GST 2002
GST 2002
GST 2002
CONTENTS
Installation Precautions ............................................................................................... 1
Preface EN 54 Information ........................................................................................... 2
Chapter 1 Product Introduction................................................................................... 3
Chapter 2 Technical Specifications ............................................................................ 4
2.1 Operating Voltage ................................................................................................. 4
2.2 Standby Batteries .................................................................................................. 4
2.3 Communication Loop Parameters ........................................................................ 4
2.3.1 RS485 Communication Loop .................................................................... 4
2.3.2 RS232 Communication Loop .................................................................... 5
2.4 Detection Loop Parameters .................................................................................. 5
2.5 Output Loop Parameters ....................................................................................... 5
2.5.1 FIRE ALARM OUTPUT (+, -) .................................................................... 5
2.5.2 F.P.E. OUTPUT (+, -) ................................................................................ 6
2.5.3 SOUNDER CIRCUIT OUTPUT (+, -) ........................................................ 6
2.5.4 FAULT OUTPUT (NC, COM, NO) ............................................................. 6
2.6 Dimensions............................................................................................................ 6
Chapter 3 Construction and Components ................................................................. 7
3.1 Appearance and Internal Construction ................................................................. 7
3.1.1 Display Area .............................................................................................. 7
3.1.2 Description of LEDs .................................................................................. 8
3.1.3 Description of Keys ................................................................................... 9
3.1.4 Zone Indication and Manual Interventional Panel (ZCP)........................ 10
3.2 Components ........................................................................................................ 11
3.2.1 Standard Components ............................................................................ 11
3.2.2 Optional Units .......................................................................................... 11
3.3 Peripheral Devices .............................................................................................. 13
3.3.1 A Series of Intelligent Fire Detectors ...................................................... 13
3.3.2 Modules ................................................................................................... 13
3.3.3 Loop Isolator ........................................................................................... 13
3.3.4 Manual Call Points .................................................................................. 13
3.3.5 Sounder Strobes ..................................................................................... 13
3.3.6 Repeater Panel ....................................................................................... 14
3.4 Defining Tool Software ........................................................................................ 14
Chapter 4 Installation ................................................................................................. 15
4.1 Component Inspection ........................................................................................ 15
4.2 Installing the Cabinet ........................................................................................... 15
4.3 Start-up Check..................................................................................................... 16
4.4 Connections of Peripheral Devices ..................................................................... 16
4.4.1 Connection of Mains Power .................................................................... 16
4.4.2 Connection of Batteries........................................................................... 17
4.4.3 Connection of Peripheral Devices .......................................................... 17
4.5 Connection Checking and Device Registration .................................................. 20
4.5.1 Connection Checking .............................................................................. 20
4.5.2 Device Registration ................................................................................. 20
4.6 Device Definition ................................................................................................. 21
Page I
Page II
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Do not attempt to install, service, or operate this unit until this manual is read and
understood.
This equipment must be installed in accordance with these instructions and the
appropriate national, regional and local regulations specific to the country and
location of the installation. Consult with the appropriate Authority Having
Jurisdiction (AHJ) for confirmation of the requirements.
GST200-2 Fire Alarm Control Panel (FACP) shall only be installed and serviced by
trained specialist.
Disconnect all sources of power before servicing. Control unit and associated
equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Page 1
Preface EN 54 Information
GST200-2 Intelligent Fire Alarm Control Panel (FACP) complies with the
EN 54
requirements of EN 54-2 1997+A1: 2006 and EN 54-4 1997+A1: 2002+A2:
√
2006. In addition to the basic requirements of these standards, the panel
conforms to the following optional requirements.
Page 2
GST200-2 Intelligent Fire Alarm Control Panel (FACP) is designed to comply with EN
54-2 standard with qualities of simple installation, operation, and easy maintenance. It is
used in fire alarm system with the following features:
It controls at most 30 zones. Each zone has its own alarm and fault/disable LEDs
and a label.
Maximum two Class A loops. The first loop can have up to 235 addressable
devices, and the second up to 242 devices. It is compatible with a series of
addressable GST products, which are intelligent sounder strobe (I-9403) complying
with EN 54-3, rate of rise and fixed temperature heat detector (I-9103) complying
with EN 54-5, photoelectric smoke detector (I-9102) complying with EN 54-7,
intelligent manual call point (I-9202) complying with EN 54-11, intelligent reflective
beam detector (I-9105R) complying with EN 54-12, input and output module
(I-9300, I-9301) complying with EN 54-18, and loop isolator (C-9503) complying
with EN 54-17.
The LCD can display 8 lines in total and 18 characters each line, assisting the 15
LEDs in displaying important information.
The memory does not lose data even if power supply is accidentally removed.
It has manual keys for each zone, which can activate/silence the sounder strobes
separately.
Automatically prompting operation steps for every alarm device and for smoke
exhaust and fire extinguishing equipment by field programming.
Page 3
Fuse: 2A delay
Page 4
Page 5
2.6 Dimensions
420mm×580mm×202mm
Page 6
Fig. 3-1
1 Clock 2 LCD 3 Printer panel 4 Zone indication and manual intervention panel (ZCP)
5 Keypad 6 LED 7 Optional units (Fireman’s Control Panel, FCP)
Fig. 3-2
1 Display control 2 Zone indication and manual intervention panel (ZCP) 3 Printer
4 Optional units (FCP-fireman’s control panel) 5 Speaker 6 Power supply
7 Loop interface board 8 Transformer 9 PSU filter 10 Loop board
3.1.1 Display Area
Page 7
Fig. 3-3
FIRE: Red. It illuminates when the FACP detects an alarm condition of connected
detectors. After fire condition is removed, the fire status can only be cleared by
pressing RESET key, and this LED goes out simultaneously.
COMMON FAULT: Yellow. It illuminates when the FACP detects fault of connected
devices or itself. It goes out automatically after the fault condition is removed.
TEST MODE: Yellow. It illuminates when any zone is in test mode. It goes out when
test mode is canceled.
POWER ON: Green. It illuminates when the mains power or battery is normal.
SYSTEM FAULT: Yellow. It illuminates if the program encounters a dead halt or the
system cannot work normally. After the fault condition is removed, only by pressing
RESET, can system fault be cleared, and this LED goes out.
POWER FAULT: Yellow. It illuminates when the mains power, battery or charger of
the FACP is in fault condition. It goes out when the fault is cleared.
F.P.E. FLT/DIS: Yellow. It flashes when F.P.E. output is in fault and illuminates
steadily after the F.P.E. output is disabled. It goes out after fault and disabled
conditions are cleared.
DELAY MODE: Yellow, it illuminates when the output is set in delay mode. It goes
out when the delay mode is canceled.
SILENCE: Yellow. It illuminates when the sounders are silenced. It goes out until a
new alarm comes, or the FACP is reset or EVAC key is pressed.
PRE-ALARM: Red. It illuminates when there is pre-alarm message.
Page 8
ACK/MUTE: Pressing this key will manually acknowledge an alarm and silence the
FACP. If new alarm comes, the FACP will sound again. In PAS (Positive Alarm
Sequence) mode, pressing this key in 15 seconds after the alarm will start the
second-stage delay.
SILENCE: For silencing all sounders in the system, and lighting the SILENCE LED.
This key requires operator password.
EVAC: For starting all sounders in the system, and lighting the EVACUATE LED.
This key requires operator password.
RESET: For clearing all alarm messages, all detector alarms, and all outputs in
order to reset the FACP to normal state. This key requires operator password.
BROWSE: Pressing this key will enter device-browsing screen to browse devices
by loop, by zone or by group, to check zones in test, to browse definition of
communication devices, to browse definition of ZCP or to browse cause and effect
equations.
LOG: For searching and browsing history records.
MODE: Pressing this key(operator password required)can enter setup screen to
set contrast, message display mode, printing mode, pre-alarm mode, and manual
start or stop mode.
VIEW FAULT: Pressing this key can check all fault messages if the LCD is not
displaying fault messages.
TEST: Pressing this key can enter test setup screen to self-test the FACP, to set a
zone into test mode, to set a zone to exit test mode, and to set all zones to exit test
mode. This key requires operator password.
LOCK: Locking the keypad when it is unlocked.
VIEW DISABLE: Pressing this key can check all disabled messages if the LCD is
not displaying disabled messages.
ENABLE/DISABLE: Pressing this key can enter ENABLE/DISABLE screen to
enable/disable devices, outputs or delayed outputs, and to delete disablement
through network. This key requires operator password.
Page 9
Fig. 3-4
On the ZCP, each unit consists of a key, two indicators and a label. The key is for
start/stop control. Device labels can be stuck on the right side of the keys, and the user
can put the corresponding names on them. Zone indication and manual intervention
panel can complete the following functions through defining.
3.1.4.1 Zone Indication
LEDs
Fire: Red. It illuminates when a fire occurs in a zone. It goes out after the FACP is
reset.
Fault/Disable: Yellow. It flashes when there is any fault with the zone. If all devices
in this zone have been disabled, the LED illuminates steadily. It goes out after the
fault conditions are cleared or the FACP is reset.
Page 10
3.2 Components
A standard FACP consists of main board, loop interface board, power supply, display
area, and zone indication and manual intervention panel (ZCP).
Main board
Main board is the core of the FACP, which contains CPU and interfaces to other
main parts and optional parts.
Loop interface board
This is the signal interface of the FACP, containing ports for communication,
detection, fire alarm output and fault output etc. The loop interface board connects
field devices and the FACP into a complete fire alarm system.
Power supply
It provides power to the main board, loop interface board and printer. Its backup
feature ensures that devices registered during commission will not be lost in case
of power fault.
Display area
This part is used to indicate and display different status of the system, and enables
relative operations through keypad (browsing, programming, printing and etc).
Zone indication and manual intervention panel (ZCP)
The ZCP can indicate fire alarm, fault/disable state of corresponding devices, and
start and stop them accordingly.
P-9901 Printer
It is a built-in micro printer. With dot matrix printing it can print 96 kinds of ASCII
code characters (capital or lower case of Latin letters, figures and symbols), 128
coded non-standard characters and chart symbol (some Chinese characters,
Greek letters, block symbol etc.), and 16 code characters (6×7 dot) which can be
defined by the user through programming, and replace any code font by command,
so as to print characters of different language.
Loop board
The loop board is used as the second Class A detection interface for connecting more
addressable devices. The construction of the loop board is shown in Fig. 3-5.
Page 11
Fig. 3-5
1 24VDC power input.
2 Communication port XS3, 20P data cable, connecting to the main board.
3 Class A output, wiring method is the same as that of Class A detection loop on
loop interface board. Refer to Section 4.4.3.4 for details.
4 Loop-shift indicator HL1, red. It illuminates when the loop line shifts.
5 Loop output shut-down indicator HL2, red. It illuminates when the loop output is
shut down.
6 Communication indicator HL3, red. It illuminates when communicating with the
main board.
Communication card
GST200-2 Intelligent Fire Alarm Control Panel (FACP) provides a multi-functional
communication port, connecting with network cards to realize networking among
GST series FACPs, to form urban fire alarm supervisory network through public
telephone network and to fulfill graphic supervision by connecting with Graphic
Monitor Center (GMC) system at the control center of buildings. The FACP
monitors the running of network cards in real time so that the card can work after
being inserted.
GST200-2 provides two kinds of network cards: Local Network Card (RS485 card)
and Monitor & Control Card (RS232 card). Their structures are shown in Fig. 3-6.
Fig. 3-6
Page 12
Note: You need to include an RS232 card in your first order of GST200-2 FACP.
Only with this card, device definition and C&E equations can be downloaded
from PC.
GST200-2 can connect with a series of fire detectors, such as I-9102, I-9103, and
I-9105R. The detectors mounted in the protected area transmit monitoring message to
the FACP through Class A loop. Every detector has its own address with which the
FACP can supervise the information of alarm, fault, and normal status of the detectors.
3.3.2 Modules
GST200-2 can connect with I-9300 Addressable Input Module and I-9301 Addressable
Single I/O Module. I-9300 module is used for receiving normally open digital signal from
fire protection devices and transmitting the signal back to the fire alarm control panel.
I-9301 module is for connecting fire protection devices that need to be controlled by the
FACP, such as smoke valve, fresh air valve, and damper valve. It can also receive
answer signal from these devices.
Loop Isolator can remove the shorted part of loop from the whole system to ensure
normal operation of other devices and to ascertain the location of the part in fault. After
the fault is repaired, the loop isolator can automatically reset the removed part into the
system.
A series of manual call points (such as I-9202) can be connected to the loop of
GST200-2. When fire is confirmed manually, pressing the glass on the MCP, alarm
signal can be sent to the FACP. After receiving the alarm signal, the FACP will show the
number and location of the MCP, and sound alarm.
Page 13
Page 14
Chapter 4 Installation
6 Define devices and C&E equations on a PC and download them to the FACP
through definition software according to engineering configuration.
Page 15
Installation Holes
Wiring Holes
Fig. 4-1
Check if the LCD showing system messages such as fire alarm is illuminated.
Check if the LEDs showing the state of system can be illuminated one by one.
Check if the LEDs showing the device state on ZCP are illuminated in turn.
Page 16
Fig. 4-2a
Refer to the Standby Battery Calculations section for the size of the batteries required
for a particular installation.
Connect the batteries according to Fig. 4-2b and then connect with the battery terminal
P4.
P4(-) P4(+)
Fig. 4-2b
Note: Do not make the final battery connections until the installation is
completed.
4.4.3 Connection of Peripheral Devices
Caution: Do not connect power to your device until you have completed all
input and output connections. Failure to do so may result in injury!
Fig. 4-3
Page 17
FAULT OUTPUT (XT8): Fault relay is closed in normal condition, and it’s opened in
fault condition.
F.P.E. OUTPUT (XT6): It outputs according to settings in Section 6.4.5 when there
is fire alarm. It can be disabled, and does not output when fire alarm occurs in
disabled state. It can be included into C&E equation, but cannot be set at delay
mode. The FACP alarms fault when connected cable in short or open circuit.
FIRE ALARM OUTPUT (XT5): It outputs when there is fire and gives fault signals
when connected circuit is short or open.
LOOP BUS (XT2, XT4): Class A loop can connect with up to 235 addressable
devices. With loop isolator in Class A loop, the detector protected by loop isolator is
not missing when there is short or open circuit. In this case, the FACP reports loop
fault.
RS-485 (XT11, XT12): To be connected with repeater panel and FACP.
earth (X8): This terminal is for checking earth fault when shorted.
F.P.E. OUTPUT, SOUNDER CIRCUIT OUTPUT and FIRE ALARM OUTPUT can
provide three output modes, which are 24VDC voltage output, normally open output and
normally closed output. You can set up the three modes through Pin X1~X7. See more
details in Table 4-1.
Table 4-1
Output 24VDC Normally Closed Normally Open
SOUNDER Short 1 to 2 & 4 to 5 of X3 Short 3 to 4 & 5 to 6 of X3 Short 2 to 3 & 5 to 6 of X3
CIRCUIT
OUTPUT Short X7 Disconnect X7 Disconnect X7
Page 18
Fig. 4-4
A 4.7kΩ resistor is connected at the SOUNDER CIRCUIT OUTPUT (XT7) as factory
default. Please remove it and keep it well before connection. Connect the loop in correct
polarity and add the resistor to the end of the line.
NOTE: The sounder strobes are polarity-sensitive. Note polarity in connection.
The maximum current of the circuit depends on the number of sounder strobes.
Do not overload.
4.4.3.2 Connection of F.P.E. OUTPUT
F.P.E. OUTPUT is shown in Fig. 4-5.
Fig. 4-5
A 4.7kΩ resistor is connected at the F.P.E. OUTPUT (XT6) as factory default. Please
remove it and keep it well before connection. Connect the loop in correct polarity and
add the resistor to the end of the line.
NOTE: F.P.E. are polarity-sensitive. Note polarity in connection. The maximum
current of the circuit depends on the number of F.P.E. Do not overload.
4.4.3.3 Connection of FIRE ALARM OUTPUT
FIRE ALARM OUTPUT is shown in Fig. 4-6.
Diode Diode
End-of-line
FIRE ALARM Fire Monitoring Fire Monitoring Resistor 4.7kΩ
OUTPUT (XT5) Device Device
Fig. 4-6
A 4.7kΩ resistor is connected at the FIRE ALARM OUTPUT (XT5) as factory default.
Please remove it and keep it well before connection. Connect the loop in correct polarity
and add the resistor to the end of the line.
NOTE: Fire supervisory devices are polarity-sensitive. Note polarity in
connection. The maximum current of the circuit depends on the number of fire
supervisory device. Do not overload.
Page 19
Loop
LOOP OUT Addressable
Isolator
(XT4) Field Devices
Loop Addressable
LOOP IN
Isolator Field Devices
(XT2)
Fig. 4-7
Note: If more than 32 devices are connected to the loop, loop isolators shall be
used and each loop isolator shall not cover more than 32 detectors.
4.4.3.5 Connection of Communication Loop
Network
FACP
FACP
A Maximum 32 FACPs
(XT11)
B
Repeater Panel
Repeater Panel
Repeater A
Maximum 10 Repeater Panels
(XT12)
B Fig. 4-8
4.5 Connection Checking and Device Registration
Check the circuit connected with the FACP. Measure the insulation resistance between
loops and between loops and ground, which should be more than 20MΩ. Measure the
load of detection loops, which should be more than 1kΩ. The resistance between cables
of FIRE ALARM OUTPUT, SOUNDER CIRCUIT OUTPUT and F.P.E. OUTPUT should
be equal to the end-of-line resistance.
Press SYSTEM and input commission password. Then press ENTER to go to system
setting menu. Then press ESC to exit system setting menu, the system enters
commission state (there will be a “-“ at the right bottom of the screen). Rebooting the
Page 20
2 Test all the detectors and make sure their positions are correct.
4 Check all C&E equations, modify improper parts, and test automatic activation by
C&E equation.
Page 21
Software
GST CO., LTD.
version number
SYSTEM ALL NORMAL
Software V*.*
Fig. 5-1
Fig. 5-2 shows the system is in normal operation but with disabled devices. Pressing
VIEW DISABLE can browse these devices.
SYSTEM NORMAL
WITH DISABLE
Software V*.*
Fig. 5-2
FIRE LED is lit when there is fire alarm signal. Speaker of the FACP sounds (fire truck
sound), and corresponding FIRE LED on the ZCP is also lit.
1. Fire alarm screen is shown like Fig. 5-3 when in zone display mode.
Page 22
Fig. 5-3
001 0f 003 !FIRE! 05:25 // There are fire alarms in three zones and this is the first.
Zone:001-Zone 1 // The number of zones with fire alarm and description of the
zone.
002/003 //There are three devices in the zone, and two of them alarmed.
Device-30 // The description of the device with the first fire alarm signal.
Zone 3 Device-061 //Description of zone with the last fire alarm and description
of the device of that zone with the first fire alarm.
2. Fire alarm screen for loop display mode is shown in Fig. 5-4.
Fig. 5-4
001 0f 006 !FIRE! 05:25 // There are six devices with fire alarm signals, and this
is the first.
Z001-L1-N030MCP // The number of zone with fire alarm and type and address
of the device in fire alarm.
Device-30 // Description of device in fire alarm.
Last! Fire! Zone:003 //Number of the zone where the last fire alarm occurs
Z-003 Device-066 // Description of zone and device of the last fire alarm.
When fire alarm occurs, first find out the location according to the information shown on
the FACP to verify whether the fire really happened.
Page 23
5.3 Fault
The indication of the fault message depends on the type of fault. Specific fault types and
causes are shown in Appendix 2.
Power fault: If the AC power is down, the battery voltage is less than 18.9V, or if
there is charging fault, the panel reports power fault, and
Light COMMON FAULT and POWER FAULT LED.
The LCD displays the type of the fault.
The panel generates fault sound.
Fault relay outputs.
System fault: The panel would report system fault if its control CPU and circuits is in
fault and the panel cannot work normally.
It lights the COMMON FAULT and SYSTEM FAULT LED.
There is no display on the LCD.
The panel generates continuous alarm sound.
The panel cannot monitor fire alarm.
The keypad cannot be used.
If system fault indication remains for less than 5 seconds, the panel will
assume that this is not a true fault and automatically clear the LED and
sounder indication and return to normal monitor state. If system fault
indication remains for more than 5 seconds, the panel will then interpret it as a
genuine fault and the LCD displays “System fault must be reset manually.
System time must be reset.” after it’s cleared. You need to press RESET key
to clear the fault indication and reset system time.
Fault relay outputs.
Keypad fault: The panel reports keypad fault if its keypad circuit is in fault:
It lights the COMMON FAULT and SYSTEM FAULT LED.
The LCD displays “Key fault”.
The panel generates continuous alarm sound.
Fault relay outputs.
Page 24
Field device fault: If there is trouble with one of the field devices, the panel reports
fault with it, and
The panel lights the COMMON FAULT LED.
The corresponding ZCP LED flashes.
The panel generates fault sound.
Fault relay outputs.
The LCD displays the fault message. The fault screen is as in Fig. 5-5 in zone
display mode, and as in Fig. 5-6 in loop display mode.
Fig. 5-5
001 0f 002 FAULT10: 18 // There are two zones reporting fault, and this is the
first fault message.
Zone: 003-floor3 // The number description of the zone with fault message.
001/012 //There are 12 devices in the zone totally, and one of them reports
fault.
Office3 // Description of the device with the fault.
Fig. 5-6
001 0f 004 FAULT10:18 // There are four devices reporting fault, and this is the
first fault message.
Z003-L2-N011Optical // The number of the zone and loop with the fault
message, and the address and type of the device with the fault message.
Page 25
There are two kinds of fault message. One is system fault, like power fault, and loop
fault. The other is field device fault, like fault with detectors and modules etc.
If the system is powered by battery for longer time than its capacity, the panel will
shut down to protect the battery. Please charge the battery in time to avoid any
possible damage to it.
If it is system fault, please check and repair in time. If the panel needs to be shut
down, please make detailed notes.
If it is field device fault, please repair it in time. You can disable it if the fault can’t be
cleared for some reason, and enable it when the fault is removed.
2 There are zone and loop display modes for fire alarm, fault, and disabled messages.
Action message only has loop display mode.
3 In any display mode, the system will return to displaying of the highest priority if
there is no operation within 20s (15s~30s).
The FACP gives police car sound when any fire extinguishing device is activated.
Page 26
6.1 Keypad
Most of the keys have double functions. Lower mark is a character and upper mark is a
command that is only activated in monitoring state. Most functional keys are controlled
by password. The characters are only active after entering the menu. Pressing ESC will
return to previous level of the menu.
Pressing a character key, all characters disappear, and the display shows the newly
input one. The cursor will indicate the next input position (The cursor always indicates
the position of the next to input, and returns to the first character after completion of a
line). Pressing △ =
= or ▽, to move the cursor to modify any character.
Pressing TAB, the highlight moves to the next position and returns to the first after the
last position. Wherever the cursor is, Pressing ENTER key, all the input data will be
saved.
If there is no keypad operation for over 1 minute, the system will exit present state
without saving the input data.
Fig. 6-1
Locking the Keypad
The keypad shall be locked after an operation or when the personnel on duty leave.
Pressing LOCK, the screen will display “Press ENTER confirm” like in Fig. 6-2.
Pressing ENTER, the keypad is locked. You will have to input password again to unlock
the keypad for any new operation.
Page 27
Fig. 6-2
The clock usually displays in hour and minute. In normal monitoring state, pressing
ENTER, month and date are displayed. Pressing ENTER again or after a minute, hour
and minute is displayed again.
The current information is highlighted when there is more than one piece of message on
the LCD. You can view details of this item by pressing ENTER or exit by pressing ESC.
When the printer is set as “All History” mode, pressing ENTER while browsing can print
the current displayed message.
6.2.2.3 Browse
Pressing BROWSE, the system enters the browsing screen as shown in Fig. 6-3.
Browse
1. Loop Devices
2. Zone Devices
3. Group Devices
4. In Test Mode Zones
5. COM Devices
6. Access
7. Browsing C&E
Fig. 6-3
From the above screen, you can operate as follows:
Entering number 1 to choose “1. Loop Devices “will enter the screen to view
devices by loop, as shown in Fig. 6-4.
Page 28
Browse Browse
Loop1: 012 Loop2: 020 Sum :012
Loop1 L1N001 Optical
Loop2 L1N002 Optical
Browse
L1N003 Optical Zone:01 office1
L1N004 Sounder
NO.001 Optical
Sensitivity:Nominal
Office1
Fig. 6-4
L1N001 Optical // Loop number, device address and device type.
Zone: 01 office1 // Zone number, and zone position description.
NO.001 Optical // Device address, device type.
Sensitivity: Nominal // Device properties.
Office1// Device position description.
Entering No. 2 will enter the screen for browsing loop devices by zone, as in Fig.
6-5.
Browse ENTER
3 Zone (008)(004)
Zone:01(001)Sum:004 ENTER
Browse
Zone:02(002)Sum:004
Zone:001 Sum :004
Zone:03(003)Sum:004
L1N001 Optical Browse
L1N002 Optical Zone:001 office1
L1N003 Optical NO.001 Optical
L1N004 MCP Sensitivity:Nominal
Office1
Fig. 6-5
3 Zone (008)(004) // 3 zones in total, 8 addressable devices on Loop 1,
and 4 on Loop 2
Zone:01(001)Sum:004 // Zone 01, (001) is the zone number with starting
zone added, total number of devices is 4.
Zone: 001 office1 // Zone number and location
NO.001 Optical // Device address and type
Sensitivity:Nominal // Device properties
Office1// Device position
Entering number 3 to choose “3. Group Devices” will enter the screen for browsing
devices by group, as shown in Fig. 6-6.
Page 29
Browse ENTER
2 Group (012)(020)
Group:01(001)Sum:004 ENTER
Browse
Group:02(002)Sum:016
Group: 01 Sum: 004
L2N001 Sounder Browse
L2N002 SM Vent Group: 01 office1
L2N003 Sounder NO.001 Sounder
L2N004 SM Vent Output: Persist
Office1
Fig. 6-6
Entering number 4 to choose “4. In Test Mode Zones” will enter the screen for
browsing zones in test mode, as shown in Fig. 6-7.
Fig. 6-7
Sum:002 // Total number of zones in test
Zone 01: office1 // Zone 1 is in test mode. Zone description is “office1”.
Zone 05: office5 // Zone 5 is in test mode. Zone description is “office5”.
Entering number 5 to choose “5: COM Devices” will enter the screen for browsing
network FACPs and repeater panels.
Entering number 6 to choose “6. Access” will enter the screen for browsing ZCP
key definition, as in Fig. 6-8.
Page 30
Browse
Sum:32
N01: L02N001 Sounder
N02: Zone 01
N03: L01N004 Sounder
Fig. 6-8
Sum:32 // Total number of keys on ZCP
N01: L02N001 Sounder // Key No. 1 is defined as a sounder of Loop 2
whose address is 001.
N02: Zone 01 //Key No. 2 is defined as Zone 1 indicator
N03: L01N004 Sounder //Key No. 3 is defined as a sounder of Loop 1
whose address is 004.
Entering No. 7 to choose “7: Browsing C&E” will enter the screen for browsing C&E
equation, as shown in Fig. 6-9.
Browse C&E
ENTER
Sum: 003
C&E 001
C&E 002
C&E 003 Browse C&E
C&E 001
G0100103 × G0100203+G0100203 ×
G0100303 + G0100103 × G0100303 +
G0100103 × G0100203 × G0100303 =
G0100413 00
Fig. 6-9
The part before “=” is the condition and that after it is the result.
“×” means “and”, and “+” means “or”.
A condition is composed of the following items:
G(S) 01 001 03
Device type
Device address/Quantity of events defined in special condition
Zone number of the device
G: General conditions S: Special conditions
General Condition: A device can be activated if its zone number, code and device
type are correct.
Special Condition: Both zone number and device type can be defined. If events
with the same zone number and device type reach a defined number, this special
condition comes into effect. Asterisk wildcard “*” represents any number used in
Page 31
01 004 13 00
Delay time
Device type
Device address
Zone number of the device
6.2.2.4 Browsing history log
Pressing LOG, the FACP enters the state of browsing history record. Using △ =
= and ▽,
you can browse every item, the screen is shown in Fig. 6-10.
History Record
NO. 200
! FIRE!
TIME: 10:23 14/08
Zone: Name
121 Optical
Fig. 6-10
NO. 200 // The two hundredth history log
Page 32
Fig. 6-11
001 of 003 Disable 12:01 //There are three disabled devices in the system and this
is the first.
Z001-L2-N004Sounder //The zone number, loop number, address and device type
of the disabled device.
Fig. 6-12
001 of 002 Disable 12:01 // There are devices from 2 zones that are disabled, and
this is the first zone.
Zone: 005 Z-005 // Zone number and description message of the disabled zone.
Fig. 6-13
002 of 002 Disable 12:01 // There are devices from 2 zones that are disabled, and
this is the second zone.
Zone: 006 Z-006 // Zone number and description message of the disabled zone.
Page 33
Pressing ACK/MUTE can stop the sound of speaker; pressing ACK/MUTE again, the
FACP is still in mute state. It will only sound by priority when new event appears.
Pressing RESET can turn off all the control modules, local outputs and reset all the
detectors, but will leave the disabled devices as they are. The LCD displays “RESET IN
SYSTEM”. LEDs will be turned off (Except for “POWER ON”, “TEST MODE”, “DELAY
MODE” LEDs). The reset information will be written into running log. If there is still fire
alarm, fault and action not acknowledged after pressing the RESET key, the FACP will
remain relative sound indications. If all messages have been acknowledged by pressing
RESET key, the system returns to normal display state.
Pressing SILENCE key can silence all sounders in the system, and light the SILENCE
indicator.
The silenced sounders will re-sound on receiving new alarms. SILENCE indicator will
go out when RESET key is pressed for reset, when EVAC key is pressed for evacuation,
or when system sounders gives new alarm sound.
6.3.3 Evacuation
Pressing EVAC key can start all system sounders, and light EVAC LED until SILENCE
or RESET key is pressed. After EVAC key is pressed, the LCD will display “EVAC IN
SYSTEM Press ENTER confirm”. Pressing ENTER in 10 seconds will start evacuation.
If ENTER key is not pressed in 10 seconds, the FACP will resume the state before
EVAC key is pressed.
6.3.4 Disable/Enable
The disabling/enabling of devices is mainly used when the trouble condition of a device
cannot be removed immediately. This device can then be temporarily disabled, and
enabled after it’s repaired.
The disabling/enabling of alarm output can be set as needed either to start or not to start
SOUNDER CIRCUIT OUTPUT and FPE OUTPUT automatically.
The disabling/enabling of delay can be set as needed. For example, if there is person
on duty, the system delay can be enabled, so that the system can select delay by C&E
equation or by the pre-set default local delay in case of an alarm. If there is nobody on
duty, the delay can be disabled and the system outputs immediately.
Page 34
*Disable/Enable*
1 Disable Devices
2 Enable Devices
3 Dis/En-able Output
4 Dis/En-able Delays
5 Delete Net Disable
Fig. 6-14
6.3.4.1 Disabling a Device
In the screen shown in Fig. 6-14, input number “1”, you can enter disable screen as
shown in Fig. 6-15, where you are able to disable devices. The panel provides four
methods for disabling devices. You can disable all devices of a zone, a single device
(single-device disable) , disable all loop sounders, or disable a device by user code.
*Disable Devices*
1 Each Zone Fully
2 Individual Points
3 All Loop Sounder
4 Use Devices Code
Fig. 6-15
Disabling a zone
Entering number “1” in the screen of Fig. 6-15 will enter disable screen as shown in Fig.
6-16.
Disabling a zone
Zone: 000
Fig. 6-16
Entering 3-digit zone number and Pressing ENTER key to confirm will disable all
devices of the zone.
Disabling a point (device)
Entering number “2” in the screen of Fig. 6-15 will enter the screen for disabling a single
device, as shown in Fig. 6-17.
Page 35
Disabling a point
Loop: 1 Point: 000
Fig. 6-17
Entering 1-digit loop number (1 or 2) and 3-digit point number (any number between 1 to
242), and then pressing ENTER will disable the selected device.
Disabling all loop sounders
Entering number “3” in the screen of Fig. 6-15 will enter the screen for disabling all loop
sounders, as shown in Fig. 6-18.
Fig. 6-18
Pressing ENTER on prompt will confirm the operation and disable all loop sounders.
Disabling a device by user code
Enter number “4” in the screen of Fig. 6-15 will enter the screen for disabling a device by
user code, as shown in Fig. 6-19.
Disable
Z000 C000 T00 NoDefine
Fig. 6-19
Enter 3-digit zone number or “*” at the cursor position after letter “Z”.
Enter 3-digit device code or “*” at the cursor position after letter “C”.
Enter 2-digit device type or “*” at the cursor position after letter “T”.
Example 1, in order to disable devices with type number 001 of Zone No.1, you need to
input in sequence the zone number 001, device number 001 and device type 03.
Example 2, in order to disable all alarm devices with type number 01~11 of Zone No.1,
you need to input in sequence the zone number 001, device code *** and device type **.
Please note that the asterisk mark “**”is not allowed for the type number of action
devices with type number 12~65.
Page 36
*Enable Devices*
1 Each Zone Fully
2 Individual Points
3 All Loop Sounder
4 Use Devices Code
Fig. 6-20
6.3.4.3 Disabling/Enabling Alarm Outputs
Entering number “3” in the screen of Fig. 6-14 will enter the screen for
disabling/enabling alarm output, as shown in Fig. 6-21.
*Dis/En-able Outputs*
1. Sounder Circuit
2. F.P.E. Output
Fig. 6-21
In this screen, the SOUNDER CIRCUIT OUTPUT and FPE OUTPUT on the loop
interface board can be disabled or enabled.
6.3.4.4 Disabling/Enabling Delays
Inputting number 4 in the screen shown in Fig. 6-14 can enter the screen of
disabling/enabling delays, as shown in Fig. 6-22.
* Delay Mode*
1. Disable
2. Enable
Fig. 6-22
In the above screen, you can operate as follows:
Selecting number 1 will disable all delay settings in the system.
Selecting number 2 will enable system to output according to the pre-set delay time,
and light DELAY MODE LED.
Page 37
Fig. 6-23
In the above screen, entering the number of the message, and pressing ENTER to
confirm will delete the disabled information from network FACP.
Pressing MODE key can enter user mode setup screen as shown in Fig. 6-24.
*User Mode*
1 LCD Contrast
2 Browse Mode
3 Print Mode
4 PAS Setup
5 Start Devices
6 Stop Devices
Fig. 6-24
In this screen, the user can setup the screen contrast, display mode, printing mode and
pre-alarm mode, and can also start or stop devices.
6.3.5.1 LCD Contrast Setup
Entering 1 in Fig. 6-24 will enter the screen for setting up LCD contrast, as shown in Fig.
6-25.
*LCD Contrast*
048
Fig. 6-25
6.3.5.2 Display Mode Setup
Entering 2 in the screen of Fig. 6-24 will enter the screen for setting up display mode, as
Page 38
*Browse Mode*
1 Zone Mode
2 Loop Mode
Fig. 6-26
In this screen, choosing “1 Zone Mode” can browse system messages by zone, and
choosing “2 Loop Mode” can browse by loop.
6.3.5.3 Printing Mode Setup
Entering 3 in the screen of Fig. 6-24 will enter the screen for setting up print mode, as
shown in Fig. 6-27.
*Print Mode*
1 Disable
2 Only Fire
3 All History
Fig. 6-27
Entering number “1” means printing is disabled.
Entering number “2” means only printing fire alarm message.
Entering number “3” means printing the currently viewed message when checking
history records.
6.3.5.4 Positive Alarm Sequence (PAS) Setup
Entering 4 in the screen of Fig. 6-24 will enter the screen for setting up pre-alarm screen,
as shown in Fig. 6-28.
*PAS Mode*
1 Disable
2 Enable
Fig. 6-28
If the panel is set to PAS mode enabled,
On receiving the first fire alarm from a detector, PRE-ALARM LED will illuminate.
The FACP generates fire alarm sound, and starts 15-second delay. The LCD
Page 39
Start-up
Z000 C000 T00 NoDefine
Fig. 6-29
6.3.5.6 Manual Stop of Loop Devices
Entering 6 in the screen of Fig. 6-24 will enter the screen for manual stop of loop devices.
The method for stopping a device is the same as starting a device.
Stop EQ
Z000 C000 T00 NoDefine
Fig. 6-30
According to definition of the ZCP, press the key corresponding to a device, and input
the requested password, you can start the device. Corresponding command LED of the
key is lit. Press the key and input password again, you can stop the device, and the
command LED turns off.
Page 40
*Test Mode*
1 Display Test
2 Each Zone In Test
3 Stop a Zone Test
4 Stop All Zone Test
Fig. 6-31
In this screen, the user can carry out self-test on audible/visual performance, setting up
single-zone testing, exiting single-zone testing mode and exiting testing of all zones.
6.3.7.1 Audible/Visual Self-test
Entering 1 in the screen of Fig. 6-31, if the system is in normal standby state, the FACP
will self-test all indicators and audible components.
6.3.7.2 Single-zone Testing Setup
Entering 2 in the screen of Fig. 6-30 will enter the screen for setting up single-zone
testing, as shown in Fig. 6-32.
Fig. 6-32
Entering the zone to test in this screen and pressing ENTER to confirm, the zone will
enter test mode, and the TEST MODE indicator will illuminate.
6.3.7.3 Exiting Single-zone Testing Mode
Entering 3 in the screen of Fig. 6-31 will enter the screen for exiting single-zone test
mode, as shown in Fig. 6-33.
Fig. 6-33
Entering the number of the zone to exit test mode and pressing ENTER to confirm will
enable the zone to exit test mode.
Page 41
Fig. 6-34
The screen for display a prompt before exit. After pressing ENTER for confirmation,
TEST MODE indicator will go out.
*System Mode*
1. Time/Date
2. Password Change
3. Network Setup
4. Zone Start Number
5. Customize
6. Initialize System
7. Devices debug
Fig. 6-35
Entering “1” in the screen of Fig. 6-35, the system enters Time/Date setting screen, as
shown in Fig. 6-36. After Entering time at highlighted position and press TAB, then the
next cell is highlighted. Pressing ENTER will save the modification.
* Time/Date Setting*
Please Input
Day Month Year
04 01 05
Hour Minute Sec
11 39 55
Fig. 6-36
Entering “2” on the screen in Fig. 6-35, the system enters the window for password
modification, as in Fig. 6-37. Now the passwords can be modified.
Page 42
Password Change
1. Operator Password
2. Manager Password
Fig. 6-37
Entering “1” or “2” can choose the password to modify, the system enters the window in
Fig. 6-38.
Modify Password
Input password
********
Fig. 6-38
After the password (8 digits from 0-9) is input, the LCD will display the screen shown in
Fig. 6-39, requesting to confirm password.
Modify Password
Confirm Password
********
Fig. 6-39
Entering the new password again, if the two passwords are the same, the LCD will
display the window shown in Fig. 6-40, meaning the modification is successful.
Success
Fig. 6-40
Page 43
*NETWORK SETUP*
1. NET Local Address
2. NET Event Display
Fig. 6-41
In the above screen,
You can set the panel’s network address by entering number 1, as shown in Fig.
6-42.
Fig. 6-42
You can set the panel to display network message or not by entering number 2, as
shown in Fig. 6-43.
*Display Mode*
1 Disable
2 Enable
Fig. 6-43
Pressing “4” on the screen shown in Fig. 6-35, you can set beginning zone number of
the FACP in network. Duplicate zone number should be avoided. The screen is shown
in Fig. 6-44. Entering the number of zones in the network on highlighted position and
pressing ENTER, the zone numbers of the FACP will start from this number. For
example, if the beginning number is 003, then the FACP zone number will be 003, 004,
005….in sequence.
Page 44
Fig. 6-44
6.4.5 Customize
Entering number 5 in the screen in Fig. 6-35 will enter the customize screen, as shown
in Fig. 6-45.
*Customize*
1. Outputs Setup
2. PAS Delay
3. Resound Configure
Fig. 6-45
In this screen you can setup the output mode and PAS delay time.
6.4.5.1 Output Setup
Entering 1 in the screen of Fig. 6-45 will enter the screen for setting up output modes, as
in Fig. 6-46.
*Outputs Setup*
1. Default Outputs
2. C&E Outputs
Fig. 6-46
Default Outputs
Selecting “1. Default Outputs” in the screen of Fig. 6-46 will set SOUNDER CIRCUIT
OUTPUT (Sounder A) on loop interface board and F.P.E. OUTPUT (F.P.E.) and the
zonal sounder to default output. That is, if any fire alarm comes,
If you have set the “Delay Mode” in Section 6.3.4.4 to “Disable”, Sounder A,
zonal sounder and F.P.E. will be automatically started.
If you have set the “Delay Mode” in Section 6.3.4.4 to “Enable”, Sounder A and
zonal sounder output after a 30-second delay, and F.P.E. immediately outputs.
C&E Outputs
Page 45
Fig. 6-47
When the “PAS Mode” in Section 6.3.5.4 is set to “Enable”, the FACP will enter the first
stage of delay on receiving a fire alarm. Pressing ACK/MUTE at this time, the FACP will
enter the second stage of delay. The delay time for the second stage can be set in the
screen shown in Fig. 6-47 as described in Section 6.3.5.4.
6.4.5.3 Resounding Loop Sounders
Choosing “3” on the screen of Fig. 6-45 will enter the screen for resounding loop
sounders, as in Fig. 6-48.
*Re-Sound Configure*
1 Another Zone
2 Self Zone
Fig. 6-48
6.4.5.3.1 Resounding Sounders of Other Zones
Choosing “1” on the screen of Fig. 6-48, the silenced sounders of all zones will be
resounded on a new fire alarm from any zone.
6.4.5.3.2 Resounding Sounders of the Same Zone
Choosing “2” on the screen of Fig. 6-48, a new fire alarm will enable to resound
sounders from the same zone. Sounders of other zones will not be resounded.
Page 46
Entering “6” on the screen shown in Fig. 6-35 can initialize system data.
Entering “7” on the screen shown in Fig. 6-35 will enter the window shown in Fig. 6-49.
Entering the equipment number and the order number can view the supervisory value of
addressable devices.
Fig. 6-49
Page 47
Page 48
Chapter 8 Maintenance
The FACP shall only be repaired by specially trained technical service personnel.
Please disconnect the power before repair!
8.3 Troubleshooter
Page 49
6 Cannot print a. Print mode is not set. a. Set the print mode.
b. Loose connection with b. Check and connect the printer
printer. well.
c. Printer damaged c. Replace the printer.
7 No response a. Loose connection with a. Check and connect, then
after pressing ZCP. register again.
keys on zone
b. The circuit board of ZCP b. Replace the circuit board of
indication and
damaged. zone indication and manual
manual
intervention panel.
intervention
panel
8 Equipment fault a. Equipment disconnected. a. Check connection
b. Equipment damaged. b. Replace equipment
9 Loop fault Loop is shorted Check the loop and repair.
10 Clock or memory a. External interference. a. Check whether ground is
fault. properly connected.
b. Corresponding parts are
aging. b. Inform our technical service
Page 50
- +
To Enclosure
Page 51
Page 52
Page 1
Page 2
Menu
BROWSE
1 Loop Devices
2 Zone Devices
3 Group Devices
4 In Test Mode Zones
5 COM Devices (Network devices)
6 Access (Displaying ZCP information)
7 Browsing C&E
LOG (History records)
VIEW FAULT
VIEW DISABLE
MODE [Operator password required]
1 LCD Contrast
2 Browse Mode
Zone Mode
Loop Mode
3 Print Mode
Disable
Only Fire
All History (Pressing PRINT when viewing
history records can print out the messages
being viewed.)
4 PAS (Positive Alarm Sequence) Setup
1 Disable
2 Enable
5 Start Devices (manually start)
6 Stop Devices (manually stop)
TEST [Operator Password required]
1 Display Test (Self-test)
2 Each Zone In Test
3 Stop a Zone Test
4 Stop All Zone Test
ENABLE/DISABLE [Operator Password Required]
1 Disable Devices
2 Enable Devices
3 Dis/En-able Output
4 Dis/En-able Delays
5 Delete Net Disable
Page 3
“△ =
=” / “▽” (Turning pages)
ESC (Canceling or exiting operation menu, or enabling the FACP to
displaying information of the highest priority)
ENTER (Confirmation an input. Shifting time display mode between
month/day and hour/minute in normal standby state. )
RESET (Resetting the FACP from fire or fault to normal standby state)
[Operator Password Required]
Page 4