Manual Ir Heat Sensor D1145-2
Manual Ir Heat Sensor D1145-2
Manual Ir Heat Sensor D1145-2
Series 5000
Type 5410 Infra-red Fire & Heat Detector
SPECIFICATION
INSTALLATION - COMMISSIONING
OPERATION - MAINTENANCE
INDEX
1. INTRODUCTION
1.1 General
1.2 Principles
2. EQUIPMENT DETAIL
3. INSTALLATION
4. COMMISSIONING
5. OPERATION
5.1 Normal
5.2 Alarm Condition
5.3 Reset
5.4 Fault Warning
5.5 Test
6. MAINTENANCE
6.1 General
6.2 Purge Air Filter
6.3 Fault Monitoring Functions
6.4 Infra-red Detection
1.2 Principles
The principle of operation is that
SOLAR
temperature dependant black body
Typical Black Body Energy Emissions
emissions occur for all materials.
These emissions range through the 320 o C 5000 RESPONSE FILTER
infra red spectrum to visible light.
Both the wavelength and level of 200 o C
peak energy emission are related to
temperature. Fig. 1
Type 5410 detectors are designed
to detect the changes in these
emissions that occur when a hot 1 2 3 4 5 6 7 8 9 10
body enters the field of view of the WAVELENGTH (Micrometres)
detector.
By the use of both optical filtering and electronic analysis of the various parameters the
system is blind to visible light from the sun or local luminaires, whilst being able to detect
relatively low temperature material moving through the field of view.
The 5000 Series system described here comprises two primary elements :-
AIR
0o to 55o 1 to 1.5 m
Fig. 2
MONITORED MATERIALS
The unit may be user selected to either of two principal operating settings which are
referenced as :-
“Relay Mode” - Operation from a 20 to 30 Vdc supply.
“Low Power Mode” - Operation from a fire alarm trigger circuit / addressable loop.
A description of these arrangements is provided in sections 2.2 and 2.3 following.
The unit is equipped with relays which are enabled in this mode.
A 24 Vdc (nom) supply is required to operate the unit (max current 24mA).
The unit’s volt free relay contacts are used for signalling of Fire and Fault conditions.
The Fire relay is normally de-energised and energises on an infra-red detection alarm.
The Fault relay is normally energised and de-energises on power supply removal, module
regulation failure or loss of purge air.
Refer to figure 3.
TRIP
FIRE RELAY
(Normally De-Energised)
ALARM
Fig.3
FAULT FAULT RELAY
(Normally Energised)
24 Vdc
SUPPLY
POWER SUPPLY
In this mode the relays are disabled and the unit’s quiescent supply current is very low and
of a similar level to conventional Smoke and Heat detectors.
By the connection of appropriate resistor values to the sensor’s “solid state” outputs the unit
will signal Normal, Fire & Fault conditions by line current levels, in a manner that permits
the unit to be connected directly to fire control panels via alarm trigger circuits, or to the
monitored inputs of addressable loop interface modules.
The unit can also be employed with the two wire connection to a remote Patol signal relay
module.
Refer to figures 4 & 5.
Fig.4
5410 SENSOR HEAD
ALARM AND
ALARM EOL RESISTORS CONVENTIONAL
* AS PER FIRE PANEL FIRE CONTROL PANEL
FAULT REQUIREMENT AND / OR
PATOL SIGNAL
SUPPLY RELAY MODULE
2 WIRE TRIGGER CIRCUIT
Solid State Output Switches
*
Fig.5
5410 SENSOR HEAD
ALARM & EOL ANALOGUE
RESISTOR ADDRESSABLE
ADDRESSABLE
LOOP INTERFACE
CONFIGURATION FIRE ALARM
AS PER FIG.2 MODULE
CONTROL PANEL
A dual detector channel sensing module is located within an ABS housing which is
mounted by means of an adjustable bracket permitting alignment in both vertical and
horizontal planes. The outer housing is equipped with an air hose spigot. The signal
cable enters through glands in both outer housing and inner module and is terminated at
screw terminals. The inner module is rated IP66.
277 120
SIGNAL CABLE
CABLE GLAND
HOSE CLIP
A’
SPIGOT 188
A’‘
CL 92
26
FIRE TRIP LED - RED
DETECTOR WINDOWS
SYSTEM ON / NORMAL LED - GREEN 60
BRACKET
BOTTOM VIEW VIEW ON A’-A’‘
2.5 Specification
2.5.1 General
2.5.4 Low Power Mode - Line current signalling via Fire Alarm Trigger Circuit
a) Supply Voltage:- 13 to 30 Vdc
b) Supply Current:- Normal / Standby - 1.8 mA (plus EOL *resistor current)
Fire (Alarm) - 5 mA (plus Alarm Load** resistor current)
Fault - <350 uA
c) Fire Output:- Solid state switch - Fit with Alarm Load** resistor
Normally Off - Alarm Load switched across supply on fire
c) Fault Output:- Solid state switch - Fit with trigger circuit EOL* resistor
Normally On - EOL open on Fault (supply <11V / air failure)
2.5.5 Detectors
a) Configuration:- 2 off - Employing reflective cone optical focusing system
Coincident fields of view arranged as separate channels
b) Field Of View:- +5°/-15°(along transit axis path) +/-38°(across transit path)
Refer to coverage chart in section
c) Characteristic Spectral Filter : 5 - 14 µm
Sensitivity : 10 - 40 µW
Transit speed : 0.5 to 6 m/s
Response : 80 - 1000 ºC (170 - 1800 ºF) - See below
Figure 7 indicates the 250mm Dia. 100mm Dia. 50mm Dia. Fig. 7
490 sq cm 78 sq cm 19.6 sq cm
correlation between the
4
temperature and size of ‘hot
spot’ anomalies for a typical 29mm Dia.
installation to produce one or 3 6.45 sq cm
1 sq inch
m ore det ect or channel
activations at various trigger 2
level settings.
Exact response is dependant 1
on the emissivity factor of the 25mm Dia.
4.9 sq cm
monitored material, sensor
orientation and target speed. 0 100 200 300 400 500 600 700 800 900 1000
Temperature Degrees C GLOWING / VISIBLE
Pole FUNCTION
OFF Internal Channel LED’s only illuminate on alarm
1
ON Internal Channel LED’s illuminate before D/K alarm
OFF Double Knock - Coincident Output
2 Table 1.
ON Single Operation - OR - Output
OFF Latching Operation
3
ON Non-latching Operation
OFF Only single detections auto-reset after scan period
4
ON All detections auto-reset after scan period
Table 2. Table 3.
Pole AUTO RESET DELAY - SCAN PERIOD Pole SENSITIVITY (A=Most : D=Least)
24Vdc
POWER SUPPLY
SUPPLY
1 10
+V
POSITIVE 2 11
SUPPLY
3 12
0V
NEGATIVE 4 13
TEST 5 14
FIRE
RELAY COIL 6 15
FIRE
OUTPUT 7 16
FAULT
RELAY COIL 8 17
FAULT
OUTPUT 9 18
21 OPTION - Green Normal LED extinguishes on:- Fig. 8
No Link : Loss of either Electric or Air supply.
22 Linked : Loss of Electric supply only.
SUPPLY
1 10
+V
POSITIVE 2 11
SUPPLY
3 12
0V
NEGATIVE 4 13
TEST 5 14
FIRE ALARM
RELAY COIL 6 RESISTOR 15
FIRE
OUTPUT 7 16
FAULT EOL (TRIM)
RELAY COIL 8 RESISTOR 17
FAULT
OUTPUT 9 18
21 No Link. In LP mode Green LED extinguishes on Fig. 9
either Electric supply or Air supply failure to
22 maintain correct fault current signalling.
Fig. 11 Fig. 12
o
A
HEIGHT o
15 o
o MONITORED
90 5 WIDTH
CONVEYOR TRANSIT PATH
Fig. 13
2m
EXAMPLE
1m
0.8m
o
o 55 o
30 45 Angle -A
o
o
0
0m 1.3m
0m 1m 2m 3m 4m 5m
MONITORED WIDTH
The example shown on the chart is for a sensor mounted 0.8m above the transit path at an
angle of 0°. This provides a maximum monitored width of 1.3m which would be suitable for
most coal conveyors. Should the most practical mounting height (e.g. 1m) produce a wider
view field than the conveyor this is perfectly acceptable, so long as the “overlap” on each
side is not so large that external hot targets, such as vehicles on an adjacent roadway, are
within the units view.
Tube ‘B’
Terminals
1 10
2 11
3 12 LEDs
4 13
5 14
6 15
Adjustment 7 16 SIL Switch
8 17
Screw 9 18
19 A - ALARM - B
20 TEST RESET
1 8
Push-buttons
VIEW ON INSIDE OF
INNER MODULE LID
Tube ‘B’
Inner Module
Fig. 15
Tube ‘A’
When armored cable or conduit is employed it may be most practical for these circuits to
terminate at a junction box adjacent to the detector. A flexible cable should then connect
the junction box to the Detector in order to permit adjustments to sensing alignment.
On certain sites (“Hazardous Areas” for example) it may be a requirement that all cables
are installed in conduit. In this case it is recommended that a short length of approved
flexible conduit is fitted between the 5410 Detector and an adjacent junction box. The outer
case cable gland must be replaced with an appropriate flexible conduit coupler, which
should be sealed with a suitable conduit sealant.
The Sensor unit is equipped with a spigot for connection to a flexible hose. The air supply
must be capable of delivering at least 5.0 ltrs/sec at this connection and maintain a
minimum pressure of 4.0 mBar (1.6” water gauge) in order to operate the sensor’s pressure
monitoring switch.
If an “on site” air supply is not available a Series 5000 Air Purge Blower (APB) should be
employed. Some units are equipped with an easily removable and washable air filter,
however these filters are intended to preserve blower life in normal conditions. The blower
should either be installed outside the dirty/dusty area or the unit inlet piped to a clean air
environment.
Intermediate rigid ducting is most readily achieved by the use of standard µPVC pipes and
fittings. 2 m of hose is provided with each purge unit for couplings at sensor & blower.
DUCT LENGTH
Fig. 15
SENSOR T Branch
BLOWER AIR INPUT
UNIT
SENSOR
Fig. 16
In most applications the ‘clean air’ input will be quite close to the blower unit and sensor(s).
In the case of over-ground conveyors, sufficiently clean air is simply obtained by ducting to
the outside of the conveyor housing cladding. A minimal amount (<6m) of ducting being
used.
However, in some applications (such as under-ground tunnels) the Sensor may need to be
remote from a ‘clean air’ area.
There are limits to the distance that any APB can deliver the required air to the Sensor
which are principally dependant on the APB specification and duct bore size. Other factors
such as the ducting inner wall surface characteristic and the air temperature/pressure also
have an effect.
For these ‘long duct’ applications consideration must be given to the exact installation
ducting parameters, together with blower specifications.
5.1 Normal
External Green Normal LED - On
Relay Mode:- Fault relay energized. Fire relay de-energized.
LP Mode:- End of line resistor connected across trigger circuit.
5.3 Reset
Latched Alarm conditions may be normalized by :-
Momentary interruption of the supply - less than 7V.
When directly connected to a Fire Panel via a trigger circuit or addressable loop
interface this condition will occur on fire panel reset operation.
A local or remote normally closed push-button may also be implemented.
Operation of the internal Reset push-button.
5.5 Test
Operation of the sensor’s internal Test push-button simulates an alarm as per 5.2.
A remote test push-button has identical result if implemented.
*Note:- Linking terminals 21 & 22 provides an option where Purge Air failure results in
‘Fault’ signalling but the Green LED will remain illuminated whilst electrical supply is
maintained. The option can only be employed in Relay Mode.
Note : Infra-red LED Torches are NOT suitable for testing 5000 Series equipment.