TRANSFOPOWER INDUSTRIES (PVT) LTD.

R&D DEPARTMENT
TECHNICAL DATA SHEET OF TRANSFORMER
Date: July27,
Nov 1, 2023
2019

Customer Chashma,AsMianwali
Standard Transformer Per IEC Ref # : TP-I-19-20-005
SPECIFICATION
Rated kVA 400 Basic Insulation Level LV LI 0 AC 3
Voltage Ratio 11000 D / 415 Y V (BIL) HV LI 75 AC 28
Frequency / Phases 50 Hz / 3 f + 2.5
Tapping Voltages (%)
Vector Group Dyn 11 - 2.5,5.0,7.5
Type of Cooling ONAN HV Terminals 3
Insulation Class A LV Terminals 4
Ambient Temperature 50 0C Service Altitude Above Sea Level 1000 meter
Top Oil 50 0C Type of Tank Conservator
Temperature Rise at Rated kVA
Winding Average 55 0C Type Indoor /Outdoor

PERFORMANCE
No Load Losses at Principle Tap Position 0.850 kW
Load Losses at Principle Tap Position & Rated Current 7.80 kW
Impedance 4.00 %
Regulation at Unity Power Factor & Rated Current 2.01 %
Regulation at 0.8 Power Factor & Rated Current 3.67 %
Efficiency at Unity Power Factor & 100% Rated Current 97.88 %
Efficiency at Unity Power Factor & 50% Rated Current 98.62 %

COMPONENTS & ACCESSORIES


Off Circuit Tap Changer Pressure Relief Valve (without contacts) (Elmek, Turkey)
Oil Filling Hole and Plug Oil Thermometer (without contacts) (Elmek, Turkey)
Oil Level Indicator Double Float Buchholz Relay (Elmek, Turkey)
Oil Drain Valve
Oil Conservator
Silicagel Breather
Cooling Tubes
Lifting Lugs
Transport Eyes
Earthing Terminals
Bi Directional Roller Wheels
Rating & Diagram Plate (Stainless Steel)
Remarks :
1) Transformer shall be offered with first filling of oil. Transformer Oil shall be in accordance with IEC-60296
2) Transformer shall be manufactured and tested as per IEC 600-76 Standard.

Total Mass of Oil = 845 kg (Approx.)


Total Mass of Transformer = 3560 kg (Approx.)