Astm e 108 A FR - Onethatch Palm

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Xiamen Tong'an

Jinyang Industrial
Co.,Ltd
TEST REPORT
SCOPE OF WORK
ONETHATCH PALM (NIPA) COMPOSITE THATCH

REPORT NUMBER
220927005SHF-001

TEST DATE(S)
2022-09-27 - 2022-10-26

ISSUE DATE
2022-10-26

PAGES
7

DOCUMENT CONTROL NUMBER


LFT-APAC-SHF-OP-10k(September 1, 2022)
© 2022 INTERTEK

Intertek Testing Services Shenzhen Ltd. Shanghai Fengxian Branch


Intertek Testing Services Shenzhen Ltd. Shanghai Fengxian Branch
Plant 5, No. 6958 Daye Road, Fengxian District, Shanghai, China
Tel: +86 21-61136116 Fax: 021-61189921
Website: www.intertek.com

Test Report

Statement
1.This report is invalid without company’s special seal for testing on the assigned page.

2.This report is invalid without an authorized person’s signature.

3.This report is invalid if altered.

4.Only the Client is authorized to permit copying or distribution of this report and then only
in its entirety. Don’t copy this report in partial without any official approval in written by our
company. This report is invalid without re-stamping the special seal for testing in copying
report.

5.This report is for the exclusive use of Intertek's Client and is provided pursuant to the
agreement between Intertek and its Client. Intertek's responsibility and liability are limited to
the terms and conditions of the agreement. Intertek assumes no liability to any party, other
than to the Client in accordance with the agreement, for any loss, expense or damage
occasioned by the use of this report. Any use of the Intertek name or one of its marks for the
sale or advertisement of the tested material, product or service must first be approved in
writing by Intertek. The observations and test results in this report are relevant only to the
sample(s) tested. This report by itself does not imply that the material, product, or service is
or has ever been under an Intertek certification program.

6.Except for the obligation, responsibility and liability (if any) for the appropriateness and
professionality of afore-mentioned testing itself within the scope and amount of the testing
fee received, Intertek does not and will not accept any other obligation or liability.

7.If the Client has any questions about the test results, Intertek B&C should be informed
within the storage period of the samples. The sample storage period ends 5 working days
after the offical report issue date. Samples of certification program are retained for the
period required by the certification rules. The samples storage period shall be calculated
according to the issue date of the original report in the case of quoting results and modifying
reports.

8.Intertek B&C will service this report for the entire test record retention period. The test
record retention period ends 6 years after this report original issue date. The test record
retention period for certification program is 10 years. Test records and other pertinent
project documentation will be retained for the entire test record retention period.

9.The report was digital signed by Shang Hai, Intertek Group plc, please using Adobe Acrobat
Reader to verify the authenticity.

Version: Sep. 01 2022 Page 2 of 7 LFT-APAC-SHF-OP-10k


Intertek Testing Services Shenzhen Ltd. Shanghai Fengxian Branch
Plant 5, No. 6958 Daye Road, Fengxian District, Shanghai, China
Tel: +86 21-61136116 Fax: 021-61189921
Website: www.intertek.com

Test Report

Issue Date: 2022-10-26 Intertek Report No. 220927005SHF-001


Applicant: Xiamen Tong'an Jinyang Industrial Co.,Ltd
Address: 1#building, No.8 Fengling'er Road, Tong'an District, Xiamen City, China
Attn: Echo Xiong
Manufacturer: Xiamen Tong'an Jinyang Industrial Co.,Ltd
Address: 1#building, No.8 Fengling'er Road, Tong'an District, Xiamen City, China
Test Type: Performance test, samples provided by the applicant.

Product Information
Product Name ONETHATCH PALM (NIPA) COMPOSITE THATCH Brand ONETHATCH
Sample Amount 24 pcs
Sample
Good Condition
Description Received Date 2022-09-22

Sample ID Model Specification


S220927005SHF.001~002 OT17098311F 980*680*1.1mm

Test Methods And Standards

Test Standard ASTM E108-20 Standard Test Methods for Fire Tests of Roof Coverings

Specification
/
Standard

The ONETHATCH PALM (NIPA) COMPOSITE THATCH identified in this report met the
Test Conclusion requirements of Class A of Spread of Flame Test in ASTM E108-20 Standard Test Methods for
Fire Test of Roof Coverings at 5:12 slope when applied to a non-combustible deck.
Note:
1.This report does not involve sampling. The report only reflects conformity of the tested items of the samples provided by
the testing applicant. Representativeness and authenticity of the submitted samples are responsibilities of the testing
applicant.

Report Authorized

Name: Harrison Li Name: Lu Cheng


Title: Reviewer Title: Project Engineer

Version: Sep. 01 2022 Page 3 of 7 LFT-APAC-SHF-OP-10k


Test Report

Issue Date: 2022-10-26 Intertek Report No. 220927005SHF-001


Test Items, Method and Results:
The tests were conducted in accordance with ASTM E108-20 Standard Test Methods for Fire Tests of Roof
Coverings. This product is being evaluated for application over a non-combustible surface only, therefore only the
spread of flame tests were conduted.
1.1 Spread-of-flame Test
Spread-of-Flame Test Results
Test Result Requirement of ASTM E108, Section 9 Pass/Fail

At no time during or after the tests shall:

a) Any portion of the roof covering material be


blown or fall off the test deck in the form of
flaming or glowing brands that continue to glow
after reaching the floor;

b) The roof deck be exposed (except for roof


coverings restricted to use over noncombustible
deck), or portions of the roof deck fall away in the
form of particles that continue to glow after
No portion of the panel fall reaching the floor;
off the test deck in the
form of flaming or glowing c) The deck shall be considered exposed whenever Pass
particles, and no flame any portion of the deck is visible and without cover
spread on the panel. from the roof covering material or its residue. The
portion of deck directly underneath burning brands
and cracks or fissures, 1⁄8 in. (3.2mm) wide or less,
shall be excluded from the requirement;

d) The flaming shall spread beyond 6 ft (1.8 m) for


Class A, 8 ft (2.4 m) for Class B, nor 13 ft (4.0 m)
(the top of the deck) for Class C. There shall be
significant lateral spread of flame from the path
directly exposed to the test flame.

Page 4 of 7
Test Report

Issue Date: 2022-10-26 Intertek Report No. 220927005SHF-001

Appendix A: Test Data


Test: Spread of flame
Test Date: 2022-09-28
Sample ID: S220927005SHF.001
Standards: ASTM E108-20, Section 9
Procedure: Class A - 10 min spread of flame test
Conditioning: 24 hours at a temperature between 16 and 32°C
Equipment:
Equipment Item ID Equipment Item ID
Test Apparatus SH1099 Stop Watch SH1042
Anemometer SH1092 Ambient Temperature SH1097
Chromel-alumel Thermocouple SH1099-1 Deck Slope Gauge SH1150

Deck Construction: Non-combustible frame (fiber cement board)


Deck Slope: 5:12
Mounting: The specimen was mounted to a non-combustible frame
Air Velocity Location 1: 5.3 m/s (76 mm from edge)
Calibration: Location 2: 5.2 m/s (measured at centre)
Location 3: 5.2 m/s (76 mm from edge)
Mean: 5.2 m/s Requirement: 5.3 ± 0.2m/s
Temperature Calibration Mean: 734.7 °C Requirement: 760 ± 28°C
Ambient Air Temperature Mean: 24.8 °C Requirement: 10-32 °C
Specimen 1:
Time (min:sec) Observations (Fall off of glowing particles, flame distance, no significant lateral spread)
0:00 Test starts.
0:14 The specimen was melted.
1:31 The specimen was transient ignition.
9:01 The specimen was steady ignition but the flame spread was no more than 6ft.
The test was discontinued. The flame spread stopped but kept burning. No lateral flame spread
10:00
on the specimen.
10:36 The flame was extinguished on the specimen.
Specimen 2:
Time (min:sec) Observations (Fall off of glowing particles, flame distance, no significant lateral spread)
0:00 Test starts.
0:13 The specimen was melted.
1:33 The specimen was transient ignition.
4:25 The specimen was steady ignition but the flame spread was no more than 6ft.
The test was discontinued. The flame spread stopped but kept burning. No lateral flame spread
10:00
on the specimen.
10:48 The flame was extinguished on the specimen.
Page 5 of 7
Test Report

Issue Date: 2022-10-26 Intertek Report No. 220927005SHF-001

Appendix B:Photographs

Fig 1 – Specimen 1 after testing

Fig 2 - Specimen 2 after testing

Page 6 of 7
Test Report

Issue Date: 2022-10-26 Intertek Report No. 220927005SHF-001

Appendix C: Sample Received Photo

Revision:
NO. Date Changes
220927005SHF-001 2022-10-26 First issue

Page 7 of 7