Signet 8550-1 Flow Transmitter English

*3-8550.090-1*
3-8550.090-1 J 4/05 English

WARNING! Contents Flow 6.25 GPM


• Remove power to unit before wiring input and out- 1. Specifications Total 1234567.8>
Signet Flow
put connections. 2. Installation Transmitter

• Follow instructions carefully to avoid personal 3. Electrical Connections ENTER

injury. 4. Menu Functions

1. Specifications
Dimensions

Optional
96 mm Rear 92 mm 82 mm 96 mm
(3.8 in.) Cover (3.6 in.) (3.23 in.) (3.8 in.)

96 mm 56 mm 106 mm 102 mm
(3.8 in.) 41 mm (2.2 in.) (4.18 in.) (4.0 in.)
(1.6 in.)
97 mm
(3.8 in.)
FRONT VIEW
SIDE VIEW SIDE VIEW SIDE VIEW
Field Mount &
Panel Mount Panel Mount Field Mount w/ Field Mount w/
8050 Universal base 8051 Integral kit

General
Compatibility: Signet Flow Sensors (w/freq out) Current output:
• 4 to 20 mA, isolated, fully adjustable and reversible
Enclosure: • Max loop impedance: 50 Ω max. @ 12 V
• Rating: NEMA 4X/IP65 front 325 Ω max. @ 18 V
• Case: PBT 600 Ω max. @ 24V
• Panel case gasket: Neoprene • Update rate: 100 ms
• Window: Polyurethane coated polycarbonate • Accuracy: ±0.03 mA
• Keypad: Sealed 4-key silicone rubber
• Weight: Approx. 325g (12 oz.) Open-collector output, optically isolated:
• 50 mA max. sink, 30 VDC maximum pull-up voltage.
Display: • Programmable for:
• Alphanumeric 2 x 16 LCD • High or Low setpoint with adjustable hysteresis
• Update rate: 1 second • Pulse operation (max rate: 300 pulses/min).
• Contrast: User selected, 5 levels
• Display accuracy: ±0.5% of reading @ 25ºC Environmental
• Thermal sensitivity shift: ±0.005% of reading per ºC • Operating temperature: -10 to 70°C (14 to 158°F)
• Storage temperature: -15 to 80°C (5 to 176°F)
Electrical • Relative humidity: 0 to 95%, non-condensing
• Power: 12 to 24 VDC ±10%, regulated • Maximum altitude: 2000 m (6562 ft)
61 mA max current • Insulation category: II
• Pollution degree: 2
Sensor Input:
• Range: 0.5 to 1500 Hz Standards and Approvals
• Sensor power: 2-wire: 1.5 mA @ 5 VDC ± 1% • CSA, CE, UL listed
3 or 4 wire: 20 mA @ 5 VDC ± 1% • Immunity & Emissions: EN61326
Optically isolated from current loop • Manufactured under ISO 9001 and ISO 14001
• Short circuit protected

2. Installation
ProcessPro transmitters are available in two styles: panel mount and field mount. The panel mount is supplied with the necessary
hardware to install the transmitter. This manual includes complete panel mounting instructions.
Field mounting requires one of two separate mounting kits. The 3-8051 integral kit joins the sensor and instrument together into a single
package. The 3-8050 Universal kit enables the transmitter to be installed virtually anywhere.
Detailed instructions for integral mounting or other field installation options are included with the 3-8051 Integral kit or the 3-8050
Universal kit.
2.1 Panel Installation panel
gasket
1. The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For mounting
terminals bracket
manual panel cutout, an adhesive template is provided as an installation guide.
Recommended clearance on all sides between instruments is 1 inch.

2. Place gasket on instrument, and install in panel. latch sr Gnd


SenIELD)
7 (SH
sr IN
SenD)
- 6 (RE
Pwr Output sr V+
System
p-
4 SenACK)
(BL
2 Loo
Pwr
5
System
p+ +
1 Loo
Output

3. Slide mounting bracket over back of instrument until quick-clips snap into latches on 3

side of instrument.

4. To remove, secure instrument temporarily with tape from front or grip from rear of
instrument. DO NOT RELEASE. Panel Mount
Installation Detail
Press quick-clips outward and remove. quick-clips

3. Electrical Connections
Caution: Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure 2
1. Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire end.
1
2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure


1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.

Terminals 3 and 4: Loop Power


12-24 VDC ±10% system power
and current loop output.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V
Terminals 7-9: Flow sensor input

System Pwr
4 Loop -
System Pwr Sensr Gnd
3 Loop + 6 Output - 9 (SHIELD)
AUX Sensr IN
2 Power - 8 (RED)
AUX Sensr V+
1 Power + 5 Output + 7 (BLACK)

Terminals 1 and 2: AUXILIARY power


Used only if the flow sensor requires more Internal open-collector Internal open-collector
output circuit output circuit Outputs
than 1.5 mA current. For Signet sensors S 15 15 1 2
S _
this is limited to the following products: Output --

• 2000 • 2507 • 2551 D


Output +
D
+
Isolation Isolation
• Open Collector Input
SINGLE CHANNEL DUAL CHANNEL

Terminals 5 and 6: Open-collector Output


A transistor output, programmable (see CALIBRATE menu) as:
• High or Low setpoint with adjustable hysteresis
• Volumetric pulse
• Frequency based on flow rate
• May be disabled (Off) if not used.

2 Signet 8550-1 Flow Transmitter


3.1 System Power/Loop Connections
Stand-alone application, no current loop used
Transmitter
Terminals
System Pwr Loop - 44 Power
- Supply
System Pwr Loop + 33
+ 12-24 VDC
AUX Power - 22
AUX Power + 11
* See AUX POWER Note

Connection to a PLC/Recorder, separate supply Connection to a PLC with built-in power supply

PLC or Recorder
Transmitter Transmitter PLC Terminals
Terminals
+ Loop Input Terminals
4-20 mA
- System Pwr Loop - 44 Loop Input
System Pwr Loop - 44 + 4-20 mA
33 System Pwr Loop + 33 -
System Pwr Loop +
22 Power AUX Power - 22 Power
AUX Power - - - Supply
Supply AUX Power + 11
AUX Power + 11
+ 12-24 VDC + 12Ð24 VDC
Internal
PLC Connection

* See AUX POWER Note * See AUX POWER Note

Example: Two transmitters connected to PLC/Recorder with separate power supply

PLC or Recorder

+ Channel 1
- 4-20 mA in

- Channel 2
Transmitter 1 Transmitter 2
4-20 mA in
Terminals + Terminals

System Pwr Loop - 4 44 System Pwr Loop -


System Pwr Loop + 3 33 System Pwr Loop +
AUX Power - 2 22 AUX Power -
AUX Power + 1 11 AUX Power +

Power
- Supply
* See AUX POWER Note

+ 12-24 VDC

Auxiliary Power note:


AUXILIARY power is used only if the flow sensor requires more than 1.5 mA current.
For Signet sensors this is limited to the following products: 2000, 2507, 2551, open collector input signals

3.2 Sensor Input Connections


Transmitter

Wiring Tips: Flow 6.25 GPM


Total 1234567.8>
Signet Flow
Transmitter

• Do not route sensor cable in conduit containing AC power wiring. ENTER

Electrical noise may interfere with sensor signal. ≤ 200 ft. (61 m)
• Routing sensor cable in grounded metal conduit will help prevent
electrical noise and mechanical damage.
• Seal cable entry points to prevent moisture damage. Maximum cable length is 200 ft. for 515/8510-XX,
• Only one wire should be inserted into a terminal. Splice double wires 525 , 2517 and any sinusoidal flow signal.
outside the terminal. Transmitter
Flow 6.25 GPM
Total 1234567.8>

Terminals No Aux Power


Signet Flow
Transmitter

Aux Power ENTER

Sensr Gnd 515/3-8510-XX


9 (SHIELD) 2000
525 2507 ≤ 1000 ft. (300 m)
Sensr IN 2100
8 (RED) 2517
2551
Open Coll.
Sensr V+ 2536/3-8512-XX Maximum cable length is 1000 ft. for
7 (BLACK) 2540
Input
2536/8512-XX, 2540, vortex, and any open
7000 Vortex
collector flow signal.

Signet 8550-1 Flow Transmitter 3


3.3 Open Collector Output
The Open collector output can be used as a switch that responds Process
when the flow rate moves above or below a setpoint, or it can be
used to generate a pulse that is relative to the flow volume or to
the flow rate. Hysteresis

• Low
Low Setpoint
Output triggers when the flow rate is less than the setpoint.
The output will relax when the flow rate moves above the setpoint
plus the hysteresis value. Time

• High Output energized


Output triggers when the flow rate is greater than the setpoint.
Output relaxed
The output will relax when the flow rate drops below the setpoint
plus the hysteresis value.
Process

• Frequency
Output is a pulse stream that is based on the input flow sensor High Setpoint
signal. Set for 1 (input frequency = output frequency). Set for
even numbers (2, 4, 6, 8 . . . . 254 maximum) to scale output
frequency. Hysteresis

• Pulse Time
Output is a pulse based on the volume of fluid that passes the
sensor. Set any value from 0.0001 to 99999.

The output may be disabled (Off) if not used.

VIEW menu
• During normal operation, the ProcessPro displays the VIEW menu.
• When using the CALIBRATE or OPTIONS menus, the ProcessPro will return to the VIEW menu if no activity
occurs for 10 minutes. Flow 6.25 GPM
Total 1234567.8>
• To select the item you want displayed, press the UP or DOWN arrow keys. The items will scroll in a Signet Flow
continuous loop. Changing the display selection does not interrupt system operations. Transmitter

• No key code is necessary to change display selection. ENTER

• Output settings cannot be edited from the VIEW menu.

View Menu
Display Description

0.0 GPM Monitor the flow rate and the resettable totalizer. Press the RIGHT ARROW key
to reset the totalizer. If the Reset is locked, you will need to enter the Key Code
Total: 12345678 > first. Lock or Unlock the totalizer in the OPTIONS menu. This is the permanent
View display.

All of the displays below are temporary. After ten minutes the display will return to the permanent display.
Perm: 12345678 Monitor the Permanent Totalizer value.

Gallons

Loop Output: Monitor the 4-20 mA Loop output.

12.00 mA

Last CAL: Monitor date for scheduled maintenance or date of last calibration. (See
description in Calibrate Menu.)
04-20-06

4 Signet 8550-1 Flow Transmitter


ProcessPro Editing Procedure:
Step 1. Press and hold ENTER key:
• 2 seconds to select the CALIBRATE menu
• 5 seconds to select the OPTIONS menu.
Step 2. The Key Code is UP-UP-UP-DOWN keys in sequence.
• After entering the Key Code, the display will show the first item in the selected menu.
Step 3. Scroll menu with UP or DOWN arrow keys.
Step 4. Press RIGHT ARROW key to select menu item to be edited.
• The first display element will begin flashing.
Step 5. Press UP or DOWN keys to edit the flashing element.
• RIGHT ARROW key advances the flashing element.
Step 6. Press ENTER key to save the new setting and return to Step 3.

Notes on Step 1: Notes on Step 2:


• The View Menu is normally displayed. If no key is pressed for 5 minutes while display is showing "Enter
• The CALIBRATE and OPTIONS menus require a KEY CODE. Key Code", the display will return to the VIEW menu.

CALIBRATE: ----
Press & Enter Key Code
ENTER
hold for
access: CALIBRATE: *---
Enter Key Code
CALIBRATE: **--
VIEW Enter Key Code
2s 5s CALIBRATE: ***-
CALIBRATE Enter Key Code

OPTIONS Flow Units: First item in CALI-


GPM > BRATE menu

Notes on Steps 3 and 4:


• Refer to pages 6 and 7 for complete listing of menu items and their use.
• From the Step 3 display, pressing the UP and DOWN keys simultaneously will
Flow Units:
GPM >
return the display to the VIEW menu.
• If no key is pressed for 10 minutes, display will also return to the VIEW menu.
Step 3

Step 3: Finished Editing? Output Setpnt:


Press the UP and DOWN keys simultaneously after Step 4
20.0 GPM >
saving the last setting to return to normal operation.

Notes on Steps 5 and 6:


Output Setpnt:
• All output functions remain active during editing. 20.00 GPM
• Only the flashing element can be edited.
Output Setpnt:
• RIGHT ARROW key advances the flashing element in a continuous loop. 10.00 GPM Step 5
• Edited value is effective immediately after pressing ENTER key.
• If no key is pressed for 10 minutes unit will restore the last saved value and return to step 3.
• Step 6 (pressing ENTER key) always returns you to Step 3. Output Setpnt:
• Repeat steps 3-6 until all editing is completed. 10.00 GPM

Output Setpnt:
Step 5: Made an Error? 9
1 .00 GPM
ENTER

Press the UP and DOWN keys simultaneously Step 6


while any element is flashing. This will recall the Output Setpnt:
last saved value of the item being edited and Saving
return you to Step 3. Output Setpnt:
19.00 GPM >

Signet 8550-1 Flow Transmitter 5


Calibrate Menu
Display
Description
(Factory settings shown)
Flow Units: The first three characters set the Flow Rate units of measure. They have no effect on
calculations. They may be any alpha or numeric character, upper or lower case.
GPM > The last character sets the Flow rate Timebase. Select S (seconds), M (minutes), H (hours)
or D (days).

Flow K-Factor: This setting tells the transmitter how to convert the input frequency from the flow sensor into
a flow rate. The K-factor is unique to the sensor model and to the pipe size and schedule.
60 > Refer to data in the sensor manual for the correct value. Limits: 0.0001 to 99999. (The
K-factor cannot be set to 0)

Total Units: This setting identifies the Totalizer units. It has no effect on any calculation. It serves as a
label only. Each character can be any alpha or numeric selection, upper or lower case.
Gallons >

Total K-Factor This setting tells the transmitter how to convert the input frequency from the flow sensor into
a volumetric total. It also is used as the basis for the Open Collector pulse mode.
60 > The setting is usually the same as the Flow K-factor, or different by x10 or x100. Limits:
0.0001 to 99999. (The K-factor cannot be set to 0)

Loop Range: GPM Select the minimum and maximum values for the 4-20 mA Current loop output. The 8550
will allow any values from 0.0000 to 99999.
000.00 → 100.00 >

Output Mode: Select the desired mode of operation for the Open Collector output. Options available are
High, Low, volumetric Pulse, or Frequency. The signal may be disabled (Off) if not used.
Low >

Output Setpnt: In Low or High Mode, the Open Collector output will be activated when the Flow rate
reaches this value. Be sure to modify this setting if you change the Flow Units.
10.0 GPM >

Output Hys: The Open Collector output will be deactivated at Setpoint ± Hysteresis, depending on High
or Low Setpoint selection. (See details on page 4.)
5.0 GPM >

Output Volume: In Pulse mode, the Open collector output will generate one pulse when this volume of flow
passes the sensor. The measurement is based on the Total K-factor. The 8550 will allow
100.00 Gallons > any value from 0.0001 to 99999.

Output PlsWdth: In Pulse mode, this setting defines the duration of the Open Collector output pulse. The
8550 allows any value from 0.1 seconds to 999.9 seconds.
0.1 Seconds >

Output Freq.: In Frequency mode, the Open Collector output will simulate the sensor frequency, divided
by this setting. Set for 1 (input frequency = output frequency). Set for even numbers
Divide by 1 > (2, 4, 6, 8 . . . 254 maximum) to scale output frequency.

Last CAL: Use this “note pad” to record important dates, such as annual recertification or scheduled
maintenance.
4-20-06

6 Signet 8550-1 Flow Transmitter


Options Menu
Display
Description
(Factory settings shown)
Contrast:
Adjust the LCD contrast for best viewing. A setting of 1 is lower contrast, 5 is higher.
3 > Select lower contrast if the display is in warmer ambient surroundings.

Flow Decimal
Set the decimal to the best resolution for your application. The display will automatically
scale up to this restriction.
*****. >
Select *****., ****.*, ***.**, **.*** or *.****

Total Decimal
Set the totalizer decimal to the best resolution for your application.
Select ********., *******.*, or ******.**
******.** >

Averaging:
OFF provides the quickest output response to changes in flow.
Longer averaging period produces more stable display and output response.
Off >
Select OFF, 8 s, 20 s, 50 s or 120 s.

Sensitivity
Sensitivity works in conjunction with Averaging to balance response time with signal
stability. Selections are 0 to 9. Select 0 (zero) for the minimum sensitivity, or 9 for the
0 > maximum sensitivity. The function is described below.

Total Reset: Lock Off : No key code required to reset the resettable totalizer.
Lock On : The Key Code must be entered to reset the resettable totalizer.
Lock Off >

Loop Adjust: Adjust the minimum and maximum current output. The display value represents the
precise current output.
4.00 mA > Adjustment limits:
• 3.80 mA < 4.00 mA > 5.00 mA
Loop Adjust: • 19.00 mA < 20.00 mA > 21.00 mA
Use this setting to match the system output to any external device.
20.00 mA >

Output Active: Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint.

Low > Active LOW: This setting is used to turn a device OFF at the setpoint.

Test Loop: Press UP or DOWN keys to manually order any output current value from 3.6 mA to
21.00 mA to test current loop output.
>

Test Output: Press UP or DOWN keys to manually toggle the state of open collector output.

>

No AVERAGING, no SENSITIVITY
With AVERAGING set to 0 (zero) and with SENSITIVITY set to zero,
the 8550 responds to every unstable shift in the flow. The dashed
red line represents the actual output of the flow sensor in unstable
flow conditions .

AVERAGING only
With AVERAGING set to 50 seconds and SENSITIVITY still set to
zero the flow rate is stabilized, but a sharp change in flow rate is not
represented for 50 seconds or longer. (dotted green line).

AVERAGING and SENSITIVITY


With AVERAGING at 50 seconds and SENSITIVITY set to 4 OR 5,
the flow rate is stabilized, while the sudden shift in flow is reflected 2s 10 s 20 s 30 s 40 s 50 s 60 s 70 s

very quickly. (Solid blue line)

NOTE: The SENSITIVITY function is ineffective if the AVERAGING function is set to zero (seconds).
Signet 8550-1 Flow Transmitter 7
Troubleshooting
Display Condition Possible Causes Suggested Solutions

“- - - - -” Flow rate exceeds display capability • Increase Flow units time base
• Move flow decimal one place to the right

“Pulse Overrun” • Open Collector pulse rate exceeds • Increase Pulse volume setting
maximum of 300 pulses per minute. • Decrease pulse width setting.
• Pulse width set too wide. • Reduce system flow rate

“Value must be more than 0” K-factors cannot be set to 0. Enter K-factor from 0.0001 to 99999

Open Collector is always • Hysteresis value too large • Change the hysteresis value
activated • Defective transmitter • Replace transmitter

Ordering Information

Mfr. Part No. Code Description


3-8550-1 159 000 047 Flow transmitter, Field mount
3-8550-1P 159 000 048 Flow transmitter, Panel mount
3-8550-2 159 000 049 Flow transmitter, Field mount with relays
3-8550-2P 159 000 050 Flow transmitter, Panel mount with relays
3-8550-3 159 000 051 Flow transmitter, Field mount with dual input/output
3-8550-3P 159 000 052 Flow transmitter, Panel mount with dual input/output

Accessories
Mfr. Part No. Code Description
3-8050 159 000 184 Universal mounting kit
3-8051 159 000 187 Flow Integral Mnt NPT
3-8050.395 159 000 186 Splashproof rear cover
3-8050.396 159 000 617 RC Filter kit (for relay use)
3-0000.596 159 000 641 Heavy duty wall mount bracket
3-5000.598 198 840 225 Surface Mount Bracket
3-5000.399 198 840 224 5 x 5 inch adapter plate for Signet retrofit
3-9000.392 159 000 368 Liquid tight connector kit for rear cover (includes 3 connectors)
3-9000.392-1 159 000 839 Liquid tight connector kit, NPT (1 piece)
3-9000.392-2 159 000 841 Liquid tight connector kit, PG13.5 (1 piece)
7300-7524 159 000 687 24 VDC Power Supply 7.5 Ω, 300mA
7300-1524 159 000 688 24 VDC Power Supply 15 Ω, 600mA
7300-3024 159 000 689 24 VDC Power Supply 30 Ω, 1.3 A
7300-5024 159 000 690 24 VDC Power Supply 50 Ω, 2.1 A
7300-1024 159 000 691 24 VDC Power Supply 100 Ω, 4.2 A

George Fischer Signet, Inc. 3401 Aerojet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057
For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090

3-8550.090-1 J 4/05 English © George Fischer Signet, Inc. 2002 Printed in U.S.A. on Recycled Paper