GENERAL NOTES

1. Residential and commercial meter loops are typically used when constructing facilities for permanent service.
All guidelines outlined in this document shall be followed by your contractor or electrician. PEC shall provide
and install a service wire drop to the member's meter loop.

2. The member shall be in compliance with the National Electrical Code (NEC) and all applicable codes and
ordinances as legally required by any local authorities having jurisdiction. PEC is in compliance with the
National Electrical Safety Code (NESC).

3. For your protection, PEC urges you or your electrician to use only NEC-approved procedures and materials.
All meter loops must be sized according to the load to be served and NEC guidelines.

4. PEC will refuse service where a known hazardous condition exists and/or if connections do not meet the
specifications outlined in this document. PEC urges the member to use a qualified electrician to prevent safety
hazards, additional costs, and delays. PEC requires that all construction meet or exceed these specifications
prior to service connection. While PEC makes all reasonable efforts to ensure good electrical practice on the
member's side, the Cooperative is not responsible for validating additional criteria that may be applicable to
the member's premises beyond the scope of this document.

5. The member will be responsible for providing, installing, replacement, and repair of the meter loop, including
the meter socket, panels, conduit, underground cable, poles, racks, weatherhead, etc. The member shall own
the meter rack and shall be solely responsible for the related construction, installation, and maintenance of all
electrical and structural components. Splicing is not permitted within meter sockets. The underground cable
used shall be an approved type for underground installation (USE type or UF type). Conductor size will be
based on member load, location of meter socket, and NEC for size of conduit. No member-owned facilities
shall be mounted on PEC-owned poles.

6. Member-owned poles shall be installed a minimum of 10' and a maximum of 40' from transformer. Never install
member-owned poles and/or PEC poles under overhead electric lines. Weatherhead shall not extend above
pole top. Steel poles must be capped to prevent water ingress and may be more than one piece if the final
product is appropriately coupled and meets all other requirements. Pole shall be buried 10% of pole height +
2', be of sufficient height above grade to meet NESC clearances (NESC Table 232-1), and meet the following
criteria:
5" minimum diameter, at the narrowest point, for creosote-treated or commercially pressure-treated
wood poles.
4.5" outside diameter and minimum 0.237" thickness for round steel poles.
4" square and minimum 0.25" thickness for square steel poles.

7. Clearances from ground level to service attachment point shall follow the requirements
of NESC Table 232-1 and associated footnotes and NESC Rule 234C3d for residential
decks. Clearances from ground level to service attachment shall be a minimum of
16' for service to a non-residential building or for residential services crossing potential
traffic exceeding 8' in height. 12' clearance is permissible for a residential driveway
accessible to pedestrians and for horseback riders less than 8' in height. 10' clearance
is permitted for areas only accessible to pedestrians. This is to include all pole-mounted
services and weatherheads mounted to the side of a structure and above
the roof line of a structure.
09/08/2023
(USE TYPE OR UF TYPE) WAS (USE OR UF TYPE),
REV D DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
MATCH 320A NOTES, RE-WORDED NOTE 7

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 1 OF 13
GENERAL NOTES
CONTINUED

8. Neutral conductor must be electrically continuous through the meter socket to the main panel and must be
attached to the meter socket. Electric contractor has the option of terminating the neutral at the meter socket
lug. Main panels will be terminated at the meter socket lugs. Neutral conductor size shall meet or exceed
NEC or local ordinance requirements. It is the responsibility of the member or their electrician to make this
determination.

9. A 200-amp meter loop is rated for breaker(s) less than or equal to 225 amps. For information on higher
amperages, refer to the 320-Amp Meter Loop Specifications.

10. The exterior of the service area shall have a weatherproof main disconnect panel fused or breaker-protected
regardless of the number of branch circuit breakers.

11. Ground cables shall be #6 copper minimum or larger per NEC Table 250.66. Ground rods shall be 5/8" x 8'
copper-clad with clamp and driven at or below grade per NEC. Service areas not bound by permits or codes
are required to install a 5/8" x 8' copper-clad ground rod. If the electric service is installed under an electrical
permit, other grounding methods may be used in accordance with NEC.

12. Bypass levers shall be equipped on all single-phase meter installations 320 amps and above, and on all
three-phase meter installations regardless of amperage.

13. For commercial/industrial/multi-family residential underground services where the meter or a bank of meters is
to be located on the building or adjacent to the load, the service (cable, conduit, and trench) from the
transformer to the load will be provided by the member/developer.

14. Members and/or contractors will have a 30-day grace period to become fully compliant when new PEC
specifications are posted. Any project started prior to the release of new specifications can be completed using
the previous specifications.

15. Please contact your PEC district office at 1-888-554-4732 prior to construction.

09/08/2023

REV E DATE 09/08/2023 REVISION REMOVED WIRE GUIDELINE CHART, MATCH 320A NOTES BY RWC CHK SSS APR MMG

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 2 OF 13
INSTALLATION NOTES
ORIENTATION:
The meter loop shall be mounted on the side of the pedestal facing the member's lot.
Weatherproof fused or breaker-protected main disconnect panel will have a main disconnect on
the outside of the building regardless of the number of circuit breakers.
RACK:
1. Racks built off of existing meter pedestals shall be self-supporting with a minimum of 2" rigid or
IMC pipes and caps, cut to the required length, with 10% of the total length +2' of the pipe set in
the ground in concrete.
2. Shall be stood away from the pedestal a minimum of 18" and not more than 24" with a 3" rigid
pipe nipple of required length.
3. The cross supports for the meter socket, panel, or panels shall be a minimum of 3/4" x 1-1/2"
unistrut of the required length, shall not extend more than 2" past the rigid pipe supports, and
shall be bolted firmly to the rigid or IMC pipe.
WIRE SIZE:
Wire shall be sized in accordance with NEC guidelines and local requirements.
INSTALLATION OF WIRE:
The wire shall run from the line side of the meter socket into the pedestal allowing 36" of tail
to connect to the pedestal connectors, and the same size wire or equivalent parallel
conductors shall be run from the load side of the meter socket to the panel or panels.
PIPE NIPPLE CONNECTIONS:
1. 2" Schedule 40, rigid, or IMC nipples shall be used between the meter
socket and 200A or 125A panels or between 200A or 125A panels and the
gutter when used.
2. Schedule 40 PVC only allowed if ground wire is installed continuously
between the panel(s) and the meter socket as shown on Page 11.
GROUNDING:
Electric services, including but not limited to, service equipment, raceways,
service distribution enclosures, junction boxes, wireways, enclosures, and any
service conductor to be grounded/bonded, shall be grounded/bonded in
accordance with the latest edition of the NEC. See Page 11 for grounding and 09/08/2023
bonding detail.
METER SOCKETS AND PEDESTALS:
Meter sockets shall have 3" knockouts. Meter pedestals shall not have a meter mounted on
the door. Meters are not allowed inside any enclosed area or any area to be enclosed in the
future. Please see Page 13 of this specification for proper clearances.

REM. DOUBLE BARREL LUG NOTES, REM. GALVANIZED


REV B DATE 09/08/2023 REVISION CHANGED RIGID PIPE NOTES, MATCH 320A NOTES, BY RWC CHK SSS APR MMG
ADDED METER SOCKETS AND PEDESTAL NOTE,
CHANGED WIRE SIZE AND GROUNDING NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 3 OF 13
METER LOOP DETAIL
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES

WEATHERHEAD

MUST HAVE AT LEAST


6" OF DRIP LOOP OUT OF
WEATHERHEAD AND
6" 30" OF TAILS

SERVICE RACEWAY SHALL BE


09/08/2023 2" SCHEDULE 40 RIGID PIPE, IMC,
EMT, OR ELECTRICAL-GRADE
SEE PAGE 11 FOR
PVC. ONLY RIGID PIPE CAN BE
GROUNDING AND
USED IF RACEWAY EXTENDS
BONDING DETAIL
THROUGH THE ROOF.
WEATHER-TIGHT
CONNECTOR MIN. 10'
CLEARANCE
TO DRIP LOOP
UL-APPROVED OVERHEAD METER
SOCKET SUPPLIED BY MEMBER

#6 COPPER MIN. OR LARGER


AS REQUIRED BY NEC
2" NIPPLE 4"

WEATHERPROOF FUSED
OR BREAKER-PROTECTED MAX. 6'
MAIN PANEL MIN. 4'

#6 COPPER MIN. OR LARGER


AS PER NEC

GROUND ROD

MAX, 6' MIN.4' WAS MAX. 6' MIN. 5'


REV B DATE 09/08/2023 REVISION MATCH 320A NOTES BY RWC CHK SSS APR MMG
ADDED GROUNDING AND BONDING NOTE

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 4 OF 13
CONSTRUCTION ON RESIDENTIAL OR COMMERCIAL
LOCATION
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES

THIS TYPE OF CONSTRUCTION IS THE MOST COMMON IN


AREAS WHERE DISTANCE TO POLES IS SUFFICIENT.
CONSTRUCTION MUST MEET OR EXCEED THESE
SPECIFICATIONS PRIOR TO SERVICE CONNECTION.

PEC WIRE WEATHERHEAD

HOUSE KNOB MUST HAVE AT LEAST


PROVIDED BY 6" OF DRIP LOOP OUT OF
MEMBER WEATHERHEAD
AND 30" OF TAILS
REFER TO NOTE 7
ON PAGE 1 FOR
SERVICE ATTACHMENT SERVICE RACEWAY SHALL BE
POINT CLEARANCES 2" SCHEDULE 40 RIGID PIPE,
IMC, EMT, OR ELECTRICAL-
GRADE PVC. ONLY RIGID PIPE
MIN. 10' CAN BE USED IF RACEWAY
CLEARANCE EXTENDS THROUGH THE ROOF.
TO DRIP LOOP

UL-APPROVED OVERHEAD
WEATHER-TIGHT METER SOCKET
CONNECTOR SUPPLIED BY MEMBER

WEATHERPROOF FUSED
OR BREAKER-PROTECTED
MAIN PANEL
MAX. 6'
MIN. 4'

#6 COPPER MIN. OR
LARGER AS PER NEC

09/08/2023
GROUND ROD
MAX, 6' MIN.4' WAS MAX. 6' MIN. 5'
REV B DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN, MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 5 OF 13
MAST-TYPE CONSTRUCTION
THROUGH ROOF
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES. THIS TYPE OF
CONSTRUCTION IS APPROPRIATE WHEN THE EXISTING STRUCTURE DOES NOT ALLOW
FOR PROPER GROUND CLEARANCE.
PIPE CLAMP TO BE
WEATHERHEAD SUPPLIED BY MEMBER

PEC WIRE

3' MAX. UNLESS MAST IS INSTALLED


WITH ADDITIONAL SUPPORT
MIN. 6" MIN. 18"
DRIP LOOP

30" OF TAILS
OUT OF
WEATHERHEAD

SERVICE RACEWAY
REFER TO NOTE 7 SHALL BE 2" RIGID
ON PAGE 1 FOR METAL CONDUIT ONLY
SERVICE ATTACHMENT (NOT IMC OR EMT)
POINT CLEARANCES

MIN. 10' WEATHER-TIGHT


CLEARANCE CONNECTOR
09/08/2023
TO DRIP LOOP

UL-APPROVED OVERHEAD METER


SOCKET SUPPLIED BY MEMBER

WEATHERPROOF FUSED
OR BREAKER-PROTECTED
MAIN PANEL
MAX. 6'
MIN. 4' #6 COPPER MIN.
OR LARGER
AS PER NEC

GROUND ROD

MAX, 6' MIN.4' WAS MAX. 6' MIN. 5'


REV B DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN, MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 6 OF 13
CONSTRUCTION OF MEMBER-OWNED METER POLES
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES
1. Member to purchase and install pole. Member-owned facilities are not permitted on PEC poles.
2. There shall be no more than two loops on any one pole. Weatherhead shall not extend above pole top.
3. Member-owned poles shall be set at a minimum depth of 10% of pole length plus 2', be of sufficient height above
grade to meet NESC clearances (NESC Table 232-1) and meet the following criteria:
5" minimum diameter, at the narrowest point, for creosote-treated or commercially pressure-treated wood
poles.
4.5" outside diameter and minimum 0.237" thickness for round steel poles.
4" square and minimum 0.25" thickness for square steel poles.
4. Steel poles must be capped to prevent water ingress and may be more than one piece if the final product is
appropriately coupled and meets all other requirements.
5. Member-owned pole may be installed no closer than 10' and no further than 40' from the transformer and/or PEC
pole. NEVER install member-owned poles under overhead electric lines.
6. Installations must comply with NEC and NESC specifications.
WEATHERHEAD REFER TO NOTE 7 ON PAGE 1 FOR
SERVICE ATTACHMENT POINT
CLEARANCES
CAP
MAX. 18" PEC WIRE
MEMBER TO SUPPLY AND
INSTALL EYE BOLT
MIN.6" WOOD POLE POLES SHALL
DRIP LOOP BE BURIED 10%
SERVICE RACEWAY SHALL OF POLE
30" OF TAILS BE 2" SCHEDULE 40 RIGID LENGTH PLUS 2'
OUT OF PIPE, IMC, EMT, OR
WEATHERHEAD ELECTRICAL-GRADE PVC
MIN. 10' WEATHER-TIGHT CONNECTOR
CLEARANCE 09/08/2023
UL-APPROVED OVERHEAD
TO DRIP LOOP STEEL POLE
METER SOCKET SUPPLIED BY MEMBER
#6 COPPER STEEL PIPE OR
WEATHERPROOF FUSED OR
MIN. OR POLE TO BE SET IN
BREAKER-PROTECTED MAIN PANEL
LARGER AS CONCRETE. POLE
PER NEC FILL ABOVE GRADE FOAM BACKFILL
WOOD POLE TO BE SET IN CONCRETE. CAN BE USED.
MAX. 6'
MIN. 4' WHERE SOIL CONDITIONS ARE LESS THAN
ROCK, POLE FOAM BACKFILL CAN BE USED.

GROUND ROD

MAX, 6' MIN.4' WAS MAX. 6' MIN. 3'


REV C DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN, MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 7 OF 13
200A SINGLE PHASE LOOP TOP TO BOTTOM
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES. METER
POLE NOTES ARE ON PAGE 7. MEMBER TO PURCHASE AND INSTALL POLE.

CAP
MEMBER TO SUPPLY AND
INSTALL EYEBOLT
MAX. 18" REFER TO NOTE 7
ON PAGE 1 FOR
SERVICE ATTACHMENT
WEATHERHEAD POINT CLEARANCES

SERVICE RACEWAY SHALL


MUST HAVE AT LEAST
BE 2" SCHEDULE 40 RIGID
6" OF DRIP LOOP OUT OF
PIPE, IMC, EMT, OR
WEATHERHEAD AND
ELECTRICAL-GRADE PVC
30" OF TAILS

WEATHER-TIGHT
CONNECTOR

MIN. 10'
CLEARANCE
UL-APPROVED OVERHEAD METER SOCKET TO DRIP LOOP
SUPPLIED BY MEMBER

09/08/2023

#6 COPPER MIN. OR
LARGER AS PER NEC
WEATHERPROOF FUSED
OR BREAKER-PROTECTED MAX. 6'
MAIN PANEL MIN. 4'
FILL ABOVE GRADE

GROUND ROD

MAX, 6' MIN.4' WAS MAX. 6' MIN. 5'


REV C DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN, MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 8 OF 13
SINGLE-PHASE LOOP (RACK TYPE) WITH SIDE MOUNT
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES. METER
POLE NOTES ARE ON PAGE 7. MEMBER TO PURCHASE AND INSTALL POLE.

MEMBER TO SUPPLY AND CAP


INSTALL EYEBOLT

MAX. 18"
REFER TO NOTE 7
ON PAGE 1 FOR
SERVICE ATTACHMENT
POINT CLEARANCES

MUST HAVE AT LEAST SERVICE RACEWAY SHALL BE


6" OF DRIP LOOP OUT 2" SCHEDULE 40 RIGID PIPE, IMC,
09/08/2023 OF WEATHERHEAD EMT, OR ELECTRICAL-GRADE PVC
AND 30" OF TAILS
SEE PAGE 11 FOR WEATHER-TIGHT
GROUNDING AND CONNECTOR
BONDING DETAIL WEATHERPROOF
200A MAIN
DISCONNECT
UL-APPROVED OVERHEAD METER SOCKET OR PANEL
SUPPLIED BY MEMBER
MIN. 10'
CLEARANCE
TO DRIP LOOP
CAP

UNISTRUT MIN.
3/4" X 1 1/2" OF
REQUIRED LENGTH 2" MAX.
EXTENSION

2" NIPPLE

#6 COPPER MIN. OR
LARGER AS PER NEC RIGID PIPE OR IMC
TO BE SET IN
FILL ABOVE CONCRETE 10%
MAX. 6' GRADE OF TOTAL HEIGHT
MIN. 4' +2' DEEP

GROUND ROD

MAX, 6' MIN.4' WAS MAX. 6' MIN. 5'


REV C DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN AND MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 9 OF 13
TYPICAL URD LOOP ON THE
SIDE OF A HOUSE
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES

SEE PAGE 11 FOR


GROUNDING AND
BONDING DETAIL

09/08/2023

UL-APPROVED UNDERGROUND
METER SOCKET SUPPLIED
BY MEMBER
WEATHERPROOF FUSED
OR BREAKER-PROTECTED
MAIN PANEL

2" NIPPLE

INCOMING CONDUIT MUST


ATTACH TO THE SIDE OF
MAX. 6' THE METER CAN OPPOSITE
MIN. 4' FROM DISCONNECT

3" SCHEDULE 80
URD LATERAL #6 COPPER MIN.
OR LARGER AS
GROUND ROD PRE NEC
MAX. 6' MIN. 4' WAS MAX. 6' MIN. 5'
REV A DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN AND MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 10 OF 13
URD FREE-STANDING RACK
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES

MEMBER WILL BE RESPONSIBLE FOR THE INSTALLATION OF UNDERGROUND CABLE FROM THE BREAKER
TO THE LOAD SIDE OF THE METER SOCKET. THE UNDERGROUND CABLE USED SHALL BE AN APPROVED
TYPE FOR UNDERGROUND INSTALLATION (USE TYPE OR UF TYPE). CONDUCTOR SIZE WILL BE BASED ON
MEMBER LOAD, LOCATION OF METER, AND NATIONAL ELECTRICAL CODE FOR SIZE OF CONDUIT.

UL-APPROVED UNDERGROUND
WEATHERPROOF FUSED
METER SOCKET SUPPLIED BY MEMBER
OR BREAKER-PROTECTED
MAIN PANEL

CAP

UNISTRUT
SUPPORT AS
NEEDED

#6 COPPER
MIN. OR 2" MAX.
4' MIN. LARGER AS EXTENSION
FROM TOP PER NEC
OF PIPE
TO GRADE
MIN. 2" NIPPLE
INCOMING BETWEEN
5' MAX.
CONDUIT PANELS
3' MIN.
MUST ATTACH
TO THE SIDE
OF THE RIGID PIPE OR
METER CAN
09/08/2023 IMC TO BE SET
OPPOSITE IN CONCRETE
#6 COPPER MIN. OR 10% OF TOTAL
FROM THE LARGER AS PER NEC
DISCONNECT HEIGHT + 2'
DEEP

GROUND ROD

ADDED GROUNDING AND BONDING INFO


REV B DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REMOVED RIDGID FROM NIPPLE NOTE

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 11 OF 13
SELF-CONTAINED METERING PEDESTAL
UNDERGROUND SERVICE
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION NOTES

Approved Meter Pedestal: 1. Other meter pedestal manufacturers are


· Milbank U5136-O-200s 200 AMP accepted but must be approved by PEC. Meter
height shall be 50" to center above final ground
grade. Meter should face street or driveway.
Mark with address number if not otherwise
posted on property.
2. Conduit to be sized by PEC and installed by
member. Source feed conduit shall be inside
enclosure 3" above opening. Underground
conduit installed according to PEC
specifications. Member shall connect to
PEC-installed conduit stub.
3. Ground rod: 5/8" x 8' copper clad, installed
inside enclosure 4" above opening. Minimum
09/08/2023 #6 copper connected to neutral lug or neutral
bar.
4. Forms: 16" x 24" Sonotube or 16" x 12" x 24"
wood form. Protective tar tape, polywrap tape,
or rubber spray paint from 2" above encased
concrete to the bottom of enclosure. All forms
WASHED ROCK
must be removed after concrete poured.
CONCRETE 5. Fill inside cavity of pedestal with washed rock
up to ground grade to restrict conduit
4" movement.
3"
6. Mule tape to be installed in conduit by member.
GROUND Schedule with PEC if source feeds from
GRADE 3"-4" energized equipment.

24"

MEMBER FEED

6"

SONOTUBE FORM WOOD-BUILT FORM


16" x 24" 16" x 12" x 24"
PEDESTAL CENTERED INSIDE FORM
GROUND ROD PEC SOURCE FEED
REV B DATE 09/08/2023 REVISION REDRAWN BY RWC CHK SSS APR MMG

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 12 OF 13
METER SOCKET VEGETATION AND
EQUIPMENT CLEARANCES
SEE PAGES 1, 2, AND 3 FOR GENERAL NOTES AND INSTALLATION GUIDELINES

SEE PAGE 11 FOR


GROUNDING AND
BONDING DETAIL

SEE NOTE 2
3' MIN. 3' MIN.

3' MIN.

MAX. 6'
MIN. 4'

3' MIN.

3' MIN. 3' MIN.

09/08/2023
NOTES:
1. PERMANENT AND/OR TEMPORARY OBSTRUCTIONS ARE NOT PERMITTED WITHIN 3' IN
ANY DIRECTION OF AN ELECTRIC METER.
2. OBSTRUCTIONS INCLUDE BUT ARE NOT LIMITED TO TREES, SHRUBS, HVAC UNITS,
GENERATORS, WALLS, FENCES, GAS METERS, WINDOWS, AND/OR BUILDINGS.

MAX. 6' MIN 4' WAS MAX. 6' MIN. 5'


REV B DATE 09/08/2023 REVISION BY RWC CHK SSS APR MMG
REDRAWN, MATCH 320A NOTES

RESIDENTIAL AND COMMERCIAL


PEDERNALES ELECTRIC 100-200-AMP METER LOOP SPECIFICATIONS
COOPERATIVE, INC. drawn: approved: date:
RWC MMG 09/08/2023 PAGE 13 OF 13