Ansul FA Design Guide
Ansul FA Design Guide
Ansul FA Design Guide
Section 4
AutoPulse Design
Using the information gathered from the hazard analysis we As a general rule, clean environments such as computer
can now design the detection and control system. This will rooms, switch gear rooms, telecommunications, and similar
include detector selection and placement, alarm selection areas incorporating clean agent fire suppression systems use
and placement, and control unit selection and placement. smoke detection. Industrial applications such as dip tanks,
lube pits, printing presses, turbine generators, etc.,
DETECTOR SELECTION incorporating CO2 or dry chemical fire suppression systems
Detectors for fire protection systems continuously monitor use rate compensated heat detectors. Petrochemical
their environment and respond to changes caused by a fire. processes and handling, such as loading racks, storage
These environmental changes are referred to as the fire tanks, pumping stations, etc., requiring fast detection
signature and occur during the four stages of fire (see Figure incorporating dry chemical or foam fire suppression systems
4-1). If the fire is to be detected during the first two stages, use flame detection.
incipient and smoldering, smoke detectors would typically be
used. If the fire is to be detected during the flame stage,
flame detectors would be used and heat detectors will
respond to the heat generated by the fourth stage of a fire.
The speed of the fire growth will vary depending on the type
of fuel and environmental conditions.
MAJOR
HAZARD
MODERATE
HAZARD
LOW
HAZARD
TIME IN MINUTES OR HOURS TIME IN MINUTES OR SECONDS
FIGURE 4-1
004029
4-1
SECTION 4 – DESIGN
The detector selected for the project must meet the rating PIGMENTS
of the environment.
AMMONIUM CHLORIDE FUME
Weather Proof – If the area is to be located outside, the
detector would need to be weather proof and a ZINC-OXIDE SMOKE
GAS
MOLECULES
specification may identify what enclosure rating is
required. The description “Weather Proof” carries little MAGNESIUM-OXIDE SMOKE
meaning without a rating included such as NEMA 4.
CHIMNEY SMOKE
Devices that are rated explosion proof are not necessarily
weather proof.
DUST IN GENERAL FACTORIES
Explosion Proof – In areas near flammable liquids the
detectors may need to be explosion proof or intrinsically DUST IN CLEAN AIR
magnetic reed switches for testing the detector. Most TO NAKED EYE THROUGH THROUGH
smoke detectors incorporate these switches to allow MICROSCOPE ULTRAMICROSCOPE
easy testing of the detection circuit. When exposed to
strong magnetic fields the switch may transfer indicating FIGURE 4-2
an alarm. Smoke detectors without these magnetic reed Flame detectors must be selected according to the radi-
switches are available and may be special order items. ant energy that is emitted from the material that may
EMI/RFI – Areas exposed to electro-magnetic burn. Some materials emit Ultraviolet (UV) light while
interference or radio frequency interference need to be others emit Infrared (IR) light. Figure 4-3 shows the spec-
addressed and detectors properly grounded and trum of a typical flame for a gasoline fire and displays the
shielded. Wiring should be in conduit that is grounded to electromagnetic spectrum used by both UV and IR detec-
reduce the chance of induced signals in the detection tors. The “invisible” Ultraviolet and Infrared light created in
circuit. Adequate clearance must be observed when a gasoline fire is easily “seen” by a flame detector.
detectors are to be located in high voltage areas.
Spectrum of “Typical” Flame (Free-Burning Gasoline)
2. TYPE OF COMBUSTIBLES
0.75
VISIBLE
The response range for each detector should be matched 0.35
with the potential fire signature of the combustible ULTRA-
INFRARED
4-2
SECTION 4 – DESIGN
4-3
SECTION 4 – DESIGN
! CAUTION
6. AIR VELOCITY
Certain detectors, such as smoke detectors, can be
affected by air velocity. Determine the air velocity in the
area the detector is to be located and verify that the
detector can be installed in that air velocity.
4-4
SECTION 4 – DESIGN
Bank Vaults . . . . . . . . . . . . . . . . P P S __ __ __ __
Battery Room . . . . . . . . . . . . . . . __ P S S __ __ __
Blast Hole Drills . . . . . . . . . . . . . N/A N/A __ P __ __ __
Cable Floor . . . . . . . . . . . . . . . . P P S __ __ __ __
Cable Tunnels . . . . . . . . . . . . . . . P P S __ __ __ __
CAD/Drafting Rooms . . . . . . . . . . . P P S __ __ __ __
Clean Room . . . . . . . . . . . . . . . . P S __ __ S S S
Coating Booth, Liquid . . . . . . . . . . N/A N/A N/A P S S S
Control Room . . . . . . . . . . . . . . . P P S __ __ __ __
Data Processing Rooms . . . . . . . . . P P S __ __ __ __
Dental X-Rays and Files. . . . . . . . . . P P S __ __ __ __
Diesel Generator Room. . . . . . . . . . __ __ __ P S S S
Emergency Generator . . . . . . . . . . __ __ __ P __ __ __
Engine Housing . . . . . . . . . . . . . . __ __ __ P S S S
Engine Test Cell . . . . . . . . . . . . . __ __ __ S P P P
False Ceiling/Service Plenum . . . . . . . P P S __ __ __ __
Film Storage/Archive . . . . . . . . . . . P P S __ __ __ __
Fire Pump House . . . . . . . . . . . . . __ __ __ P __ __ __
Flammable Liquid Storage Rooms . . . . N/A __ S P P P P
Flight Simulator . . . . . . . . . . . . . . P P S __ __ __ __
Gas Turbine. . . . . . . . . . . . . . . . __ __ __ S P S P
Hospital Special Equipment Areas . . . . P P S __ __ __ __
Industrial Fryers . . . . . . . . . . . . . N/A N/A N/A P __ __ __
Instrument Vans . . . . . . . . . . . . . . P P S __ __ __ __
Instrument/Control Rooms . . . . . . . . P P S __ __ __ __
Laboratory . . . . . . . . . . . . . . . . . P P S __ S S S
Libraries . . . . . . . . . . . . . . . . . . P P S __ __ __ __
Locomotives . . . . . . . . . . . . . . . N/A N/A N/A P __ __ __
4-5
SECTION 4 – DESIGN
Museums . . . . . . . . . . . . . . . . . P P __ __ __ __ __
Night Depositories . . . . . . . . . . . . . P P S __ __ __ __
Office . . . . . . . . . . . . . . . . . . . P P S __ __ __ __
Offshore Platform . . . . . . . . . . . . . __ __ __ S S S P
Research Laboratories . . . . . . . . . . P P S __ S S S
Satellite Link . . . . . . . . . . . . . . . . P P S __ __ __ __
Ship Machinery Spaces. . . . . . . . . . __ __ __ P S S S
Solvent Room . . . . . . . . . . . . . . N/A __ __ P S S S
Sub-Station . . . . . . . . . . . . . . . . P P S __ __ __ __
Switch Gear . . . . . . . . . . . . . . . . P P S __ __ __ __
Switch Room . . . . . . . . . . . . . . . P P S __ __ __ __
Telecommunications . . . . . . . . . . . P P S __ __ __ __
Test Laboratories . . . . . . . . . . . . . P P S __ S S S
Transformer Rooms . . . . . . . . . . . __ S P S __ __ __
Transmitter Room . . . . . . . . . . . . . P P S __ __ __ __
Turbines. . . . . . . . . . . . . . . . . . __ __ __ S P S P
UPS Room . . . . . . . . . . . . . . . . P P S __ __ __ __
Wave Solder Machines . . . . . . . . . N/A N/A N/A P __ __ __
* Detector must not have a magnetic read switch
4-6
SECTION 4 – DESIGN
3-1-01 REV. 1
4-7
SECTION 4 – DESIGN
15.8
detectors are used to operate fire suppression systems the
response time should be shorter which requires reduced
20.0
18.9
17.4
detector spacing.
FIGURE 4-5
3-1-01 REV. 1
4-8
SECTION 4 – DESIGN
4-9
SECTION 4 – DESIGN
CEILING
NO SLOPE JOIST/BEAM YES
LEVEL GREATER THAN GREATER THAN
CEILING 1 1/2 IN. (38 mm) 4 IN. (102 mm)
SPACING PER FOOT DEEP
(305 mm)
NO
YES
YES JOIST/BEAM
SLOPED CEILING – GREATER THAN
DETECTORS 3 FT. (914 mm)
NO
LOCATED AT OR SOLID GIRDER ON
WITHIN 3 FT. CENTER
CONSTRUCTION
(914 mm) OF THE
HIGHEST POINT.
SPACING BASED
ON HORIZONTAL
PROJECTION YES NO
JOIST
CONSTRUCTION
IF CEILING IS TOP OF
NO GIRDER TO
NOT ACTUALLY
LEVEL, USE SLOPE NO USE AVERAGE CEILING 4 IN.
MAXIMUM LESS THAN HEIGHT AS (102 mm) OR
HEIGHT AS 30° (REFER TO CEILING HEIGHT LESS
CEILING PAGE 4-14)
SMOOTH CEILING
HEIGHT
SPACING
YES
PARALLEL TO THE
JOISTS AND 1/2
YES SMOOTH CEILING
SPACING
GIRDER IS
PERPENDICULAR
CONSIDERED
TO THE JOISTS
USE HEIGHT AT EQUAL TO BEAM
PEAK FOR CONSTRUCTION
CEILING HEIGHT
END
CEILING
HEIGHT NO LISTED
GREATER THAN SPACING SMOOTH
10 FT. APPLIES CEILING
(3048 mm) SPACING
BEAM
YES CONSTRUCTION
END
REDUCE SPACING
PER TABLE 4-4 ON
PAGE 4-12
SMOOTH CEILING
SPACING
PARALLEL TO THE
BEAMS AND 2/3
SMOOTH CEILING
SPACING
PERPENDICULAR
TO THE BEAMS
CONTINUED ON
NEXT PAGE
FIGURE 4-10
4-10
SECTION 4 – DESIGN
FROM PREVIOUS
PAGE NFPA 72 1996
NFPA 72 1996
NFPA 72 1996 BODY
APPENDIX A
BEAM
GREATER RATIO
THAN 18 IN. OF BEAM DEPTH
NO NO
(457 mm) DEEP AND (D) TO CEILING
GREATER THAN 8 HEIGHT (H)
FT. (2438 mm) ON GREATER THAN
CENTER 0.10 (D/H)
YES
YES
EACH BAY
FORMED BY THE
BEAMS SHALL BE RATIO
TREATED AS A OF BEAM
SEPARATE AREA SPACING (W) TO NO
CEILING HEIGHT
(H) GREATER
THAN 0.40
(W/H)
YES
EACH BAY
FORMED BY THE INSTALL HEAT
BEAMS SHALL BE DETECTOR ON
TREATED AS A BOTTOM OF BEAM
SEPARATE AREA
END
4-11
SECTION 4 – DESIGN
RESTRICTIONS FOR HEAT DETECTOR SPACING For example, to install detectors in a room with a 20 ft.
(6.1 m) ceiling the listed spacing should be reduced by 64%.
(Continued)
If the listed spacing is 30 ft. x 30 ft. (9.14 m x 9.14 m) the
Ceiling Height – As the heat from a fire rises it cools, which reduced dimensions would be 64% of 30 ft. (9.14 m) which
reduces the reaction time of a heat detector. In order to equals 19.2 ft. x 19.2 ft. (5.8 m x 5.8 m).
maintain the same reaction time the detector spacing must
When using detectors to operate fire suppression systems,
be reduced for ceilings higher than 10 ft. (3048 mm). The
the percent reduction is smaller since the actual spacing has
reductions in NFPA 72 for high ceilings (see Table 4-4) is
already been reduced (see Table 4-5 and Figure 4-11). The
based on a percentage of the listed spacing.
resulting spacing must not exceed the reduction from the
TABLE 4-4 NFPA Heat Detector – Linear Spacing listed spacing.
Reductions
TABLE 4-5 ANSUL Linear Spacing Reductions For Fire
Ceiling Height Percent of Suppression Systems
feet (m) Listed Spacing
Ceiling Distance Area
Up to (Up to)
Height Spacing to Wall Coverage
10 (3.05) 100
feet (m) feet (m) feet (m) sq. ft. (m2)
12 (3.66) 91
14 (4.27) 84 Up to
16 (4.88) 77 14 (4.2) 15 x 15 (4.6 x 4.6) 7.5 (2.3) 225 (20.9)
18 (5.49) 71 20 (6.1) 13 x 13 (3.9 x 3.9) 6.5 (2.0) 169 (15.7)
20 (6.10) 64 24 (7.3) 11 x 11 (3.4 x 3.4) 5.5 (1.6) 121 (11.2)
22 (6.71) 58 28 (8.5) 9x9 (2.7 x 2.7) 4.5 (1.4) 81 (7.5)
24 (7.32) 52 30 (9.1) 8.5 x 8.5 (2.6 x 2.6) 4.25 (1.3) 72.25 (6.7)
26 (7.92) 46
28 (8.53) 40
30 (9.14) 34
45.00 FT.
40.00 FT.
35.00 FT.
30.00 FT.
SPACING
50 FT. SPACING
25.00 FT.
25 FT. SPACING
15 FT. SPACING
20.00 FT.
15.00 FT.
15 X 15
13 X 13
10.00 FT. 11 X 11
9X9
8.5 X 8.5
5.00 FT.
0.00 FT.
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
FIGURE 4-11
4-12
SECTION 4 – DESIGN
FIGURE 4-12
PLACE DETECTOR AT PEAK OR WITHIN 3 FT. (914 mm)
If solid girders are used to support the joists or beams, they
might interfere with heat transport to the detector. If the girder FIGURE 4-14
is solid and the distance from the top of the girder is 4 in.
(102 mm) or less to the ceiling, it should be considered a INCORRECT: PARALLEL
beam and the heat detector spacing adjusted accordingly. PROJECTION OF THE
CEILING – DO NOT USE.
15 .57
The ceiling height where beams are located will also affect
(4
FT m
. )
the detector placement. If the ratio of beam depth (D) to
ceiling height (H) (D/H) is greater than 0.10 and the ratio of
beam spacing (W) to ceiling height (H) (W/H) is greater than
0.40, heat detectors should be located in each beam pocket 10 FT.
(3.05 m)
(see Figure 4-13).
CORRECT: HORIZONTAL PROJECTION OF THE
CEILING. USE FOR SPACING DETECTORS.
FIGURE 4-15
FIGURE 4-13
4-13
SECTION 4 – DESIGN
8 FT.
(2438 mm)
1 1/2 IN. IN 1 FT. 8 FT.
(38 mm IN 305 mm) (2438 mm)
12 IN.
(305 mm)
1 1/2 IN. 12 IN.
(38 mm) (305 mm)
7 IN.
FIGURE 4-16 (177 mm)
FIGURE 4-18
3 FT.
(914 mm)
FIGURE 4-17
4-14
SECTION 4 – DESIGN
SPOT TYPE
SMOKE
DETECTOR
SPACING
CEILING
SLOPE GREATER NO
THAN 1 1/2 IN.
PER FOOT (1 IN.
RISE IN 8 FT.)
JOIST/
BEAM NO
SOLID GIRDER NO
GREATER
THAN 4 IN. CONSTRUCTION YES
(102mm)
DEEP
SLOPED CEILING –
DETECTORS LOCATED
AT OR WITHIN 3 FT.
USE SMOOTH (914 mm) OF HIGHEST
YES
CEILING POINT SPACING
YES
SPACING BASED ON
HORIZONTAL
PROJECTION
TOP OF
GIRDER TO NO
CEILING 4 IN. CEILING
(102 mm) OR HEIGHT IS THE
LESS AVERAGE
HEIGHT OVER
THE SLOPE
YES
YES
JOIST/
GIRDER IS BEAM
CONSIDERED NO
RUNNING
EQUAL TO BEAM
CONSTRUCTION PARALLEL
(UP) THE
SLOPE
YES
CEILILNG DETECTORS
LOCATED ON
HEIGHT 12 FT. NO SLOPE
CEILING IN SPACING FOR
(3658 mm) OR EVERY BEAM GREATER NO
LESS AND BEAM FLAT (LEVEL)
POCKET. USE THAN 10°
DEPTH 12 IN. BEAMED
SMOOTH (REFER TO
(305 mm) OR CEILING CEILINGS
PAGE 4-17)
LESS SPACING.
YES YES
APPENDIX A
DETECTORS SPACING PARALLEL
MAY BE TO THE BEAM CAN
LOCATED BE TWICE SMOOTH
EITHER ON THE CEILING SPACING
BEAM OR ON
THE CEILING
END
FIGURE 4-19
4-15
SECTION 4 – DESIGN
4 IN.
BEST HERE
(102 mm)
NEVER HERE
12 IN.
ACCEPTABLE (305 mm)
HERE (BUT NOT LESS LESS THAN
RECOMMENDED) THAN AND 12 IN. (305 mm)
12 FT.
(3658 mm)
SIDE WALL
FIGURE 4-20
Stratification – As air containing smoke particles rises it
cools. When the temperature of this air equals the
DETECTORS LOCATED EITHER ON CEILING OR BOTTOM OF BEAM
surrounding air temperature the smoke stops rising causing
stratification and the smoke does not reach the detector. This FIGURE 4-21
condition is more likely to occur in rooms with tall ceilings. If If the beam depth exceeds 1 ft. ( 305 mm) OR the ceiling is
stratification is a possibility a portion of the detectors should greater than 12 ft. (3658 mm) high, detectors shall be located
be installed a minimum of 3 ft. (914 mm) below the ceiling. on the ceiling in each pocket (see Figure 4-22).
Projected beam detectors may prove to be more appropriate
in areas where stratification may occur. When using
projected beam smoke detectors, a single detector is
considered a row of spot type smoke detectors when
determining spacing.
Ceiling Construction – If the ceiling is peaked, a row of
GREATER GREATER THAN
detectors shall be spaced at, or within 3 ft. (914 mm) of the THAN OR 12 IN. (305 mm)
peak. The spacing of the detectors at right angles to the peak 12 FT.
(3658 mm)
shall be based on the horizontal projection of the ceiling.
Refer to Figures 4-14 and 4-15.
Sloped ceilings having a rise greater than 1 ft. (305 mm) in
8 ft. (2438 mm) horizontally shall have a row of detectors
located on the ceiling within 3 ft. (914 mm) of the high side.
Refer to Figures 4-16 and 4-17. The spacing of the detectors
at right angles to the first row shall be based on the horizontal FIGURE 4-22
projection of the ceiling.
Joists/Beams on Level Ceilings – As the smoke rises, it
becomes trapped in the space created by solid joists and
beams. Joists and beams with depths less than 4 in.
(102 mm) are not considered an obstruction and the ceiling
can be considered smooth.
If solid girders are used to support the joists or beam, they
might interfere with smoke transport to the detector. If the
girder is solid and the distance from the top of the girder is
4 in. (104 mm) or less to the ceiling, it should be considered a
beam and the smoke detector spacing adjusted accordingly.
4-16
SECTION 4 – DESIGN
FIGURE 4-25
2. Since the cross-joists are 10 in. (254 mm) deep (see
Figure 4-26), the normal detector spacing perpendicular
to the beams will be reduced by 1/2 and the detectors will
be located either on the ceiling or on the bottom of the
joist .
10 IN.
(254 mm)
JOIST
2 FT.
(610 mm)
PARALLEL TO THE SLOPE
FIGURE 4-23
If the joist/beams greater than 4 in. (102 mm) deep are
running perpendicular to (across) the slope (see Figure 4-24),
the spacing for the level beamed ceilings shall be used. The
ceiling height shall be taken as the average over the slope
FIGURE 4-26
3. For INERGEN fire suppression systems, the typical area
coverage for a single smoke detector is 250 sq. ft. (23.2
m2). Taking the square root of the area coverage the
spacing will be 15.8 ft. (4.82 m).
15.8 FT.
(4.82 m)
250 FT.2
(23.2 m2)
15.8 FT.
(4.82 m)
11.1 FT.
(3.38 m)
PERPENDICULAR TO THE SLOPE
FIGURE 4-24
FIGURE 4-27
4. The effective radius of the detector is 0.7 times the
spacing per NFPA 72. This results in an 11.1 ft. (3.38 m)
radius for the detector.
4-17
SECTION 4 – DESIGN
11.1 FT.
(3.38 m)
AIR CONDITIONING
DIFFUSER
18.3 FT.
9.15 FT. (5.58 m)
(2.79 m)
AIR
MOVEMENT
FIGURE 4-32
4-18
SECTION 4 – DESIGN
300
AIR
CONDITIONING
GRILL 200
100
60 50 40 30 20 10 0
AIR CHANGES PER HOUR
FIGURE 4-34
DETECTOR AREA VS. MINUTES PER AIR CHARGE
FOR METRIC CONVERSIONS: 1 SQ. FT. = 0.0929 m2
CORRECT
900
FIGURE 4-33
800
In areas with high air flow, including subfloors, the detector
SQUARE FEET PER DETECTOR
700
spacing should be reduced. The reduction in spacing is
based on the number of air changes per hour or the minutes 600
per air change. If the CFM (cubic feet per minute) is known
500
the minutes per air change can be calculated using the
following formula: 400
For metric measurements 1 sq. ft. = 0.0929 m2 and 1 ft. = 0.3048 m RAISED FLOOR
FLOOR
UNACCEPTABLE
FIGURE 4-36
4-19
SECTION 4 – DESIGN
LINE OF SIGHT
to detect it. In addition, the detector has different response
OPTICAL AXIS
levels depending on the type of fuel it is monitoring.
The range for a flame detector is determined by testing and is
typically the distance on the optical axis of the detector to a 45°
one square foot gasoline fire that will cause the detector to
respond. If the potential fire will be larger or smaller than one
square foot the range could be increased or decreased
90° CONE
accordingly. The new distance to maintain the listed OF VISION
sensitivity can be closely approximated by using the following
formula: FIGURE 4-38
________________
New
Distance =
New
Fire ÷
Size
√
Rated
Fire
Size
x Rated
Distance
The sensitivity of the detector is typically reduced as the
angular displacement increases from the optical axis. In other
words a specific size fire viewed on the optical axis will be
If the distance is known the minimum detectable fire size can detected at a greater distance than if the same size fire were
be closely approximated by rearranging the previous formula 45° off the optical axis. Each detector has a curve that relates
as shown: the angular displacement to the reduction in sensitivity. As
the angular displacement increases from the optical axis the
New Rated
Fire =
Size ( New
Distance
÷
Rated
Distance ) 2
x Fire
Size
curve intersects a line indicating the percentage of reduction
of range. Figure 4-39 is the curve for a detector with a range
of 50 ft. (15.2 m) based on a one square foot (0.093 m2)
gasoline fire. At 30° off the optical axis (note x in Figure 4-39)
Figure 4-37 shows the relationship between fire size and the
maximum distance a flame detector should be located. For the maximum distance for detection of a one square foot
example, using the formulas a detector with a range of 50 ft. (0.093 m2) gasoline fire is 65% of the 50 ft. (15.2 m) range or
(15.2 m) to detect a one square foot (0.093 m2) gasoline fire 32.5 ft. (9.9 m). Refer to Figure 4-40.
(NORMAL)
will detect a two square foot (0.186 m2) gasoline fire at 70.7 0 ANGLE OF
15 INCIDENCE WITH
ft. (21.5 m); a 0.5 sq. ft. (0.046 m2) fire at 35.4 ft. (10.8 m); 15
RADIANT POWER
30 30
and a 9 sq. ft. (0.836 m2) fire at 150 ft. (45.7 m) CONSTANT
45 45
16
15
60 60
14
13
12
9
DISTANCE/SIZE CRITERIA FIGURE 4-39
8 FOR APPLICATION SHOULD 1 SQ. FT. FIRE
FALL IN SHADED AREA
7
6 1 SQ. FT.
FIRE
5
3 50 FT.
30° (15.2 m)
2
1 32.5 FT.
(9.9 m)
1X 2X 3X 4X
DISTANCE BETWEEN DETECTOR AND FIRE
X = RATED DISTANCE OF DETECTOR
FOR METRIC CONVERSIONS 1 SQ. FT. = 0.0929 m2
FIGURE 4-37 FIGURE 4-40
4-20
SECTION 4 – DESIGN
4-21
SECTION 4 – DESIGN
4-22
SECTION 4 – DESIGN
intensity, and number as required and shall be located so the MINIMUM 6 IN. TOP
(152 mm)
appliance can be seen by the intended viewer, regardless of
the viewer’s orientation. AUDIBLE NOTIFICATION APPLIANCE
The flash rate of visible signal notification appliances
intended for operation in the public mode should not exceed
three flashes per second nor be less than one flash every MINIMUM
90 IN.
three seconds. (See Table 4-9.) The maximum pulse (2286 mm)
duration shall be 0.2 seconds with a maximum duty cycle of CEILING
PERMITTING
40 percent. The light source color should be clear or white.
The light source should not exceed 1000 candela.
FLOOR
FIGURE 4-41
4-23
SECTION 4 – DESIGN
Area to be
Requirement protected ADA UL 1971 ANSI 117.1 NFPA 72
Light Distribution All Areas No specific “Polar” Per UL 1971 Per UL 1971
requirement1 Distribution2
Flash Rate All Areas 1 to 3 Hz4 1/3 to 3 Hz5 1/3 to 3 Hz5 1/3 to 3 Hz5
4-24
SECTION 4 – DESIGN
75 cd
W W STROBE
A A 44 FT.
L L 40 FT. (13.4 m)
L L (12.2 m)
PERCENT PERCENT
DEGREES OF RATING DEGREES OF RATING
0 100 0 100 22 FT.
5-30 90 5-25 90 (6.7 m)
35 65 30-45 75
40 46 50 55
45 34 55 45
50 27 60 40 INCORRECT – PORTION OF ROOM NOT COVERED
55 22 65 35 10 FT. (3.05 m)
60 18 70 35
65 16 75 30
70 15 80 30
75 13 85 25
80 12 90 25
85 12
90 12 15 cd 20 FT.
STROBE (6.1 m)
FIGURE 4-43
40 FT.
For rooms, a maximum separation between appliances shall (12.2 m)
not exceed 100 ft. (30.5 m). The location of wall-mounted
visible notification appliances for square rooms is based on
15 cd 20 FT.
positioning the alarm at the center point of the wall. Refer to STROBE (6.1 m)
Figure 4-44. In rooms where the appliance is not centered or
the room is not square the room shall be subdivided into
multiple squares or the square room that will entirely
22 FT.
encompass the room shall be used. Refer to Figure 4-45. (6.7 m) AREA NOT COVERED
FIGURE 4-44
4-25
SECTION 4 – DESIGN
VISIBLE APPLIANCE
15 cd
VISIBLE APPLIANCE 15 cd
VISIBLE APPLIANCE 15 cd
40 FT.
(12.2 m)
40 FT. 20 FT.
(12.2 m) (6.1 m)
20 FT.
(6.1 m)
15 cd VISIBLE APPLIANCE 15 cd
20 FT.
40 FT. (6.1 m)
(12.2 m) 40 FT.
(12.2 m)
VISIBLE APPLIANCES IMPROPERLY LOCATED
SHADED AREAS NOT COVERED
FIGURE 4-46
4-26
SECTION 4 – DESIGN
4-27
SECTION 4 – DESIGN
4-29
SECTION 4 – DESIGN
4-30
SECTION 4 – DESIGN
4-31
SECTION 4 – DESIGN
AUXILIARY POWER
Battery Charger Height: Locate the display and/or keypad of the control
unit approximately five (5) feet (1.5 m) above the floor.
The FCPS-24 Remote Power Supply battery charger can
support a maximum battery capacity of 7.0 AH. However, an Corners: When locating the control unit near a corner,
NR45-24 Automatic Float Charger, which can support make certain it is far enough from the adjacent wall to
batteries of 20 AH to 55 AH, can be connected to the FCPS- allow for the opening of the control unit door.
24 and the IQ-301 for battery backup power. Note: The AUTOPULSE Four requires a minimum of
12 in. (304.8 mm) clearance on the right side of
Remote Power
the control unit to allow the outer door to swing
The AVPS-24 Power Supply used with the AUTOPULSE IQ- open wide enough for the inner door to open.
301 and the AUTOPULSE 396X supplies an additional
Flush Mounting: Install conduit and pull wires prior to the
maximum of 3.0 Amps to the notification appliances
installation of the drywall. Remove the circuit board(s) and
connected to TB-2, circuits 3 and 4 (terminals 5, 6, 7, and 8).
control unit door(s). Package the circuit boards in anti-
This power is separate from the power supplied to TB-2,
static packaging and place in a safe location. Once box
circuits 1 and 2 (terminals 1, 2, 3, and 4).
has been securely installed replace circuit board(s) and
AUTOPULSE CONTROL UNIT PLACEMENT door(s).
When selecting a location for installing your AUTOPULSE Vibration: Avoid areas where vibration is present.
Control Unit, several items need consideration prior to the Vibration can loosen mechanical and electrical
final placement. Environment and location are two important connections and fatigue components. The control unit
factors. Extreme temperatures, humidity, water and dust can shall be installed so that accidental failure or operation
create problems for control units and their components. cannot be caused by vibration or jarring.
Locations in high traffic areas may subject the control unit to
POWER CALCULATIONS
damage. Proper planning prior to installation of the control
unit can prevent future problems and improve the reliability of Power calculations must be performed to determine Battery
your AUTOPULSE Control System. back-up power requirements and Power Supply require-
ments for every control system.
Environment The AUTOPULSE Control systems can automatically switch
Temperature: The control unit should be installed in an to operate on back-up battery power in the event that main
environment with a temperature range between 32 °F AC power is lost. The amount of battery back-up power
(0 °C) to 120 °F (48.8 °C). The optimum temperature needed will be dependent on the application and must be
range is 60 °F (15.5 °C) to 80 °F (26.6 °C). Extreme calculated for each control system.
temperatures can effect the life of the control unit back-up U.L. Standard 864 and NFPA 72 require Fire Protective
batteries and electronic components. Signaling Systems to have a secondary power source
Enclosure: The control unit enclosures are rated as capable of operating the control system for 24 hours in a
NEMA 1. NEMA 1 rated enclosures are intended for standby mode of operation and for 5 minutes in a full Alarm
indoor use and provide a degree of protection for the mode of operation. Lead acid gel cell rechargeable batteries
components inside the enclosure. are the most commonly used secondary power source.
Outdoor installation: Outdoor installations should be Factory Mutual requires a control system used with Pre-
avoided when possible. If an outdoor installation is Action and Deluge Systems to have the capability of
necessary, the complete AUTOPULSE Control Unit must operating on battery back up power for 90 hours of standby
be mounted inside a NEMA 4, 4X, or 6 enclosure. A operation and for 15 minutes of operation in a full Alarm
ventilation kit must be installed to allow for the venting of mode.
gases emitted by the charging of the back up batteries.
Auxiliary Power Requirements
Humidity: The maximum humidity is 85%, per NFPA 72.
If the control unit is to be mounted on an exterior wall, the The Auxiliary power required to operate auxiliary devices
use of a vapor barrier can help protect the control unit such as 4 wire Smoke detectors, 4 wire Flame detectors,
from humidity and condensation. Graphic Annunciators, and Auxiliary Relays must be included
in the power calculations. Make certain sufficient battery
Location back-up power is provided and the control system has the
AUTOPULSE Control Units should be installed in a capabilities to supply the auxiliary power. It also is important
convenient location which is acceptable to the Authority to take into consideration the “In Rush Current” of devices
Having Jurisdiction. Avoid installing your AUTOPULSE connected to the Auxiliary power. The total current of all
Control Unit in secluded areas such as closets, and small devices must be used to make certain the control system can
unoccupied areas. Occupants must be able to hear the provide sufficient power.
control unit Alarm and Trouble buzzers. When selecting the
control unit location, allow sufficient room for installation and
maintenance.
4-32
SECTION 4 – DESIGN
4-33
SECTION 4 – DESIGN
4-34