Psychrometric Process Lecture
Psychrometric Process Lecture
Psychrometric Process Lecture
Salem
Supply fan
Room
Recirculated air
In winter the heater battery will be on and the cooling coil will probably be
switched off for the majority of buildings.
In summer the heater battery will not need to have the same output and the
cooling coil will be switched on.
A humidifier may be required to add moisture to the air when it is 'dry'.
This is when outdoor air has a low humidity of around 20% to 30%.
In the U.K. low humidities are rare and therefore humidification is sometimes
not used.
In dryer regions humidification is required through most of the year whereas in
tropical air conditioning one of the main features of the system is the ability to
remove moisture from warm moist air.
Dampers are used in air conditioning central plant systems to control the
amount of air in each duct.
It is common to have 20% fresh air and 80% recirculated air to buildings.
1
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
In buildings with high occupancy the fresh air quantity should be calculated
based on C.I.B.S.E. data., this may require a higher percentage of fresh air (i.e.
more than 20%).
See Ventilation section for examples of fresh air rates.
Filters are required to remove particles of dust and general outdoor pollution.
This filter is sometimes called a coarse filter or pre-filter.
A removable fibreglass dust filter is positioned in the fresh air intake duct or in
larger installation an oil filled viscous filter may be used.
The secondary filter, after the mix point, is used to remove fine dust particles
or other contaminant picked up in the rooms and recirculate back into the plant.
A removable bag filter is generally used for this where a series of woven fibre
bags are secured to a framework which can be slid out of the ductwork or air
handling unit (A.H.U.) for replacement.
Air handling units (A.H.U.) are widely used as a package unit which
incorporates all the main plant items as shown below.
Pipework, ductwork and electrical connections are made after the unit is set in
place on site.
Since air conditioning plant rooms tend to be at roof level, the larger A.H.U.'s
are lifted into place by crane before the roof is fixed.
2
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
In some cases it is usual to place the fan in front of (that is upstream of) the heater
battery and cooling coil.
This is because fans operate best if the system resistance is at the outlet rather than
the inlet of the impeller.
This is shown on the schematic diagrams above.
The photograph below shows a typical air handling unit with handles on the doors for
access to equipment.
3
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Introduction
The aim of this section of the notes is to allow students to size air conditioning plant
such as;
Cooling coil
Heater battery
Humidifier
The notes are divided into several sections as follows:
1. PSYCHROMETRY FOR AIR CONDITIONING
2. THE PSYCHROMETRIC CHART
3. EXAMPLES OF PSYCHROMETRIC PROPERTIES
4. AIR CONDITIONING PLANT FOR SUMMER & WINTER
5. BASIC PROCESSES
6. TYPICAL AIR CONDITIONING PROCESSES
7. ANNOTATION AND ROOM RATIO
8. SUMMER AND WINTER CYCLES
9. EXAMPLES
The first section deals with Psychrometry for air conditioning and discusses some
properties of moist air.A simplified psychrometric chart is shown for familiarization
, and some examples of how to find air properties are provided.
A diagram of an air conditioning system is shown in schematic form in the section
entitled AIR CONDITIONING PLANT FOR SUMMER & WINTER.
4
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Before sizing takes place the student should also understand the processes that take
place in air conditioning systems.
There are four basic processes for summer and winter air conditioning systems.
The following basic processes are explained:
1. Mixing
2. Sensible Cooling and Heating
3. Cooling with Dehumidification
4. Humidification
These are as detailed in the following sections of the notes.
Summer and Winter Cycles
1. Summer cycle psychrometrics
2. Summer cycle calculations
3. Winter cycle psychrometrics
4. Winter cycle calculations
5. Duct and Fan gains.
The final section is seven examples of plant sizing using psychrometric charts.
5
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
When exposed to the environment the moisture evaporates from the wetted gauze,
which gives a lower reading on the thermometer.
This gives an indication of how ‘dry’ or how ‘moist’ the air is, since in ‘dry’ air the
water will evaporate quickly from the gauze, which depresses the thermometer
reading.
3. Moisture content
This is the amount of moisture in air given in kg of moisture per kg of dry air e.g. for
room air at 21oC dry bulb and 15oC wet bulb, the moisture content is about 0.008
kg/kg d.a.
This is a small mass of moisture ( 0.008 kg = 8 grams) per kg of dry air or 9.5 grams
per cubic metre of air.
This is the ratio of the moisture content of moist air to the moisture content of
saturated air at the same temperature.
When air is saturated it is at 100% saturation and cannot hold any more moisture.
5. Specific enthalpy
If heat is added to the air at a heater battery for example, then the amount to be added
can be determined from Specific enthalpy change.
6. Specific volume
This is the volume of moist air (dry air + water vapor) per unit mass.
6
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The six properties of air previously discussed can be shown on one chart called a
Psychrometric Chart.
One of the purposes of the Psychrometric Chart is to size heater batteries, cooling
coils and humidifiers.
If any two properties of air are known then the other four can be found from the
psychrometric chart.
7
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
EXAMPLE 1
Find the moisture content of air at 25oC dry-bulb temperature and 25oC wet-bulb
temperature.
Referring to the chart below, a vertical line is drawn upwards from 25 oC dry-bulb
temperature until it intersects at 25oC wet-bulb temperature.
This intersection point happens to be on the 100% saturation line.
The intersection point is highlighted and a horizontal line is drawn to the right to find
the corresponding moisture content.
The moisture content is therefore 0.020 kg/kg dry air.
EXAMPLE 2
Find the specific volume and wet-bulb temperature of air at 20oC dry-bulb
temperature and 50% saturation.
Referring to the chart below, a vertical line is drawn upwards from 20 oC dry-bulb
temperature until it intersects with the 50% saturation curve.
The intersection point is sometimes referred to as the state point.
The specific volume is found to be 0.84 m3/kg and the wet-bulb temperature is 14oC
8
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
EXAMPLE 3
Find the specific volume, percentage saturation and moisture content of air at 15oC
dry-bulb temperature and 10oC wet-bulb temperature.
Referring to the chart below, a vertical line is drawn upwards from 15 oC dry-bulb
temperature until it intersects with the 10oC wet-bulb temperature line.
This intersection is the state point.
The specific volume is found to be 0.823 m3/kg, the percentage saturation 52% and
the moisture content 0.0054 kg/kg d.a.
9
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
EXAMPLE 4
Find the specific volume, wet-bulb temperature, moisture content and specific
enthalpy of air at 35oC dry-bulb temperature and 30% saturation.
Referring to the chart below, a vertical line is drawn upwards from 35 oC dry-bulb
temperature until it intersects with the 30% saturation curve.
This intersection is the state point.
The specific volume is found to be 0.883 m3/kg, the wet-bulb temperature is 22oC,
the moisture content 0.011kg/kg d.a. and the specific enthalpy 65 kJ/kg.
11
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
In the summer time when cooling is required by the air conditioning plant it will be
necessary to operate the cooling coil, reheater and possibly other plant as well.
In winter time the preheater and reheater battery will probably be on to provide warm
air to overcome heat losses.
Other plant may be switched on as well. These plant items are shown in the diagram
below.
11
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
12
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
1. Mixing
Where two air streams are mixed the psychrometric process is shown as a straight
line between two air conditions on the psychrometric chart, thus points 1 and 2 are
joined and the mix point 3 will lie on this line.
Two air streams are mixed in air conditioning when fresh air (m1) is brought in from
outside and mixed with recirculated air (m2).
The resulting air mixture is shown below as (m3).
The mixing ratio is fixed by dampers.
Sometimes, in more sophisticated plant, modulating dampers are used which are
driven by electric motors to control the mixture of air entering the system.
13
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
When air is heated or cooled sensibly, that is, when no moisture is added or removed,
this process is represented by a horizontal line on a psychrometric chart.
The most commonly used method of removing water vapour from air
(Dehumidification) is to cool the air below its dew point.The dew point of air is when
it is fully saturated i.e. at 100% saturation.
When air is fully saturated it cannot hold any more moisture in the form of water
vapor.
14
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
If the air is cooled to the dew point air and is still further cooled then moisture will
drop out of the air in the form of condensate.
This can be shown on a psychrometric chart as air sensibly cooled until it becomes
fully saturated (the dew point is reached) and then the air is cooled latently to a lower
temperature.
This is apparent on the psychrometric chart as a horizontal line for sensible cooling to
the 100% saturation curve and then the process follows the 100% saturation curve
down to another point at a lower temperature.
This lower temperature is sometimes called the Apparatus dew Point (ADP) of the
cooling coil.
In reality the ADP of the cooling coil is close to the cooling liquid temperature inside
the coil.
Chilled water or refrigerant may be the cooling liquid.
The psychrometric process from state point 1 to 2 to 3 may be shown as a straight
line for simplicity as shown above with a yellow line.
15
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
In the absence of a suitable psychrometric chart the following formula may be used;
Some of the air going through a cooling coil does not come into contact with the
tubes or fins of the cooling coil and is therefore not cooled to the ADP temperature.
A mixing process therefore takes place as two air streams mix downstream of the
cooling coil as shown below.
One air stream is cooled down to the ADP and the other air stream by-passes the coil
surfaces to give an off-coil air temperature (mixed air stream) a little higher than the
ADP.
This may be looked upon as an inefficiency of the coil and is usually given as the
cooling coil contact factor.
16
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
4. Humidification
If is it necessary to add some moisture to the supply air then this is best done by
injecting steam into the air stream.
Humidification can be carried out by spraying a fine mist of water droplets into the
air but this is not recommended in rooms occupied by people due to the risk of
bacteria carry over.
Dry steam may be injected from a steam supply pipe or generated in a local packaged
unit as shown in the photograph below. A disadvantage of using an existing steam
supply is smells may be carried over into the air.
17
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The steam package unit is situated close to the air duct and is sized to meet the
maximum requirements; this is usually in winter in the U.K.
A steam pipe ( sometimes hoses are used) passes from the packaged unit to the air
duct and steam at 100oC is injected into the air stream via. a sparge pipe. The un-used
steam is drained from the system via a condensate tundish and drain. It is important
to layout the steam pipework so that any condensate will drain back to the unit.
See Summer and Winter Cycles section for calculation of amount of moisture added
at humidifier.
18
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The schematic diagram below shows a typical plant system for summer air
conditioning.
19
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The schematic diagram below shows a typical plant system for winter air
conditioning.
21
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Annotation
Room Ratio
This is the ratio of sensible to total heat in the room for summer or winter.
The total heat gain (summer) or loss (winter) will be determined by adding the Latent
and Sensible heat in a room or rooms, i.e.
The room ratio is used on a psychrometric chart to determine the supply air state
point.
A room ratio line is superimposed from the protractor on the psychrometric chart
onto the main body of the chart by a line passing through the room state point R.
The supply air state point must also be somewhere on this room ratio line to meet the
room heat gain requirements i.e. the room ratio line always passes through points R
and S.
22
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
23
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
24
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
25
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
26
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
27
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
28
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
29
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
31
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
DATA:
Outdoor condition is 28oC, 80% saturation.The outdoor air and recirculated air ratio
is 20%/80%. The Apparatus Dew Point ADP is 8oC Neglect the cooling coil contact
factor.
31
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
32
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
33
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
34
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
35
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
36
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Note:
The cooling coil output of 38.2 kW is a much higher value than the sensible heat gain
of 10.8 kW.
It should be remembered that the difference is these two values is mostly from the
fresh air cooling load.
It takes quite a lot of energy in summer to cool fresh air coming into air handling
units.
This can be minimised by bringing in minimum fresh air but not too little otherwise
the building will suffer from lack of oxygen and feel stuffy.
So, don’t size cooling coil and indoor cooling units on sensible heat gain only if there
is fresh air coming into the plant.
Size these items of plant using a psychrometric chart.
37
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
38
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
A room has a 18.0 kW sensible heat loss in winter and a 4.5 kW latent heat gain from
the occupants.
Determine the supply air temperature and heater battery load using the following
information.
DATA:
Indoor condition: 21oC dry-bulb temperature, 50% saturation.
Outdoor condition: -2oC d.b., 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
No preheating or humidification takes place in this simplified example.
39
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
4. No Preheater condition P
41
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
6. Find the mix point M by measuring the length of the line O-R and multiply this by
the mixing ratio.
On a full size CIBSE psychrometric chart this measures 110mm.
The ratio of recirculated air is 0. therefore; 110mm x 0.8 = 88mm
Measure up the O-R line from point O by 88mm.
This determines point M .
If there is more recirculated air than outside air at the mix point, then point M will be
closer to point R than point O.
7. Find the room ratio.
This is the sensible to total heat ratio.
Neglect signs ie. the total heat for the room will be Sensible loss plus Latent gain.
Total heat = 18 kW sensible + 4.5 kW latent = 22.5 kW total.
Heat ratio = 18 / 22.5 = 0.8
Plot this ratio on the protractor, top segment, on the psychrometric chart and transfer
this line onto the chart so that it passes through point R.
41
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
42
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
When the sensible heat loss and supply air temperature in winter are known then the
mass flow rate of air is calculated from the following formula:
Hs = ma x Cp ( ts - tr )
where:
Hs = Sensible heat loss (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
..............therefore:
ma = Hs / Cp ( ts - tr )
ma = 18 / 11.615
ma = 1.55 kg/s
where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)
The specific enthalpies at points S and M are shown on the psychrometric chart
below.
44
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
45
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
5. Find the mix point M by measuring the length of the line O-R and multiply this
by the mixing ratio.
On a full size CIBSE psychrometric chart this measures 85mm.
The ratio of recirculated air is 0.8. …….. therefore; 85mm x 0.8 = 68mm
Measure down the O-R line from point O by 68mm.
This determines point M .
6. Find the room ratio. This is the sensible to total heat gain ratio.
Total heat = 8 kW sensible + 2 kW latent = 10 kW total.
Heat ratio = 8 / 10 = 0.8
Plot this ratio on the protractor, bottom segment, on the psychrometric chart
and transfer this line onto the chart so that it passes through point R.
7. Plot the Apparatus Dew Point ADP of the cooling coil.
This is on the 100% saturation curve. The ADP is 80C.
46
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
47
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
When the supply air temperature has been found from the psychrometric chart then
the mass flow rate of air can be calculated from the following formula:
ma = Hs / ( Cp ( tr - ts ) )
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01
kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
ma = 8 / ( 1.01 ( 22 - 17 ) )
48
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
ma = 1.584 kg/s
where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined from
psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined from
psychrometric chart
The specific enthalpies at points M and ADP are shown on the psychrometric Chart
below.
where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg) determined
from psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg) determined
from psychrometric chart.
The specific enthalpies at points S and W are shown on the psychrometric Chart
below.
49
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The latent heat gain is 40 Watts per person (see Air Conditioning section).
Determine the preheater and reheater outputs required and the amount of moisture to
be added at the humidifier in litre/hour, by using a psychrometric chart if the plant
schematic is as shown below.
DATA:
Outdoor condition is -2oC, 80% saturation.
The outdoor air and recirculated air ratio is 50%/50%.
Maximum occupancy is 250 people.
The preheater off coil temperature is 5oC.
51
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The latent heat gain = heat gain per person x number of people
Supply air quantity (m3/h) = air change rate x room volume (m3)
Supply air mass flow rate (kg/s) = Supply air quantity (m3/s) / Specific Volume
(m3/kg)
Supply air mass flow rate (kg/s) = 2.13 (m3/s) / 0.87 (m3/kg)
51
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The fresh air flow rate (kg/s) = 2.45 kg/s x 50% = 1.23 kg/s
52
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
This is found by calculation because we have already calculated the mass flow
rate of supply air from information given in the question.
Hs = ma x Cp ( ts - tr )
where:
Hs = Sensible heat loss from room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
( ts - tr ) = Hs / ma x Cp
( ts - tr ) = 17 / 2.45 x 1.01
( ts - tr ) = 6.87 deg.C
ts = 21 + 6.87 deg.C
where:
H preheater battery = Preheater battery output (kW)
m af = mass flow rate of fresh air (kg/s)
53
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of supply air (kg/s)
hH = specific enthalpy at condition H (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)
Humidifier Output
The amount of moisture added to the air may be calculated from the following
formula:
where:
m moisture added = The amount of moisture or added or steam flow rate
(kg/s)
ma = mass flow rate of air (kg/s)
m sS = moisture content at condition S (kg/kg d.a.)
m sH = moisture content at condition H (kg/kg d.a.)
54
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
DATA:
Outdoor condition is 28oC, 80% saturation.
The Apparatus Dew Point ADP is 7.5oC.
The latent heat gain is 10.0 kW.
The sensible heat gain is 12.0 kW.
Maximum occupancy is 200 people.
The cooling coil contact factor is unknown at present and should be calculated.
55
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Use CIBSE guide B2 (2001) to determine air flow rates and calculate the mass flow
rate of fresh air and supply air to the room.
The lecture room may be taken as an Assembly hall.
The room is a non-smoking area.
Information from CIBSE Guide B2 (2001) Table 3.3 is as follows (see Ventilation –
Ventilation rates section);
The recommended outdoor air rate is 8 l/s/person for non-smoking.
Information from CIBSE Guide B2 (2001) Table 3.1 is as follows (see Ventilation –
Ventilation rates section);
Assembly halls and auditorium refers to Table 3.6 (see Ventilation – Ventilation rates
section);
The recommended total air supply rate is 6 – 10 air changes per hour for high level
mechanical strategy.
Fresh air rate = 8 l/s/p x 200 people = 1600 l/s = 1.6 m3/s
The specific volume at the outside condition may be determined from a
psychrometric chart. It is 0.88 m3/kg.
Mass flow rate = Volume flow rate / specific volume
Mass flow rate (Fresh Air) = 1.6 / 0.88 = 1.82 kg/s .
56
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
If the maximum ventilation supply air rate is taken from Table 3.6 to be 10.0 air
changes per hour, then the mass flow rate can be calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate (ac/h)
Volume of room (m3) = 15 x 10 x 6 = 900 m3
Volume flow rate (m3/h) = 900 (m3) x 10 (ac/h)
Volume flow rate (m3/h) = 9000 m3/h
Volume flow rate (m3/s) = 9000 / 3600 = 2.5 m3/s.
Mass flow rate = Volume flow rate / specific volume
The specific volume at the supply condition may be approximated at this stage from a
psychrometric chart. It is 0.834 m3/kg.
Mass flow rate (Supply Air) = 2.5 / 0.834 = 3.0 kg/s.
57
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
In this example the supply air temperature will be found by rearranging the following
formula:
Hs = ma x Cp ( tr - ts )
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
( tr - ts ) = Hs / ( ma x Cp )
( tr - ts ) = 12 / ( 3.00 x 1.01 )
( tr - ts ) = 3.96 deg.C
since tr = 22oC
ts = 22 - 3.96 = 18.04 oC
ts = 18 oC approx.
58
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
59
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined
from psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg)
determined from psychrometric chart
The specific enthalpies at points M and ADP are shown on the psychrometric Chart
above.
where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg) determined
from psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg) determined
from psychrometric chart.
The specific enthalpies at points W and S are shown on the psychrometric Chart
above.
61
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
DATA:
Indoor condition all year - 22oC dB temperature, 50% saturation.
Outdoor condition summer - 28oC dB temperature, 80% saturation.
Outdoor condition winter - -3oC dB temperature, 80% saturation.
Maximum occupancy - 1000 people.
ADP of the cooling coil - 8oC
Fresh air requirement - 12 l/s/person
Supply air rate - 8 air changes per hour.
o
Frost off coil temperature - 7 C.
Latent heat gain - 40 W/person
Sensible heat gain in summer - 100 W/person + 20.5 kW fabric, lights, solar &
ventilation gains.
Sensible heat loss in winter - 20 W/m3 air volume (estimated)
Fresh air rate = 12 l/s/p x 1000 people = 12,000 l/s = 12.0 m3/s
The specific volume at the outside condition may be determined from a
psychrometric chart.
It is approximately 0.88 m3/kg.
Mass flow rate = Volume flow rate / specific volume
Mass flow rate (Fresh Air) = 12.0 / 0.88 = 13.64 kg/s.
The ventilation supply air rate is taken from table B2.3 and is given as 8 air changes
per hour; the mass flow rate can be calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate (ac/h)
62
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
It is not unusual to have a high percentage of fresh air in a high occupancy room such
as a Concert Hall.
The air flows are shown on the schematic diagram below.
63
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Heat Gains
Heat Loss
In this example the supply air temperature will be found by rearranging the following
formula:
Hs = ma x Cp ( tr - ts )
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
On a full size psychrometric chart the length of the line from point M to point ADP is
116mm.
The distance from point M to point W is 107mm.
65
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined
from psychrometric chart.
66
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
The specific enthalpies at points M and ADP are shown on the psychrometric Chart
above.
NOTE:
The cooling coil output is very high and a lot of energy would be required to provide
this amount of cooling.
The cooling coil load would probably be spread over several air handling units but
the it could be examined with a view to some reduction.
The coil output is high because the mass flow rate of supply air is high (17.05 kg/s)
and the proportion of fresh air is also high (80%).
The mix point M is at approximately 27oC dry-bulb so there is little advantage in
recirculation in this instance.
It would be advantageous to consider the supply airflow rate to see if a lower rate
would be acceptable for this building.
If 6 air changes per hour are used as the ventilation rate then this would reduce the
mass flow rate of supply air.
Also the engineer may consider other methods of air-conditioning a hall with a large
volume such as using partial radiant cooling where surfaces are cooled rather than air.
67
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
determined from psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg)
determined from psychrometric chart.
The specific enthalpies at points W and S are shown on the psychrometric Chart
above.
H heater battery = 17.05 ( 34 - 28)
H heater battery = 102.3 kW
68
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
Hs = ma x Cp ( ts - tr )
where:
Hs = Sensible heat loss from room (kW)
ma = mass flow rate of air (kg/s) same as summer rate
for constant volume systems.
Cp = Specific heat capacity of humid air (approx.1.01
kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature(oC)
( ts - tr ) = Hs / ma x Cp
( ts - tr ) = 128 / 17.05 x 1.01
( ts - tr ) = 7.43 deg.C
ts = 22 + 7.43 deg.C
ts = 29.43 oC say 29.5 oC.
69
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
H preheater battery = Preheater battery output (kW)
maf = mass flow rate of fresh air (kg/s)
hP = specific enthalpy at condition P (kJ/kg)
hO = specific enthalpy at condition O (kJ/kg)
where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of supply air (kg/s)
hH = specific enthalpy at condition H (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)
NOTE:
The heater battery load may be reduced by using other forms of heating for some of
the load, e.g. perimeter convectors or radiators.
The amount of moisture added to the air may be calculated from the following
formula:
where:
m moisture added = The amount of moisture or added or
steam flow rate (kg/s)
ma = mass flow rate of air (kg/s)
msS = moisture content at condition S (kg/kg d.a.)
msH = moisture content at condition H (kg/kg d.a.)
DATA:
Outdoor condition is 27oC, 80% saturation.
The Apparatus Dew Point ADP is 8oC
The internal latent heat gain is 40 W per person, plus additional gain of 5 kW.
The internal sensible heat gain is 200 Watts per computer, 100W per person and 15
W/m2 floor area for lights.
The solar gain through windows is 6.0 kW
Maximum occupancy is 80 people.
Number of computers is 80.
The cooling coil contact factor is 0.8.
Duct and fans gains are 2oC.
Fresh air, recirculated air ratio is 20%/80%.
HEAT GAINS
When the supply air temperature has been found from the psychrometric chart then
the mass flow rate of air to offset heat gains can be calculated from the following
formula:
72
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
ma = Hs / ( Cp ( tr - ts ) )
where:
H s = Sensible heat gain to room (kW)
m a = mass flow rate of air (kg/s)
C p = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
73
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
where:
Hcooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined from
psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined from
psychrometric chart
The specific enthalpies at points M and ADP are shown on the psychrometric Chart
above.
where:
Hheater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg) determined from
psychrometric chart.
hD = specific enthalpy at condition D (kJ/kg) determined from
psychrometric chart.
The specific enthalpies at points S and D are shown on the psychrometric Chart
above.
74
Psychrometric Process for Air Conditioning System Lecture By Badran M. Salem
75