Solar Gas Compressor Wet Seal
Solar Gas Compressor Wet Seal
Solar Gas Compressor Wet Seal
NOTICE: Technical Letters are proprietary to Solar Turbines Incorporated, P.O. Box 85376, San Diego, CA 92186-5376.
The information in these Technical Letters shall not be used in any communication with a customer or third
parties. Only qualified Solar Personnel should attempt the described procedures. Personnel not trained to Solar
standards, or use of material not meeting Solar’s Engineering and Quality Control Standards may cause or result
in damage to the equipment or bodily injury.
NUMBER: 13.2/103
ISSUED: August 2000
REVISED:
PRODUCT: All
MODEL(S): All
Specifics:
Purpose:
Functional description of Wet Seal Systems and assistance in trouble shooting
GENERAL INFORMATION:
Solar standard wet seal systems underwent several evolutionary changes since the introduction of
the first Solar compressors. This Technical Letter summarizes and explains the changes introduced
in the last 20 years in a general way.
The Technical Letter discusses basic principals rather than specific hardware and should be used
together with Service Bulletin 13.2/109, which is still reasonably current.
The following changes in the seal oil/ buffer gas system were introduced after the release of
S.B.13.2/109 and were not discussed in that bulletin:
None of these changes alters the basic principal of the seal oil/ buffer gas system as described in
S.B.13.2/109.
Until the middle of the 1980’s, conventional wet seals were used exclusively. Since this time, an
increasing amount of new gas compressors are equipped with dry seals.
This Technical Letter is limited to wet seals and dry seals are not further discussed.
A gaseous medium ("buffer gas"; usually natural gas) is then used in a similar way to prevent the
migration of the seal oil into the compressor and to avoid any contact between seal oil and process
gas (process gas may be heavy or sour). Part of the seal oil and the buffer gas mix inside the capsule
and are then routed to an external device (trap) for separation and recycling.
Solar compressors use large seal oil and buffer gas flows when compared with products from other
manufacturers. Large seal oil flows increase the amount of oil exposed to buffer gas and more oil
must be cleaned in the degassing tank. However, large buffer gas and seal oil flows indicate large
seal clearances. Large clearances make a compressor less sensitive to contamination introduced
with the process gas. Solar compressors with wet seals are therefore often found in gas "gathering"
applications near a well head, where a marginal and changing process gas demands tolerance to
contamination of all kind.
For a full seal system write up and matching flow sketches see Service Bulletin 13.2/109; para.3.4.2.
See Technical Letter TL 10.0/103 and Product Information Letter (PIL) 140 for general information
regarding dry seals and information about cleaning of dry seals. Further information can also be
found in the "Failure Analysis" report STD129, "Gas Compressor Dry Gas Seal Contamination".
The report can be found on Solar’s Intranet Homepage under:
See the Operation and Maintenance Manuals for further information and recommendations for trou-
ble shooting of dry seal systems.
2) BALANCE PISTON:
2.1) Purpose
All radial compressor wheels produce axial thrust. This thrust can be taken up in a large thrust
bearing or can be compensated internally by stacking wheels back to back (often done in pumps).
Solar compressors utilize a balance piston for thrust compensation. A pressure differential across
a piston on the rotor counteracts the axial thrust produced by the compressor wheels. Discharge
pressure from the last compressor wheel acts on the inboard side of the balance piston. Some of this
gas leaks past the balance piston labyrinth seals into the balance piston outboard cavity. From this
cavity the leak-gas is routed back to the suction port via an external line (balance piston gas return
line). The balance piston gas return line must be large enough to accommodate the whole balance
piston leak gas flow with minimal losses. Due to the flow losses in the external balance piston gas
return line and the connectors, the pressure in the balance piston outboard cavity is slightly above
suction pressure (para. 2.3).
The lowered pressure in the balance piston outboard cavity not only produces axial thrust, but also
simplifies the seal system design. The high compressor discharge pressure is not seen by the seal
system. The process pressures acting upon the suction and the discharge capsules are nearly iden-
tical. A single seal oil regulator and a single buffer gas regulator can be used to supply the seals for
both capsules.
In most Solar compressors, the thrust bearing is installed in the suction capsule. Under normal
running condition and thrust direction, a Solar compressor therefore runs on its inboard thrust
bearing.
In Solar compressors with acceptable seal clearances (not necessarily new), the balance piston out-
board pressure is about 5 to 30 PSID above suction pressure. This pressure can be considerably
higher in compressors with high suction pressures and/or high-pressure ratios.
Small compressors in high ratio applications (e.g., the final C160 compressor in a tandem applica-
tion) are prone to high balance piston outboard cavity pressure. The large pressure drop across the
balance piston labyrinth seals produces high flow rates. This increased flow generates considerable
pressure losses in the return line due to the limited size of the capsule ports and the balance piston
gas return line.
A small pressure drop from the injected buffer gas pressure to suction pressure enforces a flow of
buffer gas past labyrinth seals into the compressor interior and prevents the escape of process gas.
The amount of buffer gas flowing into the compressor interior is minimized by carefully regulating
the buffer gas supply pressure to a value just above the process gas pressure.
To avoid potential control problems, Solar uses simple regulators set at a differential pressure of
15 to 20 PSID. The excess pressure is reduced in additional orifice(s) installed in series with the
labyrinth seals.
• In newer packages, the flow limiting orifice(s) are installed in the buffer gas return line
between the trap(s) and compressor suction. They elevate the trap and capsule drain
pressures to 6 to 12 PSID above suction pressure.
• Older Solar compressor packages use small hand valves (needle valves) or check valves as
flow limiting devices in the trap gas output line (check valves have a fixed pressure drop
regardless of flow).
Solar compressors with wet seals are relatively insensitive to buffer gas quality. Large oil seal
clearances require increased seal oil flows, but make the seal system insensitive to unfiltered or
marginally filtered buffer gas.
Figure 1 Throttling Type Buffer Gas System With "External" Gas Supply
The process gas is contained without the use of an external buffer gas supply. Internal compressor
leak-gas taken from the balance piston outboard cavity is used as buffer gas. This arrangement cuts
down on parasitic losses by eliminating the need of an external buffer gas source. Since process gas
is used as buffer gas and comes into direct contact with seal oil, the system can be used only on
compressors handling sweet process gas. See para. 3.6 for a full description of this system.
NOTE
When compressor discharge gas is used as buffer gas, the gas buffering
system does not work during turbine start up and during low speed op-
eration. The compressor by-pass valve is open during this time and the
compressor discharge pressure is low. Not enough discharge gas pressure
is available for complete buffering and some seal oil will find its way into the
interior of the compressor (oil consumption).
• The system is used if sour or untreated process gas mandates sweet gas buffering to avoid
the escape of any process gas and to avoid the contact between process gas and seal oil. For
full protection, the buffer gas regulator must be referenced to balance piston output pressure
(see 3.4.1).
• "Pressurized hold".
The auxiliary seal oil pump must operate if a customer wants to keep a compressor
pressurized after a package shut down. In most cases, the slow accumulation of seal oil
inside the compressor cannot be tolerated. The buffer gas system must remain operable
during this time. An external source of gas (e.g., from a common discharge header)
must be used as buffer gas to prevent the entry of seal oil into the compressor interior.
Unfortunately, most of the externally supplied buffer gas will enter the compressor interior,
slowly increasing the pressure in the isolated compressor and associated piping.
Equalize the pressure before a package re-start or keep the loading valve open during the
whole "pressurized hold" to "lock" the compressor pressure to suction pressure.
NOTE
Only a small part of the total balance piston leak flow passes under the
inboard buffer gas labyrinth seals from the balance piston outboard cavity
into the buffer gas cavity. Most of the balance piston leak gas still returns
from the balance piston outboard cavity directly to suction via the external
balance piston leak gas return line.
The highest process gas pressure seen by either the suction or the discharge capsule seals is in the
balance piston outboard cavity (balance piston backpressure). To avoid the escape of process gas,
the buffer gas regulator is referenced to this balance piston outboard cavity. This guarantees that the
All Solar gas compressors built since about 1980 are equipped with a static balance piston out-
board cavity pressure sensing port to allow balance piston backpressure sensing (1/8" NPT tap on
discharge side of compressor).
Balance piston backpressure sensing is especially effective when combined with a true external
buffer gas system and an external sweet gas supply (see 3.3.2). The system guarantees, that sweet
gas is forced into the compressor at all times and the contact of wet, heavy or sour process gas with
seal oil (or the escape of this gas into the atmosphere) is prevented. As long as the required buffer
gas pressure does not exceed the limits of the sweet gas source, the arrangement reliably prevents
any contact between seal oil and process gas and the escape of process gas into the atmosphere.
Disadvantage:
High compressor ratios or worn balance piston seals increase the balance piston outboard cavity
pressure and raise the buffer gas regulator reference pressure. The regulated buffer gas pressure
raises to remain above reference pressure. This increases the differential pressure between buffer
gas and suction pressure and therefore increases the buffer gas flow. At a certain flow rate through
the outboard labyrinth seals, the "seal mix out" lines and the trap(s), the trap(s) cease to separate
the seal oil from the gas and the compressor starts using oil (see 8.1).
When the process gas is of pipeline quality, buffer gas is normally supplied directly from the com-
pressor discharge (para 3.3.1). Buffer gas and process gas are identical and it is not mandatory that
the buffer gas pressure remains above the process gas pressure under all circumstances. The buffer
gas regulator can safely be referenced to suction pressure.
Operation:
The buffer gas regulator output pressure is controlled to 20 PSI above suction pressure regardless of
the pressure in the balance piston outboard cavity. When the pressure in the balance piston outboard
cavity increases (high pressure ratio, labyrinth seal wear), the buffer gas pressure regulator does not
sense the change and the buffer gas pressure supplied by the regulator does not increase. Buffer
gas flow does not increase and the gas / oil separation in the trap(s) is not affected.
Depending on balance piston outboard cavity pressure, the system may operate in any one of four
different modes:
If compensation of the balance piston outboard cavity pressure is important (3.4.1), the external
balance piston gas return line can be used as reference for the buffer gas regulator. The sensing
tap should be as near as possible to the balance piston gas exit port (compressor discharge side)
to compensate for the pressure losses in the external gas return line. Obviously, the system cannot
compensate for port and line losses inside the discharge capsule.
The system can only be used with compressors handling pipeline quality gas due to the use of
balance piston leak gas as buffer gas. See para. 3.5.2 for a description of the different seal gas flow
paths inside the capsule.
• Throttling type buffer gas dP regulator with suction pressure sensing and worn balance
piston labyrinth seals. The balance piston outboard pressure is above the setting of the
buffer gas pressure regulator (3.4.2; modes 3 and 4).
• Old buffer gas systems without external gas supply (3.6). The external buffer gas line is just
a simple connection between suction and discharge capsule buffer gas cavities.
3.6.1) OPERATION:
A bypassing type differential pressure regulator ("Rivett" valve) is installed in the external balance
piston gas return line. The regulator has no external sensing line. The "Rivett" valve increases the
pressure drop in the gas return line by an additional 15 - 20 PSID and elevates the pressure in the
balance piston outboard cavity by the same amount. The elevated balance piston outboard pressure
becomes the source of buffer gas and enforces a flow of balance piston leak gas through the buffer
gas system. The system works in exactly the same way as described under para 3.4.2; Mode 4.
3.6.2) ADVANTAGE:
The bypassing type buffer gas system with internal gas supply is well suited for smaller compressors
with relatively low flows and/or power. Parasitic losses are minimized since no external buffer gas
supply is required. The system is found mainly on older, smaller compressors driven by Saturn or
Centaur turbines.
3.6.3) DISADVANTAGE:
The system is only suitable for smaller compressors handling clean process gas due to the following
limitations:
Service Bulletin 13.2/109 recommends a change to an external buffer gas system, if seal oil con-
sumption cannot be controlled in a package with the old type system. For best results, two seal oil
traps should be used.
Two carbon seal rings are installed into each capsule as oil seals. The rings are located on the com-
pressor rotor outboard of the buffer gas labyrinth seals. Seal oil at a pressure above the highest
gas pressure seen inside the capsules is supplied by external pump(s) and is injected into the space
between the carbon rings.
• Seal oil leaking underneath the outboard carbon seal ring towards the bearing and the
compressor exterior enters an atmospheric drain where it mixes with lube oil coming from
A differential pressure regulator with an external reference pressure sensing line maintains the seal
oil pressure at a level slightly above reference pressure. To prevent the collection of seal oil or other
liquids in the regulator or the sensing line, the regulator should be installed above the pressure sens-
ing port and the sensing line should have a continuous downwards slope away from the regulator.
Different seal oil regulator reference pressures can be found on Solar compressors.
The seal mix drain cavities are the ideal reference point for the seal oil pressure regulator, but are
not directly accessible. However, the trap(s) are directly connected to those cavities and the pressure
differential between the two is minimal. The trap(s) are therefore used as seal oil pressure regulator
reference point on all Solar compressor packages built in the last 15 years.
• Newer packages use the buffer gas return line after the seal oil trap (trap gas out line before
the throttling orifice) as reference point for the seal oil regulator. The oil / gas mixture has
been stripped (separated) at this point and the reference gas is free of oil, preventing sensing
line contamination.
If two traps are used, the trap serving the discharge capsule has normally a slightly
higher pressure and is the preferred reference point. All newer compressor packages use a
pneumatic "high pressure selector" (shuttle valve) in the seal oil regulator sensing line and
automatically select the higher of the two trap pressures as reference point.
• Service Bulletin 13.2/109 handles packages with one trap only. It recommends the use
of trap input pressure as seal oil regulator reference point. Though basically correct, this
recommendation must be used carefully.
Seal oil regulator instability may be experienced if the regulator sensing line fills with oil.
The sensing line should branch off from the trap input line in an upward direction and
should avoid low points. Figure 21 in Service Bulletin 13.2/109 is a bad example.
Any increasing pressure in the balance piston outboard cavity will increase the buffer gas pressure.
The increasing buffer gas pressure in turn will elevate the trap and seal-mix-out-cavity pressures.
The elevated seal-mix-out-cavity pressure might eventually exceed the seal oil pressure (which re-
mains fixed to suction pressure in this system), blowing gas through the oil seals and into the lube
oil drain system.
Service Bulletin 13.2/109 from September 1982 urges all users with this type of equipment to
modify the system to trap pressure sensing. See Service Bulletin 13.2/109 for further descriptions,
modification procedures and pressure settings before and after the modification.
5.1) General
Seal oil and buffer gas leaving the capsules as a mixture is separated again in the external seal oil
trap(s). The velocity of the incoming oil/gas mixture (mostly gas when measured by volume) is
lowered inside the trap(s) to such an extent (large volume and cross section), that the tiny liquid oil
droplets cannot stay in suspension any longer and fall out.
Additionally, the seal oil/buffer gas mixture is separated inside the trap(s) by centrifugal action,
as the incoming oil/gas mix is deflected into a tangential flow path around the interior wall of the
trap. The heavier oil particles are thrown against the wall by centrifugal force and cannot reach the
buffer gas exit at the top center of the trap (small, new style trap).
• The stripped buffer gas returns to the compressor suction line via a gas flow limiting orifice
and joins the process gas stream.
• The separated seal oil collects at the bottom of the trap and is periodically drained to the
degassing flue / tank by a float mechanism.
Most of the oil droplets carried by the returning gas are so fine, that they cannot be seen in the sight
glass(es) installed in the trap gas return line(s).
Experience indicates, that the intended effect is minimal. The filter/coalescer assembly requires
frequent maintenance, increases the risk of filter blockage (dirty gas) and can be removed from
most traps without noticeable increase in oil consumption. A blocked filter element inside the trap
can actually increase oil consumption, as it increases the pressure drop across the trap and restricts
the outboard buffer gas flow.
Reduced buffer gas flow inside the capsules might allow seal oil to find its way across the buffer
gas labyrinth seals into the compressor interior.
The float valve must be able to drain the seal oil trap under all existing pressure conditions. Different
drain orifice sizes are used to cover the whole suction pressure range of Solar compressors:
• Packages with high suction pressures produce large differential pressures across the trap
drain orifice. The drain orifice is kept relatively small (3/32" dia.) to ensure, that the limited
upward force of the float (buoyancy) can open the valve at all pressures.
Trap drainage (when the float valve opens) is no problem as long as the compressor is
pressurized. The high differential pressure forces the accumulated seal oil through the orifice
into the degassing tank. The trap might not drain properly if the auxiliary seal oil pump
operates whilst the compressor is de-pressurized. Even if the float valve opens, process gas
pressure is missing to drive the accumulated seal oil through the relatively small drain orifice
into the degassing tank. It is likely that the trap remains flooded, spilling seal oil into the
compressor interior.
• Lower suction pressures (900 PSI max.) mean lower differential pressures across the trap
drain orifice. The drain orifice is larger (3/16" diameter) to ensure, that all the accumulated
seal oil drains through the orifice. The buoyancy of the float is sufficient to open the drain
valve under all conditions, since differential pressures remain relatively low.
The oil remaining inside the trap acts as a seal and prevents the escape of process gas into the de-
gassing tank. When removed from the trap, a correctly adjusted float valve pushes the drain valve
plug (small sphere) into its seat (drain orifice) whilst both lever arms rest horizontally without
touching each other or the base-plate.
Some Solar packages with two traps per compressor use the discharge trap pressure as reference
point for the seal oil regulator. In most applications, a shuttle valve automatically selects the trap
with the higher pressure as reference point (see also 4.1).
6) OVERHEAD TANK:
Some customers rely on an overhead tank to guarantee a seal oil flow to the compressor during
emergency shutdowns. Before a gas compressor can be pressurized, the overhead tank must be
filled with seal oil (identical to lube oil in most of Solar’s applications). The overhead tank must
contain enough seal oil to allow a safe compressor depressurization without the help of an auxiliary
seal oil pump.
During normal package operation, the overhead tank is nearly full with seal oil. Only a small volume
of gas remains inside the tank at the top. Since the seal oil pressure and therefore the overhead
tank pressure must track the gas compressor suction pressure; the small volume of gas inside the
overhead tank is connected to the compressor discharge trap (reference point). In this way, the
overhead tank follows all suction pressure changes.
As explained in chapter 4.1) the seal oil trap(s) are the logical reference point for a seal oil system
in a wet seal system. Consequently, the discharge trap pressure is used as reference point for the
pressure in the overhead tank.
A float valve in the overhead tank keeps the oil level (and therefore also the volume of the residual
gas pocket) constant. A gas line from the reference point (discharge trap gas return line before
the orifice) to the top of the overhead tank ties the tank pressure to reference pressure and allows
process gas to enter and exit the overhead tank.
In the overhead tank, process gas comes into direct contact with seal oil. Overhead tanks are there-
fore only acceptable in compressor applications with clean and dry process gas (pipeline applica-
tions).
Gas is a compressible medium. Since the oil level and the volume of the gas pocket in the overhead
tank remain constant, gas must flow in and out of the overhead tank during suction pressure changes
to compensate for the changes in gas density. The residual gas volume in the overhead tank is kept
small and the interconnecting gas line is relatively large to increase the system response time.
• During all suction pressure increases (e.g., compressor pressurization), the volume of
the residual gas pocket in the overhead tank tends to decrease. The seal oil pump cannot
instantly replace this lost gas volume with oil from the lube oil tank. A large check valve
allows process gas (coming from the reference point) to enter the overhead tank and
rapidly replenish the shrinking gas volume. As a result, the overhead tank pressure follows
the compressor reference pressure and the oil level remains practically constant.
• During slowly decreasing suction pressures, the gas in the overhead tank expands slightly
and lowers the seal oil level. The float valve opens and let some gas escape through its
output orifice to the reference point and back to compressor suction.
• During rapid gas compressor depressurizations (e.g., a package trip), the gas in the overhead
tank cannot escape fast enough through the float valve orifice. The tank pressure temporarily
exceeds the reference pressure. The seal oil differential pressure and therefore the seal oil
flow increase during this critical period of rapid compressor decompression, preventing any
escape of gas. During this time, the buffer gas system is unstable and some seal oil might
enter the compressor interior. However, preventing oil consumption is clearly of secondary
importance during this critical time.
• When filling the overhead tank with oil during start up, gas will exit the overhead tank
and will flow back to the reference point through the float valve orifice. Once the tank is
Seal oil and buffer gas meet under high pressure in the "seal-mix-drain" cavity of the capsule. At
high pressures, the seal oil absorbs some of the buffer gas. Lighter components of the absorbed gas
flash out of the oil during de-pressurization in the exit of the seal oil trap.
In the degassing flue, this "flash-gas" has time to separate from the oil, coalesce and rise to the sur-
face. To remove the gasses, the degassing flue requires an atmospheric vent piped to a safe location
or to a common flare. A "flame arrestor" must be installed into this vent line not more than 15 feet
from the end of the line.
Light, sweet "pipeline-quality" gas (mainly Methane) separates readily from the seal oil even in a
simple degassing flue. If heavier hydrocarbon components are present in the buffer gas (wet, heavy
wellhead gas), a simple degassing flue or tank is not sufficient to remove those components from
the oil. The heavy components must to be driven out of the seal oil in the degassing tank by heat,
vacuum, agitation or sparging:
• Heating the degassing tank is the easiest way to drive heavier gasses out of the seal oil.
Unfortunately, a considerable amount of additional hardware (heater, temperature and level
switches etc.) together with the necessary controls is required to heat the oil in a safe way
and to avoid the danger of exposing the heating elements to the air-gas mixture above the
oil level.
• Vacuum chambers are very effective in driving residual gases out of the seal oil. True
vacuum chambers are not used by Solar due to their complexity and due to the relatively
large amount of oil to be cleaned. However, simple extraction fans are often installed into
the degassing tank vent line to lower the tank pressure.
• Agitation is not normally used by Solar.
• If required, sparging is used in combination with a degassing tank heater and extraction fan
and is very effective. Finely dispersed air or light sweet gas "bubbles" are injected into the
oil at the bottom of the degassing tank. During their slow rise through the hot seal oil, the
air or sweet gas bubbles drive the heavier gases out of solution and coalesce with them into
larger "bubbles", which rise to the surface and burst.
Gas released from the oil tank after the engine is shut down might accumulate in poorly vented
areas of the tank and might increase the gas concentration in the tank above a safe level. A maximum
concentration of 25 to 40% LEL (Lower Explosive Limit) is normally considered safe. The gas
concentration in the tank will increase if the compressor is pressurized without turbine operation
(package start up or pressurized hold) or if a heavy gas is used as buffer gas.
Centaur compressor set packages built between 1974 and 1982 without a degassing tank or flue are
most prone to high gas levels in the lube oil tank. Lube oil tank purge kits and/or degassing tanks
and flues are available as retrofit kits if problems are encountered with this design.
High gas concentrations in the lube oil tank during package start up are not always coming from
the compressor. Pneumatic starters operating on gas may leak gas into the accessory drive box and
into the tank. Inspect / replace the starter output shaft seals.
Older packages with seal oil consoles use a 1/4" needle valve in the trap gas out line to limit the
buffer gas flow instead of a fixed orifice.
• An elevated balance piston outboard pressure in a gas compressor (due to balance piston
labyrinth seal wear or a small, restricting balance piston gas return line) not only increases
the internal gas recirculation and decreases the compressor efficiency, but also elevates
the reference pressure used by the buffer dP regulator. As a result, the buffer gas regulator
increases its output pressure in order to maintain a fixed pressure above this reference
pressure (increased buffer gas supply pressure).
• The increased buffer gas supply pressure increases the dP and flow across the inboard
labyrinth seal in the suction capsule, wasting buffer gas. (The pressure drop and flow across
the inboard seal of the discharge capsule is kept constant by the buffer gas dP regulator.)
• The buffer gas flow across the outboard labyrinth seals increases, raising the gas velocity
in the labyrinth seals, the seal mix out lines and in the seal oil trap(s).
• The flow increase in the seal oil trap(s) prevents the complete separation of the seal oil/buffer
gas mixture. Oil is carried back to compressor suction with the returning buffer gas.
• To correct the root problem, the balance piston outboard cavity pressure (backpressure)
must be lowered by replacing the balance piston seal or by increasing the balance piston gas
return line. As a short-term fix, the increased oil consumption can probably be corrected by
decreasing the size of the orifice in the trap output.
Normally, less than one Gallon of oil is lost during a package start up. The actual oil consumption
depends on the length of operation without the minimum discharge pressure necessary to generate
sufficient buffer gas flow.
The trap input pressure and the pressure in the seal mix out cavities are elevated to such a point, that
the gas flow across the outboard buffer gas labyrinth seals drops below a minimum value or stops
completely. Seal oil can migrate against the normal gas flow path into the compressor interior.
Increase the trap output orifice size and/or completely remove the coalescer and filter element in
the tall, old style trap.
At risk are compressors with by-passing type buffer gas systems or throttling type regulators with
suction reference, single traps and high balance piston outboard pressures. Process gas leaks from
the balance piston outboard cavity into the discharge capsule, increasing the buffer gas pressure in
this capsule. The throttling type buffer gas regulator (if existing) is fully closed and the buffer gas
flow to the suction capsule comes from the discharge capsule instead of the buffer gas regulator
(3.4.2, operating Mode 4).
Due to line losses in the connectors and the interconnecting buffer gas line, the buffer gas pressure
in the suction capsule can be considerably lower than the pressure in the discharge capsule.
The orifice in the "trap gas out" line may restrict the gas flow through the trap to such an extent,
that the trap pressure exceeds the buffer gas pressure in the suction capsule (the discharge capsule
is still fed from the balance piston outboard cavity). This prevents the drainage of the suction "seal
mix out" cavity and forces seal oil into the compressor interior.
The flow in the "seal mix out" line from the suction capsule to the "tee" upstream of the trap re-
verses. Part of the oil/gas mixture flowing from the discharge capsule to the trap bypasses the trap
and flows from the "tee" directly to the suction capsule and into the compressor interior.
Increasing the buffer gas pressure to correct the oil consumption problem will only worsen the
situation in this case, since even more gas is flowing through the eductor, increasing its effect.
Before proceeding further, all equipment and instrumentation must be properly maintained and in
fully operational condition (compressor labyrinth and carbon seals, differential pressure regulators,
flow regulators, seal oil trap(s), gauges and transmitters etc.). See the Operation and Maintenance
Instructions for information regarding the service of individual components.
If a gas compressor with wet seals still uses oil after servicing the individual components, the basic
principals discussed in previous chapters must be applied. Eliminating compressor oil consumption
always means restoring the correct flows and directions of flow in the different buffer gas and seal
oil paths.
Monitoring the static pressure in the balance piston outboard cavity gives valuable information
about the health of the labyrinth seals. The pressure is typically about 5 to 30 PSID above suction
pressure, but can climb considerably higher on gas compressors with worn balance piston seals
and/or high suction pressures or pressure ratios. Service Bulletin 13.2/106B limits the balance pis-
ton outboard cavity pressure to 50 PSID (C28 = 30 PSID only) in order to protect the thrust bear-
ing. Certain high ratio/low flow machines (e.g., some C160 compressors) can run successfully with
All newer Solar compressors are equipped with a static balance piston pressure sensing tap, even
when the connection is not used as buffer gas pressure reference point. Any seal oil system trouble
shooting should begin by measuring this pressure as a differential pressure to suction. The same
gauge can afterwards be used to measure the differential pressure between trap(s) and suction (nor-
mally around 6 to 12 PSID). Based on these measurements, the operation of the seal oil/buffer gas
system can be evaluated and, if required, correcting action initiated.
• Please observe, that packages with the seal oil dP regulator referenced to trap pressure are
allowed to operate with lower seal oil regulator dP settings compared to packages with
suction pressure reference (e.g., 12 PSID instead of 20 PSID, if the alarm and shut down
switches permit).
• A throttling type buffer gas dP regulator should be set to about 20 PSID, if suction pressure
referencing is used. Is the regulator referenced to balance piston outboard pressure, a
differential pressure setting of 15 PSID is sufficient.
There is no mandatory relationship between buffer gas differential pressure and seal oil differential
pressure. It cannot be generally stated that the buffer gas dP must be higher than the seal oil dP (or
vice versa).
To solve a chronic seal oil consumption problem, the reference point for a throttling type buffer gas
regulator may be moved from balance piston outboard pressure (see 3.4.1) to suction pressure (see
3.4.2). The regulator setpoint has to be increased from 15 PSID to about 20 PSID if referenced to
suction pressure.
This modification lowers the buffer gas supply pressure by lowering the reference point. A lower
supply pressure lowers the gas flow (and velocity) across the buffer gas system labyrinth seals and
the trap(s), increasing the chances for proper separation of the gas/oil mixture in the trap.
After re-referencing, all or part of the buffer gas might be supplied by internal leak gas (process
gas) rather then by the external regulator. The modification can therefore only be considered on
compressors using discharge gas as buffer gas or when the process gas is sweet, light, clean and
dry.
The modification works best on high ratio machines or on compressors with an elevated pressure in
the balance piston outboard cavity. Due to the new reference point, the buffer gas supply pressure
is fixed to 20 PSID above suction pressure and is not affected, when the balance piston outboard
pressure increases.
NOTE
Increased balance piston outboard cavity pressure always indicates re-
duced compressor efficiency. Increased balance piston back-pressure also
affects the thrust load. After first decreasing, the thrust load reverses and
starts to load the normally unloaded axial bearing.
The main goal is always to enforce the correct flow of seal oil and buffer gas under all circumstances
and to improve the seal oil/ buffer gas separation in the trap.