by a single Float, including necessary wiring
and conduiting from probes to display panel/motor control panels and to
provide Audible Alarm for low level for each underground tank. (The cost of
required cabling from probe to Display/ Control panel and from Display to
Motor control panels to be paid separately).
8.7 Providing, fixing, testing and commissioning of dust, damp and vermin
proof, free floor standing factory built sheet steel enclosed nondrawout
modular panel for water supply pumps, fabricated out of suitable sized
square tubular section and covered with 2.0mm thick CRCA sheet, hinged
doors of 2mm thick CRCA sheet, duly painted complete with earth bus,
necessary metering protections & indications and mounted with the
following including all inter connection etc. (Including earthing).
a) One No. 150 amps TP incoming MCCB complete with the following:
i) 1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and fuses. (1
set).
ii) 1 No. 0-200 amps 96x96sq.mm ammeter with 60/5 amps ratio CT's and
selector switch.
iii) Over voltage and under voltage tripping machanism for persistent voltage
fluctations of more than ±10% of the rated voltage for more than 5 minutes.
(1set)
iv) Phase indicating lamps with toggle switches.
v) Indication lamps for ON/OFF/TRIP status of motors.
b) Aluminium bus bar of 200 amps for three phase and neutral.
c) Outgoing Feeders/Starters.
i) 16 amps TPN MCB with DOL starter each suitable 3 HP filter feed pumps
(2 Nos).
ii) 100 amps TPN MCCB each suitable for 20 HP hydropneumatic pumps
panel for domestic water supply (1 Set)
iii) 16 amps TPN MCB each suitable for 2 HP hydropneumatic pumps panel for
domestic water supply for RO water supply (1 Set)
iv) 63 amps TPN MCB each suitable for 10 HP RO panel (1 No.)
v) 32 amps TPN MCB each suitable for 5 HP drainage pumps panel in
pumproom (1 Set).
vi) 16 amps TPN MCB each suitable for 2 HP drainage pumps panel in chilled
water plant & basement (2 Sets).
vii) 16 amps TPN MCB each suitable for 2 HP submersible open well pump
panel in rain water collection tank (2 Sets).
viii) 32 amps TPN MCB each suitable for 5 HP tubewell pumps panel (2 Sets).
xi) Note :
a) All switch gear/panels shall be suitable for 10 KA rating.
b) All outgoing will have 96 sq. mm size ammeter and CT.
c) All starter will have spare 10 amps 230 V coil auxiliary contractor for
building Automation system.
d) All starter units for pumps to be provided with 3 level liquid level contractor.
e) Lamps.
f) All pumps to be provided with duty selector switch.
g) All pumps to be provided with sequence timer 220/440 V AC/DC and
alternate working of pumps between 6 to 8 hours or alternate use of pumps
after one service in sequence.
h) All pumps to be provided with over load relay.
i) All starter to be provided with single phase preventor.
j) Necessary cable alleys for space switches, level controller internal wiring
and copper earthing of all equipment shall also be included. All switch
gears/control gears shall be motor duty rating.
xi) Provisions of BMS system for pumps to be included in electrical
control panel. The panel manufacuturer shall include the following:
a) PF contact at Pumps Starter panels for Pumps Start/Stop Command for all
pumps indicated above.
b) PF contact at Pumps Starter panels for Pumps Run Status for all pumps
indicated above.
c) PF contact at Pumps Starter panels for AUTO/MANUAL switches for all
pumps indicated above.
d) PF contact at Pumps Starter panels for over load relay trip signals for all
pumps indicated above.
e) Cabling from BMS system to this panels will be done by BMS contractor.
Each 1
8.8 Providing, fixing, testing and commissioning of dust, damp and vermin
proof, wall mounted factory built sheet steel enclosed nondrawout modular
panel for water supply pumps, fabricated out of suitable sized square
tubular section and covered with 2.0mm thick CRCA sheet, hinged doors
of 2mm thick CRCA sheet, duly painted complete with earth bus,
necessary metering protections & indications and mounted with the
following including all inter connection etc. (Including earthing). (For
drainage pumps in chilled water plant & basement & submersible open well
pump panel in rain water collection tank ).
i) PF contact at Pumps Starter panels for Pumps Start/Stop Command for all
pumps indicated above.
ii) PF contact at Pumps Starter panels for Pumps Run Status for all pumps
indicated above.
iii) PF contact at Pumps Starter panels for AUTO/MANUAL switches for all
pumps indicated above.
iv) PF contact at Pumps Starter panels for over load relay trip signals for all
pumps indicated above.
v) Cabling from BMS system to this panels will be done by BMS contractor.
Set 4
8.9 Providing, fixing, testing and commissioning of dust, damp and vermin
proof, wall mounted factory built sheet steel enclosed nondrawout modular
panel for water supply pumps, fabricated out of suitable sized square
tubular section and covered with 2.0mm thick CRCA sheet, hinged doors
of 2mm thick CRCA sheet, duly painted complete with earth bus,
necessary metering protections & indications and mounted with the
following including all inter connection etc. (Including earthing). (For
drainage pumps in pump room).
i) PF contact at Pumps Starter panels for Pumps Start/Stop Command for all
pumps indicated above.
ii) PF contact at Pumps Starter panels for Pumps Run Status for all pumps
indicated above.
iii) PF contact at Pumps Starter panels for AUTO/MANUAL switches for all
pumps indicated above.
iv) PF contact at Pumps Starter panels for over load relay trip signals for all
pumps indicated above.
v) Cabling from BMS system to this panels will be done by BMS contractor.
Set 1
8.10 Providing, laying, jointing, testing, & commissioning the PVC insulated &
sheathed FRLS Armoured cables of 1.1 K.V. Aluminium Conductor
including supplying and making and termination with brass compression
glands: