LX3V-2ADI-BD
1. Mounting instruction
Make sure to power off the PLC before mounting the LX3V-2ADI-BD module and removing the top
cover of PLC, screwed to the PLC.
Caution:
1) This BD module only support the following firmware versions or later. Users can check the PLC
firmware version in D8001.
LX3VP:25103;
LX3VE: 25201;
LX3V-A2:25014;
LX3V-A1: 22006;
2) When mounting module to PLC, all the lights are blinking after power ON PLC, it means this PLC
can’t support LX3V-2ADI-BD, please purchased new PLC.
3) Please fixed BD module on the PLC, poor contact may lead to failure.
4) BD module and top cover of PLC’s tightening torque is 0.3 ~ 0.6 N.m.
Warring:
Make sure to power off the PLC before mounting or removing the BD module and put the cover in
right place.
2. Special feature
1) LX3V-2ADI-BD module equips with 2 channels analog input. This module will be mounted in the
PLC.
2) The input current of LX3V-2ADI-BD module between 4 mA to 20mA, and the digital value will be
saved in special system address, but the numerical relationship between input and output value
cannot be changed.
Table 2-1 description of system address
Expansion port 1 (far away from PLC light)
Address Description
The flag of switching Input mode in CH1
M8112
OFF: Current input mode (4mA~20mA, 0~2000) ON: Retain
M8113 The flag of switching Input mode in CH2
3. Dimension
4. Specification
1) Please refer to the LX3V user manual for the general specification of LX3V-2ADI-BD;
2) LX3V-2ADI-BD is powered supply by LX3V main unit;
3) Performance
Table 4-1
Specification
Item
Current input
Input range DC 4-20mA (Input resistance:250Ω)
Digital output 12 bits binary
Resolution 8uA (4mA-20mA/2000)
Precision ±1% (4-20mA: ± 0.16mA)
AD conversion time One PLC scanning cycle
Characteristic
5. Wiring
Caution:
1) Do not put the LX3V-2ADI-BD module near high-voltage power cable. Keep away the power
cable at least 100mm;
2) Do not solder any terminal with the others device;
3) Do not connect any unsuitable cable;
4) Please fix cable;
5) Do not connect any unit to the unused terminal;
Table 5-1
Line type Cross sectional area(mm2) End-of-pipe treatment
AWG26 0.1288 Stranded cable: stripped jacket, rub
...... ...... Conductor, then connect the cable.
Single-core cable: stripped jacket,
AWG16 1.309
Then connect the cable.
5.2 Input
6. Example
The analog value (4~20mA) in each channel will be saved in system address (D8112, D8113). It will
be saved automatically when “END”, and convert into digital value.
AD conversion:
Caution:
1) There are extra program for multiplication and division, so the real accuracy and resolution of
analog-digital conversion are different from product specifications;
2) The range for analog output is constant;
3) Suppose the user needs 4000-20000, and save in D0, so D0=8*(D8112 or D8113) +4000, the
program as following shows.