Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual Ir Heat Sensor D1145-2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Patol Limited

Series 5000
Type 5410 Infra-red Fire & Heat Detector

SPECIFICATION
INSTALLATION - COMMISSIONING
OPERATION - MAINTENANCE

Applicable to unit Part Numbers 720-002 / 720-012


Serial Numbers : 98538-01 Onwards

Document Ref : D1145

Issue Change Date Remarks


1 Original 18/03/09 Based on D1140
2 Table 3 - B reference corrected to D 15/11/12 Page 8

Rectory Road, Padworth Common, Reading,


Berkshire. RG7 4JD United Kingdom.
Tel : +44 (0) 118 9701 701
Patol Limited Fax : +44 (0) 118 9701 700
Email : info@patol.co.uk
Web : www.patol.co.uk

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 1 of 16


Patol Limited

INDEX
1. INTRODUCTION

1.1 General
1.2 Principles

2. EQUIPMENT DETAIL

2.1 General Description


2.2 Relay Mode
2.3 Low Power Mode
2.4 Sensor Arrangement
2.5 Specification
2.6 Operational Programmability - SIL Switch
2.7 Connections

3. INSTALLATION

3.1 Detection Coverage


3.2 Supply / Signal Cable
3.3 Purge Air Supply

4. COMMISSIONING

4.1 Cable Checks


4.2 Controller Set Up
4.3 Power Up Procedure
4.4 Purge Air Supply and Pressure Switch
4.5 Hot Body Simulation Tests

5. OPERATION

5.1 Normal
5.2 Alarm Condition
5.3 Reset
5.4 Fault Warning
5.5 Test

6. MAINTENANCE

6.1 General
6.2 Purge Air Filter
6.3 Fault Monitoring Functions
6.4 Infra-red Detection

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 2 of 16


Patol Limited
1 INTRODUCTION
1.1 General
The Patol 5000 Series of equipment is specifically designed for the protection of
establishments and systems where a movement of materials with a potential fire hazard is
a routine occurrence.
The 5410 Detector employs enhanced Infra-red monitoring technology that enables the
detection of fire initiating materials, whilst they are being transported, and before they have
reached a flame condition.
The system has many applications within industries such as Power Generation, Coal
Mining, Process Plant, Road Transportation and Rail Networks and has been specifically
designed to both meet the rigors of these environments and to provide the reliability
required.
The equipment monitors for fire and fire potential of materials in transit. The system can
detect anomalies where combustion has not yet been reached, but where there is sufficient
energy for a fire initiation upon destination arrival.
A typical example is in the coal feed systems on power stations where coal on the ‘out field
stack’ may very well smoulder with little adverse effect for long periods of time. However, if
imported to the power station it may have devastating effects on conveyor systems, holding
hoppers, blending plants etc.
 Detection of hazards at temperatures below flame point including both embers and
buried hot spots.
 Air purged system for Dusty environments with air pressure monitoring.
 Two wire operation - Powered by direct connection to standard fire trigger circuits or
addressable loop interfaces - Signalling mode user configurable to simulate smoke &
heat detector protocols.
 Patol remote controllers/interfaces available for two wire operation.
 Volt free relay contact output operation selectable as standard.
 Twin high integrity detection circuit channels for maximum reliability.
 Unique reflective cone lensing system provides wide uniform coverage superior to
some ember/spark detectors.
 Coincidence - Double Knock - option for unit detector channels as standard.
 Timed auto reset / coincidence analyser circuit.
 Tuned response - solar blind.
 High degree of ingress protection - IP66.
 Specifically designed for high EMC compliance - CE Marked.

1.2 Principles
The principle of operation is that
SOLAR
temperature dependant black body
Typical Black Body Energy Emissions
emissions occur for all materials.
These emissions range through the 320 o C 5000 RESPONSE FILTER
infra red spectrum to visible light.
Both the wavelength and level of 200 o C
peak energy emission are related to
temperature. Fig. 1
Type 5410 detectors are designed
to detect the changes in these
emissions that occur when a hot 1 2 3 4 5 6 7 8 9 10
body enters the field of view of the WAVELENGTH (Micrometres)
detector.
By the use of both optical filtering and electronic analysis of the various parameters the
system is blind to visible light from the sun or local luminaires, whilst being able to detect
relatively low temperature material moving through the field of view.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 3 of 16


Patol Limited
2. EQUIPMENT DETAIL

2.1 General Description

The 5000 Series system described here comprises two primary elements :-

 Detector unit - Type 5410


 Air Supply / Blower Unit
The Detector is located above the materials transit path (e.g. conveyor) by means of the
adjustable mounting bracket and aligned such that the monitored hazard passes through
the unit’s field of view. The height and angle of the sensor determine the width of the
monitored path.
The Type 5410 Detector outer case is equipped with an air hose spigot for connection of an
air supply. This is required such that a positive air pressure is maintained around the inner
module sensor “windows”.
There is a continuous air flow from the outer case optical path aperture which stops dust
settling on the inner sensor module. Also, by maintaining a positive pressure within the
enclosure, ingress of explosive gas or dust is prevented. The arrangement can permit the
unit to be employed in a Hazardous Area depending on applicable local regulations.
The air purging is essential in dusty environments such as coal conveyors, and is
recommended in even relatively clean applications. A series 5000 air purge blower and
filter unit is employed when an ‘on site’ air supply is not available. (See section 2.7)
A pressure switch is located within the unit to monitor the purge air and signals a loss of
pressure as a Fault.
AIR PURGE UNIT AIR HOSE
SIGNAL/SUPPLY CABLE

AIR

AIR FILTER SENSOR

110 / 230 Vac

0o to 55o 1 to 1.5 m

Fig. 2
MONITORED MATERIALS

The unit may be user selected to either of two principal operating settings which are
referenced as :-
 “Relay Mode” - Operation from a 20 to 30 Vdc supply.

 “Low Power Mode” - Operation from a fire alarm trigger circuit / addressable loop.
A description of these arrangements is provided in sections 2.2 and 2.3 following.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 4 of 16


Patol Limited
2.2 Relay Mode

The unit is equipped with relays which are enabled in this mode.
A 24 Vdc (nom) supply is required to operate the unit (max current 24mA).
The unit’s volt free relay contacts are used for signalling of Fire and Fault conditions.
The Fire relay is normally de-energised and energises on an infra-red detection alarm.
The Fault relay is normally energised and de-energises on power supply removal, module
regulation failure or loss of purge air.
Refer to figure 3.

5410 SENSOR HEAD VOLT FREE CONTACTS

TRIP
FIRE RELAY
(Normally De-Energised)
ALARM
Fig.3
FAULT FAULT RELAY
(Normally Energised)
24 Vdc
SUPPLY
POWER SUPPLY

2 WIRE SUPPLY CIRCUIT

2.3 Low Power Mode

In this mode the relays are disabled and the unit’s quiescent supply current is very low and
of a similar level to conventional Smoke and Heat detectors.
By the connection of appropriate resistor values to the sensor’s “solid state” outputs the unit
will signal Normal, Fire & Fault conditions by line current levels, in a manner that permits
the unit to be connected directly to fire control panels via alarm trigger circuits, or to the
monitored inputs of addressable loop interface modules.
The unit can also be employed with the two wire connection to a remote Patol signal relay
module.
Refer to figures 4 & 5.
Fig.4
5410 SENSOR HEAD
ALARM AND
ALARM EOL RESISTORS CONVENTIONAL
* AS PER FIRE PANEL FIRE CONTROL PANEL
FAULT REQUIREMENT AND / OR
PATOL SIGNAL
SUPPLY RELAY MODULE
2 WIRE TRIGGER CIRCUIT
Solid State Output Switches
*
Fig.5
5410 SENSOR HEAD
ALARM & EOL ANALOGUE
RESISTOR ADDRESSABLE
ADDRESSABLE
LOOP INTERFACE
CONFIGURATION FIRE ALARM
AS PER FIG.2 MODULE
CONTROL PANEL

TWO WIRE CONNECTION

2 WIRE ADDRESS LOOP

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 5 of 16


Patol Limited
2.4 Sensor Arrangement

A dual detector channel sensing module is located within an ABS housing which is
mounted by means of an adjustable bracket permitting alignment in both vertical and
horizontal planes. The outer housing is equipped with an air hose spigot. The signal
cable enters through glands in both outer housing and inner module and is terminated at
screw terminals. The inner module is rated IP66.

277 120
SIGNAL CABLE

CABLE GLAND

HOSE CLIP

Fig.6 AIR HOSE

A’

SPIGOT 188

A’‘

SIDE VIEW END VIEW


ADJUSTMENT
CL
MOUNTING HOLES 4.5 Dia (3off) 14
14
HANGING PLATE
BRACKET
26

CL 92

26
FIRE TRIP LED - RED
DETECTOR WINDOWS
SYSTEM ON / NORMAL LED - GREEN 60
BRACKET
BOTTOM VIEW VIEW ON A’-A’‘

2.5 Specification
2.5.1 General

a) Outer Case:- Material : ABS


Finish : RAL 7035
b) Inner Module:- Material : Polycarbonate
Finish : RAL 7035
Ingress Rating : IP66
c) External Lamps Green Normal LED
Red Trip LED
d) Termination:- Within inner module : Two part rising clamp terminals
Cable Core Size : 2.5mm² - 14AWG
e) Temperature :- -20°C to +70°C
f) Weight:- 1.5 kg
g) Purge Air Supply:- Pressure : 4 mBar (1.6”WG)
Delivery : 5.0 litres / sec (11 cubic feet per min)
Input Fitting : 45mm (1 3/4”) dia. hose spigot

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 6 of 16


Patol Limited
Specification - Continued
2.5.2 Internal / Maintenance Features - Accessed on inner module cover removal
a) Indications:- 2 off Red LEDs - One per sensor channel
b) Controls:- Test Push-button
Reset Push-button
c) Program Switch:- Sensitivity : 4 Levels
(SIL 8 Way) Alarm Operation : ‘OR’ / ’AND’ - Latching / Auto-Reset
Auto Reset Timer : 4 Settings
2.5.3 Relay Mode - Direct Supply - Relays Enabled
a) Supply Voltage:- 20 to 30 Vdc
b) Supply Current:- Standby - 11 mA Fire (Alarm) - 26 mA (max)
c) Alarm-Trip O/P:- Fire Relay Contacts - 2 sets
Volt free change over - 30 Vdc 500 mA
Normally De-energised
c) Monitor Output:- Fault Relay Contact - 1 set
Volt free change over - 30 Vdc 500 mA
Normally Energised - De-energises on supply / air failure

2.5.4 Low Power Mode - Line current signalling via Fire Alarm Trigger Circuit
a) Supply Voltage:- 13 to 30 Vdc
b) Supply Current:- Normal / Standby - 1.8 mA (plus EOL *resistor current)
Fire (Alarm) - 5 mA (plus Alarm Load** resistor current)
Fault - <350 uA
c) Fire Output:- Solid state switch - Fit with Alarm Load** resistor
Normally Off - Alarm Load switched across supply on fire
c) Fault Output:- Solid state switch - Fit with trigger circuit EOL* resistor
Normally On - EOL open on Fault (supply <11V / air failure)
2.5.5 Detectors
a) Configuration:- 2 off - Employing reflective cone optical focusing system
Coincident fields of view arranged as separate channels
b) Field Of View:- +5°/-15°(along transit axis path) +/-38°(across transit path)
Refer to coverage chart in section
c) Characteristic Spectral Filter : 5 - 14 µm
Sensitivity : 10 - 40 µW
Transit speed : 0.5 to 6 m/s
Response : 80 - 1000 ºC (170 - 1800 ºF) - See below

Figure 7 indicates the 250mm Dia. 100mm Dia. 50mm Dia. Fig. 7
490 sq cm 78 sq cm 19.6 sq cm
correlation between the
4
temperature and size of ‘hot
spot’ anomalies for a typical 29mm Dia.
installation to produce one or 3 6.45 sq cm
1 sq inch
m ore det ect or channel
activations at various trigger 2
level settings.
Exact response is dependant 1
on the emissivity factor of the 25mm Dia.
4.9 sq cm
monitored material, sensor
orientation and target speed. 0 100 200 300 400 500 600 700 800 900 1000
Temperature Degrees C GLOWING / VISIBLE

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 7 of 16


Patol Limited
2.6 Operational Programmability - SIL Switch
An eight pole SIL switch is located within the inner sensor module which programs the unit’s
operation. Most of the various option features are for special applications, factory test,
commissioning or maintenance purpose.
A summary of the switch functions is as follows:-

2.6.1 LED Operation - Pole 1


Normally the internal LEDs will only illuminate on ‘Alarm’ signalling. In the case of
coincident (double knock) operation the LEDs only illuminate when both channels
have triggered. This is to obviate momentary increases in line current for single
channel operations. For factory test and maintenance purpose Pole 1 of the switch
allows the LEDs to individually illuminate irrespective of operating mode. Ref. table 1.

2.6.2 Channel AND / OR selection - Pole 2


The unit can operate such that detection by either sensor channel results on an
alarm output (single knock / OR operation). Alternatively the unit may be set an
alarm output only occurs on detection by both sensor channels (double knock /
coincident / AND operation). Refer to table 1.

2.6.3 Non-latching option. - Pole 3


The sensor channels normally latch on detection. A non-latching setting is available
for maintenance, factory test and special application analysis. Refer to table 1.

2.6.4 Auto Reset operation. - Pole 4


When in double knock mode an auto reset is applied after a preset delay .
This only occurs if only a single channel has operated within the delay time. If both
channels have operated then the auto reset is prevented. The delay time is in effect
the scan period for coincidence. An option to auto reset ‘AND alarms’ is provided for
maintenance test purpose. Refer to 2.6.5 and table 1.

2.6.5 Auto Reset Delay (Scan Period) - Poles 5 & 6


The duration is set by these switch poles . Refer to table 2.

2.6.6 Sensitivity. - Poles 7 & 8


The unit detection level sensitivity is set by these switch poles. The range
approximates to 10 - 40 μW. Refer to table 3.

Pole FUNCTION
OFF Internal Channel LED’s only illuminate on alarm
1
ON Internal Channel LED’s illuminate before D/K alarm
OFF Double Knock - Coincident Output
2 Table 1.
ON Single Operation - OR - Output
OFF Latching Operation
3
ON Non-latching Operation
OFF Only single detections auto-reset after scan period
4
ON All detections auto-reset after scan period

Table 2. Table 3.
Pole AUTO RESET DELAY - SCAN PERIOD Pole SENSITIVITY (A=Most : D=Least)

5 OFF OFF ON ON 7 OFF OFF ON ON


2.6s 1.3s 0.9s 0.6s A B C D
6 OFF ON OFF ON 8 OFF ON OFF ON

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 8 of 16


Patol Limited
2.7 Connections

2.7.1 Relay Mode - Direct Supply - Relays Enabled

24Vdc
POWER SUPPLY

RESET REMOTE TEST


(OPTIONAL)

SUPPLY
1 10
+V
POSITIVE 2 11
SUPPLY
3 12
0V
NEGATIVE 4 13
TEST 5 14
FIRE
RELAY COIL 6 15
FIRE
OUTPUT 7 16
FAULT
RELAY COIL 8 17
FAULT
OUTPUT 9 18
21 OPTION - Green Normal LED extinguishes on:- Fig. 8
No Link : Loss of either Electric or Air supply.
22 Linked : Loss of Electric supply only.

2.7.2 Low Power Mode - Line Powered - Trigger Circuit Connection

FIRE ALARM PANEL


OR
ADDRESSABLE LOOP INTERFACE
REMOTE TEST
TRIGGER CIRCUIT (OPTIONAL)

SUPPLY
1 10
+V
POSITIVE 2 11
SUPPLY
3 12
0V
NEGATIVE 4 13
TEST 5 14
FIRE ALARM
RELAY COIL 6 RESISTOR 15
FIRE
OUTPUT 7 16
FAULT EOL (TRIM)
RELAY COIL 8 RESISTOR 17
FAULT
OUTPUT 9 18
21 No Link. In LP mode Green LED extinguishes on Fig. 9
either Electric supply or Air supply failure to
22 maintain correct fault current signalling.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 9 of 16


Patol Limited
3. INSTALLATION

3.1 Detection Coverage


The angle and height of mounting determine the monitored width.

Fig. 11 Fig. 12

o
A
HEIGHT o
15 o
o MONITORED
90 5 WIDTH
CONVEYOR TRANSIT PATH

Fig. 13
2m

EXAMPLE

1m
0.8m

o
o 55 o
30 45 Angle -A
o
o
0
0m 1.3m
0m 1m 2m 3m 4m 5m
MONITORED WIDTH

The example shown on the chart is for a sensor mounted 0.8m above the transit path at an
angle of 0°. This provides a maximum monitored width of 1.3m which would be suitable for
most coal conveyors. Should the most practical mounting height (e.g. 1m) produce a wider
view field than the conveyor this is perfectly acceptable, so long as the “overlap” on each
side is not so large that external hot targets, such as vehicles on an adjacent roadway, are
within the units view.

3.2 Supply / Signal Cable


The Type 5410 Detector outer case is fitted with a 20mm gland as standard, which is
suitable for cables of 6 to 12mm overall diameter. A second 20 mm gland is fitted to the
inner sensor module.
Cable terminations are made at plug-in rising clamp screw terminal connectors located
within the inner module. The terminals accept wires of up to 2.5mm² (14AWG). Refer to
section 2.7 for connections.
To access the terminals it is necessary to remove the covers / lids to both the outer case
and the inner sensor module.
The air pressure switch is located on the inside of the inner sensor module lid. The switch
wiring may be ‘un-plugged’ from the rear board by means of the two part terminal, and the
air tube ‘A’ may be removed from the rear of case nipple in order to fully remove the
module lid.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 10 of 16


Patol Limited
When re-fitting the inner module lid, the switch wires must be plugged into the rear board
(TM 19/20), and air switch tube ’A’ must be re-fitted to the nipple located at the rear of the
outer compartment. When re-fitting the outer case lid it is essential that the air switch tube
‘B’ is inserted into the neck of the air inlet spigot such that the tube end lies in the air input
hose.

VIEW WITH BOTH Fig. 14


LIDS REMOVED
Tube ‘A’

Tube ‘B’

Pressure Switch Pressure Switch Cable Glands


Air Tube Nipple

Terminals
1 10
2 11
3 12 LEDs
4 13
5 14
6 15
Adjustment 7 16 SIL Switch
8 17
Screw 9 18
19 A - ALARM - B
20 TEST RESET
1 8

Push-buttons
VIEW ON INSIDE OF
INNER MODULE LID

Tube ‘B’

Inner Module

Fig. 15

Tube ‘A’

Pressure Switch Tube Nipple

When armored cable or conduit is employed it may be most practical for these circuits to
terminate at a junction box adjacent to the detector. A flexible cable should then connect
the junction box to the Detector in order to permit adjustments to sensing alignment.

On certain sites (“Hazardous Areas” for example) it may be a requirement that all cables
are installed in conduit. In this case it is recommended that a short length of approved
flexible conduit is fitted between the 5410 Detector and an adjacent junction box. The outer
case cable gland must be replaced with an appropriate flexible conduit coupler, which
should be sealed with a suitable conduit sealant.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 11 of 16


Patol Limited
3.3 Purge Air Supply

The Sensor unit is equipped with a spigot for connection to a flexible hose. The air supply
must be capable of delivering at least 5.0 ltrs/sec at this connection and maintain a
minimum pressure of 4.0 mBar (1.6” water gauge) in order to operate the sensor’s pressure
monitoring switch.

If an “on site” air supply is not available a Series 5000 Air Purge Blower (APB) should be
employed. Some units are equipped with an easily removable and washable air filter,
however these filters are intended to preserve blower life in normal conditions. The blower
should either be installed outside the dirty/dusty area or the unit inlet piped to a clean air
environment.

Intermediate rigid ducting is most readily achieved by the use of standard µPVC pipes and
fittings. 2 m of hose is provided with each purge unit for couplings at sensor & blower.

SENSOR AIR FLOW PURGE AIR BLOWER UNIT CLEAN AIR

DUCT LENGTH
Fig. 15

In coal handling plant applications twin conveyors may be required to be monitored.


A single blower may purge both sensors by employing a “T” branch in the air ducting.

SENSOR T Branch
BLOWER AIR INPUT
UNIT
SENSOR
Fig. 16

In most applications the ‘clean air’ input will be quite close to the blower unit and sensor(s).
In the case of over-ground conveyors, sufficiently clean air is simply obtained by ducting to
the outside of the conveyor housing cladding. A minimal amount (<6m) of ducting being
used.

However, in some applications (such as under-ground tunnels) the Sensor may need to be
remote from a ‘clean air’ area.

There are limits to the distance that any APB can deliver the required air to the Sensor
which are principally dependant on the APB specification and duct bore size. Other factors
such as the ducting inner wall surface characteristic and the air temperature/pressure also
have an effect.

For these ‘long duct’ applications consideration must be given to the exact installation
ducting parameters, together with blower specifications.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 12 of 16


Patol Limited
4. COMMISSIONING
4.1 Cable Checks
The installation wiring should be checked for correct connection, continuity and insulation.
These checks should include cabling to both detector and air blower (if appropriate).
For relay mode implementation the relay coil link connections at terminals 8/17 & 9/18
should be checked. Refer to figure 8 section 2.7.1.
For line powered (trigger circuit) mode the Alarm resistor at terminals 2/8, and EOL (end of
line) resistor at terminals 3/9 should be checked for both correct value and fitment. Refer to
figure 8 section 2.7.1.
4.2 Controller Set Up
The Controller program SIL switch must be set for the required operation.
In most applications the selected operation will be for double channel coincident detection
with the unit latching until manually reset.

It is recommended that initially, detection is set to the most sensitive level.


The SIL switch setting for this “Double Knock” configuration is:-

POLE 1 POLE 2 POLE 3 POLE 4 POLE 5 POLE 6 POLE 7 POLE 8


OFF OFF OFF OFF OFF ON OFF OFF

4.3 Power Up Procedure


Note: The unit has three signaled / output states which are monitored by remote
equipment. These are referenced as Normal - Fire - Fault in the following.
For relay mode : Normal = Fire relay de-energized & Fault relay energized.
For low power mode : Normal = EOL resistor connected across trigger circuit.
Fault = EOL resistor disconnected from trigger circuit.
Fire = Alarm resistor connected across trigger circuit.
4.3.1 Apply power to the detector. (Connect supply or trigger circuit)
Check supply = 20 to 30 Vdc for relay mode or 13 to 30 Vdc for relay mode.
Operate detector Test PB - Check : Internal & External Red LEDs illuminate.
Operate detector Reset PB - Check : LEDs extinguish.
4.3.2 A general check of detector field of view may be conducted at this stage whilst the
module LEDs, Reset PB and SIL switch is still accessible. Refer to section 4.5.
For “Single Knock” mode Pole 3 may be set ON for non-latching alarms.
For “Double Knock” mode Pole 4 may be set ON for auto-reset.
The SIL switch must be returned to the setting of 4.2 before proceeding to 4.3.3.
4.3.3 Fit detector inner and outer lids, switch wires & air tubes . (Refer to section 3.2.)
Check that the air supply is connected and operational. If a 5000 Series blower is
employed this must be powered.
4.3.4 Check at the Detector that purge air is blowing from the optical aperture.
Check that the external Green LED is illuminated and the unit is signaling Normal.
Note : The purge air is monitored by a pressure switch located within the inner
sensor module. If the air delivery is too low to operate the switch then the detector
will signal Fault. The Green LED will extinguish (if appropriate). Refer to 4.4
4.3.5 Momentarily remove the purge air supply and check that the Green Normal LED
extinguishes (if appropriate), and the unit signals Fault for the duration of the air
supply interruption.
4.3.6 Momentarily remove the electrical supply and check that the Green Normal LED
extinguishes and the unit signals Fault for the duration of the supply interruption.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 13 of 16


Patol Limited
4.4 Purge Air Supply, Pressure Switch and Normal LED
The purge air is monitored by a pressure switch located within the inner sensor module.
The operation of the switch is dependant on the differential pressure between the air input
point to the outer detector case and the external atmosphere.
Terminals 21/22 permit selection of the Green Normal LED operation. When unlinked the
LED extinguishes on either electrical or air supply failure. If linked the LED extinguishes on
electrical supply failure only. This latter option is only permissible in Relay Mode.
Should the detector remain in Fault at stage 4.3.3, even though it is apparent that purge air
is present, the switch’s electrical connection and monitoring tubes should be checked for
correct connection / positioning.
The switch is correctly factory set to operate at approximately 3.74 mBar (1.5 inch WG).
However, should the switch setting have become incorrect for the air flow/pressure being
achieved on the installation, an on site adjustment can be made as in the following.

Check & Adjustment Procedure


Refer to section 3.2 - figures 14 & 15
4.4.1 Remove the outer case lid slowly such as to be able to check that the end of
pressure switch Tube A was resident in the air inlet spigot / hose. Check that
Tube B is fitted to the nipple at the back of the compartment.
4.4.2 Remove the inner module lid - this may require loosening of the outer case cable
gland. Check that both tubes are fitted to the pressure switch and that the switch
wires connect to the rear board via plug-in terminals 19/20.
4.4.3 If all tube and electrical connections have been correct then the pressure switch
may need adjustment:-
 Un-plug terminals 19-20 and monitor with a multi-meter set to ohms. The
reading should be open circuit.
 Using a screwdriver turn the adjustment screw clockwise until the switch
closes - meter indicates zero ohms.
 Turn the adjustment anti-clockwise (counter-clockwise) until the switch opens.
Continue for one quarter of a turn.
4.4.4 Plug terminal 19/20 into the rear board connector and re-fit the sensor lid.
4.4.5 Re-fit the outer case lid ensuring Tube A is connected to the rear of case nipple,
and the Tube B sits in the inlet spigot / hose.

4.5 Hot Body Simulation Tests


A heat simulation test should be conducted.
The test is conducted by moving a “hot” (IR emitting) target into the view field of the Sensor
Head and observing / checking the consequential Alarm operation.
It is preferable that the “test target” is of sufficient size and temperature that the simulation
can be conducted at the plane of the monitored path (conveyor) such that the view field of
the Sensor can be validated. However, a smaller and cooler “test target” may be employed
so as to at least confirm basic operation of the sensor. It will be necessary with a “target” of
this nature to introduce it to the view field nearer to the Senor than the “monitored plane”.
When the 5410 detector is connected to fire panel via a conventional trigger circuit or
addressable loop detector interface, latched 5410 detections are normalized by Alarm
Reset operation at the fire panel. Similarly, when in relay mode, reset is conducted by
momentary supply interruption by an external push-button or other means.
Field of view test confirmation (which requires a number of alarm triggers) may more easily
be conducted when the unit’s covers are removed and the internal LEDs, Reset PB and
program SIL switch are still accessible. Refer to section 4.3.2.
If the location of the Sensor is classified as a “Hazardous Area” it will be necessary to make
special arrangements for this testing as the electrical / hot nature of the test simulation may
breach normal site regulations. It may even be that the test is precluded.
Refer to section 6.4 for information on “test targets”.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 14 of 16


Patol Limited
5. OPERATION

5.1 Normal
 External Green Normal LED - On
 Relay Mode:- Fault relay energized. Fire relay de-energized.
 LP Mode:- End of line resistor connected across trigger circuit.

5.2 Alarm Condition


An Alarm condition will occur on abnormal Infra-red detection by the Sensor Head.
Normally this status will Latch On, however in special configurations the condition can be
set to momentary operation - auto resetting after a selected delay.
During the ALARM :-
 External Red Fire Trip LED - On
 Either or both internal red LED indicators illuminated.
 Relay Mode:- Fire relay energized.
 LP Mode:- Alarm resistor switched across trigger circuit.

5.3 Reset
Latched Alarm conditions may be normalized by :-
 Momentary interruption of the supply - less than 7V.
When directly connected to a Fire Panel via a trigger circuit or addressable loop
interface this condition will occur on fire panel reset operation.
A local or remote normally closed push-button may also be implemented.
 Operation of the internal Reset push-button.

5.4 Fault Warning


 External Green Normal LED - Off *
 Relay Mode:- Fault relay de-energized
 LP Mode:- End of line resistor disconnected from trigger circuit.
A fault warning may occur for any of the following:-
 Low / failed supply.
Supply less than 20V in Relay Mode.
Supply less than 13V in LP Mode. (Note:- An Alarm will remain latched below the fault
threshold so long as the Reset voltage is not reached.)
 Unit internal power regulation circuit fault.
 Loss of Purge Air *
The output will automatically normalize on rectification of the fault.

5.5 Test
Operation of the sensor’s internal Test push-button simulates an alarm as per 5.2.
A remote test push-button has identical result if implemented.

*Note:- Linking terminals 21 & 22 provides an option where Purge Air failure results in
‘Fault’ signalling but the Green LED will remain illuminated whilst electrical supply is
maintained. The option can only be employed in Relay Mode.

Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 15 of 16


Patol Limited
6. MAINTENANCE
6.1 General
It is recommended that a System Log Book / File is raised at the Commissioning Stage and
that the system configuration and initial settings recorded. These should include:-
 Operation configuration and Sensitivity - SIL switch set-up.
 Supply voltage.
Subsequently all system events should be recorded in the log.
These should include all maintenance activity, changes to settings, Fault warnings and
Alarm occurrences. (including cause and actions taken ).
An operational regime should be developed that includes both frequent inspection of the
Sensor for undue accumulation of dust, and to confirm air (blower) operation. The regime
may encompass use of the Test facility to check basic operation.
In addition, the system should be subjected to a periodic service as defined in the
following.

6.2 Purge Air Filters (if fitted)


Some blower units have integral air filters, and some installations may employ ducting
filters. If installed these should be removed and washed using a warm water soap solution.
The use of solvent cleaners is not recommended for Patol Series 5000 blowers.

6.3 Fault Monitoring Functions


Tests should be conducted to confirm the correct operation of the fault monitoring circuits :-
6.3.1 Purge Air Pressure - Check as per 4.3.5
6.3.2 Supply Failure - Check as per 4.3.6

6.4 Infra-red Detection


A heat simulation test should be conducted by moving a “hot” (IR emitting) target into the
view field of the Sensor and checking the consequential Alarm operation.
It is preferable that the “test target” is of sufficient size and temperature to enable
simulation at the plane of the monitored path (conveyor) in order to validate the view field of
the Sensor . Smaller and/or cooler “test targets” may be used closer to the Sensor so as to
at least confirm basic operation of the Sensor.
Fig.7 in Section 2.5 indicates the relationship between the surface area and temperature
required for triggering at the various trip settings.
It may be necessary to make special arrangements for this testing as the electrical / hot
nature of the test simulation may breach normal site regulations. It may even be that the
test is precluded.
Potential “test targets” are :-
Type 5501 Infra-red Radiator - Test and Commissioning Platen - Patol product.
100W Lamp Bulb - (The Sensor responds to the glass temperature - not the visible light).
Domestic Flat Iron (smoothing iron).
Electrical or Catalytic soldering iron.

Note : Infra-red LED Torches are NOT suitable for testing 5000 Series equipment.

Rectory Road, Padworth Common, Reading,


Patol Limited Berkshire, United Kingdom. RG7 4JD
Tel: +44 (0) 118 9701701 email : info@patol.co.uk
Fax: +44 (0) 118 9701700 Web: www.patol.co.uk
Series 5000 - Manual 5410 D1145 - Issue 2 - 15 November 2012 Page 16 of 16

You might also like