Electric Fire Pump
Electric Fire Pump
Electric Fire Pump
Work under this section shall consist of furnishing all labor, materials, equipment and
appliances necessary and required to completely install electrically operated pumps and as
required by drawings and specified hereinafter or given in the schedule of rates.
a. Electrically operated pumps with motors common base plates, coupling, coupling guard
and accessories.
GENERAL REQUIREMENTS
Pumps shall be installed true to levels on suitable concrete foundations. Base plate shall be firmly
fixed by properly grouted foundation bolts.
Pumps and motors shall be truly aligned by suitably instruments. Record of such alignment shall be
furnished to the Project Manager.
All pump connections shall be standard flanged type with number of bolts as per relevant
standard requirement for the working pressure. Companion flanges shall be provided with the
pumps.
Contractor shall provide necessary test certificates, type test certificates, performance curves and
NPSH curves of the pumps from the manufacturer when called for. The contractor shall provide
facilities to the Project Manager & Consultant for inspection of equipment during manufacturing and
also to witness various tests at the manufacturer’s works without any cost to the Project Manager or
Consultant.
Seismic isolation and clamping for each pump and flexible connection on the suction as well as the
discharge side shall be provided.
The contractor shall submit with this tender a list of recommended spare parts for three years of
normal operation and quote the prices for the same as a separate submittal / annexure.
Drive
The pump shall be direct driven by means of a flexible coupling. Coupling guard shall also be
provided.
FIRE PUMP
The fire pump shall be horizontally mounted centrifugal Multi Stage Multi Outlet type. It shall have a
capacity to deliver 2280 LPM as specified, and developing adequate head so as to ensure a minimum
pressure of 3.5 Kg/Sq.cm at the farthest outlet.
The pump shall be capable of giving a discharge of not less than 150 per cent of the rated
discharge, at a head of not less than 65 per cent of the rated head. The shut off head shall be within
120 per cent of the rated head.
Provision of Jockey Pump shall be made. The pump shall be vertical Multi Stage Multi Outlet type and
of detail as in schedule of quantity. The Jockey pump shall be of 180 LPM.
Motor
The motor shall be squirrel cage A.C. induction type suitable for operation on 415 volts 3 phase 50
Hz. system. The motor shall be totally enclosed fan cooled type conforming to protection clause IP
55. The class of insulation shall be F. The synchronous speed shall be 1500/ 2900 RPM as specified.
The motor shall be rated for continuous duty and shall have a horse power rating necessary to
drive the pump at 150 per cent of its rated discharge with at least 65 per cent rated head. The motor
shall conform to I.S.325-1978.
Casing: C.I.
Impeller: Bronze.
Shaft: SS-410.
MOC OF PUMP:
Casing: C.I.
Impeller: Bronze.
Shaft: SS-410.
Shaft Sleeve: SS-410.
MOC OF PUMP:
Casing: C.I.
Impeller: Bronze.
Shaft: SS-410.
Head: 50 M.
MOC OF PUMP:
Casing: C.I.
Impeller: Bronze.
Shaft: SS-410.
GENERAL REQUIREMENTS-
Pumps shall be installed true to level on suitable concrete foundations; Base plate shall be firmly fixed
by foundation bolts grouted in the concrete foundations. Foundations shall be casted on the
reinforcement steel of the floor.
All pump connections shall be standard installation; connections and commissioning shall be followed
with respect to all pumps and accessories.
TYPE OF PANEL:
All the PCC's / PDB's / MCC's shall be metal clad, totally enclosed, rigid, floor mounted, air -
insulated, cubical type suitable for operation on three phase / single phase, 415 / 230 volts, 50 Hz.
The PCC's / MCC's shall be designed to withstand the heaviest conditions at site, with minimum
expected ambient temperature of 45 degree Celsius, 80 percent humidity and dusty weather.
Panel shall conform to Indian Electricity Act and rules (till last amendment) & approved as per FIA
norms.
NOTES-
a. Jockey pump shall start and stop through pressure switch automatically.