Conrad and Rossanley Control Station Upgrade

CIP #63-09 (336)


Addendum #2

Item No. Specification Location and Description of Change

1. Volume II Section 01 11 00 SUMMARY OF WORK:


Technical
Specifications Remove: three 500 hp horizontal split case pumps

Add: one (1) 500 hp horizontal split case pumps


2. Volume II Section 26 24 19 LOW-VOLTAGE MOTOR CONTROL, 2.04.F.6
Technical
Specifications Add: 6. Ground Fault Protection:
a. Suitable for 480-volt, three-phase, three-wire,
solidly grounded wye system.
b. Ground sensors to encircle phase conductors
and neutral conductor where used, and
connected to ground relays with adjustable
pickup settings and time-current characteristics
indicated.
c. Circuit breaker shunt trip and relay operating
from fused 120-volt ac control source within
control center.
d. Manufacturers and Products:
1) Cutler-Hammer; GFR.
2) General Electric; GFM.

3. Volume II Section 40 80 01 PROCESS PIPING LEAKAGE TESTING


Technical 3.01.b.3.b; at end of paragraph ad the following line
Specifications
Add: This may include visual inspection of the joint for
leakage under normal system operating pressure during
startup.

4. Volume II Section 44 42 56.02 – SUPPLEMENT – 1, PERFORMANCE


Technical REQUIREMENTS; Maximum Shutoff Pressure (Ft):
Specifications
Remove: 335

Replace with: 361


5. Volume II Section 44 42 56.02 – SUPPLEMENT – 2, PERFORMANCE
Technical REQUIREMENTS; Max. NPSH Required at Rated Capacity (Ft.
Specifications Absolute):

Remove: 19

Replace with: 28.1

1
Conrad and Rossanley Control Station Upgrade
CIP #63-09 (336)
Addendum #2

Item No. Specification Location and Description of Change

6. Volume II Section 44 42 56.02 – SUPPLEMENT – 3, PERFORMANCE


Technical REQUIREMENTS; DRIVE MOTOR
Specifications
Remove: Motor nameplate horsepower shall not be
exceeded at any head-capacity point on pump curve.

Replace with: The pump maximum power shall not exceed


510 horsepower at any head-capacity on the pump curve.
7. Volume III
DWG 503-D-2001 Replace with new sheet 13, Rev. Addendum #2
Sheet 13
8. Volume III
DWG 503-D-3001 Replace with new sheet 14, Rev. Addendum #2
Sheet 14
9. Volume III
DWG 503-M-2001 Replace with new sheet 15, Rev. Addendum #2
Sheet 15
10. Volume III
DWG 503-M-3001 Replace with new sheet 16, Rev. Addendum #2
Sheet 16
11. Volume III
DWG 505-M-2001 Replace with new sheet 24, Rev. Addendum #2
Sheet 24
12. Volume III Detail 4091-305B:
DWG 999-N-5001
Sheet 33 Remove: ½” V-307 and ½” SST PIPE

Add: ½” V-300 and 1/2" COPPER PIPE


13. Volume III Detail 4022-005:
DWG 999-S-5001
Sheet 34 Remove: 3’-0” x 3’-0” MAX OPENING

Replace with: 3’-6” x 3’-6” MAX OPENING

2
Conrad and Rossanley Control Station Upgrade
CIP #63-09 (336)
Addendum #2

Item No. Specification Location and Description of Change

14. Volume III Add new design details: 0330-061, 1 OF 2 PIPE


Standard Details Refer to supplemental detail SUPPORT – CONCRETE
packet SADDLE
0330-061, 2 OF 2 PIPE
SUPPORT – CONCRETE
SADDLE
0330-105 ADHESIVE
DOWEL
0330-143 CONCRETE
DEMOLITION
4005-500 PIPE SUPPORT
4005-518 BASE BEND