The Protection of Electrical Transformers: July 2021
The Protection of Electrical Transformers: July 2021
The Protection of Electrical Transformers: July 2021
net/publication/353390547
CITATIONS READS
0 6,372
2 authors, including:
Karrar S. Faraj
Al-Ma'moon University College
156 PUBLICATIONS 43 CITATIONS
SEE PROFILE
All content following this page was uploaded by Karrar S. Faraj on 22 July 2021.
AC Machines Report
Figure (1)
Abstract:
Understand how to protect transformers from internal and external faults
and differential protection, how to use them to protect transformers, learn
about transformer protection from overloads, and learn information about
Bucholoz transformer protection device
Introduction:
The protection method for electrical transformers depends entirely on the
function and location of the transformer in the network as well as the rating
of the transformer. For example, distribution transformers with rated
minimum of 2.5 MVA are protected by fuses. As for transformers whose
rated power ranges from 2.5 MVA to 5MVA, they are protected using one of
the following two methods :
1. The high impedance differential protection and the type of relay used is
usually a gravitating case relay which has a high separation speed.
2. Harmonic Biased Differential Protection and the type of relay used is
most often an Induction Disc (Relay) relay.
-1-
Types of faults and their impact:
Design A suitable protection system for power transformers It is essential to be
familiar with most of the faults that the transformer is exposed to. Figure (2)
shows the types of errors expected to occur in the transformer, which are ...
1. an external (ground) shortness at the ends of the high voltage coils cables .
2. External shortness (between two sides) to the terminals of the high voltage coil
cables .
3. Internal (ground) shortness of a high voltage coil .
4. Internal shortness (between two sides) towards high voltage .
5. Short circuit between the windings of the high voltage coil .
6 . An external (ground) fault at the terminals of one of the Low voltage coil
cables.
7. An external short (between the two sides) to the terminals of the low-voltage
coil cables.
8. Internal (ground) short of one of the low voltage windings.
9. Internal shortness (between the two sides) of the low voltage windings.
10. An electrical short between the windings of the low voltage coil.
11. A land palace near the birthplace.
12. Shortening between two sides of the birthplace.
-2-
Differential protection:
The use of differential relays does not meet all the necessary conditions for
protection in the power system. We have observed that the separation time always
increases towards the source regardless of the gradient method used, and this in
turn may pose a threat to the generating stations as well as the switching stations
in addition to a direct effect on the grid balance. Therefore, unit protection or
differential protection is used to protect generators, transformers, motors, and
busbars.
Figures (3)
Differential and fault protection outside the protection zone
(the relay should not work)
-3-
Figures (4)
Differential and fault protection within the protection zone
(relay must work)
Figure (3) shows that the relay does not work if a fault occurs outside the
protected area because the current that passes through the relay equals zero and
this is what is required. But in fact, we find that the current through the relay in
this case is equal to the difference between the magnetising currents passing
through the CT, CT2. Even if we use absolutely similar current transformers in
terms of rated current, manufacturer and conversion ratio, we cannot guarantee
that they will have the same magnetizing currents. In other words, in practice
there will be a difference in the magnetic properties of the transformers. This
difference, no matter how slight, will lead to imbalance in the operation of the
relay, especially as a result of faults outside the protection area. In practice, this
problem is solved in one of the following two ways:
1. Use of high-impedance differential relays.
2. Use of bias differential relays.
-4-
1- Separate differential protection:
In this case, the primary and secondary windings are protected separately and
the principle of action of this protection can be understood through the single-
sided transformer. The differential protection theory is based on the balance
between the current entering and leaving the transformer windings. In this type
of protection, two transformers are used, with one relay in each side of the
primary and secondary. For the protection system to be balanced, the following
conditions must be met:
*** The relays used in the case of discrete transformer differential protection
are usually of the high impedance attracted case relays. The advantage of high
impedance is to ensure that the shielding devices will not work due to the
commonness of a current transformer due to an external fault.
• This protection system is affected by the internal faults of the ground and the
external faults between the facets and this is required.
-6-
Transformer protection against overload:
Transformer overload protection A load bypass relay is used. Figure (5) shows
how the conductive transformer delta / star is protected against current overflow
and against earth fault.
Figure (5)
Transformer protection against over current and earth fault
-7-
2. In the event of a severe fault inside the transformer (a shortness between the
coils or a shortness between the coils and the ground accompanied by a high
spark), the formation of gas bubbles will be very severe and in the form of a
fountain of gases causing the change of the position of the second float,
which closes the contacts connected to the main circuit breaker. In this case
the Buchholz relay acts as a backup protection for the differential protection
(the Buchholz relay is slower than the differential relay in action and faster
than the surge relay O / C relay). The good thing about this relay is that it is
also equipped with a valve that can open and take samples of the collected
gases for analysis. From analyzing the sample of dissolved gases in oil, it is
possible to know the quality of the gases in the oil, and thus it is possible to
diagnose the quality of the failure that the transformer has suffered and thus
isolate the transformer from the network manually if necessary before the
error becomes worse and this is called Preventive maintenance. The
dissolved gases inside the oil that result from faults inside the converter are
hydrogen gas H2, carbon monoxide CO, CH4, ethane C2H6, acetylene C2H2
and carbon dioxide CO2. These gases can be used as a diagnostic tool for
faults. For example, the presence of hydrogen gas and acetylene gas indicates
the presence of an electric arc inside the arcing oil between the metal parts.
The presence of gases such as CH2, C2H4, C2H6, CO2 indicates the
presence of hot spots inside the oil coils.
Figure (6)
-8-
Results of Report:
Learn about the ways to protect the transformers from internal and
external faults. And differential protection and how to use it to
protect the transformer and know the protection of the transformer
against overloads. Identify the Bucholoz device to protect the
transformer.
References
• ELECTRIC MACHINERY FUNDAMENTALS by Stephan J. Champan 4th edition
-9-