Ba Eng HPS+XXXDD
Ba Eng HPS+XXXDD
Ba Eng HPS+XXXDD
Ԏ The hps+ sensor measures the level ble from NOC to NCC. Ԏ Read the operating instructions hps+ sensors are delivered factory Î In normal operating mode shortly
in a vessel in up to 6 bar overpres- Ԏ The sensors are adjustable manually prior to start-up. made with the following settings: push T1. The LED display shows
sure contactless. The G1 and G2 using the numerical LED display or Ԏ Connection, installation and ad- Ԏ Switching outputs on NOC »PAr.«
threaded pipe end permits the may be trained via Teach-in proces- justment works may only be car- Ԏ Detecting distances at operating Each time you tap push-button T1 the
mounting and sealing of the sensor ses. ried out by expert personnel. range and half operating range actual settings of the analogue output
in a flange of the vessel. The pnp Ԏ Useful additional functions are set Ԏ No safety component in ac- Ԏ Measurement range set to maxi- are shown.
switching outputs are set according in the Add-on-menu. cordance with the EU Machine mum range at ≥2 bar overpressure
to the adjusted detect distances. Ԏ Using the LinkControl adapter (op- Directive, use in the area of per- Ԏ Sensitivity at normal pressure
Ԏ The surfaces of the ultrasonic trans- tional accessory) all TouchControl sonal and machine protection Maintenance
ducers of the hps+ sensors are pro- and additional sensor parameter not permitted hps+ sensors work maintenance free.
tected by a PTFE film and sealed settings can be adjusted by a Win- Proper Use Small amounts of dirt on the surface
with a FFKM O-ring against the dows® Software. hps+ ultrasonic sensors are used for do not influence function. Thick layers
Operating Manual sensor housing. Therefore the sur- non-contact detection of objects. of dirt and caked-on dirt affect the
face of the ultrasonic transducer sensor function and therefore must be
hps+ Ultrasonic Sensors can be cleaned from cakings or
for application in overpressure The hps+ sensors indicate a blind removed.
spots. zone, in which the distance cannot be
with two switching outputs Ԏ All settings are done with two push- Notes
measured. The operating range indi- Ԏ In operation in overpressure it is re-
hps+25/DD/TC/E/G1 buttons and a three-digit LED dis-
hps+35/DD/TC/E/G1 cates the distance of the sensor that commended to adjust the sensitivi-
play (TouchControl). can be applied in normal atmospheric
hps+130/DD/TC/E/G1 ty of the hps+ sensor: choose the
Ԏ Light emitting diodes (three-colour
hps+340/DD/TC/E/G2 pressure with sufficient function reser- parameter A14 in the Add-on menu
hps+340/DD/TC/G2 LEDs) indicate the switching status. ve. and set it to sensitivity E2 for atmos-
Installation pheric pressure from 1 to 3 bar or
Diagram 1: Set sensor parameters numerically using LED display
Î Assemble the sensor at the installa- to sensitivity E3 for atmospheric
tion location. pressure >3 bar.
Start here Î If necessary seal the sensor with Ԏ hps+ sensors have internal tempe-
T1 + T2 the enclosed Viton®-O-ring rature compensation. Because the
(34 x 2,5 mm or 60 x 4 mm) sensors heat up on their own, the
Press T1 and T2 simultaneously for about against the flange. temperature compensation reaches
3 s until welcome message has passed. Î Plug in the connector cable to the its optimum working point after
M12 connector, see Fig. 1. approx. 30 minutes of operation.
Ԏ During normal operating mode, a
Set switching output D1 Set switching output D2 2 1 yellow LED signals that the corres-
3 5 4 ponding switching output is set.
T1 T2 T1 T2 colour Ԏ During normal operating mode, the
1 +UB brown
3 –UB blue
measured distance value is dis-
4 D2 black played on the LED display in mm (up
T1 + T2
2 D1 white to 999 mm) or cm (from 100 cm).
5 Sync/Com grey Scale switches automatically and is
Set detect distance in
T1 T2
mm or cm. Fig. 1: Pin assignment with view onto sensor indicated by a point on top of the
plug and colour coding of the microso- digits.
1
T1 + T2 1 2 nic connection cable
Ԏ During Teach-in mode, the hystere-
Start-up sis value is set back to factory set-
For single switching For window mode Î Connect the power supply. tings.
point press T2 operation set far
T2 until »– – –« is T1 T2 switching point in Î Set the parameters of the sensor Ԏ If no objects are placed within the
displayed. mm or cm. manually via TouchControl (see detection zone the LED display
Fig. 2 and Diagram 1) shows »– – –«.
T1 + T2 Î or use the Teach-in procedure to Ԏ If no push-buttons are pressed for
adjust the detect points (see Dia- 20 seconds during parameter set-
Choose » « for NCC or
T1 T2 gram 2). ting mode, the parameter changes
» « for NOC.
cm mm % Measuring Range are saved and the sensor returns to
T1 + T2 3-digit normal operating mode.
LED-display Ԏ The sensor can be reset to its facto-
LED D1 and D2 ry setting, see »Key lock and facto-
T1 T2 Push-buttons T1 and T2 ry setting«, Diagram 3.
T1 D1D2 T2
Ready
Diagram 2: Set sensor parameters via Teach-in procedure Diagram 3: Key lock and factory setting
Place object at position 1 . Place object at position 1 . Place reflector at position 1 . While pressing T1 turn While pressing T1 turn
supply voltage ON. supply voltage ON.
Diagram 4: Useful additional functions in Add-on menu (for experienced users only, settings not required for standard applications)
Start here
T1 + T2
T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2
T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2
T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2
T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2
T2 T1
T1 + T2 »C01«: Display Minimum value: Minimum value: »F00«: no filter Defines the strength Delay in seconds Minimum value: »00«: synchronisati- To optimize multi- Minimum value: Put plane reflector Affects the size of
bright »001« »001« »F01«: standard of the chosen filter. between the detec- blind zone on plex speed the hig- sensor-distant vertically disposed in the detection zone.
tion of an object hest sensor address window limit front of sensor: in
Ready »C02«: Display
dimmed
Maximum value:
difference between
Maximum value:
difference between
filter
»F02«: averaging
»P00«: weak filter
up to
and the output of
Maximum value: ne-
arwindow limit - 1
»01« to »10«: sensor
address for multi- may be set. Maximum value: an exact distance of
»E01«: high
»E02«: standard
maximum range and maximum range and the measured dis- plex mode Setting range »01« 999 mm for 250 mm for
»C03«: Display off filter »P09«: strong filter tance in case of ob- hps+ 25... and »E03«: slight
switching point - 1 switching point - 1 »oFF«: synchronisati- to »10« hps+25/...,
»F03«: foreground ject approach (beha- hps+35/..., hps+35... and
During window During window filter ves as on-delay). on deactivated 900 mm for all other
mode operation mode operation 999 cm for types.
hysteresis influences hysteresis influences »F04«: background "00": 0 s (no delay) hps+130/...,
both switching both switching filter up to hps+340/... Adjust display to
250 mm or 900 mm.
Note points. points. "20": 20 s response Confirm calibration
Changes in the Add-on menu time with T1+T2.
may impair the sensor func-
tion.
A6, A7, A8, A10, A11, A12
have influence on the res-
ponse time of the sensor. Low power mode Hysteresis switching Hysteresis switching Measurement filter Filter strength Response time Foreground Multiplex mode Multiplex mode Measurement range Calibration Detection zone
output D1 output D2 suppression device addressing highest address display sensitivity
Technical data
hps+25... hps+35... hps+130... hps+340... hps+340...
G2 ISO 228
G2 ISO 228
G1 ISO 228
G1 ISO 228
G1 ISO 228
5
D2
Sync/Com
3
–UB
M12x1
M12x1
M12x1
M12x1
M12x1
2 pnp switching outputs
58 58 58
91 12.5 91 12.5 91 12.5 15 15
38 37 38 37
103.5 103.5 103.5 108 108
10 cm
0.8 m
0.4 m
0.4 m
0.8 m
1.6 m
0.8 m
0.8 m
1.6 m
1.6 m
0.8 m
0.8 m
1.6 m
20 cm
10 cm
10 cm
20 cm
5 cm
0 cm
5 cm
0 cm
for different objects:
0m
0m
0m
The dark grey areas are determi- 0 cm 0 cm 0m 0m 0m
ned with a thin round bar and in-
dicate the typical operating range
of a sensor. In order to obtain the 5 cm
10 cm 0.8 m 0.8 m
light grey areas, a plate (500 x Plate 0.4 m Plate Plate
Plate
500 mm) is introduced into the Plate
beam spread from the side. 10 cm 1.6 m 1.6 m
20 cm
In doing so, the optimum angle Round bar ø 10 mm Round bar ø 27 mm Round bar ø 27 mm
Round bar ø 10 mm 0.8 m
between plate and sensor is al- 15 cm Round bar ø 10 mm 2.4 m 2.4 m
ways employed. This therefore 30 cm
indicates the maximum detection 1.2 m
zone of the sensor. It is not possi- 35 cm
20 cm 1.3 m 3.2 m 3.2 m
ble to evaluate ultrasonic reflec- 40 cm 3.4 m 3.4 m
tions outside this area.
Displayed is the detection zone at 25 cm 1.6 m 4m 4m
standard pressure. At 1 bar over- 50 cm
pressure the sensitivity of the sen-
sor will increase 5 times. 30 cm 4.8 m 4.8 m
2m
60 cm
35 cm 5.6 m 5.6 m
operating voltage UB 9 to 30 V DC, reverse polarity protection (Class 2) 9 to 30 V DC, reverse polarity protection (Class 2) 9 to 30 V DC, reverse polarity protection (Class 2) 9 to 30 V DC, reverse polarity protection (Class 2) 9 to 30 V DC, reverse polarity protection (Class 2)
voltage ripple ±10 % ±10 % ±10 % ±10 % ±10 %
no-load supply current ≤80 mA ≤80 mA ≤80 mA ≤80 mA ≤80 mA
ambient pressure up to 6.0 bar up to 6.0 bar up to 6.0 bar up to 6.0 bar up to 6.0 bar
housing Stainless steel 1.4571, plastic parts: PBT, TPU; Stainless steel 1.4571, plastic parts: PBT, TPU; Stainless steel 1.4571, plastic parts: PBT, TPU; Stainless steel 1.4571, plastic parts: PBT, TPU; Plastic parts: PVDF, PBT, TPU;
Ultrasonic transducer: PTFE film, FFKM O-ring Ultrasonic transducer: PTFE film, FFKM O-ring Ultrasonic transducer: PTFE film, FFKM O-ring Ultrasonic transducer: PTFE film, FFKM O-ring Ultrasonic transducer: PTFE film, FFKM O-ring
process connection G1 G1 G1 G2 G2
class of protection to EN 60529 IP 67 IP 67 IP 67 IP 67 IP 67
norm conformity EN 60947-5-2 EN 60947-5-2 EN 60947-5-2 EN 60947-5-2 EN 60947-5-2
type of connection 5-pin initiator plug, PBT 5-pin initiator plug, PBT 5-pin initiator plug, PBT 5-pin initiator plug, PBT 5-pin initiator plug, PBT
controls 2 push-buttons (TouchControl) 2 push-buttons (TouchControl) 2 push-buttons (TouchControl) 2 push-buttons (TouchControl) 2 push-buttons (TouchControl)
indicators 3-digit LED display, 2 three-colour LEDs 3-digit LED display, 2 three-colour LEDs 3-digit LED display, 2 three-colour LEDs 3-digit LED display, 2 three-colour LEDs 3-digit LED display, 2 three-colour LEDs
programmable TouchControl and LinkControl TouchControl and LinkControl TouchControl and LinkControl TouchControl and LinkControl TouchControl and LinkControl
operating temperature –25 to +70 °C –25 to +70 °C –25 to +70 °C –25 to +70 °C –25 to +70 °C
storage temperature –40 to +85 °C –40 to +85 °C –40 to +85 °C –40 to +85 °C –40 to +85 °C
weight 210 g 210 g 210 g 1,200 g 350 g
switching hysteresis 1) 3 mm 5 mm 20 mm 50 mm 50 mm
switching frequency 2) 11 Hz 9 Hz 5 Hz 3 Hz 3 Hz
response time 2) 68 ms 84 ms 160 ms 240 ms 240 ms
time delay before availability <300 ms <300 ms <300 ms <380 ms <380 ms