Ba sgr1 05 12 Norm en
Ba sgr1 05 12 Norm en
Ba sgr1 05 12 Norm en
2
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Table of contents
8. Signals..................................................................................................................................... 20
8.1. Feedback signals from actuator 20
9. Commissioning...................................................................................................................... 21
9.1. End stops in part-turn actuator 21
9.1.1 End stop CLOSED: set 21
9.1.2 End stop OPEN: set 22
9.2. Swing angle 22
9.2.1 Swing angle: modify 23
9.3. Switch compartment: open 23
9.4. Torque switching: set 24
9.5. Limit switching: set 25
9.5.1 End position CLOSED (black section): set 25
9.5.2 End position OPEN (white section): set 26
9.6. Intermediate positions: set 26
9.6.1 Running direction CLOSE (black section): set 27
9.6.2 Running direction OPEN (white section): set 27
9.7. Test run 27
9.7.1 Direction of rotation: check 27
9.7.2 Limit switching: check 28
9.8. Potentiometer setting 28
9.9. Electronic position transmitter RWG: set 29
9.10. Mechanical position indicator: set 30
9.11. Switch compartment: close 30
9.12. Operating time: set 31
10. Corrective action.................................................................................................................... 32
10.1. Faults during commissioning 32
10.2. Motor protection (thermal monitoring) 32
11. Servicing and maintenance................................................................................................... 33
11.1. Preventive measures for servicing and safe operation 33
11.2. Maintenance 33
11.3. Disposal and recycling 33
12. Technical data......................................................................................................................... 34
12.1. Features and functions of actuator 34
12.2. Service conditions 35
12.3. Further information 36
13. Spare parts............................................................................................................................. 37
13.1. Part-turn actuators SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 37
14. Certificates.............................................................................................................................. 39
14.1. Declaration of Incorporation and EC Declaration of Conformity 39
15. Index........................................................................................................................................ 40
Addresses............................................................................................................................... 41
3
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Safety instructions
1. Safety instructions
1.1 Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/war- All personnel working with this device must be familiar with the safety and warning
nings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2 Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.
butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
4
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Safety instructions
● Escalators
● Continuous duty
● Buried service
● Permanent submersion (observe enclosure protection)
● Potentially explosive areas, with the exception of zone 22
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3 Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP 67 or IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
● In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
● The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.
● The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are prere-
quisites for compliance with the maximum surface temperature of devices.
● The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.
● The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.
● The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
● As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe opera-
tion of actuators.
1.4 Warnings and notes
5
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Safety instructions
Information The term Information preceding the text indicates important notes and information.
6
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Identification
2. Identification
2.1 Name plate
Each device component (actuator, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
7
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Transport, storage and packaging
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2 Storage
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3 Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
8
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Assembly
4. Assembly
1. Remove cap nut [1] and pull out ball handle [2].
2. Insert ball handle [2] in correct position and fasten with cap nut [1].
9
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Assembly
4.3.1 Coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Screw
10
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Assembly
11
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
5. Electrical connection
5.1 Basic information
Wiring diagram/terminal
The pertaining wiring diagram/terminal plan (in German and English language) is
plan attached to the device in a weather-proof bag, together with these operation
instructions. It can also be obtained from AUMA (state commission no., refer to name
plate) or downloaded directly from the Internet (www.auma.com).
Delay time
The delay time is the time from the tripping of the limit or torque switches to the motor
power being switched off. To protect the valve and the actuator, we recommend a
delay time < 50 ms. Longer delay times are possible provided the operating time,
output drive type, valve type, and the type of installation are considered. We
recommend switching off the corresponding contactor directly by limit or torque
switch.
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current value for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet).
Limit and torque swit-
Limit and torque switches can be provided as single, tandem, or triple switches. Only
ches the same potential can be switched on the two circuits (NC/NO contact) of each
single switch. If different potentials are to be switched simultaneously, tandem
switches or triple switches are required. When using tandem/triple switches:
● For signalling use the leading contacts TSC1, TSO1, LSC1, LSO1.
● For switching off use the lagging contacts TSC, TSO, LSC, LSO.
Type of current, mains Type of current, mains voltage and mains frequency must match the data on the
voltage and mains fre- motor name plate.
quency
12
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
● Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
● Control contacts (1 to 50): max. 2.5 mm²
5.2.1 Terminal compartment: open
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
13
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
14
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
15
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of cover [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3 Accessories for electrical connection
— Option —
5.3.1 Parking frame
Application Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
16
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Electrical connection
17
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Operation
6. Operation
Information Turning the handwheel during motor operation extends or reduces the operating time,
depending on the direction of rotation.
Controls are required to operate an actuator during motor operation. If the actuator
is to be operated locally, additional local controls are required.
18
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Indications
7. Indications
7.1 Mechanical position indicator/running indication
Mechanical position indicator:
● Continuously indicates the valve position
(For a swing angle of 90°, the indicator disc [2] rotates by approximately 180°.)
● Indicates whether the actuator is running (running indication)
● Indicates that the end positions are reached (via indicator mark [3])
Figure 14: Mechanical position indicator
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
19
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Signals
8. Signals
8.1 Feedback signals from actuator
Information The switches can be provided as single switches (1NC and 1 NO), as tandem swit-
ches (2 NC and 2 NO) or as triple switches (3 NC and 3 NO). The precise version
is indicated in the terminal plan or on the order-related technical data sheet.
20
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
9. Commissioning
Information When leaving the factory (without valve), the screws [1] are not fastened, i.e. the
end stops must be set. If the actuator is mounted onto the valve with the screws [1]
fastened, the valve manufacturer has already performed the end stop setting. In this
case, the end stops must only be checked (use the handwheel to drive valve into
end positions).
9.1.1 End stop CLOSED: set
[1] Screws
[2] End stop nut
[3] Protective cap
1. If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns.
2. Move valve to end position CLOSED with handwheel. Check whether end stop
nut [2] rotates simultaneously.
→ Otherwise: Turn end stop nut [2] clockwise until end stop is reached.
3. In case end position CLOSED has been passed: Turn back the handwheel by
several turns and approach end position CLOSED again.
4. Turn end stop nut [2] counterclockwise by 1/8th turn.
Information: In this process, the protective cap [3] must not be unfastened.
➥ Thus, the end stop CLOSED within the part-turn actuator is set to a slightly
higher swing angle (approx. 1°) than the valve end position.
5. Fasten screws [1] crosswise at 25 Nm.
21
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
● Following end stop setting, the limit switching for end position CLOSED
can be set (refer to <Limit switching: set> chapter). For this, the switch
compartment must be opened and the indicator disc removed (refer to
<Switch compartment: open> chapter).
● In general, the end stop OPEN does not require setting due to fact that
the swing angle was already set in the factory.
9.1.2 End stop OPEN: set
[1] Screws
[2] End stop nut
[3] Protective cap
1. If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns.
2. Move valve to end position OPEN with handwheel. Check whether end stop
nut [2] rotates simultaneously.
→ Otherwise: Turn end stop nut [2] counterclockwise until end stop.
3. In case end position OPEN has been passed: Turn back the handwheel by
several turns and approach end position OPEN again.
4. Turn end stop nut [2] clockwise by 1/8th turn.
Information: In this process, the protective cap [3] must not be unfastened.
➥ Thus, the end stop OPEN within the part-turn actuator is set to a slightly higher
swing angle (approx. 1°) than the valve end position.
5. Fasten screws [1] crosswise at 25 Nm.
● Subsequent to this setting, the limit switching for end position OPEN can
be set (refer to <Limit switching: set> chapter). For this, the switch com-
partment must be opened and the indicator disc removed (refer to <Switch
compartment: open> chapter).
● In general, the end stop CLOSED does not require setting due to the fact
that the swing angle was already set in the factory.
9.2 Swing angle
The swing angle must only be changed if the swivel range for end stop setting is not
sufficient.
The swing angle set in the factory is indicated on the name plate.
In the standard version the swing angle can be adjusted within the range of 80° to
110°. Optional swivel ranges: refer to technical data pertaining to the order.
22
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
The switch compartment must be opened to perform the following settings (options).
23
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
1. Loosen screws [2] and remove cover [1] from the switch compartment.
Figure 19:
24
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
25
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
3. To prevent that the end stop is reached (due to overrun) before the limit switch
has tripped, turn handwheel 4 turns (overrun) in the opposite direction.
4. Press down and turn setting spindle [1] with screw driver in direction of the
arrow and observe the pointer [2]: While a ratchet click is felt and heard, the
pointer [2] moves 90° every time.
5. If the pointer [2] is 90° from mark [3]: Continue turning slowly.
6. If the pointer [2] moves to mark [3]: Stop turning and release setting spindle.
➥ The end position CLOSED setting is complete.
7. If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.5.2 End position OPEN (white section): set
Black section:
[1] Setting spindle: Running direction CLOSE
[2] Pointer: Running direction CLOSE
[3] Mark: Intermediate position CLOSED is set
White section:
[4] Setting spindle: Running direction OPEN
[5] Pointer: Running direction OPEN
[6] Mark: Intermediate position OPEN is set
26
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
27
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
[1] Potentiometer
28
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
4. Perform fine-tuning of the zero point at external setting potentiometer (for remote
indication).
9.9 Electronic position transmitter RWG: set
— Option —
The electronic position transmitter RWG records the valve position. On the basis of
the actual position value measured by the potentiometer (travel sensor), it generates
a current signal between 0 – 20 mA or 4 – 20 mA.
29
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
30
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Commissioning
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
31
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Corrective action
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1. Turn test button [1] in direction of the TSC arrow: Torque switch CLOSED trips.
2. Turn test button [2] in direction of the TSO arrow: Torque switch OPEN trips.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1. Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2. Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
10.2 Motor protection (thermal monitoring)
In order to protect against overheating and impermissibly high temperatures at the
actuator, PTC thermistors or thermoswitches are embedded in the motor winding.
They trip as soon as the max. permissible winding temperature has been reached.
Behaviour during failure If the signals are correctly wired within the controls, the actuator is stopped and can
only resume its operation once the motor has cooled down.
Possible causes Overload, running time exceeded, max. number of starts exceeded, ambient
temperature is too high.
Remedy Check cause, eliminate if possible.
32
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Servicing and maintenance
AUMA
AUMA offer extensive service such as servicing and maintenance as well as customer
Service & Support product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com) .
33
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Technical data
34
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Technical data
35
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Technical data
36
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Spare parts
37
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Spare parts
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type
001.0 Housing
002.0 Worm shaft Sub-assembly
002.4 End stop nut (included in sub-assembly 002.0)
003.0 Manual drive worm Sub-assembly
004.0 Worm wheel Sub-assembly
005.0 Mounting flange Sub-assembly
010.0 End stop Sub-assembly
016.1 Protective cap
017.0 Torque finger Sub-assembly
021.0 Limit drive finger Sub-assembly
029.0 Manual drive bearing Sub-assembly
032.0 Planetary gearing Sub-assembly
034.0 Motor Sub-assembly
034.1 Motor brake Sub-assembly
034.2 Cover plate Sub-assembly
041.0 Socket carrier with motor cable harness Sub-assembly
061.0 Torque switching head Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Plug cover Sub-assembly
525.0 Coupling
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
553.0 Mechanical position indicator Sub-assembly
556.0 Potentiometer for position transmitter Sub-assembly
556.1 Potentiometer without slip clutch
557.0 Heater Sub-assembly
558.0 Blinker transmitter including pins at wires (without impulse disc and insulation plate) Sub-assembly
559.0-1 Control unit with torque switching heads and switches Sub-assembly
559.0-2 Control unit with magnetic limit and torque transmitter (MWG) for Non-intrusive version in combination Sub-assembly
with AUMATIC integral controls
560.0-1 Switch stack for direction OPEN Sub-assembly
560.0-2 Switch stack for direction CLOSE Sub-assembly
560.1 Switch for limit/torque switching
560.2 Switch case
566.0 Position transmitter RWG Sub-assembly
566.1 Potentiometer for RWG without slip clutch Sub-assembly
566.2 Electronic board RWG Sub-assembly
566.3 Wire harness for RWG Sub-assembly
567.1 Slip clutch for potentiometer Sub-assembly
S1 Seal kit, small Set
S2 Seal kit, large Set
38
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Certificates
14. Certificates
14.1 Declaration of Incorporation and EC Declaration of Conformity
39
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1
Index
O
Index Operating time 31
Operation 4 , 18
A
Accessories (electrical 16 P
connection) PTC thermistors 32
Ambient temperature 36 Packaging 8
Applications 4 Parking frame 16
Assembly 9 Position indicator 30
Position transmitter RWG 29
C Potentiometer 28
Commission number 7 Power supply 12
Commissioning 4 , 21 Protection cover 17
Corrective action 32 Protection on site 12
Corrosion protection 8 , 35 Protective measures 4
Cross sections 13
Current consumption 12 Q
Qualification of staff 4
D
DUO limit switching 26 R
Declaration of Incorporation 39 RWG 29
Delay time 12 Range of application 4
Direction of rotation 27 Recycling 33
Directives 4 Running indication 19
Disposal 33
Double sealed 17 S
Safety instructions 4
E Safety instructions/warnings 4
EC Declaration of Conformity 39 Service 33
Electrical connection 12 Service conditions 35
Electronic position transmitter 29 Servicing 33
Enclosure protection 35 Short-circuit protection 12
End stops 21 Signals 20
Spare parts 37
H Standards 4
Handwheel 9 Storage 8
I Support 33
Identification 7 Swing angle 22
Indications 19 Switch check 32
Indicator disc 19 , 30 Switches 12
Inspection record 7 T
Intermediate frame 17 Tandem switches 12
Intermediate positions 26 Technical data 34
L Technical data for switches 35
Limit switches 12 Terminal plan 7 , 12
Limit switching 25 , 28 Test run 27
Lubrication 33 Thermal monitoring 32
Thermoswitches 32
M Torque switches 12
Mains frequency 12 Torque switching 24
Mains voltage 12 Transport 8
Maintenance 4 , 33 , 33 Type and size 7
Manual operation 18 Type of current 12
Mechanical position indicator 19 , 30
Motor heater 15 W
Motor operation 18 Wiring diagram 12
Motor protection 32
N
Name plate 7 , 12
40
AUMA worldwide
41
AUMA worldwide
Asia Australia
AUMA Actuators (Tianjin) Co., Ltd. BARRON GJM Pty. Ltd.
CN 300457 Tianjin AU NSW 1570 Artarmon
Tel +86 22 6625 1310 Tel +61 294361088
Fax +86 22 6625 1320 Fax +61 294393413
mailbox@auma-china.com info@barron.com.au
www.auma-china.com www.barron.com.au
42
AUMA worldwide
43
AUMA Riester GmbH & Co. KG
P.O.Box 1362
D 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
riester@auma.com
www.auma.com
Y000.234/003/en/4.12