Bu0255 6072552 en 3920 Desk
Bu0255 6072552 en 3920 Desk
Bu0255 6072552 en 3920 Desk
2 BU 0255 en-3920
Table of Contents
BU 0255 en-3920 3
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 3 /Allgemei n/Steuermodule/Inhaltsv erzeic hnis @ 0\mod_1317978518480_388.docx @ 4078 @ @ 1
Table of Contents
=== Ende der Liste für T extm arke Inhaltsv erz eichnis ===
1 Introduction ................................................................................................................................................. 6
1.1 General .............................................................................................................................................. 6
1.1.1 Documentation ..................................................................................................................... 6
1.1.2 Document history.................................................................................................................. 6
1.1.3 Copyright notice.................................................................................................................... 6
1.1.4 About this manual ................................................................................................................. 7
1.2 Other applicable documents .............................................................................................................. 7
1.3 Presentation conventions ................................................................................................................... 7
1.3.1 Warning information ............................................................................................................. 7
1.3.2 Other information .................................................................................................................. 7
1.3.3 Text markings ....................................................................................................................... 8
1.3.4 List of abbreviations.............................................................................................................. 9
2 Safety ......................................................................................................................................................... 10
2.1 Intended use .................................................................................................................................... 10
2.2 Selection and qualification of personnel ........................................................................................... 10
2.2.1 Qualified personnel............................................................................................................. 10
2.2.2 Qualified electrician ............................................................................................................ 10
2.3 Safety information ............................................................................................................................ 11
3 AS interface - Fundamentals .................................................................................................................... 12
3.1 Characteristics ................................................................................................................................. 12
3.2 General information about AS-i interfaces ....................................................................................... 12
3.3 Extended data transmission by double slave ................................................................................... 13
4 Data transmission ..................................................................................................................................... 14
4.1 Introduction ...................................................................................................................................... 14
4.1.1 Process data....................................................................................................................... 14
4.1.2 Parameter data ................................................................................................................... 14
4.2 Structure of application data ............................................................................................................ 15
4.3 Message types ................................................................................................................................. 17
4.3.1 Standard Read order .......................................................................................................... 17
4.3.2 NORD-specific read order .................................................................................................. 19
4.3.3 NORD-specific write order .................................................................................................. 20
4.3.4 NORD-specific write/read order .......................................................................................... 21
4.3.5 Error messages .................................................................................................................. 22
4.4 Transmission times .......................................................................................................................... 24
4.5 Structure of the process data ........................................................................................................... 25
4.5.1 Control word ....................................................................................................................... 25
4.5.2 Status word......................................................................................................................... 26
4.5.3 Frequency inverter status machine..................................................................................... 27
4.5.4 Setpoints and actual values ................................................................................................ 31
4.6 Parameter data transmission ........................................................................................................... 33
4.6.1 Details of the PKW area ..................................................................................................... 34
4.6.1.1 Parameter label PKE 34
4.6.1.2 Parameter index IND 37
4.6.1.3 Parameter value PWE 37
5 Examples ................................................................................................................................................... 38
5.1 Example telegrams .......................................................................................................................... 38
5.1.1 Switch-on block → Standby ................................................................................................ 38
5.1.2 Enable with 50% setpoint ................................................................................................... 39
5.1.3 Parameter changes ............................................................................................................ 40
5.1.4 Reading of parameter P701 actual error, Index 0 (last fault) .............................................. 41
5.1.5 Writing of parameter P102 acceleration time, Index 1 ........................................................ 41
6 Parameters ................................................................................................................................................. 42
7 Appendix .................................................................................................................................................... 43
7.1 Repair information ............................................................................................................................ 43
7.2 Service and commissioning information ........................................................................................... 43
7.3 Documents and software ................................................................................................................. 44
4 BU 0255 en-3920
Table of Contents
Pos : 6 /Anl eitung en/El ektr onik /Bussys tem e/Alle Baur eihen/1. (1.)Ei nleitung/!Kapitel Ei nleitung @ 8\m od_1441625462919_388.docx @ 2235978 @ 1 @ 1
BU 0255 en-3920 5
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
1 Introduction
Pos : 7 /Anl eitung en/El ektr onik /Bussys tem e/Alle Baur eihen/1. (1.)Ei nleitung/!Absc hnitt Allgemei nes @ 8\mod_1441352725095_388.docx @ 2235719 @ 2 @ 1
1.1 General
Pos : 8 /Anl eitung en/El ektr onik /Bussys tem e/Alle Baur eihen/1. (1.)Ei nleitung/AS-Interfac e CTT 2 [BU 0255]/Dok um entation [AS-i / CTT 2] @ 19\mod_1510149657175_388.docx @ 2370599 @ 3 @ 1
1.1.1 Documentation
Name: BU 0255
Material number 6072552
Series: AS-i CTT2 protocol for frequency inverter series
NORDAC LINK (SK 270E-FDS and SK 280E-FDS)
Pos : 9 /Anl eitung en/El ektr onik /Bussys tem e/Alle Baur eihen/1. (1.)Ei nleitung/AS-Interfac e CTT 2 [BU 0255]/Dok um enthis torie [AS-i / CTT 2] @ 50\mod_1601015267335_388.docx @ 2673170 @ 3 @ 1
Publisher
Getriebebau NORD GmbH & Co. KG
Getriebebau-Nord-Straße 1 • 22941 Bargteheide, Germany • http://www.nord.com/
Fon +49 (0) 45 32 / 289-0 • Fax +49 (0) 45 32 / 289-2253
6 BU 0255 en-3920
1 Introduction
Pos : 13 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/1. (1.) Einl eitung/AS-Interface CTT 2 [BU 0255]/Z u diesem H andbuch @ 18\m od_1498458576879_388.docx @ 2358447 @ 3 @ 1
DANGER
This warning information warns against personal risks, which may cause severe injury or death.
WARNING
This warning information warns against personal risks, which may cause severe injury or death.
CAUTION
This warning information warns against personal risks, which may cause slight or moderate injuries.
NOTICE
This warning warns against damage to material.
Information
This information shows hints and important information.
Pos : 17 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
BU 0255 en-3920 7
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 18 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/1. (1.) Einl eitung/AS-Interface CTT 2 [BU 0255]/T extausz eichnungen [AS-i / C TT2] @ 18\m od_1498211765318_388.docx @ 2357917 @ 3 @ 1
Text
Type of information Example Marking
Instructions 1. Instructions for actions whose sequence must be
2nd complied with are numbered sequentially.
Bullet points • Bullet points are marked with a dot.
Parameter P746 Parameters are indicated by the prefix "P", a three-
digit number and bold type.
Arrays [-01]) Arrays are indicated by square brackets.
Factory settings { 0,0 } Factory settings are indicated by curly brackets.
Software descriptions "Cancel" Menus, fields, buttons and tabs are indicated by
quotation marks and bold type.
Numbers
Type of information Example Marking
Binary numbers 100001b Binary numbers are indicated by the suffix "b"
Hexadecimal numbers 0000h Hexadecimal numbers are indicated by the suffix "h"
Symbols used
Type of information Example Marking
Cross-reference Chapter Internal cross-reference A mouse click on the text
Section calls up the stated point in the document.
Supplementary External cross-reference
manual
Hyperlink http://www.nord.com/ References to external websites are indicated in
blue and underlined. A mouse click calls up the
website.
Type designations
Designation Description
SK 270E-FDS Series SK 250E-FDS frequency inverter as field distributor with integrated
AS-i interface
SK 280EFDS Series SK 250E-FDS frequency inverter as field distributor with integrated
AS-i interface and STO
Pos : 19 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
8 BU 0255 en-3920
1 Introduction
Pos : 20 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/1. (1.) Einl eitung/AS-Interface CTT 2 [BU 0255]/Abkürz ungsv erz eichnis [AS-i / CTT 2] @ 18\m od_1498209594508_388.doc x @ 2357809 @ 3 @ 1
Abbreviation Meaning
AK Order label/response label
CTT2 Combined Transaction Type 2
DIN Digital input
DO Digital output
FDS Frequency inverter as field distributor
IND Index
I/O Input, Output
IW Actual value
PKE Parameter label
PLC Programmable Logic Control
PKW Parameter label value
PNU Parameter number
PWE Parameter value
PZD Process data
PLC Programmable Logical Controller
STW Control word
SW Setpoint
USS Universal serial interface
ZSW Status word
Pos : 22 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/2. (-) Sicher heit/!Kapitel Sic herheit @ 8\mod_1441952463663_388.docx @ 2236460 @ 1 @ 1
BU 0255 en-3920 9
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
2 Safety
Pos : 23 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/2. (-) Sicher heit/AS-Inter fac e CTT 2 [BU 0255]/Bestimm ungsg emäß e Verw endung AS- Interfac e CTT 2 @ 18\m od_1498210231459_388.docx @ 2357881 @ 2 @ 1
The integrated AS-i interface from the NORD DRIVESYSTEMS Group is used for communication by
this devices with a PLC in an operator's AS interface field bus system. It cannot be used
independently of this. Therefore the specific safety information for the particular frequency inverter
applies in full. This can be obtained from the relevant manual ( Section 7.3 "Documents and
software").
The function extension with the CTT2 protocol is essentially used as a solution for complex drive tasks
with extended functionality, which are implemented with frequency inverters with an integrated AS-i
interface from NORD.
Any other use beyond this description is deemed to be incorrect use.
Pos : 24 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/2. (-) Sicher heit/AS-Inter fac e CTT 2 [BU 0255]/Ausw ahl und Qualifikation des Pers onals_01 [AS-i / CTT 2] @ 18\mod_1498213479816_388.docx @ 2357953 @ 2 @ 1
10 BU 0255 en-3920
2 Safety
2.3 Safety information
Only use bus interfaces and frequency inverters from NORD DRIVESYSTEM Group for their intended
purpose, Section 2.1 "Intended use".
To ensure safe operation of the bus interface, observe all of the instructions in this manual, and in
particular the warning information in the other applicable documents, Section 7.3 "Documents and
software".
Only commission bus interfaces and frequency inverters in their technically unchanged form and not
without the necessary covers. Take care that all connections and cables are in good condition.
Work on and with bus interfaces and frequency inverters must only be carried out by qualified
personnel, Section 2.2 "Selection and qualification of personnel".
Pos : 29 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/3. (2.) Grundlagen/AS- Interfac e CCT 2 [BU 0255]/!Kapitel AS-Interfac e-Gr undlag en @ 18\mod_1498213855319_388.docx @ 2357991 @ 1 @ 1
BU 0255 en-3920 11
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
3 AS interface - Fundamentals
Pos : 30 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/3. (2.) Grundlagen/AS- Interfac e CCT 2 [BU 0255]/Eigensc haften [AS-i / CTT2] @ 18\m od_1498214004920_388.docx @ 2358027 @ 2 @ 1
3.1 Characteristics
The following only describes serial communication of application traffic via the CTT2 protocol.
Parameterisation of the Bus IO bits is carried out as for all NORDAC frequency inverters.
Basic information about the AS interface of the NORDAC LINK frequency inverter can be found in the
manual of the device ( Section 7.3 "Documents and software").
Pos : 31 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/3. (2.) Grundlagen/AS- Interfac e CCT 2 [BU 0255]/Allgem eines z ur AS-Interface Sc hnitts tell e [AS-i / CTT 2] @ 18\mod_1498141432994_388.docx @ 2357594 @ 2 @ 1
In general, the serial interface is suitable for applications in which non time-critical process data and
parameter data orders are carried out. For one-off parameter initialisation, reading of information
parameters (P7xx) for diagnosis and variable, non time-critical changes to setpoints (SW) the CTT2
protocol is a useful alternative to a higher level field bus system, especially if this can enable a
reduction of the number of field bus systems.
However, time-critical control functions should be implemented via the BusIO bits of the AS interface,
as due to the system, relatively long transmission times may result with the CTT2 protocol (for further
details see Section 4.4 "Transmission times"). In the case of acyclic data exchange, the AS-i bus
master must first send a message (order telegram) to the 2nd slave. This slave responds to the
message with a corresponding response (response telegram).
12 BU 0255 en-3920
3 AS interface - Fundamentals
• NORD-specific Write/Read order
Reading out process data (PZD) and parameter data (PKW) from the frequency inverter and write
process data (PZD) and parameter data (PKW) into the frequency inverter with a single command.
Pos : 32 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/3. (2.) Grundlagen/AS- Interfac e CCT 2 [BU 0255]/Erwei terter D atentransfer durc h D oppelslav e [AS-i / CTT 2] @ 18\m od_1498226365271_388.doc x @ 2358248 @ 2 @ 1
BU 0255 en-3920 13
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
4 Data transmission
Pos : 35 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Einführung [AS-i / CTT 2] @ 18\m od_1498220660242_388.docx @ 2358140 @ 2 @ 1
4.1 Introduction
For data transmission between the frequency inverter and the AS-i bus master, process data and
parameter data are exchanged.
The process and parameter data are only transmitted via the CTT2 telegram and by the selection of
the relevant message type.
Pos : 36 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Proz ess daten [AS-i / CT T2] @ 18\m od_1498206040631_388.docx @ 2357674 @ 3 @ 1
Pos : 38 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
14 BU 0255 en-3920
4 Data transmission
Pos : 39 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Struk tur der N utz daten_01 [AS-i / CTT 2] @ 18\m od_1498457143338_388.docx @ 2358411 @ 2 @ 1
Item Meaning
A Order telegram
1 Control word and setpoints (PZD area)
2 Parameter order (PKW area)
3 Processing
B Response telegram
4 Status word and actual values (PZD area)
5 Parameter response (PKW area)
Processing of the process data is carried out in the frequency inverter with high priority, in order to
ensure that a rapid response to control commands or a change in status can be transmitted to the AS-i
bus master without delay.
Processing of PKW data is carried out with low priority and can take considerably longer.
The process and parameter data traffic is therefore carried out via the three NORD-specific message
types which are defined in the CTT2 protocol, with which both process data (PZD) as well as
parameter data (PKW) are acyclically transmitted from the AS-i bus master to the 2nd slave (read
orders and / or write orders).
Pos : 40 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
BU 0255 en-3920 15
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 41 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Struk tur der N utz daten_02_ CTT 2_T elegramm aufbau [AS-i / CTT 2] @ 18\m od_1498199034453_388.doc x @ 2357639 @ 55 @ 1
Code
Code
(Message type)
ID object OK Data
Standard
Read length
Read order Diagnostic Error
object Error
code
NORD-specific OK Data
Read length
Read order PZD channel
Channels
Three different channels are defined for NORD-specific message types:
Channel Description
Pos : 42 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/N achric htenty pen [AS-i / CTT 2] @ 18\m od_1498222523736_388.doc x @ 2358176 @ 2 @ 1
16 BU 0255 en-3920
4 Data transmission
4.3 Message types
The coding for the 4 different message types, indices, response codes, the permissible data lengths
and the structure of the various objects are explained in detail in the following sections.
The address of the frequency inverter, which must be stated for the channels PZD and PKW (with
address)is always "1". If the channel PKW (without address) is used, statement of the address of the
frequency inverter is not required.
The number of bytes to be transmitted is always stated in read length and write length.
Pos : 43 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Standar d Leseauftr ag [AS-i / CTT2] @ 18\m od_1498548995904_388.docx @ 2359567 @ 355555 @ 1
Length
Code Meaning Contents Index No. Object (permissible)
0 ID object max. 14
16 Read order Index, length
1 Diagnostic object max. 3
80 Read response OK Data
144 Read response not OK Error code
6 AS-i mode
BU 0255 en-3920 17
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Example of a query of the ID object
Order telegram
Byte 1 2 3
Meaning Code Index Length
Value 16 0 14
Response telegram
Byte 1 2 3 … 15
Meaning Code Manufacturer ID Manufacturer ID … Configuration
High byte Low byte Low byte
Value 80 1 137
Example of an incorrect response for the ID object with an error code with regard to utilisation
Diagnostic object
The diagnostic object consists of a total of 3 bytes and is structured as follows:
Byte Definition
Diagnosis code Meaning
0 No error
1
255 Error
3 Microcontroller temperature
Response telegram
Byte 1 2 3 4
Error no.
Meaning Code No error (Frequency inverter)
Temperature
Value 80 0 0 45
Pos : 44 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/N ORD Les eauftrag [AS-i / CTT 2] @ 18\m od_1498554551328_388.doc x @ 2359639 @ 355 @ 1
sp
18 BU 0255 en-3920
4 Data transmission
4.3.2 NORD-specific read order
The structure or coding of the NORD-specific read order consists of the following objects.
Length
Code Meaning Contents Index No. Object (recommended)
3 PZD channel 3, 5, 7, 9 1)
18 Read order Index, length 4 PKW channel with address 9 2)
47 PKW channel without address 8 3)
82 Read response OK Data
146 Read response not OK Error code
1) The data length can be freely selected up to the maximum length of the channel, i.e. up to 9 bytes for PZD.
2) The data length can be freely selected up to the maximum length of the channel, i.e. up to 9 bytes for PKW with address.
3) The data length can be freely selected up to the maximum length of the channel, i.e. up to 8 bytes for PKW without address.
The current process data PZD can be queried at any time via the PZD channel by means of the
NORD-specific Read order. In contrast, to read parameter data PKW by means of the PKW channel, a
previous corresponding Write order is mandatory. The Read order returns the last response telegram
of the PKW channel as often as is necessary.
Example for a query of process data ZSW, IW1, IW2 and IW3)
Order telegram
Byte 1 2 3
Meaning Code Index Length
Value 18 3 9
Response telegram
Byte 1 2 3 4 5
Meaning Code Address Status word Status word IW1
USS High byte Low byte High byte
Value 82 1 (Bit 8 to 15) (Bit 0 to 7) (Bit 8 to 15)
Response telegram
Byte 6 7 8 9 10
Meaning IW1 IW2 IW2 IW3 IW3
Low byte High byte Low byte High byte Low byte
Value (Bit 0 to 7) (Bit 8 to 15) (Bit 0 to 7) (Bit 8 to 15) (Bit 0 to 7)
Note: Byte 3 to 10 corresponding to USS – Protocol (also compare examples in chapter 5 "Examples")
BU 0255 en-3920 19
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 45 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/N ORD Schr eibauftrag [AS-i / C TT2] @ 18\m od_1498556000617_388.docx @ 2359675 @ 35 @ 1
Length
Code Meaning Contents Index No. Object (mandatory)
3 PZD channel 3, 5, 7, 9
Index, length,
19 Write order 4 PKW channel with address 9
data
47 PKW channel without address 8
83 Write response OK
147 Write response not OK Error code
In the case of process data PZD, with a NORD-specific Write order via the PZD channel, the control
word STW and up to 3 setpoints (SW1 – SW3) can be transmitted. For parameterisation of the
frequency inverter via the PKW channel, the USS telegram is attached as a data package.
I.e. the parameter order always contains the PKW area at the end of the telegram.
Two transmission options are available with the PKW channel:
• PKW channel with address
• PKW channel without address
With Index No. 4, i.e. PKW channel with address, the address of the frequency inverter is stated in the
first byte of the data (i.e. Byte 4). Subsequently (from byte 5) the PKW of the USS telegram follow. In
the case of index 47, however, the address is omitted. The PKW of the USS telegram thus start from
the byte 4.
Order telegram
Byte 1 2 3 4 … 11
Meaning Code Index Data length USS telegram
(PKW)
Value 19 47 8
Note: Byte 4 to 11 corresponding to USS – Protocol (also compare examples in chapter 5 "Examples")
Example for the response after a successful write order via the PKW channel with response code from
the frequency inverter
Response telegram
Byte 1
Meaning Code
Value 83
Here it should be noted that the response code does not state whether the parameter order has been
executed by the frequency inverter. For this a NORD-specific Read order must be explicitly carried out
with the PKW channel.
20 BU 0255 en-3920
4 Data transmission
Pos : 46 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/N ORD Schr eib-/Leseauftr ag [AS-i / CTT2] @ 18\m od_1498570526360_388.docx @ 2359751 @ 355 @ 1
Length
Code Meaning Contents Index No. Object (mandatory)
For a NORD-specific Write/Read order, the two message types or orders are executed with a single
telegram order. To write the control word STW, write three setpoints SW1 – SW3 and to read e.g. only
two of the actual values IW1 and IW2, the following telegram structure would be selected.
Example for query of process data (writing of STW and SW1, SW2, SW3)
Order telegram
Byte 1 2 3 4 5
Meaning Code Index Read length Write length Address
(Frequency inverter)
Value 29 3 7 9 1
Order telegram
Byte 6 7 8 9 10
Meaning Control word Control word SW1 SW1 SW2
High byte Low byte High byte Low byte High byte
Value (Bit 8 to 15) (Bit 0 to 7) (Bit 8 to 15) (Bit 0 to 7) (Bit 8 to 15)
Order telegram
Byte 11 12 13
Meaning SW2 SW3 SW3
Low byte High byte Low byte
Value (Bit 0 to 7) (Bit 8 to 15) (Bit 0 to 7)
BU 0255 en-3920 21
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Example for process data response (reading of ZSW, IW2 and IW2)
Response telegram
Byte 1 2 3 4 5
Meaning Code Address Status word Status word IW1
(Frequency inverter) High byte Low byte High byte
Value 93 1 (Bit 8 to 15) (Bit 0 to 7) (Bit 8 to 15)
Response telegram
Byte 6 7 8
Meaning IW1 IW2 IW2
Low byte High byte Low byte
Value (Bit 0 to 7) (Bit 8 to 15) (Bit 0 to 7)
Pos : 47 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/F ehl ermel dungen [AS-i / CTT 2] @ 18\m od_1498738458682_388.doc x @ 2359979 @ 355 @ 1
1 Invalid index
2 Invalid length
4 Full capacity (order not completely executed within the time window)
Error code "1" "Invalid index" occurs if an index is accessed, which is not implemented in the
frequency inverter. The indices "0" and "1" for standard Read orders and indices "3", "4" and "47" for
the three NORD-specific message types are implemented in the frequency inverter. All other indices
are invalid and are indicated acknowledged with a corresponding error message or indicated with error
code 1.
The length of the data which can be written or read is specified separately for each index and can be
obtained from the relevant chapters for the message types. For Read orders in which fewer data are
requested than are defined for the particular index, only the requested data without error message
(without error code) are returned. If more data are requested, only the defined data without error
messages (no error code) are returned.
22 BU 0255 en-3920
4 Data transmission
For Write orders in which more data are to be written than is specified for the relevant index, the error
object with error code "2" is returned. Only complete parameter data PKW orders can be executed,
therefore for the PKW channel, all data lengths which do not correspond to the defined length receive
a response with error code "2".
For the PZD channel, the Write order must consist of at least the address and the control word STW.
The number of setpoints SW can be varied as required between 0 to 3 setpoints, however both of the
bytes (High and low byte) of which the setpoint consists must be transmitted.
If the data length for the PZD channel does not comply with the defined requirement or the stated
length in the CTT2 protocol, error code "2" is returned.
Orders which are not implemented in the double slave receive the response "Standard Read response
not OK" and error code "3".
Each order must be responded to by the double slave before a new order can be sent. If this rule is
breached, the slave returns the error code "5" after the second order has been received.
Orders which are received by the double slave must be responded to by the 2nd slave within 200 ms.
For the measurement of the timeout, the period between receipt of the complete order telegram and
the start of the response telegram is decisive. If the time is exceeded, the double slave signals a
timeout to the AS-i bus master. Error code "4" is returned. The frequency inverter is overloaded and
could not process the request within the specified time window.
BU 0255 en-3920 23
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 49 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Ü bertr agungszei ten [AS-i / CCT 2] @ 18\mod_1498545562753_388.docx @ 2359495 @ 2 @ 1
24 BU 0255 en-3920
4 Data transmission
Pos : 51 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Proz ess datenaufbau [AS-i / CTT 2] @ 19\mod_1499336721819_388.docx @ 2360349 @ 2 @ 1
BU 0255 en-3920 25
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 54 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
26 BU 0255 en-3920
4 Data transmission
Pos : 55 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/Z ustandsm asc hine des Freq uenz umrichters @ 27\mod_1550232066512_388.docx @ 2487670 @ 355 @ 1
Fault
Fault
Not ready to switch-on
active
Fault
Switch-on inhibit
Ready to switch-on
Switched on
Item Meaning
A…H Frequency inverter statuses ( Table "Frequency inverter statuses")
1…15 Status transitions ( Table "Status transitions")
BU 0255 en-3920 27
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Status Description
A Not ready to switch-on Initial state after switching on the frequency inverter. As soon as the loading
relay engages, the frequency inverter automatically changes to the status
"Switch-on inhibit".
B Switch-on inhibit Second status after switching on the frequency inverter, which can only be
exited with the control command "Shut-down". The charging relay is switched
on.
C Ready to switch-on In this status, initialisation of the frequency inverter is complete. The output
voltage is blocked.
Information
During the initialisation process the response to a bus master telegram does
not yet contain the response to the control command which has been issued.
On the basis of the response from the bus participant, the control system must
determine whether the control command has been executed.
D Switched on Frequency inverter ready for operation.
E Operation enabled The frequency inverter receives and processes setpoints.
F Quick stop active Quick stop function is being executed (the drive is stopped), the frequency
inverter changes to the status "Switch-on inhibit".
G Fault active If a fault error occurs, the frequency inverter changes to this status and all
functions are blocked.
H Fault After processing of the response to the fault (fault active), the frequency inverter
changes to this status, which can only be exited with the control command
"Acknowledge fault".
28 BU 0255 en-3920
4 Data transmission
Status transitions
BU 0255 en-3920 29
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
6 5 4 3 2 1 0
Switch-on inhibit 1 X X 0 0 0 0
Ready to switch-on 0 1 1 0 0 0 1
Switched on 0 1 1 0 0 1 1
Operation enabled 0 1 1 0 1 1 1
Fault 0 X X 1 0 0 0
Fault active 0 X X 1 1 1 1
30 BU 0255 en-3920
4 Data transmission
Pos : 57 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Sollw ert und Istw ert [AS-i / CTT 2] @ 18\mod_1498460326813_388.docx @ 2358519 @ 3 @ 1
SK 270E-FDS, SK 280E-FDS
To slave / frequency inverter Setpoint 1 P546, Array [-01]
Setpoint 2 P546, Array [-02]
Setpoint 3 P546, Array [-03]
To AS-i bus master Actual value 1 P543, Array [-01]
Actual value 2 P543, Array [-02]
Actual value 3 P543, Array [-03]
Percentage transmission
The process value is transmitted as an integer with a value range of -32768 to 32767 (8000 hex to
7FFF hex). The value "16384" (4000 hex) corresponds to 100 %. The value "-16384" (C000 hex)
corresponds to -100 %.
For frequencies, the 100% value corresponds to parameter P105 Maximum frequency of the
frequency inverter. For current, the 100% value corresponds to parameter P112 Torque current limit
of the frequency inverter.
Frequencies and currents result from the following formulae:
Binary transmission
Inputs and outputs as well as digital input bits and bus output bits are evaluated bit-wise.
BU 0255 en-3920 31
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Transmission of positions
In the frequency inverter, positions have a value range of -50000.00....50000.00 rotations. A rotation of
the motor can be subdivided into a maximum of 1000 increments. The subdivision depends on the
encoder which is used.
The 32 Bit value range is divided into a "Low" and a "High" word, so that two setpoints or actual values
are required for the transmission.
Only the "Low" word for the position can also be transmitted. This results in a limited value range from
32,767 to -32,768 rotations. This value range can be extended with the ratio factor (Parameter P607
Ratio and P608 Reduction Ratio), however this reduces the resolution accordingly.
Pos : 58 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
32 BU 0255 en-3920
4 Data transmission
Pos : 59.1 /Anl eitungen/Elek tronik/Bus systeme/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/M odule für Modulgruppe # Param eterdatenübertr agung # [AS-i / CTT2]/Par ameter datenübertragung_01 [AS-i / CTT 2] @ 18\mod_1498466683551_388.docx @ 2358590 @ 2 @ 1
BU 0255 en-3920 33
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 59.3 /Anl eitungen/Elek tronik/Bus systeme/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/M odule für Modulgruppe # Param eterdatenübertr agung # [AS-i / CTT2]/D etails z um PKW-Bereic h [AS-i / CTT 2] @ 18\m od_1498466741050_388.doc x @ 2358841 @ 3 @ 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SPM
AK PNU
PNU Bits 0…10 contain the number of the required parameters in the response telegram from the
frequency inverter.
Parameter numbers can be found in manual frequency inverter.
SPM Bit 11 is the toggle-bit for spontaneous messages. This function is not supported.
AK Bits 12...15 contain the order or response label.
34 BU 0255 en-3920
4 Data transmission
The label for a negative response is always the value "7" (order cannot be executed) for all order
labels. In case of a negative response, an error message is also listed in the response from the field
distributor in PWE2.
BU 0255 en-3920 35
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 59.6 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
36 BU 0255 en-3920
4 Data transmission
Pos : 59.7 /Anl eitungen/Elek tronik/Bus systeme/All e Baurei hen/6. (6.) D atenübertragung/PR OFIN ET IO [BU 2400]/Module für Modulgruppe # Param eterdatenübertr agung # [PNT , PNS + PBR]/Param eterindex [PN T, PNS, PBR] @ 13\m od_1476869316987_388.doc x @ 2265934 @ 4 @ 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
P1…P4 No information (all "0")
Arrays 1…64 P1…P4
Sub-index
For values which depend on the parameter set, the parameter set can be selected via Bit 8 and Bit
9 of the index (0 = Parameter set 1, 1 = Parameter set 2 etc.).
For array parameters the sub-index can be addressed via Bit 10 to Bit 15 (0 = Array element 1, 1 =
Array element 2 etc.).
For parameters which do not depend on the parameter set, Bit 8 to Bit 15 are used for the sub-
index. In order for the sub-index to be effective, the corresponding order label (numbers 6, 7, 8 and 11
and 12) must be used.
Examples for address formation for array parameters which depend on parameter sets
Array element Parameter set
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 1 0 1 0 1 No information (all "0")
5 (0001 01b) 2 (01b)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 1 0 1 0 1 1 1 No information (all "0")
21 (0101 01b) 4 (11b)
Structure of parameter and sub-index values Manual for the relevant frequency inverter.
Pos : 59.8 /Anl eitungen/Elek tronik/Bus systeme/All e Baurei hen/6. (6.) D atenübertragung/PR OFIN ET IO [BU 2400]/Module für Modulgruppe # Param eterdatenübertr agung # [PNT , PNS + PBR]/Param eterwert PWE [PNT, PNS, PBR ] @ 13\m od_1476869322988_388.docx @ 2265969 @ 4 @ 1
99.99 × 1
99.99 s = 0.01 = 99.99 × 100 = 9999
BU 0255 en-3920 37
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
5 Examples
Various examples are shown below to clarify the control and parameterisation of the frequency
inverter with the bus system. Please note that the datas concerning the word or byte depends on
the selected message type (code) according to section 4.3 "Message types". Therefore they are to
be considered as examples.
Pos : 62 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Beis piel tel egramme [AS-i / CTT2]/Beis piel tel egramme [AS-i / CTT2] @ 50\m od_1601016015765_388.docx @ 2673246 @ 2333 @ 1
Procedure
1. Check the last status word (e.g. "0B70h").
Telegram
Byte 2 1 3 4
Type STW SW1
Value 04h 7Eh 00h 00h
38 BU 0255 en-3920
5 Examples
3. Check the response telegram (status word "0B31h").
As soon as the frequency inverter is in "Standby" status, it sends a response telegram:
Telegram
Byte 1 2 3 4
Type ZSW IW1
Value 0Bh 31h 00h 00h
Procedure
1. Check the last status word (ZSW "0B31h").
Telegram
Byte 1 2 3 4
Type ZSW IW1
Value 0Bh 31h 00h 00h
2. Generate the control word ("047Fh") and specify the setpoint (SW1 "2000h" = 50%).
To switch the frequency inverter to "Operation enabled" status and set the setpoint, the following
telegram must be sent:
Telegram
Byte 1 2 3 4
Type STW SW1
Value 04h 7Fh 20h 00h
3. The frequency inverter accelerates the motor in the ramp. As soon as the frequency inverter has
reached the 50% setpoint, it sends a response telegram:
Telegram
Byte 1 2 3 4
Type ZSW IW1
Value 0Bh 37h 20h 00h
BU 0255 en-3920 39
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Procedure
• • Specify the order label (Change parameter value = 7),
• • Select the parameter (P102 = "66h").
• • Select parameter set 3 (IND = 02h)
• • Set the parameter value ("3E8h").
Telegram
Byte 1 2 3 4 5 6 7 8
Type PKE IND PWE PWE
Value 70h 66h 00h 02h 00h 00h 03h E8h
• • When the order has been fully implemented by the frequency inverter, it sends the response
telegram:
Telegram
Byte 1 2 3 4 5 6 7 8
Type PKE IND PWE PWE
Value 40h 66h 00h 02h 00h 00h 03h E8h
Pos : 63 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
40 BU 0255 en-3920
5 Examples
Pos : 64 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Beis piel tel egramme [AS-i / CTT2]/Beis piel e für die Param eterüber tragung_02 [AS-i / CTT 2] @ 50\mod_1601017653875_388.docx @ 2673287 @ 3 @ 1
Example telegram
Field Data size Byte Value Explanation
Order label AK 1 Byte (upper 0 1h Order parameter value (read)
Nibble)
and 1 Byte 1 2BDh Parameter number P701 = 2BDh
parameter value PWE
12BDh
Parameter index 2 Byte 2 00h Parameter sub-index
3 00h
Parameter value 4 Byte 4 00h Setting value not set with read order
5 00h
6 00h
7 00h
Pos : 65 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/6. (6.) D atenübertragung/AS-Interface CCT2 [BU 0255]/Beis piel tel egramme [AS-i / CTT2]/Beis piel e für die Param eterüber tragung_03 [AS-i / CTT 2] @ 50\mod_1601018071445_388.docx @ 2673325 @ 3 @ 1
Example telegram
Field Data size Byte Value Explanation
Order label AK 1 Byte (upper 0 2h Order parameter value (read)
Nibble)
and 1 Byte 1 66h Parameter number P102 = 66h
parameter value PWE
2066h
Parameter index 2 Byte 2 01h Parameter sub-index
3 00h
Parameter value 4 Byte 4 00h The time "2.5 s" (250 = FAh) is to be set.
5 00h
6 00h
7 FAh
Pos : 67 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/7. (4.) Param eter/AS-Inter fac e / CTT 2 [BU 0255]/!Kapitel Param eter @ 19\m od_1499265162513_388.docx @ 2360301 @ 1 @ 1
BU 0255 en-3920 41
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
6 Parameters
The frequency inverter parameters are communicated as words (16 Bit/Word). Exceptions to this are
position values (POSICON), which are communicated as double words (32 Bit).
For field bus operation, several parameters must be set on the frequency inverter.
The parameters can be set with
• • An external control or ParameterBox ( Manual BU 0040),
• • NORDCON software ( Manual BU 0000) or
• • The operator's PLC project.
Pos : 68 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/7. (4.) Param eter/AS-Inter fac e / CTT 2 [BU 0255]/Param etereinstellungen am Frequenz umrichter - Z us atz par ameter [AS-i / CT T2] @ 50\m od_1601019124954_388.docx @ 2673367 @ 5 @ 1
Additional parameters
The following table contains a list of additional parameters which are relevant for the bus interface.
Pos : 69 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/7. (4.) Param eter/AS-Inter fac e / CTT 2 [BU 0255]/Param etereinstellungen FU - Inform ations par ameter _01 [SK 270E-FDS / SK280E-FDS] @ 18\m od_1498473195359_388.doc x @ 2359308 @ @ 1
Information parameter
Information parameters are used to display current and archived error messages, as well as current
operating states and settings.
The following table contains a list of information parameters which are relevant for the bus interface.
42 BU 0255 en-3920
7 Appendix
7 Appendix
Pos : 72 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/9. (7.) Anhang/Repar aturhi nweis e @ 42\mod_1589956872993_388.docx @ 2612990 @ 2 @ 1
Information
Third party accessories
Getriebebau NORD GmbH & Co. KG cannot accept liability for third party accessories if these are
returned with the device.
Information
Accompanying document
Please complete the accompanying document for the return. This can be found on our homepage
www.nord.com or directly under the link Warenbegleitschein
BU 0255 en-3920 43
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
Pos : 75 /Anl eitungen/Elek tronik/Bus system e/All e Baurei hen/9. (7.) Anhang/AS-i CTT2 [BU 0255} /Dok um entati on und Softw are [AS-i / CT T2] @ 18\m od_1498231574401_388.docx @ 2358284 @ 2 @ 1
Documentation Contents
BU 0250 Manual for NORDAC LINK SK 250E-FDS, frequency inverter as field distributor
BU 0000 Manual for use of NORD CON software
BU 0040 Manual for use of NORD parameterisation units
Software
Software Description
NORD CON Parametrisation and diagnostic software
44 BU 0255 en-3920
Key word index
Pos : 77 /Allgem ein/Steuermodul e/Stic hwortv erz eichnis @ 0\m od_1317978518730_388.doc x @ 4101 @ @ 1
Parameter T
BU 0255 en-3920 45
NORDAC LINK (SK 270E-FDS ... SK 280E-FDS) – Supplementary manual for AS-Interface CTT2
46 BU 0255 en-3920
Key word index
BU 0255 en-3920 47
6072552 / 3920