Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ground-Fault Monitor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

SE-701 MANUAL

GROUND-FAULT MONITOR
January 18, 2008

Revision 6

Copyright © 2008 by Startco Engineering Ltd.

All rights reserved.


Publication: SE-701-M
Document: S95-C701-00000
Printed in Canada.
This page intentionally left blank.
Startco Engineering Ltd. Page i
SE-701 Ground-Fault Monitor Rev. 6

TABLE OF CONTENTS LIST OF FIGURES


PAGE PAGE
Table of Contents .............................................................. i 1. SE-701 Outline and Mounting Details...................3
List of Figures ................................................................... i 2. Typical Connection Diagram .................................4
List of Tables..................................................................... i 3. EFCT-1 Sensitive Earth-Fault CT..........................5
4. EFCT-2 Sensitive Earth-Fault CT..........................6
1. Introduction ......................................................... 1 5. EFCT-26 Sensitive Earth-Fault CT........................7
1.1 General .................................................................. 1 6. PMA-55 Panel-Mount Adapter ..............................8
1.2 Current-Transformer Selection.............................. 1 7. PMA-60 Panel-Mount Adapter ..............................9
8. Ground-Fault-Test Circuits ..................................12
2. Operation ............................................................. 1
2.1 Configuration-Switch Settings .............................. 1
2.1.1 Relay Operating Mode................................ 1
2.1.2 Trip Inhibit.................................................. 1
2.1.3 CT Verification ........................................... 1 LIST OF TABLES
2.1.4 Filter Selection............................................ 1 PAGE
2.1.5 Reset Mode ................................................. 1 1. Trip-Features Comparison .....................................4
2.2 Front-Panel Controls ............................................. 2 2. Ground-Fault-Test Record ...................................12
2.2.1 Ground-Fault Trip Level............................. 2
2.2.2 Ground-Fault Trip Time ............................. 2
2.2.3 Reset ........................................................... 2
2.2.4 Test ............................................................. 2
2.3 Front-Panel Indication........................................... 2
2.3.1 Power .......................................................... 2 DISCLAIMER
2.3.2 Trip ............................................................. 2
2.3.3 Trip Inhibit.................................................. 2 Specifications are subject to change without notice.
2.4 Analog Output ....................................................... 2 Startco Engineering Ltd. is not liable for contingent or
2.5 Self Diagnostics..................................................... 2 consequential damages, or for expenses sustained as a
result of incorrect application, incorrect adjustment, or a
3. Installation ........................................................... 2 malfunction.

4. SE-701 Compatibility .......................................... 4

5. Technical Specifications.................................... 10

6. Ordering Information ....................................... 11

7. Warranty............................................................ 11

8. Ground-Fault Performance Test...................... 12

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page ii
SE-701 Ground-Fault Monitor Rev. 0

This page intentionally left blank.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 1
SE-701 Ground-Fault Monitor Rev. 6

1. INTRODUCTION 2. OPERATION
1.1 GENERAL 2.1 CONFIGURATION-SWITCH SETTINGS
The SE-701 is a microprocessor-based ground-fault See Fig. 1.
monitor for resistance-grounded and solidly grounded
systems. It is uniquely suited for use on systems with 2.1.1 RELAY OPERATING MODE
significant harmonic content. Its output relay can operate Switch 1 is used to set the operating mode of the output
in the fail-safe or non-fail-safe mode for undervoltage or relay. In the fail-safe mode, the output relay energizes
shunt-trip applications. The SE-701 has one output relay when the ground-fault circuit is not tripped. In the fail-
with isolated normally open and normally closed contacts safe mode, non-volatile memory retains the trip status of
for use in independent control circuits. Additional the SE-701. If tripped, and the supply voltage is cycled,
features include LED trip, power, and inhibit indication, the SE-701 will remain tripped, with the trip relay
autoreset or latching trips with front-panel and remote de-energized and the TRIP LED on, until reset.
reset, trip memory, test switch, self diagnostics, 0- to 5-V In the non-fail-safe mode, the output relay energizes
analog output, inputs for standard and sensitive ground- when a ground-fault trip occurs. In the non-fail-safe
fault current transformers, CT verification for sensitive mode, trip status is not retained in non-volatile memory.
current transformers, digital selector switches, switch-
selectable algorithms for fixed-frequency or variable- 2.1.2 TRIP INHIBIT
frequency applications, and an inhibit that can be enabled Switch 2 is used to select Class I or Class II operation.
to prevent the output relay from operating during a high- In the OFF position, high-current trip inhibit is off for
current ground fault. Class I operation. In the ON position, high-current inhibit
Ground-fault current is sensed by a core-balance zero- is on for Class II operation. If high-current trip inhibit is
sequence current transformer (CT). The trip level of the on and ground-fault current escalates above eleven times
ground-fault circuit is switch selectable in 1% increments the CT-primary rating before the ground-fault circuit
from 1 to 99% of the CT-primary rating. trips, the output relay will not operate until ground-fault
current falls below eight times the CT-primary rating.
1.2 CURRENT-TRANSFORMER SELECTION This feature allows overcurrent protection to operate in
An SE-701 has inputs for 1-, 5-A, and sensitive 50-mA- applications where the ground-fault current can be larger
secondary CT’s. Choose a CT that provides the required than the interrupting capacity of the device tripped by the
ground-fault-trip range. SE-701.
For ground-fault detection, the ground-fault trip level
must be substantially below the prospective ground-fault 2.1.3 CT VERIFICATION
current. In a solidly grounded system, prospective ground- Switch 3 is used to enable CT verification with an
fault current is similar to phase-fault current. In a resistance- EFCT-series CT. In the ON position, a trip will occur if
grounded system, prospective ground-fault current is the CT is disconnected. Switch 3 must be in the OFF
defined by the neutral-grounding-resistor let-through-current position when an EFCT-series CT is not used.
rating.
In a solidly grounded system, protection against arcing 2.1.4 FILTER SELECTION
ground faults requires a ground-fault CT that will detect Switch 4 is used to select the filtering algorithm for a
low-level fault current but not saturate up to the operating fixed-frequency (50/60 Hz) or variable-frequency
value of the system overcurrent protection. In general, application. The FIXED FREQUENCY setting uses a
immunity to saturation is proportional to CT mass. DFT filter that allows lower trip levels to be used by
To eliminate nuisance tripping, surge current must not rejecting harmonics that can cause nuisance tripping.
saturate the CT. The VARIABLE FREQUENCY setting uses a peak-
For low-level ground-fault protection use an EFCT-1, detection algorithm with a wider band width for fault
EFCT-2, or EFCT-26 sensitive earth-fault CT with a 5-A- detection in variable-frequency drive applications.
primary rating. However, protection at this level might not
be possible because of high surge current or prospective 2.1.5 RESET MODE
ground-fault current. Switch 5 is used to select autoreset or latching trips.
For CT-selection assistance, see Technical Information See Section 2.2.3.
11.1 available at www.startco.ca

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 2
SE-701 Ground-Fault Monitor Rev. 5

2.2 FRONT-PANEL CONTROLS 2.3.2 TRIP


2.2.1 GROUND-FAULT TRIP LEVEL The red LED labeled TRIP indicates a trip. A solid red
The % CT PRIMARY selector switches are used to set LED indicates a ground-fault trip. A regularly flashing
the ground-fault trip level as a percentage of the LED indicates a trip initiated by a CT fault. Two fast
CT-primary rating. flashes indicate a diagnostic trip. See Section 2.5.
In tripping systems, a ground-fault trip level of 10 to
20% of the prospective ground-fault current is often used. 2.3.3 TRIP INHIBIT
In alarm-only systems, a value of 50% of the prospective The yellow LED labeled INHB indicates that output-
ground-fault current is often used. To avoid sympathetic relay operation was inhibited during a high-current
tripping, the trip level must be above the charging current ground fault. See Section 2.1.2. When a ground-fault
of the protected feeder. trip occurs during a high-current ground fault, both the
A 0% selection provides protection at 1%. TRIP and INHB LED’s will be ON. Inhibit indication is
reset when the ground-fault trip is reset. Inhibit operation
2.2.2 GROUND-FAULT TRIP TIME and indication will not respond if the trip-inhibit switch is
The SE-701 has a definite-time trip characteristic. The in the OFF position.
TIME (s) selector switch is used to set the ground-fault
trip delay time for coordination with upstream and 2.4 ANALOG OUTPUT
downstream ground-fault devices. Coordination requires The non-isolated, 0- to 5-V analog output indicates
the same trip level for all ground-fault devices in a system ground-fault current sensed by the ground-fault CT. The
and the trip time to progressively increase upstream. The output is 5 V when ground-fault current is 100% of the
amount of equipment removed from the system will be a CT-primary rating.
minimum if the first ground-fault device to operate is the
one immediately upstream from the fault. 2.5 SELF DIAGNOSTICS
A diagnostic trip is indicated by two flashes of the
2.2.3 RESET TRIP LED. It can be caused by a diagnostic problem
If the Reset Mode switch is in the LATCHING detected by the watchdog timer or from an incorrect
position, a trip remains latched until the RESET switch is reading from non-volatile memory. Press RESET or
pressed or the remote-reset terminals are momentarily cycle supply voltage. If the problem persists, consult
connected. In the non-fail-safe mode, cycling the supply Startco.
voltage will also reset the SE-701.
If the Reset Mode switch is in the AUTORESET 3. INSTALLATION
position, a trip will reset when the fault is removed.
The reset circuit responds only to a momentary closure An SE-701 can be surface or DIN-rail-mounted. See
so that a jammed or shorted switch will not prevent a trip. Fig. 1. Panel mounting requires a PMA-55 or PMA-60
The front-panel RESET switch is inoperative when the Panel-Mount Adapter. See Figs. 6 and 7.
remote-reset terminals (6 and 7) are connected. Pass the phase conductors through the CT window as
shown in Fig. 2 (for 4-wire and single-phase systems, also
2.2.4 TEST pass the neutral conductor through the CT window). Do
The TEST switch is used to test the ground-fault not pass ground conductors through the CT window. In
circuit, the indication, and the output relay. When the applications that require shields or drain wires to pass
TEST switch is pressed for one second, a test signal is through the CT window, return them through the CT
applied to the ground-fault-detection circuit, the circuit window before connecting them to ground. If a ground
will trip, the TRIP LED will light, and the output relay fault CT with a 5-A secondary is used, connect it to
will operate. If high-current inhibit has been selected, the terminals 2 and 3 (terminals 1 and 3 with a 1-A
INHB LED will light. secondary) and ground terminal 3. If an EFCT-x is used,
connect it to terminals 4 and 5, connect the shield to
2.3 FRONT-PANEL INDICATION terminal 5, and ground terminal 5. Remove the
2.3.1 POWER connection to terminal 9 for dielectric-strength testing
The green LED labeled PWR indicates the presence of —all inputs and outputs have ANSI/IEEE C37.90 surge-
supply voltage. protection circuits that conduct above 300 Vac. See
Figs. 3, 4, and 5 for sensitive EFCT-x dimensional
drawings.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 3
SE-701 Ground-Fault Monitor Rev. 6

55.0
(2.17)
8.7 37.5
(0.34) (1.48)

CONFIGURATION
SWITCHES

RESET MODE LATCHING 5 AUTORESET NOTE 2


FIXED VARIABLE
FILTER SELECTION 4 FREQUENCY
FREQUENCY
CT VERIFICATION OFF 3 ON

(2.95)
(2.41)
TRIP INHIBIT OFF ON

61.2

75.0
RELAY OPERATING MODE FAIL-SAFE 1 NON-FAIL-SAFE

NOTE 5

1A 5A C S1 S2 RS

(0.27)
1A/5A CT EFCT RESET ANALOG

6.9
OUTPUT
1 2 3 4 5 6 7 8 MOUNTING DETAIL

118.0 (NOTE 3)
(4.65)
TOP 110.0
(4.33) 6.3
55.0
(2.17) (0.25)

G R O U N D FA U L T M O N I T O R

PWR I N H B TRIP
4 5 6 4 5 6 .40 .50 1.0
3 7 3 7 .30 1. 5
(2.95)
75.0

2 8 2 8 . 20 2.0
1 9 1 9 .1 0 2. 5
0 0 .05
% CT PRIMARY TIME (s )

TEST RESET
STARTCO SE-701
ENGINEERING LTD.

FRONT SIDE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).

9 10 11 12 13 14 15 16 2. MOUNTING SCREWS: M4 OR 8-32.


L2 L1
N
3. OVERALL DIMENSION WHEN MOUNTED ON
DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL.

4. ADJUSTMENT KNOBS ARE REMOVABLE.

5. CONFIGURATION SWITCHES SHOWN


IN DEFAULT POSITION.
BOTTOM
FIGURE 1. SE-701 Outline and Mounting Details.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 4
SE-701 Ground-Fault Monitor Rev. 6

XXX:5

L N
1 2 3 4 5 XXX:1 OR EFCT-X

1A 5A C S1 S2 START
STOP O/L
13 14
1M
ISOLATED CONTACTS 1M
15 16

11 10 1 2 3 4 5
L1 L2
N
REMOTE RESET SE-701 1A 5A C S1 S2
6
RS
RESET
SE-701
7 Technical Information 11.1
LEAKAGE ANALOG provides additional
8 OUTPUT information on CT selection.
V 9
ALTERNATE CT
CONNECTIONS
FIGURE 2. Typical Connection Diagram.

4. SE-701 COMPATIBILITY
The current SE-701 has been enhanced with the
addition of non-volatile trip memory for the fail-safe
relay operating mode. Prior to hardware revision 07, a
mechanical flag was used instead of non-volatile trip
memory. The current revision of the SE-701 can
directly replace previous revision 00 to 06 units. The
hardware-revision number is listed on the SE-701
model/serial-number label affixed to the SE-701
enclosure. Both generations of SE-701 are compared
in Table 1.
TABLE 1. TRIP-FEATURES COMPARISON
HARDWARE REVISION
00 to 06 ≥ 07
LED trip indication Yes Yes
Mechanical flag trip indication Yes No
Non-volatile trip memory No Yes
Trip LED: Off Trip LED: On
Fail-safe Trip relay: Energized Trip relay: De-energized
Device state after supply voltage cycled Trip flag: Red
when tripped (ground-fault removed) Trip LED: Off Trip LED: Off
Non-fail-safe Trip relay: De-energized Trip relay: De-energized
Trip flag: Red

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 5
SE-701 Ground-Fault Monitor Rev. 6

P1
S2 S1

121.0 121.0
(4.76) (4.76)
20.5 80.0
(0.81) (3.15)

NOTE 2

(2.21)

(1.81)
(1.18)

56.0

46.0
30.0

M5 SCREWS
TOP MOUNTING DETAIL
25.0 30.0
(0.98) (1.18)

EFCT-1 EARTH FAULT CT


6 0 0 V I N S U L AT I O N C L A S S
APPROVAL NUMBER: QMD 997465 XU
R LR 53428 STARTCO
E N G I N E E R I N G L T D.
C US

.0
82 3)
138.0 MAX

.2
(3
(5.43)

(4.96)
69
.8 126.0
(2. 5.0 (0.20) 0
75 RECESSED FOR
EFCT-1FC )
FLUX 8-mm HEX NUT
CONDITIONER
(OPTIONAL) 1.0 (0.04) DEEP
(0.87)
22.0

5.5 110.0 5.5 56.0


(0.22) (4.33) (0.22) (2.21)
FRONT SIDE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
3. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED.
FIGURE 3. EFCT-1 Sensitive Earth-Fault CT.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 6
SE-701 Ground-Fault Monitor Rev. 6

US C
E N G I N E E R I N G L T D.
STARTCO LR 53428 R

APPROVAL NUMBER: QMD 997465 XU


6 0 0 V I N S U L AT I O N C L A S S
EFCT-2 EARTH FAULT CT

215.0
(8.46)
215.0
26.5 162.0
(8.46)
(1.04) (6.38)

P
M5 OR 10-32 TAP
(2.52)

(1.22)

S1 2S2

(2.06)
64.0

31.0

52.3
P1

M5 SCREWS

TOP MOUNTING DETAIL


25.0 31.0
(0.98) (1.22)

S1
P1
236 MAX
(9.29)

139.7

(8.46)
215.0
(5.50)
FLUX CONDITIONER
(INCLUDED) 5.0 (0.20) DIA
BONDING
SCREW
(2.36)
60.0

8.5 198.0 8.5


(0.33) (7.80) (0.33)

FRONT SIDE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).

2. MOUNTING SCREWS: M5 OR 10-32.

FIGURE 4. EFCT-2 Sensitive Earth-Fault CT.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 7
SE-701 Ground-Fault Monitor Rev. 6

68.0 68.0
(2.68) (2.68)

17.0 34.0
(0.67) (1.34)

M4 OR 8-32 TAP

(2.07)
(1.04)

(1.68)
52.5
26.5

42.6
P
S1 2S2
P1

M5 SCREWS

TOP MOUNTING DETAIL


110.0 MAX
(0.43)

25.0 26.5
(0.98) (1.04)

EFCT-26 EARTH FAULT CT


6 0 0 V I N S U L AT I O N C L A S S

R LR 53428 STARTCO
E N G I N E E R I N G L T D.
C US

4.0 (0.16) 0
(2.83)
72.0

.0 RECESSED FOR
26 2) 7-mm HEX NUT
.0 3.0 (0.12) DEEP
(1
(1.34)
34.0

(0.87)

58.0
7.0

(2.28)

5.0 5.0 52.5


(0.20) (0.20) (2.07)

FRONT SIDE

MOUNTING FOOT
NOTES:
INSTALLATION 1. DIMENSIONS IN MILLIMETRES (INCHES).
TOOL
2. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL ‘A’)
3. MOUNTING SCREWS: M4 OR 8-32.
DETAIL ‘A’

FIGURE 5. EFCT-26 Sensitive Earth-Fault CT.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 8
SE-701 Ground-Fault Monitor Rev. 4

110.0
(4.33)
85.0
(3.35) PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)

6-32
(1.67)
42.5

G R O U N D FA U L T M O N I T O R

PWR I N H B TRIP
5 5
4 6 4 6 .40 .50 1.0

(2.95)
3 7 3 7 .30 1. 5

75.0
(3.35)
2 8 2 8 . 20 2.0

85.0
1 9 1 9 .1 0 2. 5 6-32
0 0 .05
% CT PRIMARY TIME (s )

TEST RESET
STARTCO SE-701
ENGINEERING LTD.

BRACKET
55 mm (2.2) WIDE
MONITOR
BEZEL
FRONT VIEW SIDE VIEW

85.0
(3.35)
72.0
(2.83)
6.0 60.0 6.0
(0.37)
9.5

(0.24) (2.36) (0.24)

INSTALLATION INSTRUCTIONS:
2.0 (0.08) RAD 1. REMOVE BEZEL AND LATCH MONITOR TO
MAXIMUM BRACKET.
(1.67)
42.5

4.0 (0.16) DIA


(1.18)

2. INSERT BRACKET THROUGH FRONT OF PANEL


30.0

CUTOUT AND SECURE WITH FLAT WASHERS AND


8.7 (0.34) DIA LOCKNUTS PROVIDED.
(2.36)

(3.11)
60.0

79.0

4.3 (0.17) RAD 3. CONNECT WIRING TO TERMINALS.

ALTERNATE 4. INSTALL BEZEL USING 6-32 x 0.31 SCREWS


CONFIGURATIONS PROVIDED.

NOTE:
1. DIMENSIONS IN MILLIMETRES (INCHES).
(0.37)
9.5

PANEL CUTOUT DETAIL

FIGURE 6. PMA-55 Panel-Mount Adapter.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 9
SE-701 Ground-Fault Monitor Rev. 1

116.0
(4.57)
99.0
(3.90) PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)

M4
(1.73)
44.0

G R O U N D FA U L T M O N I T O R

PWR I N H B TRIP
4 5 6 4 5 6 .40 .50 1.0

(2.95)
3 7 3 7 .30 1. 5

75.0
(3.46)
2 8 2 8 . 20 2.0

88.0
1 9 1 9 .1 0 2. 5 M4
0 0 .05
% CT PRIMARY TIME (s )

TEST RESET
STARTCO SE-701
ENGINEERING LTD.

BRACKET
55 mm (2.2) WIDE
MONITOR
TRANSPARENT COVER
(NOTE 2)
FRONT VIEW SIDE VIEW

99.0
(3.90)
72.0
(2.83)
6.0 60.0 6.0
(0.37)
9.5

(0.24) (2.36) (0.24)

INSTALLATION INSTRUCTIONS:
2.0 (0.08) RAD 1. WITH COVER REMOVED LATCH MONITOR TO
MAXIMUM
BRACKET.
(1.73)
44.0

4.5 (0.18) DIA


(1.18)
30.0

2. INSERT BRACKET THROUGH FRONT OF PANEL


8.7 (0.34) DIA CUTOUT AND SECURE WITH FLAT WASHERS
AND LOCKNUTS PROVIDED.
(2.36)

(3.11)
60.0

79.0

4.3 (0.17) RAD


3. CONNECT WIRING TO TERMINALS.
ALTERNATE
CONFIGURATIONS 4. ATTACH COVER USING THUMB SCREWS
PROVIDED.

NOTE:
1. DIMENSIONS IN MILLIMETRES (INCHES).
(0.37)
9.5

2. MEETS NEMA 3, IP53.


PANEL CUTOUT DETAIL

FIGURE 7. PMA-60 Panel-Mount Adapter

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 10
SE-701 Ground-Fault Monitor Rev. 1

5. TECHNICAL SPECIFICATIONS Thermal Withstand:


Continuous ..................... 5 x CT-Secondary Rating
Supply: 1-Second......................... 80 x CT-Secondary Rating
01 Option...............................2.5 VA, 120 Vac, Burden:
(+15, -40%), 50/60 Hz 5-A input ........................ < 0.01 Ω
02 Option...............................2.5 VA, 240 Vac, 1-A input ........................ < 0.05 Ω
(+15, -40%), 50/60 Hz EFCT input..................... 2 Ω
03 Option...............................2.5 VA, 24 Vac,
(+15, -40%), 50/60 Hz Analog Output:
0U Option..............................2.5 VA, 120 to 240 Vac, Range .................................. 0 to 5 Vdc,
(+20, -55%) 50/60 Hz 5 V = 100% CT Rating
2.0 W, 100 to 240 Vdc, Output Impedance .............. 220 Ω
(+20, -25%)
0D Option..............................2.0 W, 12 to 30 Vdc, Reset ........................................... Front-Panel Switch and
(+20, -25%) Remote N.O. Momentary
0T Option ..............................2.0 W, 40 to 55 Vdc, Contact
(+20, -25%)
Functional Test........................... Front-Panel Switch
Trip-Level Range..........................1 to 99% CT-Primary
Rating in 1% increments Relay Contacts:
(50 mA to 4.95 A with Configuration .....................Isolated N.O. and N.C.
EFCT-x) Operating Mode .................Fail-Safe or Non-Fail-Safe
CSA/UL Contact Rating .......8 A resistive 250 Vac,
Trip-Time Settings........................0.05, 0.10, 0.20, 0.30, 8 A resistive 30 Vdc
0.40, 0.50, 1.0, 1.5, 2.0, Supplemental Contact Ratings:
and 2.5 s Make/Carry 0.2 s ..........20 A
Break:
Accuracies (1): dc ...............................30 W resistive,
Trip Level (2) ..........................Largest of 5% of setting or: 15 W inductive (L/R = 0.04)
1-A input: ac ...............................2,000 VA resistive,
1% setting ..............-10, +15 mA 1,400 VA inductive
2 – 99% setting.......10 mA (PF = 0.4)
5-A and EFCT (4) inputs: Subject to maximums of 8 A and 250 V (ac or dc).
1% setting ..............-35, +60 mA
2 – 99% setting.......35 mA Operating Mode ......................... Latching or Autoreset
Trip Time (3) ..........................5% of setting
(-25, +20 ms minimum) Terminals.................................... Wire-clamping,
24 to 12 AWG
Trip Inhibit: (0.2 to 2.5 mm2) conductors
Off .........................................Class I
On ..........................................Class II Dimensions:
Level .................................11 x CT-Primary Rating Height.................................. 75 mm (3.0")
Width................................... 55 mm (2.2")
Input: Depth................................... 115 mm (4.5")
Algorithms ............................DFT or Peak
DFT 3 dB Frequency Resp..32 to 86 Hz Shipping Weight......................... 0.45 kg (1 lb.)
Peak 3 dB Frequency Resp..20 to 420 Hz
CT..........................................1- or 5-A Secondary Environment:
Rating, or EFCT-x Operating Temperature ...... -40 to 60°C
CT Detection ....................Open-Circuit Detection Storage Temperature .......... -55 to 80°C
with EFCT-x Humidity ............................. 85% Non-Condensing

Surge Withstand......................... ANSI/IEEE 37.90.1-1989


(Oscillatory and Fast
Transient)

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 11
SE-701 Ground-Fault Monitor Rev. 0

EMC Tests: 6. ORDERING INFORMATION


Verification tested in accordance with EN 50263:2000
Electrostatic Discharge...... IEC 61000-4-2, EN 61000-4-2, SE-701-0
6 kV Contact Discharge
8 kV Air Discharge 1 120-Vac Supply
2 240-Vac Supply
Radiated RF....................... IEC 61000-4-3, EN 61000-4-3 3 24-Vac Supply
10 V/m, 80-1000 MHz, U Universal 120/240-Vac/Vdc Supply
80% AM (1 kHz) D 12/24-Vdc Supply
10 V/m, 900 MHz, T 48-Vdc Supply
200 Hz Pulse Modulated
EFCT-1............ Sensitive Earth-Fault CT,
Fast Transient.................... IEC 61000-4-4, EN 61000-4-4 5-A-primary rating, 82-mm (3.2") window
±2 kV Common Mode EFCT-1FC....... Flux Conditioner for EFCT-1,
±1 kV Differential Mode 70-mm (2.7”) window
EFCT-2............ Sensitive Earth-Fault CT, with
Surge Immunity................. IEC 61000-4-5, EN 61000-4-5 Flux Conditioner, 5-A-primary rating,
±2.0 kV Common Mode 139-mm (5.5”) window
±1.0 kV Differential Mode EFCT-26.......... Sensitive Earth-Fault CT,
5-A-primary rating,
Conducted RF ................... IEC 61000-4-6, EN 61000-4-6 26-mm (1”) window
10Vrms, 0.15-80 MHz,
80% AM (1 kHz) PMA-55 ........... Panel-Mount Adapter, NEMA 1
PMA-60 ........... Panel-Mount Adapter, NEMA 3, IP53
Magnetic Field .................. IEC 61000-4-8, EN 61000-4-8 PMA-3 ............. Adapter Plate, GES/MCGG
50 Hz, 30 A/m (continuous) PMA-6 ............. Adapter Plate, FPL-GFRM
50 Hz, 300 A/m PMA-15 ........... Adapter Plate, MGFR
(1 to 3 seconds)
SE-EFVC......... Voltage Clamp
Voltage Interruption.......... IEC 255-22-11, EN 60255-11
100% for 2, 5, 10, 20, 50, Consult factory for custom mounting adapters.
100 & 200 ms
7. WARRANTY
MHz Burst......................... IEC.255-22-1, EN 60255-22-1 The SE-701 Ground-Fault Monitor is warranted to be
1 kV Differential Mode free from defects in material and workmanship for a
2.5 kV Common Mode period of five years from the date of purchase.
Startco Engineering Ltd. will (at Startco’s option)
RFI Compliance ..................... FCC Part 15, Subpart B, repair, replace, or refund the original purchase price of an
Class A – Unintentional SE-701 that is determined by Startco to be defective if it
Radiators is returned to the Startco factory, freight prepaid, within
the warranty period. This warranty does not apply to
Certification .............................. CSA, Canada and USA repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
R LR 53428
C US
care. Startco Engineering Ltd. does not warrant products
repaired or modified by non-Startco Engineering Ltd.
Australia personnel.

NOTES:

(1)
Over operating temperature range of –40 to 60°C.
(2)
CT accuracy not included.
(3)
Trip time at 3 x trip-level setting.
(4)
For maximum lead resistance of 1 Ω.

Pub. SE-701-M, January 18, 2008.


Startco Engineering Ltd. Page 12
SE-701 Ground-Fault Monitor Rev. 0

8. GROUND-FAULT PERFORMANCE TEST a) USING SE-400


XXX:5
To meet the requirements of the National Electrical
FROM
Code (NEC), as applicable, the overall ground-fault POWER LOAD
protection system requires a performance test when first SOURCE
installed. A written record of the performance test is to
be retained by those in charge of the electrical
installation in order to make it available to the authority 1 2 3 4 5

having jurisdiction. A test-record form is provided for 1A 5A C S1 S2


recording the date and the final results of the L
11
L1
performance tests. The following ground-fault system N
10 SE-701
L2/N
tests are to be conducted by qualified personnel:
a) Evaluate the interconnected system in accordance 11
OP1 OP2
12

with the overall equipment manufacturer’s detailed L


3
L1
instructions. N
5
L2
b) Verify proper location of the ground-fault current 1 SE-400
transformer. Ensure the cables pass through the
ground-fault-current-transformer window. This 8 RMT1
REMOTE
check can be done visually with knowledge of the TEST 9
circuit. The connection of the current-transformer RMT2

secondary to the SE-701 is not polarity sensitive. b) USING SE-100T


XXX:5
c) Verify that the system is correctly grounded and that
alternate ground paths do not exist that bypass the FROM
current transformer. High-voltage testers and POWER
SOURCE
LOAD

resistance bridges can be used to determine the


existence of alternate ground paths.
d) Verify proper reaction of the circuit-interrupting 1 2 3 4 5

device in response to a simulated or controlled 1A 5A C S1 S2


ground-fault current. To simulate ground-fault L
11
L1
current, use CT-primary current injection. Fig. 8 (a) N
10 SE-701
L2/N
shows a test circuit using a Startco SE-400 Ground-
Fault-Relay Test Unit. The SE-400 has a 0.65 A
C LO
programmable output of 0.5 to 9.9 A for a duration of 2.75 A
0.1 to 9.9 seconds. Set the test current to 120% of L L1 HI
REMOTE
the SE-701 setting. Fig. 8 (b) shows a test circuit TEST N L2 SE-100T
using a Startco SE-100T Ground-Fault-Relay Tester.
The SE-100T provides a test current of 0.65 or 2.75
RMT
A for testing 0.5- and 2.0-A trip levels. Inject the test
current through the current-transformer window for FIGURE 8. Ground-Fault-Test Circuits
at least 2.5 seconds. Verify that the circuit under test
has reacted properly. Correct any problems and re- TABLE 2. GROUND-FAULT-TEST RECORD
test until the proper reaction is verified.
DATE TEST RESULTS
e) Record the date and the results of the test on the
attached test-record form.

NOTE: Do not inject test current directly into CT-input


terminals 1, 2, 3, 4, and 5.

Retain this record for the authority having jurisdiction.

Pub. SE-701-M, January 18, 2008.

You might also like