Failure Analysis of SA-213TP347H High-Temperature
Failure Analysis of SA-213TP347H High-Temperature
Failure Analysis of SA-213TP347H High-Temperature
1. Introduction
SA-213TP347H austenitic stainless steel not only has good intergranular corrosion resistance, high-
temperature oxidation resistance, creep performance, but also has good welding and thermal
processing performance, which has been widely used in the high-temperature heating surface tubes of
ultra-supercritical or supercritical large-capacity boiler [1]. However, in the production of SA-
213TP347H steel, some domestic manufacturers did not carry out solid solution heat treatment after
cold processing in strict accordance with the standard requirements, or even did not carry out solid
solution treatment at all, which caused a great impact on the service performance of TP347H steel,
especially the performance of elbow.
On June 22, 2018, the high-temperature reheater of a power plant leaked. On July 12, the leakage
of the high-temperature reheater tube happened again. After the leakage, the relevant personnel of the
Electric Power Academy rushed to the scene for the first time, and preliminarily judged that the first
explosion port was the sixth of the 40nd screen tube from the left of the furnace, and the burst tube
was the inside of the U-shaped elbow of the high-temperature reheater. The burst tube material was
SA-213TP347H, and the specification was Φ 51 mm x 4.5 mm. The burst tube sample (No. 1) and the
spare part (No. 2) were cut off on site, and the tube was analyzed by optical microscope (OM),
scanning electron microscopy (SEM) and energy dispersive spectroscopy (EDS), etc., so as to find out
the reason why the high-temperature reheater frequently leaked.
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution
of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.
Published under licence by IOP Publishing Ltd 1
2019 International Conference on Boilers and Heat Exchangers (ICBHE2019) IOP Publishing
IOP Conf. Series: Materials Science and Engineering 721 (2020) 012061 doi:10.1088/1757-899X/721/1/012061
2. Experiment
2
2019 International Conference on Boilers and Heat Exchangers (ICBHE2019) IOP Publishing
IOP Conf. Series: Materials Science and Engineering 721 (2020) 012061 doi:10.1088/1757-899X/721/1/012061
Figure 1. Microstructure of the burst tube Figure 2. Microstructure of the spare part
Figure 4. EDS of the precipitates. (b) EDS of the precipitates on grain boundary of (a)
3
2019 International Conference on Boilers and Heat Exchangers (ICBHE2019) IOP Publishing
IOP Conf. Series: Materials Science and Engineering 721 (2020) 012061 doi:10.1088/1757-899X/721/1/012061
4. Conclusion
Based on the above analysis, one of the reasons for the frequent bursting of the high-temperature
reheater is that due to the influence of the manufacturing quality, the defects in the bending process
and the elliptic deformation exceed the standard, resulting in a decrease in the mechanical strength of
the tube. Since the high-temperature reheater tube is not solution treated, the dislocations and residual
stresses at the elbow increase, which accelerate the precipitation of the Cr element carbide at the grain
boundary, and the grain boundary is sharply depleted in Cr, resulting in a decrease in grain boundary
corrosion resistance. With the operation of the unit, the SA-213TP347H without solution treatment of
the high-temperature superheater is frequently bursting under the combined action of steam pressure,
thermal stress, residual stress and corrosive medium.
References
[1] Li, Z.L., Wang, J.A., Xiao, M.Y. (2015) Failure analysis of SA-213TP347H steel reherater
tube. Heat Treatment of Metals., 40: 191-194.
[2] Ma, Q., Liang, P., Yang, S.E., et al. (2009) Investigation of high-temperature steam
oxidation for TP347H steel. Transactions of Materials and Heat Treatment., 30: 172 -176.
[3] Ma, G.B., Li, X.H., Xie, A.M. (2008) Short-time cracking analysis of TP347H tubes of
high temperature heat delivery surfaces of boilers. Engineering Journal of Wuhan
University., 40: 80-84.
4
2019 International Conference on Boilers and Heat Exchangers (ICBHE2019) IOP Publishing
IOP Conf. Series: Materials Science and Engineering 721 (2020) 012061 doi:10.1088/1757-899X/721/1/012061
[4] Tao, J., Yao, Z.J., Xue, F. (2006) Fundamentals of Material Science. Chemical Industry
Press, BeiJing.
[5] Wang, J.A., Li, J.P., Li, J. et al. (2015) Failure analysis of tube-burst of SA-213TP347H
high-temperature reheater of 600 MW supercritical unit. Transactions of Materials &
Heat Treatment., 36:122-127.
[6] Zhang, D.K. (1982) Local Corrosion of Stainless Steel. Science Press, BeiJing.
[7] Long, H.G., Chen, H.D., Wan, K.Y. (2008) Failure analysis of high temperature super-
heater bend for boiler. Corrosion & Protection, 29: 157-159.
[8] Natesan, K., Kraus, C. (1998) Corrosion performance of structural alloys in oxygen/ sulfur/
chlorine-containing environments. In: 12th Fossil Energy Materials. Knoxville. pp. 18-
30.
[9] Natesan, K., Baxter, D.J. Oxygen-sulfhr corrosion of metals in mixed-gas atmospheres. In:
3rd Corrosion-Erosion Wear of Materials at Elevated Temperatures. Houston. pp. 67-86.