Kaeser Sigma Control 2 Screw Fluid 4.1.X 9 - 9450 - 08e
Kaeser Sigma Control 2 Screw Fluid 4.1.X 9 - 9450 - 08e
Kaeser Sigma Control 2 Screw Fluid 4.1.X 9 - 9450 - 08e
Controller
Manufacturer:
KAESER KOMPRESSOREN SE
96410 Coburg • PO Box 2143 • GERMANY • Tel. +49-(0)9561-6400 • Fax +49-(0)9561-640130
http://www.kaeser.com
/KKW/SSC 2.08 en IBA-SIGMA CONTROL FLUID
/KKW/SSC 2.08
20180814 091827
Contents
7 Installation
7.1 Reporting Transport Damage ........................................................................................... 48
7.2 Machine identification ....................................................................................................... 48
8 Initial Start-up
8.1 Outline .............................................................................................................................. 49
8.2 Setting the controller ........................................................................................................ 49
8.2.1 Selecting menu options ...................................................................................... 50
8.2.2 Setting the language ........................................................................................... 51
8.2.3 Noting the user name ......................................................................................... 52
8.2.4 User log-in with RFID Equipment Card ............................................................... 53
8.2.5 Generating a password ....................................................................................... 54
8.2.6 Manual user log-in .............................................................................................. 55
8.2.7 Create the master RFID Equipment Card ........................................................... 56
8.2.8 Checking/setting time and date .......................................................................... 57
8.2.9 Set the time zone ................................................................................................ 59
8.2.10 Set display formats ............................................................................................. 59
8.2.11 Setting the display illumination ........................................................................... 62
8.2.12 Setting the contrast and the brightness .............................................................. 63
8.2.13 Activating the remote control ............................................................................. 63
8.2.14 IP configuration .................................................................................................. 64
8.2.15 Setting the e-mail function ................................................................................. 65
8.2.16 Setting the time server ....................................................................................... 67
8.3 KAESER CONNECT benefits .......................................................................................... 68
8.3.1 Open KAESER CONNECT ................................................................................. 69
8.3.2 System status menu ........................................................................................... 70
8.3.3 Graphs menu ...................................................................................................... 72
8.3.4 Messages menu ................................................................................................. 74
8.3.5 I/O display menu ................................................................................................. 74
8.3.6 User management menu .................................................................................... 75
8.3.7 Settings menu ..................................................................................................... 78
8.3.8 Save data menu .................................................................................................. 79
8.3.9 KAESER CONNECT exit .................................................................................... 79
8.4 Pressure parameters of the machine .............................................................................. 80
8.4.1 Displaying pressure parameters ......................................................................... 81
8.4.2 Setting pressure parameters .............................................................................. 81
8.4.3 Activating/deactivating the «LOAD/IDLE» key .................................................... 84
8.5 Machine start and machine stop ...................................................................................... 85
8.5.1 Automatic start/stop in timer mode .................................................................... 85
8.5.2 Setting the company shut-down ........................................................................ 89
8.5.3 Controlling machine from a remote location ...................................................... 90
8.5.4 Activating the remote control ............................................................................. 92
8.5.5 "Venting" function .............................................................................................. 93
8.5.6 "Autostart" function ............................................................................................ 93
8.6 Control modes ................................................................................................................. 96
8.6.1 Setting the control mode ..................................................................................... 96
8.6.2 Setting the DUAL control mode .......................................................................... 97
8.6.3 Setting the QUADRO control mode .................................................................... 98
8.7 Electronic Thermal Management .................................................................................... 99
8.7.1 Activating the heat recovery for machine type 2 ................................................. 99
8.7.2 Activating the heat recovery for machine type 3 ................................................. 101
8.7.3 Deactivating heat recovery ................................................................................. 102
8.8 Refrigeration dryer .......................................................................................................... 103
8.8.1 Setting the operating mode ................................................................................. 103
8.8.2 Output messages ................................................................................................ 104
8.8.3 Fault in the refrigeration dryer – compressed air quality has priority .................. 105
8.8.4 Fault in the refrigeration dryer – compressed air supply has priority .................. 106
8.9 Setting the machine for local mode .................................................................................. 107
8.9.1 Menu Load control ............................................................................................. 107
8.9.2 Setting the nominal pressure change via timing program .................................. 107
8.9.3 Setting the nominal pressure change via timer ................................................... 110
8.10 Setting the machine for master control operation ............................................................ 112
8.10.1 Overview of the different master operating modes ............................................. 112
8.10.2 SAM 4.0 mode ................................................................................................... 113
8.10.3 Setting PROFIBUS operation (SIGMA AIR MANAGER) .................................... 116
8.10.4 Master control of two machines in master/slave operation ................................ 124
8.10.5 Configuring master control using the LOAD remote contact (e.g., 130
SIGMA AIR MANAGER BASIC) ........................................................................
8.10.6 Setting the master control with local/LOAD remote contact .............................. 132
8.10.7 Setting the nominal pressure pre-selection via remote contact ......................... 136
8.10.8 Master control for machines regulated by pressure switch ................................ 137
8.10.9 Examples of time settings for equal overall load ............................................... 142
8.11 Setting input and output signals ....................................................................................... 143
8.11.1 Output operational states of machine on digital outputs ..................................... 143
8.11.2 Output input signals on the display ..................................................................... 145
8.11.3 Output measured values on the display ............................................................. 149
8.11.4 Switching and/or triggering messages with thresholds ....................................... 155
8.12 Timer ................................................................................................................................ 159
8.13 Activating remote acknowledgement .............................................................................. 160
8.13.1 Setting the remote acknowledgement function ................................................... 161
8.13.2 Activating the remote control .............................................................................. 161
8.13.3 Assigning an input .............................................................................................. 162
8.14 Linking to an external pressure transducer ..................................................................... 163
8.14.1 Pressure control menu ........................................................................................ 163
8.14.2 Assigning an input to an external pressure transducer ...................................... 163
8.15 Commissioning the machine ........................................................................................... 164
9 Operation
9.1 Switching the compressed air station on and off .............................................................. 166
9.1.1 Switching on ....................................................................................................... 166
9.1.2 Switching off ....................................................................................................... 167
9.2 Switching off in an emergency ......................................................................................... 167
9.3 Acknowledging alarm and warning messages ................................................................. 168
9.4 Displaying messages ...................................................................................................... 169
9.4.1 Status – Messages menu ................................................................................... 170
9.5 Displaying the current operating mode ........................................................................... 172
9.6 Setting the working pressure ............................................................................................ 173
9.7 Displaying analogue data ................................................................................................ 173
9.8 Displaying operating data ................................................................................................ 174
9.8.1 Checking the operating hours ............................................................................. 174
9.8.2 Checking the switching cycles ............................................................................ 175
9.9 Displaying the frequency converter settings ................................................................... 176
9.10 Setting the maintenance interval ..................................................................................... 177
9.11 Check the safety valve .................................................................................................... 178
9.12 Excessive temperature shut-down test ........................................................................... 180
9.13 Save data ........................................................................................................................ 182
10 Fault Recognition and Rectification
10.1 Basic instructions ............................................................................................................. 184
10.2 Interpreting fault messages .............................................................................................. 184
Settings can be made after log-in with the RFID Equipment Card and access level 2.
2.2 Copyright
This operating manual is protected by copyright. Any queries regarding the use or duplication of
this documentation should be referred to KAESER. Correct use of information will be fully suppor‐
ted.
2.2.1 Software
The software used in SIGMA CONTROL 2 contains copyright-protected software packages which
are licensed as Open Source.
A copy of these licenses is contained in SIGMA CONTROL 2.
Display the licenses by pointing your browser to the "COPYING" file in the root directory of
SIGMA CONTROL 2.
URL:
http:// <Hostname>/COPYING
The licenses can be also found under these addresses:
http://www.gnu.org/licenses
http://code.google.com/p/curve25519-donna/
Within three years from receipt of SIGMA CONTROL 2, you may obtain the complete source code
of the copyright-protected software packages by sending a corresponding order to the following ad‐
dress:
Technical Office Electrical Design
KAESER KOMPRESSOREN SE
96450 Coburg, Postfach 2143
Germany
This offer is valid for anybody having this information.
2.3 Certification
This product has the following approvals:
■ This equipment has been tested and found to comply with the limits for a Class B digital de‐
vice, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
─ Reorient or relocate the receiving antenna.
─ Increase the separation between the equipment and receiver.
─ Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
─ Consult the dealer or an experienced radio/TV technician for help.
■ This device complies with part 15 of the FCC rules. The operation is subject to the following
two conditions:
─ this device may not cause harmful interference, and
─ this device must accept any interference received, including interference that may cause
undesired operation.
■ This device fulfils the provisions of the Industry Canada Licence, with the exception of the RSS
rules. The operation is subject to the following two conditions:
─ this device may not cause harmful interference, and
─ this device must accept any interference received, including interference that may cause
undesired operation.
In order to ensure permanent compliance with the FCC rules, unless explicitly approved by
the authority responsible for compliance with the provisions, no changes must be carried out
(for example: when connecting to computers or peripheral equipment use shielded cables on‐
ly).
2.5.1 Warnings
Warning notices indicate dangers that may result in injury when disregarded.
Warning notices indicate three levels of danger identified by the corresponding signal word:
Signal term Meaning Consequences of non-compliance
DANGER Warns of an imminent threat of danger Will result in death or severe injury
WARNING Warns of possible danger May result in death or severe injury
CAUTION Warns of a potentially dangerous situation May result in a moderate physical injury
Warning notices preceding a chapter apply to the entire chapter, including all sub-sections.
Example:
DANGER
These show the kind of danger and its source.
The possible consequences of ignoring a warning are shown here.
If you ignore the warning notice, the "DANGER" signal word indicates a lethal or severe in‐
jury will occur.
➤ The measures required to protect yourself from danger are shown here.
Warning notes referring to a sub-section or the subsequent action are integrated into the procedure
and numbered as an action.
Example:
1. WARNING!
These show the kind of danger and its source.
The possible consequences of ignoring a warning are shown here.
If you ignore the warning notice, the "WARNING" signal word indicates that a lethal or severe
injury may occur.
➤ The measures required to protect yourself from danger are shown here.
2. Always read and comply with warning instructions.
Example:
NOTICE
These show the kind of danger and its source.
Potential effects when ignoring the warning are indicated here.
➤ The protective measures against the damages are shown here.
Material Here you will find details on special tools, operating materials or spare parts.
Precondition Here you will find conditional requirements necessary to carry out the task.
Here conditions relevant to safety are named that will help you to avoid dangerous situations.
3 Technical Specifications
3.1 Controller SIGMA CONTROL 2
Industrial PC
■ Internal temperature monitoring
■ Internal undervoltage monitoring
■ Battery-buffered real-time clock
─ Battery service life: more than 10 years
─ Battery replaceable
Display
Characteristic Value
Graphical display [px] 255 x 128
Width [mm] 82
Height [mm] 41
Maximum number of lines/characters 8/30
Colours Black/white with grey scale
Lighting LED backlit
px ≙ pixel
Characteristic Value
Hardware on the SIGMA CONTROL 2 controller RFID write/read device
Hardware (external) RFID Equipment Card
Recognition distance [m] max. 0.05
Characteristic Value
Frequency [MHz] 13.56
Emitted maximum transmitting power at 10 m dis‐ 11
tance [dB(µA/m)]
Tab. 13 RFID
The RFID read/write device transmits at a frequency of 13.56 MHz and is permitted for use in
EU member states.
Input/Output Number
Digital input (DI), 24 VDC 8
Digital output transistor (DOT), 24 VDC, 0.5 A 2
Analogue input current (AII), 0–20 mA 2
Analogue input resistor (AIR), PT100 2
Digital output relay (DOR), 250 VAC, 4 A 5
There are three different types of input/output modules with different numbers of inputs and out‐
puts.
The number of input/output modules actually available depends on the machine type and the avail‐
able options.
Refer to the machine's wiring diagram for the input/output modules installed in your equipment.
IOM 1
Input/Output Input/output module 1
Internal, in available in External, in
the control parallel on the compres‐
cabinet both sides sor interior
Digital input (DI), 24 VDC 4 10 2
Analogue input current (AII), 0–20 mA – 1 2
Analogue input resistor (AIR), PT100 – 1 3
Digital output relay (DOR), 250 VAC, 8 A 8 – –
Digital output transistor (DOT), 24 VDC, 0.5 A – 2 1
Analogue output current (AOI), 0–20 mA – – –
Tab. 16 SC2IOM-1
IOM 2
Input/Output Input/output module 2
Internal, in available in External, in
the control parallel on the compres‐
cabinet both sides sor interior
Digital input (DI), 24 VDC 6 – 2
Analogue input current (AII), 0–20 mA – 1 2
Analogue input resistor (AIR), PT100 – 3 –
Digital output relay (DOR), 250 VAC, 8 A 4 – –
Digital output transistor (DOT), 24 VDC, 0.5 A – 2 2
Analogue output current (AOI), 0–20 mA – 1 –
Tab. 17 SC2IOM-2
IOM 3
Input/Output Input/output module 3
Internal, in available in External, in
the control parallel on the compres‐
cabinet both sides sor interior
Digital input (DI), 24 VDC 6 – 2
Analogue input current (AII), 0–20 mA – 1 3
Analogue input resistor (AIR), PT100 – 3 8
Digital output relay (DOR), 250 VAC, 8 A 8 – –
Digital output transistor (DOT), 24 VDC, 0.5 A – 1 1
Analogue output current (AOI), 0–20 mA – 1 –
Tab. 18 SC2IOM-3
Characteristic Value
Degree of protection within the machine IP 54
Degree of protection within the control cabinet IP 20
Characteristic Value
Width [mm] 125
Height [mm] 250
Depth [mm] 44
3.1.5 Sensors
Pressure transducer
Characteristic Value
Output signal [mA] 0/4–20
Characteristic Value
Connection Two-core
Resistance thermometer
Characteristic Value
Sensing resistance (to DIN IEC 751) PT100
Connection Two-core
Components
Function
Typical application:
■ Operators log on at the machine.
(Manual input of the password not required)
5.3 Display
Use the display to read information and to check entered data. The display comprises 8 lines, each
of 30 characters.
During operation, the display will indicate the operating mode.
Press «Enter» or one of the arrow keys to open the main menu. Here, you can set the language to
be used for the display of texts or open the various submenus.
Header
The header is the topmost line on the display. It is always shown as white text on a black back‐
ground.
Important information and values are displayed in the header.
Depending on the settings, either the current state of the machine or a menu text is shown in line 3.
The following parameters with their current values are displayed in line 5:
■ Remote control yes/no
■ Time control yes/no
■ Pressure control
The following parameters with their current values are displayed in lines 7 and 8:
■ The hours during which the machine was activated
■ The hours during which the machine ran in operating mode LOAD.
■ Remaining time of the machine until the next maintenance
Representation
The main menu is the top menu level. You open the individual submenus in the main menu.
A scrollbar appears at the right side of the display if you open a menu with more than 6 lines. It
represents the currently visible portion of the menu. A short scrollbar thus indicates that the opened
menu is very long as only a small portion can be displayed.
The image above provides an example for the appearance of the main menu (without scrollbar).
Numbering
Active line
The active line is always shown as white text on a dark background. In deviation of this, the header
is also shown as white text on a dark background, but cannot be selected.
Press «Enter» to open a menu in the active line. This opens the selected menu.
You change parameters in Setting mode.
Setting parameters
Press «Enter». The value of the parameter will flash indicating that it can be changed.
The «Enter» key affects only the active line.
In some lines, you can change more than one parameter.
In this case, you must first select the specific parameter with the «Left» or «Right» keys.
In order to reset current parameters to zero, activate the check box for Reset in the active line of
the display.
First, press «Enter» to switch into setting mode. The check box Reset will flash.
You then press «Up». The check box is activated and flashes.
Press «Enter» to save the settings.
The display no longer flashes and the parameters are reset. The check box for Reset is again de‐
activated.
Further information For opening KAESER CONNECT, login and other procedures, please see chapter 8.3.
Subsequently, the software is loaded and the current operating mode is displayed (example):
6.1bar 08:15AM 80° C Header
------------------------------
Load Current operating mode
------------------------------
Key – on ¦ pA – on Operating parameters
------------------------------
Run 2500h Load 2490h Operating parameters
Maintenance in 500h Maintenance indicator
Main menu
Navigation Function/Sub-menu
1 Status ■ Messages
■ Statistics
■ Current pressure control
■ Current operating mode
■ DI/DO status
■ pN/ADT curve
■ pN/n curve 1)
Navigation Function/Sub-menu
2 Performance data ■ Compressor
─ System pressure pNloc
─ Internal pressure pi
─ ADT
─ Oil separator
─ Starting temperature
─ Inlet temperature
─ PD temperature
─ Air filter
■ Compressor motor
─ Motor temperature (if available)
─ Speed 1)
─ Current 1)
─ UzK 1)
─ Torque 1)
─ Reference value 1)
■ Fan
─ Speed 1)
─ Current 1)
─ UzK 1)
─ Torque 1)
■ Analogue values
■ SIGMA CONTROL 2
3 Operating data ■ Operating hours
─ Compressor
─ On load
─ Motor
─ Compressor block
─ SIGMA CONTROL 2
─ Partial load valves
■ Switching cycles
─ Load valve on
─ Mains contactor on
■ kWh counter
1)
Power switching with frequency converter
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
Navigation Function/Sub-menu
4 Maintenance Oil filter
Oil separator
Oil change
Air filter
Valve inspection
Belt/coupling inspection
Compressor motor
Bearing lube
Bearing change
Fan motor(s)
Bearing lube
Bearing change
Electrical equipment
Annual maintenance due
5 Configuration For details of the Configuration menu, please
see table 34.
6 Compressor clock Key clock
Reset
Switching point 01:
Switching point 02
Switching point 03
Switching point 04
Switching point 05
Switching point 06
Switching point 07
Switching point 08
Switching point 09
Switching point 10
7 User Name
Password
Current access level:
8 Communication ■ Ethernet/SIGMA NETWORK
■ Com-Module 3)
Key remote
For details of the Communication menu, please
see table 37.
9 Machine test ■ TÜV inspection
1)
Power switching with frequency converter
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
Navigation Function/Sub-menu
10 Components ■ Compressor motor
─ Power switching
Navigation Function/Sub-menu
1.1 Messages ■ Current messages
■ Message history
─ Compressor messages
─ Diagnostic messages
─ System messages
■ Address error
─ Incorrect parameterisation in 2)
Status report
current Alarms
current Warnings
1.2 Statistics Load (hours)
since/Reset:
Load (speed) 1)
since/Reset:
Network actual pressure pNloc
Internal pressure
Motor starts
since/Reset:
Motor starts /d
Motor starts /h
Motor starts T↓
Last load run
Last idle run
Last motor off
1)
Power switching with frequency converter
2)
only visible in the event of parameterization error
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
Navigation Function/Sub-menu
1.3 Current pressure control SIGMA CONTROL 2
Cut-out pressure
SP/SD
Network actual pressure
Frequency converter 1)
Setpoint pressure 1)
Actual pressure 1)
Speed nominal value 1)
Speed actual value 1)
Speed limits 1)
1.4 Current operating mode Compressor on
Load control
Control mode
Idle period
Acknowledgement
Heat recovery (if available)
1.5 DI/DO status 1st I/O module
DI/DO display
2nd I/O module
DI/DO display
3rd I/O module
DI/DO display
1.6 pN/ADT curve Diagram:
Nominal pressure/airend discharge temperature
1.7 pN/n curve 1) Diagram:
Nominal pressure/Speed
1)
Power switching with frequency converter
2)
only visible in the event of parameterization error
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
Navigation Function/Sub-menu
5.1 General ■ System information
─ SIGMA CONTROL 2 MCS 3)
─ Software
─ KAESER:PN/SN
─ Controller manufacturer:PN/SN
─ MFGDT (Manufacturing date)
─ Compressor
─ EN (Equipment number)
─ PN (Material number)
─ SN ( Serial number)
─ I/O modules
─ First IOM
─ Second IOM (if available) 3)
─ FC information 1)
─ Compressor motor
─ Oil-/air cooler fan
─ Oil cooler fan
Model:
Date/time
Time zone
■ Time server
─ active:
─ IP address
Date format
Time format
Pressure unit
Temperature unit
Display lighting
5.2 Pressure control ■ Pressure sensors
■ Pressure settings
■ Load control
■ Network actual pressure
Navigation Function/Sub-menu
5.3 Control mode Local mode:
■ Venting period 4)
■ DUAL
■ QUADRO 4)
■ Partial load valves 4)
5.4 Compressor start ■ Compressor on
■ Compressor off
Autostart:
Start inhibit:
Starting temperature
5.5 Acknowledgement Remote mode:
RC ack
Key remote
5.6 ETM Heat recovery
Local mode:
Remote mode:
current
RC DI
Key remote
Heat recovery
ADT controller
Thermostat valve
Oil cooler
Thermostat valve
ADT controller
■ Oil cooler
■ Heat recovery
5.7 I/O periphery ■ DO functions
■ Analogue values
■ External messages
■ Switch
Navigation Function/Sub-menu
5.8 Timer on
off
DOR
current
5.9 Refrigeration dryer (if available) Control mode
Compressor ready:
Compressor Clk/RC/RB off:
Temperature ↑
DOR
DOT
Temperature ⇟
DOR
DOT
Safe compressed air supply/Safe compressed
air quality
Error operation without RD
active:
Run time max.:
Reset Alarm:
5.10 Save data Language:
Save data
1)
Power switching with frequency converter
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
4)
SIGMA CONTROL 2 FLUID
Navigation Function/Sub-menu
5.2.1 Pressure sensors System pressure pNloc
Internal pressure pi
1)
Power switching with frequency converter
4)
SIGMA CONTROL 2 FLUID
5)
SIGMA CONTROL 2 VAC
Navigation Function/Sub-menu
5.2.2 Pressure settings System pressure high 5)
pRV (Safety valve actuating pressure)
Pressure rise 4)
pE SP/SD
ΔpFC 1)
Nominal pressure
Setpoint pressure
pA SP/SD
pB SP/SD
System pressure low
Cut-in pressure min
Pressure fall 5)
5.2.3 Load control Local mode
Remote mode
■ pA/pB Clock
(Menu see Remote mode)
pA/pB Cycle
pA/pB RC
pA/pB DO
Load RC
loc.-load RC
Key remote
Key idle
5.2.4 Network actual pressure pNloc (localer network pressure)/FC USS 1)/AII
AII
For sensor error:
Type of message:
Warning
Alarm
1)
Power switching with frequency converter
4)
SIGMA CONTROL 2 FLUID
5)
SIGMA CONTROL 2 VAC
Navigation Function/Sub-menu
5.7.1 DO functions Controller on
DOR
DOT
Compressor on
DOR
DOT
Motor running
DOR
DOT
Idle
DOR
DOT
On load
DOR
DOT
Group alarm
DOR
DOT
Group warning
DOR
DOT
Remote mode
DOR
DOT
Clock active
DOR
DOT
■ Clock contact
DOR
DOT
EMERGENCY STOP
DOR
DOT
1)
Power switching with frequency converter
Navigation Function/Sub-menu
5.7.2 Analogue values ■ AnMod (Analogue modules)
─ AnMod_p_1
─ AnMod_p_2
─ AnMod_p_3
─ AnMod_p_4
─ AnMod_T_1
─ AnMod_T_2
─ AnMod_T_3
─ AnMod_T_4
─ AnMod_I_1
─ AnMod_I_2
■ AI (Analogue inputs)
─ AI_p_1
─ AI_p_2
─ AI_T_1
─ AI_T_2
─ AI_I_1
─ AI_I_1
■ AO (Analogue outputs)
─ AO_p_1
─ AO_p_2
─ AO_T_1
─ AO_T_2
─ AO_I_1
─ AO_I_2
─ AO_n_1 1)
■ PD (Process data)
─ PD_p_1
─ PD_p_2
─ PD_T_1
─ PD_T_2
─ PD_I_1
─ PD_I_2
5.7.3 External messages ■ External message 1
■ External message 2
■ External message 3
■ External message 4
■ External message 5
■ External message 6
1)
Power switching with frequency converter
Navigation Function/Sub-menu
5.7.4 Switch ■ System pressure pNloc
■ Internal pressure pi
■ ADT
■ Inlet temperature
■ PD temperature
■ n Compressor motor
1)
Power switching with frequency converter
Navigation Function/Sub-menu
8.1 Ethernet/SIGMA NETWORK ■ IP configuration
─ IP address
─ Subnet mask
─ Gateway
─ DNS Server 1
─ DNS Server 2
─ Restart network
■ Connections
─ SIGMA CONTROL 2
─ SAM 4.0
Restart
Timeout
Cycle time
For details of the Connections menu, please see
table 38.
■ E-mail
─ active:
Compressor number:
Language:
Repeat cut-off time:
Use SSL:
─ Sender address:
Sender name:
Contact telephone:
Receiver address:
─ SMTP Server:
User name:
Password:
─ Port/Timeout
Resend after:
MAC: MAC address
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
Navigation Function/Sub-menu
8.2 Com-Module 3) The content of the menu depends on the type of
the communication module identified.
Navigation Function/Sub-menu
8.1.2 Connections ■ SIGMA CONTROL 2
─ Status
─ Mode
─ Port
─ Communication partner
─ IP address
─ Communication error
Start td
Timeout
■ SAM 4.0
─ Status
─ SAM 4.0 active:
Send/receive
Send
─ IP address
─ Port
─ Communication error
Start td
Timeout
Restart
Timeout
Cycle time
Navigation Function/Sub-menu
10.1 Compressor motor USS status: Run/Error
■ Power switching
─ Star-delta start
─ DOL start
─ High-voltage cell 3)
─ SFC USS 1)
─ Softstart 3)
─ Customer-provided 3)
Navigation Function/Sub-menu
10.1.1 Power switching ■ Star-delta start
─ Temp. warm start
─ Star time T↑
─ Star time T↓
─ Υ/Δ switching time
─ Overload relay
─ Mains contactor
─ Star contactor
─ Delta contactor
■ DOL start
─ Run-up period:
─ Overload relay
─ Mains contactor
─ Delta contactor
■ High-voltage cell 1)
─ Run-up period:
─ ready
─ Mains contactor
■ SFC USS 1)
USS status: Run/Error
─ Run-up period:
─ Service operation
─ Heavy load monitoring
─ Mains contactor
─ STO channel A
─ STO channel B
■ Softstart 1)
─ ready
─ Motor running
─ Start-up ended
─ Start
─ Reset
─ Mains contactor
■ Customer-provided 1)
─ Temp. warm start
─ Run-up period T↑
─ Run-up period T↓
─ ready
─ Mains contactor/Alarm td
─ Redundancy contactor/Alarm td
1)
Power switching with frequency converter
3)
SIGMA CONTROL 2 (Prepared for connection to control centre)
READY
The compressor motor / engine starts as soon as network pressure is lower than the network nomi‐
nal pressure (cut-off pressure).
In addition, timing and/or remote control may affect the start of the motor.
LOAD
IDLE
The compressor motor / engine runs unloaded with low power consumption.
■ The inlet valve is closed.
■ The minimum pressure/check valve isolates the oil separator tank from the air system
■ The venting valve is open
A small volume of air circulates through the bypass bore in the inlet valve, through the airend and
back to the inlet valve via the venting line.
DUAL
In the DUAL control mode, the machine is switched back and forth between LOAD and IDLE to
maintain the machine working pressure between the preset minimum and maximum values. When
maximum pressure is reached, the machine switches to IDLE. When the preset idling time has
elapsed, the machine switches to READY.
The idling time is factory preset according to the maximum starting frequency of the compressor
motor / engine. The shorter the idling time setting, the sooner (and more frequently) the drive mo‐
tor / engine is stopped.
QUADRO
In contrast to the the DUAL regulating mode, the machine will switch from LOAD to READY in
QUADRO mode after periods with low compressed air consumption.
After periods with a high compressed air consumption, the machine will switch from LOAD to
READY after passing through IDLE.
In this control mode, the controller requires two specified times: The minimum run-time and the
unloaded period.
The shorter these times are set, the sooner (and more frequently) the motor / engine is stopped.
VARIO
The VARIO mode is based on the DUAL control mode. The difference to DUAL is that the idling
time is automatically lengthened or shortened to compensate for higher or lower machine starting
frequencies.
CONTINUOUS
In the CONTINUOUS control mode, the machine is switched back and forth between LOAD and
IDLE, in order to maintain the machine's working pressure between the preset minimum and maxi‐
mum values. When maximum pressure is reached, the machine switches to IDLE. However, the
machine does not switch to READY.
DYNAMIC
In contrast to the the DUAL regulating mode, the machine will switch from LOAD to READY in
DYNAMIC mode at low drive motor / engine temperature.
And from LOAD via IDLE to READY at a high drive motor / engine temperature.
The lower the drive motor / engine temperature, the sooner (and, therefore, more often and longer)
it is stopped.
The MODULATING control is an additional mechanical regulation. It continuously changes the flow
rate within the machine's control range.
A control valve, the proportional controller, changes the degree of opening of the inlet valve when
the machine transports compressed air into the air network (LOAD)
The load and power consumption of the drive motor / engine rises and falls with the air demand.
Outside the frequency converter's range of control the machine reverts to the selected control
mode.
DUAL:
The minimum controllable speed is reached and the machine switches to IDLE mode. The drive
engine runs unloaded with low power consumption.
When the preset idling time has elapsed, the machine switches to READY.
VARIO/QUADRO/CONTINUOUS:
The minimum controllable speed is reached and, depending on the air demand at the time, the ma‐
chine switches either to READY or to IDLE. The machine remains in IDLE at least for the duration
of the venting time, before it switches to READY.
DYNAMIC:
The minimum controllable speed is reached and, depending on the air temperature of the drive mo‐
tor / engine, the machine switches either to READY or to IDLE. The machine remains in IDLE at
least for the duration of the venting time, before it switches to READY.
The frequency converter runs the motor / engine up to a speed at which air delivery matches the
air demand.
The inlet valve opens and the machine delivers compressed air.
The speed of the drive motor / engine is regulated according to the air demand.
NOTICE
UV radiation!
Direct sunlight (UV radiation) can destroy the display screen.
➤ Do not allow the display screen to be subjected to direct sunlight.
7 Installation
7.1 Reporting Transport Damage
1. Check the machine for visible and hidden transport damage.
2. Inform the carrier and the manufacturer in writing of any damage without delay.
➤ Label the starting device in the remote control centre as follows (suggestions):
➤ Attach the following notice to indicate the ON/OFF timer program machine operation (sugges‐
tion):
8 Initial Start-up
8.1 Outline
SIGMA CONTROL 2 was designed and developed for a number of applications. The settings that
can be made are correspondingly varied.
It is possible that only a few of these settings are needed for the initial start-up. This depends on
the application involved.
8.2: Setting the controller (display format, units, languages, etc.)
8.3: Using KAESER CONNECT
8.4: Pressure parameters of the machine
8.5: Machine start and stop
8.6: Control modes
8.7: Electronic Thermal Management
8.8: Refrigeration dryer
8.9: Setting the machine for local mode
8.10: Setting the machine for master control operation
8.11: Input and output signals
8.13: Activating remote acknowledgement
8.14: Linking to an external pressure transducer
8.15: Commissioning the machine
2. Press «Enter».
The Main menu is displayed.
6.1bar 08:15AM 80° C Header
Main menu
----------------English GB---------------- Current language
▶1 Status Sub-menu
▶2 Performance data Sub-menu
▶3 Operating data Sub-menu
▶4 Maintenance Sub-menu
▶5 Configuration Active line
7. Use «Up» or «Down» to select a menu item in the General sub-menu such as System
information.
8. Press «Escape» repeatedly to leave this menu.
Depending on the selected language, the system automatically sets the units and the time
and date formats. You can manually change these settings (see chapter 8.2.10).
1. Press «Enter».
The Main menu is displayed.
6.1bar 08:15AM 80° C Header
Main menu
----------------English GB---------------- Current language
▶1 Status Active line
▶2 Performance data Sub-menu
▶3 Operating data Sub-menu
▶4 Maintenance Sub-menu
▶5 Configuration Sub-menu
3. Press «Enter».
The currently set language flashes.
4. Use «Up» or «Down» to select the desired language.
5. Press «Enter».
Name: E00019895
Level: 2
2. Press «Enter».
The access right is confirmed.
The RFID Equipment Card is damaged or lost?
➤ Manually enter the user name and password, see chapter 8.2.6.
You have noted your user name and stored it at a suitable location (see chapter 8.2.3). In the next
step, generate a password on SIGMA CONTROL 2. Note this generated password as well, and
store it a suitable location. If your RFID Equipment Card is damaged or lost, the card won't be nec‐
essary to manually log on to SIGMA CONTROL 2 when you have these two pieces of information.
Name: E00019895
Level: 2
Precondition The user name (see chapter 8.2.3) and password (see chapter 8.2.5) are known.
The operating mode is displayed.
Result You are now logged on to SIGMA CONTROL 2 with access level 2, having manually input your
user name and the password.
Precondition The RFID Equipment Card delivered with the machine and at least one additional teachable RFID
Equipment Card are available.
The operating mode is displayed.
1. Hold the RFID Equipment Card delivered with the machine in front of the RFID reader.
Users are always logged on with access level 2.
6.1bar 08:15AM 80° C Header
Log-in successful Menu
Button to change password Prompt, whether the password is to be changed
------------------------------
Name: E00019895
Level: 2
2. Within 10 minutes, hold the master RFID Equipment Card to be taught in front of the RFID
reader.
The master RFID Equipment Card is not registered at the machine.
6.1bar 08:15AM 80° C Header
Registration successful The master RFID Equipment Card has been regis‐
tered
------------------------------
Name: E00017326
Level: 2
3. Repeat the above steps at the next machine if the master RFID Equipment Card is to be regis‐
tered at other machines.
Result You have registered a master RFID Equipment Cards at the machine.
➤ When operating the machine with a timer program, check the time settings at least once
a year.
➤ You can automatically synchronise date and time using a time server. Manual setting of
the time is no longer required in this case. See chapter 8.2.16.
1. Open the 5.1 <Configuration – General> menu.
2. Use «Up» or «Down» to select the Date/time line.
4. Press «Enter».
The display for days 00.00.00 flashes.
5. Use «Up» or «Down» to set the day.
6. Press the «Right» arrow.
The display for months 00.00.00 flashes.
4. Press «Enter».
The time zone display flashes.
5. Use «Up» or «Down» to set the time zone.
6. Press «Enter».
The setting is applied.
7. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The MM/DD/YY display flashes.
4. Use «Up» or «Down» to set the date format.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The hh:mm:ssAM/PM indication flashes.
3. Press «Enter».
The display for the set unit flashes.
4. Use «Up» or «Down» to set the unit.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
3. Press «Enter».
The display for the set unit flashes.
4. Use «Up» or «Down» to set the unit.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Mode 1 2 3
Indication automatic on off
Function The illumination extin‐ Permanent setting Permanent setting
guishes after the time- Illumination "on" Illumination "off"
out has elapsed.
4. Press «Enter».
The display for the set mode flashes.
5. Use the «Up» or «Down» keys to set the auto. mode.
6. Press «Enter».
The setting is applied.
7. Press the «Right» arrow.
8. Set the value for the Timeout in the same manner: 1 min, for example.
9. Press «Enter».
10. Press «Escape» repeatedly to leave this menu.
Result The display illumination is set for automatic operation with deactivation after one minute without
user intervention.
5. Press «Enter».
The «Remote control» key is activated.
6. Press «Escape» repeatedly to leave this menu.
Proceed in the same manner to deactivate the «remote control» key.
8.2.14 IP configuration
For the SIGMA CONTROL 2 to be connected to the network, you must set the IP configuration (for
KAESER CONNECT for example).
If you use SIGMA CONTROL 2 as the master control of two machines, you set other network
parameters in the IP configuration menu (see chapter 8.10.4).
The network parameters for the IP configuration must be specified manually. You cannot use
DHCP for an automatic IP configuration.
4. Press «Enter».
The first group of numbers of the IP address flashes 169.254.100.101.
5. Use «Up» or «Down» to set the first group of numbers of the IP address.
6. Press the «Right» key.
The SECOND group of numbers of the IP address flashes 192.168.100.101.
7. Use «Up» or «Down» to set the second, third and fourth group of numbers of the IP address.
The IP address is correctly set.
8. Press «Enter».
The setting is applied.
9. Press «Down».
The Subnet mask line is displayed.
10. Set the remaining network parameters as described above:
3. Press «Enter».
The check box active: will flash.
4. Press «Up».
The check box is deactivated.
5. Press «Enter».
The e-mail function is deactivated.
6. Set the e-mail parameters as described above:
7. Activating the e-mail function: Activate the active: check box as described above.
8. Press «Escape» repeatedly to leave this menu.
Result The e-mail parameters are set and the e-mail function is activated.
3. Press «Enter».
The first group of numbers of the IP address flashes 192.053.103.103.
4. Use «Up» or «Down» to set the first group of numbers of the IP address.
5. Press the «Right» key.
The second group of numbers of the IP address flashes 192.053.103.103.
6. Use «Up» or «Down» to set the second, third and fourth group of numbers of the IP address.
The IP address is correctly set.
7. Press «Enter».
The setting is applied.
8. Use «Up» or «Down» to select the active: line.
9. Press «Enter».
The check box active: will flash.
10. Press the «Up» key.
The check box is activated.
6.1bar 08:15AM 80° C
5.1.2 Time server Menu
active: ☑ The time server function is activated.
IP address 192.053.103.103 Example address, time server
■ System status
■ Graphs
■ Messages
■ I/O display
■ User management
■ Settings
■ Backup
■ Data recording
Thus, KAESER CONNECT provides an excellent option for an easy and quick check of the econo‐
my and energy efficiency of your machines.
For KAESER CONNECT to be able to use the Internet-capable device, it must be registered
in the same network as SIGMA CONTROL 2.
To be able to use KAESER CONNECT, the browser installed on the Internet-capable device
must be able to display HTML5 content. For security reasons, we strongly recommend to use
only up-to-date browser versions.
1. Use an Ethernet cable to connect SIGMA CONTROL 2 to the Internet-capable device or net‐
work.
2. In the web browser, enter the IP address of the controller.
The log-in mask is displayed.
You can display the automatically-recorded machine data for any time in the past.
Precondition An SD card with sufficient free memory is inserted in the X5 SD card slot
The SD card was inserted for the entire operating time of the machine.
The SIGMA CONTROL 2 data recorder function is activated.
1. Enter the date and time for the start time in the required time period in Start:.
2. Enter the date and time for the end time in the required time period in End:.
3. Click 6 .
The machine data for the specified time interval are loaded and displayed.
Parameters Explanation
pRV Display:
Actuating pressure of the safety valve on the oil separator tank
pE Pressure increase
Setting:
■ pE SP: Switching point for pressure increase; upper safety limit for machine
maximum pressure; in an external LOAD control, this value is used to switch
the machine from LOAD to IDLE in the event of a fault.
■ pE SD: Switching differential of pressure increase
ΔpFC Limiting value for machines with frequency-controlled drive (SFC).
Setting:
■ dp FC: Limit of lowest flow rate. When the value [switching point system set-
point pressure +dp FC] is exceeded, the compressor switches from LOAD to
IDLE.
Nominal Display:
pressure Nominal press.:The compressor is designed for this pressure (maximum network
nominal pressure)
Setpoint Network nominal pressure can be regulated to 2 values: pA and pB.
pressure
Setting:
■ Switching point pA or control pressure pA in machines with frequency convert‐
er (SFC)
■ Switching point pB or control pressure pB in machines with frequency convert‐
er (SFC)
System A warning message is displayed when the limit value for the network pressure is
pressure low reached.
Setting:
■ SD: Switching differential for network pressure low
↓: Switching point for network pressure low
■ Option: Configure the output signal
Warning message displayed or an additional output signal is sent, e.g., to a
control centre
Parameters Explanation
Cut-in Display:
pressure min For design reasons, pressure can only be built up above this value.
Tab. 54 Setting limits for the network nominal pressure (* Cut-in pressure min)
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the pA SP value.
5. Press «Enter».
The setting is applied.
6. Set the SD switching differential in the same manner.
7. If necessary, adjust the value for the pB SP and the SD switching differential in the same way.
8. Press «Escape» repeatedly to leave this menu.
Result The parameters for the network nominal pressure pA and pB are set.
When the network pressure drops to the value System pressure low, SIGMA CONTROL 2 displays
a warning message for insufficient network pressure.
The switching differential influences the pressure at which the message can be acknowledged or
the optionally activated output will again switch:
Message Output
5.0 bar Message coming Active
5.5 bar Message going Inactive
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the value for System pressure low.
5. Press «Enter».
The setting is applied.
6. If necessary, adjust the value for the SD switching differential in the same way.
7. Press «Escape» repeatedly to leave this menu.
The pressure increase pE SP serves as a safety limit when the machine is externally controlled.
When the network nominal pressure reaches the value pE SP (for example, when the external con‐
trol functions incorrectly) the machine switches to IDLE. The warning message External load
signal? is triggered.
The parameter for pE SP pressure increase is pre-set and cannot be changed. You can, however,
adjust the SD switching differential.
3. Press «Enter».
The setting mode is active.
4. Use «UP» or «DOWN» to set the required value for SD.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
5. Press «Enter».
The «IDLE» key is de-activated.
6.1bar 08:15AM 80° C Header
5.2.3 Load control Menu
Logic : +
loc.-load RC DI1.07 ☑
Logic : +
·········
Key remote: ☐
Key idle: ☐ Active line with deactivated check box
Result Thus, it is ensured that unauthorised users can press the «IDLE» key without the machine switch‐
ing to IDLE.
When setting a clock programme for the first time, note first the switching times on the "User-
defined clock programme" table for example.
You can also program an OFF time (plant vacation shut-down) (see Section 8.5.2).
Example
■ Machine ON: On weekdays 06:30AM – 05:00PM, Fridays 06:30AM – 03:00PM
■ Machine OFF: Sat – Sun and during midday break 12:00PM – 01:00PM
3. Press «Enter».
The n.a. indication flashes.
4. Use «Up» or «Down» to set the weekdays.
5. Press the «Enter» key.
The setting is applied.
6. Press the «Right» key.
7. Press «Enter».
The display for hours, 00:00 flashes.
8. Use «Up» or «Down» to set the hours.
9. Press the «Right» arrow.
10. The display for minutes, 00:00 flashes.
11. Use «Up» or «Down» to set the minutes.
Result Weekdays, time and the Compressor ON/Compressor OFF actions are set for all switching points
of the user-defined clock program.
➤ Press the «Time control» key on the SIGMA CONTROL 2 operating panel to activate the time
control.
Result The Time control LED on the operating panel of the SIGMA CONTROL 2 signalises with green
continuous light that the machine is operated with activated time control.
The time control of SIGMA CONTROL 2 switches the machine according to the defined switching
points of the time program.
3. Press «Enter».
The display for days 00.00.00 flashes.
4. Use «Up» or «Down» to set the day.
5. Press the «Right» arrow.
The display for months 00.00.00 flashes.
6. Use «Up» or «Down» to set the month.
7. Press the «Right» arrow.
The display for years 00.00.00 flashes.
8. Use «Up» or «Down» to set the years.
9. Press «Enter».
The setting is applied.
10. Press «Down».
11. Press «Enter».
The display for hours 00:00:00 flashes.
12. Use «Up» or «Down» to set the hours.
13. Press the «Right» arrow.
The display for minutes 00.00.00 flashes.
14. Use «Up» or «Down» to set the minutes.
Result In this example, a company shut-down (standstill time) for the time between 12/23/16 / 05:00PM
until 01/04/17 / 06:30AM has been set for the machine.
Overview
■ Make the electrical connection (a spare input for the remote contact is to be found in the elec‐
trical wiring diagram for the machine, DI 1.07 being preferred).
■ Switch machine start to remote mode
■ Activating the «remote control» key
■ If necessary, activate the «Time control» key and configure the clock program (see chap‐
ter 8.5.1.2).
■ If required, assign a different input for the remote contact RC.
■ Press the «Remote control» key.
Two methods are available to start the machine remotely from a control centre:
■ Variant A: Start the machine with the input signal from the remote control centre.
■ Variant B: Starting the machine from the remote control centre in addition to a configured
ON/OFF clock program.
The machine can be started from the remote control centre even though the time control is ac‐
tivated and the ON/OFF program has selected OFF at this point in time.
6. Press «Enter».
The setting is applied.
6.1bar 08:15AM 80° C Header
5.4.1 Compressor on Menu
Local mode:
Key
Remote mode:
Key + remote contact Active line
------------------------------
RC DI1.07 ok ☑
Result The machine start is set to Remote mode Key + remote contact.
2. Press «Enter».
The display for the currently set input flashes.
3. Select another input with the «Up» or «Down» keys.
4. Press «Enter».
The input has now been assigned.
5. Press the «Remote control» key to enable the machine to be started from the remote control
centre.
If your entry is rejected it means that the input is already assigned.
➤ Select a different input.
3. Press «Enter».
The check box Venting period will flash.
4. Press «UP».
The check box is deactivated.
6.1bar 08:15AM 80° C Header
5.4.2 Compressor off Menu
Venting period : ☐ Active line with deactivated check box
·········
Holidays : ☐
Start : 01/01/16
00:00AM
End : 01/01/16
5. Press «Enter».
The setting is applied.
Apart from the discontinuation of the pressure or load requirement, venting of the machine is also
executed when the «OFF» key is pressed.
Press the «OFF» key twice to immediately shut the machine off.
➤ Press the «OFF» key twice.
3. Press «Enter».
The Target display flashes.
4. Use «Up» or «Down» to set the time delay in seconds.
6.1bar 08:15AM 80° C Header
5.4 Compressor start Menu
▶1 Compressor on Active line
▶2 Compressor off
·········
Autostart: ☑ Autostart activated
Target 12s ¦ Actual 0s
·········
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Result The delay time for an autostart after a power failure has been adjusted from 10 s to 12 s.
2. Press «Enter».
The check box Autostart: will flash.
3. Press «Up» key.
The check box Autostart: is deactivated.
4. Press «Enter».
The Autostart: function can be activated in the same manner.
■ The standard setting of the control mode depends on the machine type.
■ The machine-dependant venting phase between the LOAD and READY operating modes
ensures load changes at minimum material stresses.
3. Press «Down».
The currently set control mode is displayed.
4. Press «Enter».
The currently active control mode flashes.
6.1bar 08:15AM 80° C Header
5.3 Control mode Menu
Local mode: Active line
DUAL
------------------------------
▶1 Venting period Venting period menu
·········
▶2 DUAL
3. Press «Enter».
The seconds display flashes.
4. Use «Up» or «Down» to set the seconds.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
2. Use the «Up» or «Down» keys to select the Min. run period line.
3. Press the «DOWN» key.
4. Press «Enter».
The seconds display flashes.
6. Press «Enter».
The setting is applied.
7. If necessary, adjust the target value for the Unloaded period switching differential in the same
way.
8. Press «Escape» repeatedly to leave this menu.
Further information See chapter 5.7 for an overview of the control modes.
Note:
■ The machine runs with increased airend discharge temperature when heat recover is set to ac‐
tive.
■ An increased airend discharge temperature causes poorer efficiency of the compressed air
generation.
7. If a load remote contact controls the remote control, set the remote contact option.
6.1bar 08:15AM 80° C Header
5.6 ETM Menu
Remote mode:
remote contact
current active Status of heat recovery
------------------------------
RC DI1.07 ok ☑ Active line
Key remote :☑
8. Subsequently, set the requested digital input DI in line RC and activate the corresponding
check box.
9. Activate the «Remote control» key (see chapter 8.2.13).
Result The heat recovery system in "remote operation" has been activated.
The «Remote control» key is activated.
No other settings are required.
The current status for the heat recovery is displayed in the current line.
Further information The setpoint value for the airend discharge temperature for the regulator of the electrically control‐
led heat recovery valve can be set manually; see chapter 8.7.2.1.
8.7.2.1 Setting the setpoint value for the airend discharge temperature
The airend discharge temperature and the water outlet temperature are related. To increase
the value for the water outlet temperature, you must increase the setpoint value for the airend
discharge temperature.
Maximum setting = 92 °C.
The specific value of the discharge temperature depends on the respective application for the
heat recovery at the customer's.
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the setpoint for the ADT controller.
6.1bar 08:15AM 80° C Header
5.6 ETM Menu
·········
Oil cooler
ADT controller Active line
·········
▶1 Oil cooler Indication
▶2 ADT controller Indication
5. Press «Enter».
The setting is applied.
Result The setpoint value of the airend discharge temperature for the regulator of the electrically control‐
led heat recovery valve is set.
➤ Set the heat recovery to "inactive" if you cannot use the machine's exhaust heat.
➤ It is mandatory to follow the procedures indicated according to the priorities established for the
compressed air quality or compressed air supply!
4. Press «Enter».
The currently active operating mode flashes.
6. Press «Enter».
The setting is applied.
7. Press «Escape» repeatedly to leave this menu.
Result The CONTINUOUS operating mode has been switched to the TIMER operating mode.
6. Press «Enter».
The setting is applied.
7. Press the «Right» key.
8. Press «Enter».
The setting mode is active.
9. Press «UP».
6.1bar 08:15AM 80° C Header
5.9 Refrigeration dryer Menu
Temperature ↑ Temperature high
DOR1.05 ok ☑¦Logic : + Active line
DOT1.01 ☐¦Logic : +
Temperature⇟ Temperature low
DOR1.03 ☐¦Logic : +
DOT2.01 ☐¦Logic : +
8.8.3 Fault in the refrigeration dryer – compressed air quality has priority
After a fault occurs in the refrigeration dryer, the SIGMA CONTROL 2 shut the machine down.
No compressed air is delivered.
Because compressed air quality (dried compressed air) is crucial, you must call
KAESER SERVICE immediately.
Precondition The operator decides: Compressed air quality has a higher priority than the compressed air supply
1. Keep machine shut down because the required compressed air quality is no longer delivered.
2. Immediately contact KAESER SERVICE.
The KAESER Service Technician eliminates the fault and executes a reset.
The machine is ready for the delivery of high-quality, dried compressed air.
8.8.4 Fault in the refrigeration dryer – compressed air supply has priority
NOTICE
Higher residual humidity in the compressed air
Corrosion due to higher residual humidity in the compressed air.
➤ Assess a "Fault mode without refrigeration dryer" in respect to the further use of the
compressed air.
After a fault occurs in the refrigeration dryer, the SIGMA CONTROL 2 shut the machine down.
In order to ensure compressed air supply for a defined period of time, the operator can activate the
Error operation without RD function. The quality of the compressed air (dried compressed air) is
compromised in this case. The 0069 Error operation without RD
→ Call service! warning message is displayed. The 0069 warning message remains active for the
entire time of operation in fault mode.
Precondition The operator decides: Compressed air supply has a higher priority than the compressed air quality
Access level 2 is activated.
4. Press «Enter».
The setting mode is active.
5. Press the «Up» key.
The check box is activated.
6.1bar 08:15AM 80° C Header
5.9 Refrigeration dryer Menu
·········
Safe compressed air quality
·········
Error operation without RD
active: ☑ Active line
Run time max.: 8h Running time (fixed)
6. Press «Enter».
The setting is applied.
The compressed air delivered in this mode contains a higher residual humidity because the func‐
tion of the refrigeration dryer is defective.
1. Open the 5.2.3 <Configuration – Pressure control – Load control > menu.
The Load control menu is displayed.
Overview
■ Deleting an existing timing program
■ Entering the weekday for the first switching point
■ Enter the time of the first switching point.
■ Set the nominal pressure for the first switching point pA or pB
■ Set up any further switching points.
■ Select the operating mode pA/pB Clock : see chapter 8.9.3.3.
When setting a clock programme for the first time, note first the switching times on the "User-
defined clock program" table for example.
Example
■ Base load period: Weekdays from 06:30AM–05:00PM, Fridays 06:30AM–03:00PM
■ Low load period: Midday from 12:00PM–01:00PM and remaining time
The timing program is established with the following switching points (maximum 10 switching
points available):
1. Open the 5.2.3 <Configuration – Pressure control – Load control > menu.
2. Use the «Up» or «Down» keys to select the pA/pB Clock line.
3. Press the «Enter» key.
The Timing program menu is displayed.
4. Use the «Up» or «Down» keys to select the Reset line.
6.1bar 08:15AM 80° C Header
5.2.3.1 pA/pB Clock Menu
Reset :☐ Active line
·········
01 Mon-Fri 06:30AM pA
02 Mon-Fri 12:00PM pB
03 Mon-Fri 01:00PM pA
04 Mon-Thu 05:00PM pB
1. Open the 5.2.3.1 <Configuration – Pressure control – Load control – pA/pB Clock > menu.
The Timing program menu is displayed.
6.1bar 08:15AM 80° C Header
5.2.3.1 pA/pB Clock Menu
Reset :☐
·········
01 n.a. 00:00AM pA
02 n.a. 00:00AM pA
03 n.a. 00:00AM pA
04 n.a. 00:00AM pA
Observe and keep to the configuration sequence. The pA/pB Cycle operating mode must not
be activated when configuring the timer period.
➤ First set the timer and then the operating mode, or set another operating mode before‐
hand.
1. Open the 5.2.3 <Configuration – Pressure control – Load control > menu.
2. Use the «Up» or «Down» keys to select the pA/pB Cycle line.
3. Press the «DOWN» key.
The pA line is displayed.
4. Press the «Enter» key.
The display for the cycle duration in hours, 00 flashes.
5. Use «Up» or «Down» to set the hours.
1. Open the 5.2.3 <Configuration – Pressure control – Load control > menu.
2. Use the «Up» or «Down» keys to select the Local mode line.
3. Press the «Enter» key.
The display for the set operating mode flashes.
6.1bar 08:15AM 80° C Header
5.2.3 Load control Menu
Local mode : pA/pB Cycle Active line
Remote mode : pB
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
4. Press the «Up» or «Down» keys to set the desired operating mode (pA , pB , pA/pB Clock ,
pA/pB Cycle ).
5. Press the «Enter» key.
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Further information Examples of timing programs for equal machine loading are given in section 8.10.9.
Precondition SIGMA CONTROL 2 is connected to SAM 4.0 via SIGMA NETWORK and ready for operation (see
the SAM 4.0 operating manual in the chapter “Installation”)
Network pressure pB is set as the pressure for the “SAM 4.0 manual mode".
Access level 2 is activated.
The remote control is activated (see chapter 8.2.13)
3. Set the IP address for SIGMA CONTROL 2 using the following pattern:
169.254.100.(SAM 4.0 machine number +102)
(for the setting see chapter 8.2.14).
The IP address for SAM 4.0 has been set on SIGMA CONTROL 2 at the factory:
169.254.100.100 and must not be changed. The same applies to Port 2000.
3. Press «Enter».
The SAM 4.0 active: check box flashes.
4. Press «UP».
The check box is activated.
5. Press «Enter».
The setting is applied.
6. Press the «DOWN» key.
7. Press «Enter».
The currently active operating mode flashes.
Result SIGMA CONTROL 2 communicates with SAM 4.0 via SIGMA NETWORK.
The communication is working smoothly when neither SIGMA CONTROL 2 nor SAM 4.0 report any
communication fault.
After switching on the power supply, monitoring for communication malfunctions is suppressed for
a period of time which can be defined by means of the Start td parameter. The setting depends on
the time passing at the bus master between return of voltage and start of communication via the
bus.
For the communication with SAM 4.0, the value of Start td must be set to 30 s.
SIGMA CONTROL 2 can monitor the bus communication at user level. For this purpose, the bus
master reads a value ("toggle bit") that changes with every bus cycle and returns it without change.
SIGMA CONTROL 2 returns a communication malfunction if the value does not change for a time
longer than set (Timeout).
Monitoring for communication malfunction can be activated if needed. For this purpose, the
Send/receive option must be set for the data exchange. Activate the Communication error
check box to enable monitoring for communication malfunctions.
Overview:
■ PROFIBUS DP-V0 Retrofit Kit required
■ Establishing the electrical connection
■ Set the remote operating mode pB.
■ Set the PROFIBUS interface
■ Activating the «remote control» key
Pin Assignment
1 Spare
2 Spare
3 PROFIBUS connection B
4 TTL signal RTS
5 Earth
6 +5 V for bus terminal
7 Spare
8 PROFIBUS connection A
9 Spare
1. Connect the bus subscribers one after the other according to the pin assignment below.
2. Connect the screening to the plug housings at both ends.
3. Set the terminating resistor in the plug to ON for the first and last subscribers to the
PROFIBUS connection.
Result The terminals for the remaining bus conduit (2A/2B) are switched off.
The SIGMA CONTROL 2 communication interface is closed with a plastic cover when shipped
from the factory. Before you can insert the communication module in the X4 interface, you must
remove the plastic cover from the SIGMA CONTROL 2 . The designation of the interfaces is provi‐
ded on the rear of the SIGMA CONTROL 2.
Overview:
■ Set the slave number
■ Set reaction for a communication malfunction.
■ Activate the communications module
■ Activate the remote mode
Precondition The communication module is plugged and screwed into the X4 interface.
The bus is wired to the bus master.
The machine's voltage supply is activated.
The machine is parametrised as a slave in the bus master.
The bus master is operational.
➤ Proceed as shown.
You must set the slave address for the communication with the SIGMA AIR MANAGER.
When connected to a SIGMA AIR MANAGER, the slave address is determined as follows:
Compressor number used at SIGMA AIR MANAGER +102.
3. Press «Enter».
The display for the slave address flashes.
4. Use «Up» or «Down» to set the slave address 104.
5. Press «Enter».
The setting is applied.
6.1bar 08:15AM 80° C Header
8.2 Com-Module Menu
Send/receive
Com-Module active : ☑
Reset : ☐
Slave No. : 104 Active line
·········
Communication error : ☑ Monitoring for communication malfunction is active.
Exchange of data with a PROFIBUS connection takes place in fixed cycles. The PROFIBUScon‐
nection can be monitored with the help of the cycle time:
The bus connection is considered to be interrupted if no data is exchanged between the bus mas‐
ter and the controller (as bus subscriber) after expiry of a set time period (time-out).
Time-out monitoring is activated. You may neither adjust nor deactivate time-out for
SIGMA AIR MANAGER.
After switching on the power supply, the communication malfunction can be suppressed tem‐
porarily.
Monitoring for communication malfunction can be deactivated if needed. For this purpose, the
Send option must be selected for the data exchange.
■ Settings for SIGMA AIR MANAGER without SIGMA AIR CONTROL PLUS
─ Start: 30 seconds
■ Settings for SIGMA AIR MANAGER with SIGMA AIR CONTROL PLUS
─ Start: 40 seconds
2. Press «Enter».
The check box Communication error will flash.
3. Press «Up».
The check box is activated.
The monitoring for communication malfunctions is active.
4. Use «Up» or «Down» to select the Starttd line.
6.1bar 08:15AM 80° C Header
8.2 Com-Module Menu
Reset : ☐
Slave No. : 103
·········
Communication error : ☑ Communication monitoring is activated
Start td 30s active line
Timeout : 5s ☑
5. Press «Enter».
The 00 seconds display flashes.
6. Use «Up» or «Down» to set the seconds.
7. Press «Enter».
The setting is applied.
If two machines with SIGMA CONTROL 2 are to work in master-slave mode, their controllers
must have the same software version.
You need the following accessories to create the network connection with SIGMA NETWORK or
Ethernet:
■ SIGMA NETWORK cable (7.9679.0) or Ethernet cable with a maximum connection length of
100 m each
■ For each machine with SIGMA CONTROL 2:
─ Retrofit kit LAN RJ45 (7.5250.01870)
■ For connecting the machines to a network (LAN) or switch:
─ 2x RJ45 plug (7.7628.1)
➤ Create the electrical connection according to the local condition. For more information, see the
installation manual for the retrofit kit LAN RJ45 (7.5250.01870)
Use a cross-linked Ethernet cable for the direct connection of two machines.
Connect the Ethernet cable for each machine to the LAN connection or switch.
1. Attach the RJ45-plug to the cable end.
2. Plug the RJ45plug into the network socket until it latches.
■ 1: Clock program
■ 2: Timer
➤ Setting the target pressure change with a clock program; see chapter 8.9.2.
In this mode the automatic base load change between the two machines is carried out in a manner
that idle times of the two compressors are prevented and the energy-efficiency of the compressed
air generation is increased.
Master IP configuration
If the controllers of both machines are linked directly, they must be given different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
1. Set IP address for the master: For instructions, see chapter 8.2.14, IP address for the above
example.
The IP address of machine 1 (master) is set correctly.
2. Open the 8.1.2.1 <Communication – Ethernet/SIGMA NETWORK – Connections – SIGMA
CONTROL 2> menu.
3. Use «Up» or «Down» to select the Mode line.
4. Press «Enter».
The setting mode is active.
6.1bar 08:15AM 80° C Header
8.1.2.1 SIGMA CONTROL 2 Menu
Status Run 0 ¦ Error 0
------------------------------
Mode : Master Active line
Port : 2.001
·········
Communication partner
4. Press «Enter».
The setting is applied.
5. Press «Down».
The pB line is displayed.
6. If necessary, adjust the value for the pB switching differential in the same manner.
Slave IP configuration
If the controllers of both machines are linked directly, they must be given different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
1. Set IP address for the master: For instructions, see chapter 8.2.14, IP address for the above
example.
The IP address of machine 2 (slave) is set correctly.
8.10.5 Configuring master control using the LOAD remote contact (e.g.,
SIGMA AIR MANAGER BASIC)
Overview
■ Establish the electrical connection for LOAD remote contact
■ Set the LOAD remote contact operating mode and assign the input
■ If required, set temporary pressure increase pE.
■ Activating the «remote control» key
8.10.5.1 Establish the electrical connection for remote LOAD contact (excerpt)
Machine (example)
8.10.5.2 Setting the remote LOAD contact operating mode and assigning the input for LOAD remote contact
3. Use «Up» or «Down» to select the input for the LOAD remote contact.
4. Press «Enter».
The setting is applied.
5. Press the «Right» key.
6. Press «Enter».
The check box Load RC will flash.
7. Press «Up».
The check box is activated.
8. Press «Enter».
ok is displayed to the left of the check box.
The operating mode is set.
➤ Set the SD switching differential of the pressure increase as described in chapter 8.4.2.3.
Further information Detailed information on the pressure parameters is provided in chapter 8.4.2.
8.10.6.2 Set the local/LOAD remote contact operating mode and assign the input.
3. Press «Enter».
The currently active operating mode Remote mode flashes.
6.1bar 08:15AM 80° C Header
5.2.3 Load control Menu
Local mode: pA/pB Cycle
Remote mode : loc.-load RC Active line
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
Assign an input for the local/LOAD remote contact for switching the pressure control
3. Use «Up» or «Down» to select a new input for local/LOAD remote contact.
4. Press «Enter».
The input for local/LOAD remote contact is assigned.
3. Press «Enter».
The operating mode display flashes.
6.1bar 08:15AM 80° C Header
5.2.3 Load control Menu
Local mode: pB
Remote mode : loc.-load RC Active line
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
8.10.6.5 Assign an input for the LOAD remote contact for switching the pressure control
4. Use «Up» or «Down» to select the input for the LOAD remote contact.
5. Press «Enter».
The input for LOAD remote contact is assigned.
Overview
■ Setting up remote contact mode pA/pB
■ Assigning the remote contact input
■ Activating the remote control
2. Press «Enter».
The DI display flashes.
6.1bar 08:15AM 80° C Header
5.2.3 Load control Menu
pA/pB RC DI1.05 ☑ Active line
Logic : +
pA/pB DO DOR1.04 ☐
Logic : +
·········
Load RC DI1.07 ok ☑
Result The input for remote contact has now been assigned.
Requirement:
A machine with SIGMA CONTROL 2 (e.g. series BSD) and a conventional machine without
SIGMA CONTROL 2 with the same flow rate are to run in sequence as base load or peak load
machines.
Suggestion:
■ Set the clock program or clock on SIGMA CONTROL 2.
■ Select local mode with time control pA/pB Clock or clock pA/pB Cycle.
■ Select the network nominal pressures pA and pB analogous to the required values. They must
be identical to the pressure switch settings on the machine without SIGMA CONTROL 2.
■ To make the nominal pressure changeover between the two machines possible, a floating re‐
lay contact must be assigned to the selected local operating mode. An auxiliary contactor can
be energised via this contact to activate the pressure switches for pA and pB on the compres‐
sor without SIGMA CONTROL 2. See the example wiring diagram below.
Overview
■ Establishing the electrical connection
■ Set the network nominal pressure pA and pB.
■ Set operating mode in local operating mode
■ Assigning the floating relay contact
■ Set local operating mode
-K3 A1
A2
07-S0629
1. Open the <5.2.2 – Pressure control – Pressure settings> menu (see chapter 8.4.1).
2. Use «Up» or «Down» to select the pASP line.
3. Press «Enter».
The setting mode is active.
The Setpoint pressure pAdisplay flashes.
6.1bar 08:15AM 80° C Header
5.2.2 Pressure settings Menu
Setpoint pressure
pA SP: 8.5bar ¦ SD: −0.5bar Active line
pB SP: 8.2bar ¦ SD: −0.5bar
·········
System pressure low ☐
↓ < 5.0bar ¦ SD: 0.50bar
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the required output.
5. Press «Enter».
The setting is applied.
Result This output can now be used for the changeover between the two pressure switches.
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the pA/pB Clock or pA/pB Cycle operating mode.
5. Press «Enter».
The setting is applied.
Requirement:
A machine with SIGMA CONTROL 2 (e. g. type BSD) and high flow rate is to work as a base load
machine. A second machine (e.g., SK) without SIGMA CONTROL 2 is to supply air in times of low
demand.
Suggestion:
■ Select the system set-point pressures pA and pB of the BSD machine for the switching point of
the SK machine's pressure switch to be in between. When pB is activated for the periods of
low demand, the SK machine automatically functions as the base load machine.
■ Set the required values for a clock program on SIGMA CONTROL 2.
■ Select local mode pA/pB Clock.
■ Activate the compressor timer
Function diagram:
Period t1–t7: high air demand Period t8–t14: low air demand
t1 t8:
Air demand rises. Air demand rises.
System pressure pNloc drops. System pressure pNloc drops.
t2 t9:
BSD switches to LOAD. SK switches to LOAD.
t3: t10:
Network nominal pressure pA reached. Network nominal pressure pB reached.
BSD switches to IDLE. SK switches to IDLE.
t4: t11:
BSD switches to LOAD. BSD switches to LOAD.
Air demand not covered. Air demand not covered.
Period t1–t7: high air demand Period t8–t14: low air demand
t5: t12:
SK also switches to LOAD. SK switches to LOAD.
System pressure pNloc begins to rise. System pressure pNloc begins to rise.
t6: t13:
SK switches to IDLE. SK switches to IDLE.
t7: t14:
BSD switches to IDLE. BSD switches to IDLE.
1. Open the <5.2.2 – Pressure control – Pressure settings> menu (see chapter 8.4.1).
2. Use «Up» or «Down» to select the pASP line.
6.1bar 08:15AM 80° C Header
5.2.2 Pressure settings Menu
Setpoint pressure
pA SP: 8.5bar ¦ SD: −0.5bar Active line
pB SP: 8.2bar ¦ SD: −0.5bar
·········
System pressure low ☐
↓ < 5.0bar ¦ SD: 0.50bar
3. Press «Enter».
The pA display flashes.
Variant A: Daily switch between network nominal pressure pA and network nominal pressure pB
after 24 hours
The machines start with a network nominal pressure pB at 0:00 hours. A timer triggers the switch
between network nominal pressure pA and network nominal pressure pB (local operating mode:
pA/pB Cycle local mode).
Precondition The network nominal pressure pA/pB is configured the same for both machines.
A timer triggers the switch between network nominal pressure pA and network nominal pressure
pB (local operating mode pA/pB Clock.
Precondition The network nominal pressure pA/pB is configured the same for both machines.
Tab. 72 Example for a clock program for equal duty cycling during the day
A timing program triggers the switch between network nominal pressure pA and network nominal
pressure pB (local operating mode: pA/pB SC2Clk).
Precondition The network nominal pressure pA/pB is configured the same for both machines.
Tab. 73 Example for a timing program for equal duty cycling during the week
The requested message can be assigned to a free digital output (DOR orDOT).
4. Press «Enter».
The output of the selected message flashes.
6.1bar 08:15AM 80° C Header
5.7.1 DO functions Menu
Controller on Active line
DOR1.05 ok ☐ ¦ Logic : + Active line with assigned output
DOT1.02 ☐ ¦ Logic : +
Compressor on
DOR1.03 ☐ ¦ Logic : +
DOT1.02 ☐ ¦ Logic : +
Result A message about the operational state is now sent via the assigned digital output.
Overview
Use the External messages menu for specifying the settings.
■ Enter the message text
■ Assign and activate the input
■ Set the time delay
■ Setting the logic
3. Press «Enter».
The cursor is located at the first character of the message text.
A column with alphanumeric characters is displayed.
The selected character flashes.
4. Select the required character with the «Up» or «Down» keys.
5. Press the «Right» arrow.
The cursor jumps to the next position of the message text.
6. Enter the remaining characters of the message text in the same manner.
7. Press «Enter».
The message text has been entered.
8. Press «Enter».
The setting is applied.
8. Press «Enter».
ok is displayed.
The input is assigned and activated.
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the td line.
2. Press «Enter».
The td delay time flashes.
6.1bar 08:15AM 80° C Header
5.7.3.1 External message 1 Menu
External message 1 Message text
DI1.07 ok ☑ Input selected
td: 0s ¦ Logic : + set time delay td
DOR1.04 ☐
Warning ☑ Example: Warning message type
5. Press «Enter».
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
6.1bar 08:15AM 80° C Header
5.7.3.1 External message 1 Menu
External message 1 Message text
DI1.07 ok ☑ Input selected
td: 0s ¦ Logic : + active line, set logic control field
DOR1.04 ☐
Warning ☑ Example: Warning message type
4. Press «Enter».
The message type is set.
Result The signal at the DI digital input is available as External message 1 and as output signal at the
selected DOR output.
Overview
Use the Analogue values or Switch menus for specifying the settings.
■ Enter the message text
■ Select and activate measured value
■ Set the time delay
■ Setting the logic
■ Selecting the message type
■ Assign and activate the output
Below, the settings are displayed based on an example in the Analogue values menu. Use the
Switch menu analogously for specifying the settings.
In the following example, a message from the analogue module is defined by pressure value p1.
1. Use «Up» or «Down» to select the AnMod line.
2. Press «Enter».
The 5.7.2.1 AnMod menu is displayed.
6.1bar 08:15AM 80° C
5.7.2.1 AnMod Menu
▶1 AnMod_p_1 AnMod_p_1 measured value
▶2 AnMod_p_2
▶3 AnMod_p_3
▶4 AnMod_p_4
▶5 AnMod_T_1
▶6 AnMod_T_2
5. Press «Enter».
The cursor is located at the first character of the message text.
A column with alphanumeric characters is displayed.
The selected character flashes.
6. Select the required character with the «Up» or «Down» keys.
8. Press «Enter».
The measured value is assigned and activated.
2. Press «Enter».
The display for the current value of the switching point flashes.
3. Use «Up» or «Down» to set the SP value.
4. Press «Enter».
The setting is applied.
5. If necessary, adjust the value for SD in the same manner
Result The threshold value for the SP switching point and the SD switching differential are set.
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the td line.
2. Press «Enter».
The td delay time flashes.
6.1bar 08:15AM 80° C Header
5.7.2.1.1 AnMod_p_1 Menu
AnMod_p_1 Title 0.0 bar Message text
pNloc ☑ selected analogue measured value, activated
·········
SP: 8.0bar ¦ SD: −0.5bar Switching point (SP) and switching differential (SD)
td: 0s Time delay (td)
·········
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
6.1bar 08:15AM 80° C Header
5.7.2.1.1 AnMod_p_1 Menu
td: 0s Time delay (td)
·········
Warning ☐ set message type, in the example: Warning
·········
DOR1.02 ☐ ¦ Logic: +
DOR1.03 ☐ ¦ Logic: +
4. Press «Enter».
5. Press the «Right» arrow.
6. Press «Enter».
The check box assigned to the message type flashes.
7. Press the «Up» key.
The check box is activated.
8. Press «Enter».
By triggering the message one or two digital DOR outputs can be switched.
1. Use «Up» or «Down» to select the DOR line.
2. Press «Enter».
The DOR display flashes.
3. Select the output with the «Up» and «Down» keys.
4. Press «Enter».
The setting is applied.
6.1bar 08:15AM 80° C Header
5.7.2.1.1 AnMod_p_1 Menu
td: 0s Time delay (td)
·········
Warning ☐ set message type, in the example: Warning
·········
DOR1.02 ☐ ¦ Logic: + active line (DOR output)
DOR1.03 ☐ ¦ Logic: +
8. Press «Enter».
The output is assigned and activated.
9. Press the «Right» arrow.
10. Press «Enter».
The control field Logic flashes.
11. Use «UP» or «Down» to set the desired behaviour, see table 75.
12. Press «Enter».
Result The pNloc measured value at the analogue AnMod_p_1 input is available as a message and as
output signal at the selected DOR output.
Example: Setting for the local network pressure at compressor output System pressure pNloc.
2. Press «Enter».
The display for the current threshold of the switching point flashes.
3. Use the «Up» or «Down» keys to set the SP threshold.
4. Press «Enter».
The setting is applied.
5. If necessary, adjust the value for the SD switching differential in the same way.
Result The threshold for the SP switching point and the SD switching differential are set.
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the td line.
2. Press «Enter».
The td delay time flashes.
6.1bar 08:15AM 80° C Header
5.7.4.1 System pressure pNloc Menu
active: ☐
·········
SP: 0.50bar ¦ SD: −0.6bar Switching point (SP) and switching differential (SD)
td: 0s ¦Logic + Delay (td) and logic
DOR1.01 ☐ Output DOR
Operation ☐ Type of message
Once the threshold has been reached you can switch a digital output DOR.
1. Use «Up» or «Down» to select the DOR line.
2. Press «Enter».
The DOR display flashes.
3. Select the output with the «Up» and «Down» keys.
4. Press «Enter».
The setting is applied.
6.1bar 08:15AM 80° C Header
5.7.4.1 System pressure pNloc Menu
active: ☐
·········
SP: 0.50bar ¦ SD: −0.6bar Switching point (SP) and switching differential (SD)
td: 0s ¦Logic + Delay (td) and logic
DOR1.03 ok ☑ Output DOR
Operation ☐ Type of message
8. Press «Enter».
The output is assigned and activated.
ok is displayed.
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
6.1bar 08:15AM 80° C Header
5.7.4.1 System pressure pNloc Menu
active: ☐
·········
SP: 0.50bar ¦ SD: −0.6bar Switching point (SP) and switching differential (SD)
td: 0s ¦Logic + Delay (td) and logic
DOR1.03 ok ☑ Output DOR
Warning ☑ Type of message
4. Press «Enter».
5. Press the «Right» arrow.
6. Press «Enter».
The check box assigned to the message type flashes.
7. Press «Up» key.
The message is activated.
8. Press «Enter».
Result In the above example the switching point for System pressure pNloc has been set and is active. If
the pressure is reached or exceeded and remains longer than the set time delay td, the message is
triggered with the set message type and the set output DOR is switched. If the pressure falls below
the threshold SP + switching differential SD, the message and output are reset. The switching be‐
haviour is inverted by setting "-" of Logic parameter.
The settings for the other measured values are carried out in the same manner.
8.12 Timer
SIGMA CONTROL 2 is equipped with an integrated timer that can control an adjustable DOR out‐
put for customer-specific applications. Valid setting values for the cutting in and out duration are
between 24 h ≥ t ≥ 15 m.
Overview
■ Select the <Configuration – Acknowledgement> menu.
■ Set the "Remote acknowledgement" function.
■ Activating the remote control
■ Assigning an input
■ Press the «Remote control» key.
CAUTION
Machine damage can result from acknowledging a fault message without remedying its
cause!
➤ Find the failure cause.
6. Press «Enter».
The setting is applied.
2. Press «Enter».
The DI display flashes.
3. Use «Up» or «Down» to set the input.
4. Press «Enter».
The input has now been assigned.
5. Press the «Right» arrow.
6. Press «Enter».
The check box assigned to the input flashes.
7. Press the «Up» key.
The check box is activated.
8. Press «Enter».
The input is assigned and activated.
6.1bar 08:15AM 80° C Header
5.5 Acknowledgement Menu
Remote mode:
Key + remote contact
------------------------------
RC ack DI1.06 ok ☑ Input for remote contact assigned and activated
Key remote :☑
Result Should a message occur, it can now be acknowledged from a control centre.
Overview
Example: The external pressure transducer is connected to SIGMA CONTROL 2.
■ Open the <Configuration – Pressure control> menu.
■ Assigning an input
1. Open the 5.2.4 < Configuration – Pressure control – Network actual pressure> menu.
The Network actual pressure menu is displayed
6.1bar 08:15AM 80° C Header
5.2.4 Network actual pressure Menu
pNloc 6.1bar Active line (local pressure transducer)
AII1.01 ☐ 0.0bar
For sensor error:
Alarm
3. Press «Enter».
The AII input is set.
4. Press «Down».
The line for activating the input is displayed.
5. Press the «Right» key.
6. Press «Enter».
The check box assigned to the input flashes.
6.1bar 08:15AM 80° C Header
5.2.4 Network actual pressure Menu
AII 6.1bar Active line
AII1.01 ok ☑ 0.0bar
For sensor error:
Alarm
7. Press «UP».
The check box is activated.
ok is displayed.
8. Press «Enter».
The setting is applied.
1. Check and confirm all the items in the check list before first start-up of the machine.
When power is applied to the machine the controller boots and carries out a self test.
The display and the Controller on LED illuminate.
6.1bar 08:15AM 80° C Header
------------------------------
Load Current operating mode
------------------------------
Key – on ¦ pA – on Operating parameters
------------------------------
Run 2500h Load 2490h Operating parameters
Maintenance in 500h Maintenance indicator
9 Operation
9.1 Switching the compressed air station on and off
Always switch the machine on with the «ON» key and off with the «OFF» key.
Precondition A power supply isolating device has been installed by the user.
9.1.1 Switching on
Precondition No personnel are working on the machine.
All maintenance doors and removable panels are in place and secured.
The ambient conditions as described in Chapter "Installation and Operating Conditions" are met
Result At the first switching-on after the power has been restored, the compressor starts as soon as net‐
work pressure is lower than the network nominal pressure.
Result The Voltage applied to controller LED extinguishes. The machine is switched off and disconnected
from the mains supply.
In rare cases, you may want to shut down the machine immediately and cannot wait until the
automatic shut-down process is finished.
➤ Press «OFF» once again.
Switching off
Result The EMERGENCY STOP command device remains latched after actuation.
The compressor's pressure system is vented and the machine is prevented from automatically re-
starting.
Switching on
1. Turn the EMERGENCY STOP command device in the direction of the arrow to unlatch it.
2. Acknowledge any existing alarm messages.
Alarm message
If the machine has been stopped with the EMERGENCY STOP control device
➤ First turn the EMERGENCY STOP control device in the direction of the arrow to unlatch
it.
➤ Then acknowledge the alarm message.
Further information A list of possible alarm messages occurring during operation are shown in chapter 10.2.
Warning message
If maintenance work is to be carried out or if the warning is displayed before an alarm, the yel‐
low warning LED flashes.
Further information A list of possible warning messages occurring during operation are shown in chapter 10.3.
Line Submenu/Segment/Text
3 Text:
■ Message text
■ –
2. Press «Enter».
The 1.1.2.1 Compressor messages menu is displayed.
The third line displays the last fault or warning message.
6.1bar 08:15AM 80° C
1.1.2.1 Compressor messages Menu
0300 W c 04/16/16 01:32:49PM Last message
SD card write error Message text for message 0300
0015 W a 04/16/16 01:06:43PM
Com-Module communication error Message text for message 0015
0034 O c 04/13/16 08:15:37AM
E-mail send unsuccessful! Message text for message 0034
Further information A detailed explanation of all pressure parameter settings is given in chapter 8.4.
➤ Reset the run times after replacing the compressor block or the compressor motor.
➤ Reset the mains contactor switching cycle counter after replacing the mains contactor.
The running times of the compressor motor and compressor block components can be adjusted.
This may be required after a replacement, for example.
4. Use «Down» or «Up» key to set the value for operating hours to zero.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
Result The operating hours for the new airend are set to 0 h.
2. Compare the maximum permissible number of switching cycles with the value displayed by the
switching cycle counter.
6.1bar 08:15AM 80° C Header
3.2 Switching cycles Menu
Load valve on 3 Active line
·········
Mains contactor on
max: 1100000¦ 10227 Maximum value/switching cycle timer
Reset: ☐
If the displayed value of the mains contactor exceeds the maximum permissible number of
switching cycles, SIGMA CONTROL 2 generates the warning message 0024 Mains contactor
operations ⇞.
The mains contactor must be replaced.
➤ Have the mains contactor replaced by authorised KAESER SERVICE.
NOTICE
Unauthorised extended maintenance intervals
Progressing damage to the machine up to functional incapacity.
➤ Observe the maintenance intervals of the manufacturer.
Maintenance menu
4. Press «Enter».
The setting mode is active.
5. Use «Up» or «Down» to set the new value for the maintenance interval.
Keep the «Up» key pressed to change the maintenance interval in increments of 10, 100 or
1000.
6. Press «Enter».
The setting is applied.
7. Press «Escape» repeatedly to return to the main menu.
When the check mode is activated, the threshold value for the blow-off protection is raised
and regulation of the network pressure is deactivated.
The measured value of the pi pressure value is used to describe the test below.
WARNING
Danger of injury from pressurised components!
➤ Perform the following actions in the sequence provided.
1. Note the safety valve's actuating pressure from the machine's nameplate.
2. Press the «Off» key to shut down the machine.
3. Close the user's shut-off valve between the machine and the air distribution network.
4. Log on with access level 2.
5. Open the 9.1 <Machine test – TÜV inspection> menu.
6.1bar 08:15AM 80° C Header
9.1 TÜV inspection Menu
Safety valve :☐ Active line with check box
pRV: 16.0bar ¦ pi ⇞ 0.0bar Safety valve actuating pressure (example)
Reset : ☐
·········
ADT ⇞ :☐
Offset 0°C ¦ ADT ⇞ 0.0°C
5. WARNING!
Risk of hearing damage when safety valve blows off!
➤ Close all access doors, replace and secure all removable panels.
➤ Always wear ear protection.
6. WARNING!
Risk of burns due to released cooling oil and compressed air when blowing off the safety
valve!
➤ Close all access doors, replace and secure all removable panels.
➤ Wear eye protection.
7. Press the «ON» key. After the motor / engine start is completed, keep the «LOAD/IDLE» key
pressed. Otherwise, the machine remains in IDLE and is stopped after two minutes.
The machine switches to LOAD and the machine's pi pressure rises.
8. Use the display to monitor the pi pressure rise during the TÜV check.
9. If the pi pressure increases to 11 % above the actuating pressure of the safety valve, immedi‐
ately release the «LOAD/IDLE» key.
10. Shut down the machine with the «OFF» key and immediately replace the safety valve.
If the alarm message pRV ⇞ appears, the safety valve is defective. pi pressure has exceeded
the actuating pressure of the safety valve by 2.0 bar.
➤ Have the safety valve replaced immediately.
Avoid oil mist:
➤ Release the «LOAD/IDLE» key immediately as soon as the safety valve actuates, in or‐
der to prevent unnecessary oil mist.
1. Press «Enter».
The check box Safety valve will flash.
2. Press the «DOWN» key.
The check box is deactivated.
3. Press «Enter».
The test mode is de-activated and the test is completed.
4. Press «Escape» repeatedly to leave this menu.
5. Open the user's shut-off valve between the machine and the air distribution network.
Resetting
If the test is cancelled when opening the safety valve, SIGMA CONTROL 2 will indicate the highest
measured value as internal pressure.
To reset the saved value, activate the Reset check box.
➤ Activate the Reset check box.
Overview
■ Allow the machine to warm up, then shut it down and allow it to cool down slightly
■ Performing the inspection
■ Correct conclusion of the test
■ Resetting
The offset value of 35.0°C displayed in activated test mode refers to the discharge tempera‐
ture of 73°C as shown in the example.
Precondition Allow the machine to warm up. Shut down the machine as soon as the discharge temperature
(VET) has stabilised.
Machine has cooled down by approx. 5°C (from discharge temperature of warmed up machine)
Access level 2 is activated.
3. Press «Enter».
The ADT ⇞ check box flashes.
4. Press the «Up» key.
The check box is activated.
5. Press the «Enter» key.
The display Offset switches to 35.0°C.
The display ADT ⇞ switches to 108°C.
The test mode is now activated.
6.1bar 08:15AM 7 3° C Header
9.1 TÜV inspection Menu
Safety valve :☐
pRV: 16.0bar ¦ pi ⇞ 0.0bar Safety valve actuating pressure (example)
Reset : ☐
·········
ADT ⇞ :☑ Active line with check box
Offset 35.0°C ¦ ADT ⇞ 108°C
1. Press «Enter».
The setting mode is active.
The check box flashes in line ADT ⇞.
2. Press the «DOWN» key.
The check box is deactivated.
3. Press «Enter».
The offset is reset to 0°C.
Resetting
SIGMA CONTROL 2 will display the highest measured value if the test for switching off at exces‐
sive temperature is aborted.
Activate the Reset check box in order to reset the stored value.
➤ Activate the Reset check box.
Precondition An SD card with compatible file system (FAT32) and minimum 50 MB free memory is plugged into
the SD card slot X5 of SIGMA CONTROL 2
The write protection of the SD card has been deactivated.
Access level 2 is activated.
3. Press «Enter».
The display for the set language flashes.
4. Use «Up» or «Down» to select the desired language.
5. Press «Enter».
The setting is applied.
7. Press «Enter».
The check box Save data will flash.
8. Press the «Up» key.
The check box is activated.
9. Press «Enter».
A security query is displayed.
10. Press «Enter».
The messages valid for your machine are dependent on the controller and individual equipment.
1. Do not attempt fault rectification measures other than those given in this manual!
2. In all other cases:
Have the fault rectified by an authorised KAESER SERVICE technician.
Consequences:
■ The red LED flashes:
■ The controller switches the machine off.
Fault messages are identified with the letter A.
The message numbers are not numbered consecutively.
In this table, you will see "%d" for a variable value, e.g. a number, duration or I/O address.
1)
Messages 0073-0078 and 0081-0098 are customer-specific.
Complete possible causes and remedies for your defined message text (see chapter 8.11).
External message 1
0074 A 1)
External message 2
0075 A 1)
External message 3
0076 A 1)
External message 4
0077 A 1)
External message 5
0078 A 1)
External message 6
0081 A 1)
AnMod_p_1
AnMod_p_2
0083 A 1)
AnMod_p_3
0084 A 1)
AnMod_p_4
0085 A 1)
AnMod_T_1
0086 A 1)
AnMod_T_2
0087 A 1)
AnMod_T_3
0088A 1)
AnMod_T_4
0089A 1)
AnMod_I_1
0090 A 1)
AnMod_I_2
0092 A 1)
T-Switch inlet
temperature
0093 A 1)
p-Switch pi
0094 A 1)
T-Switch ADT
0095 A 1)
p-Switch pN
0096 A 1)
T-Switch PDT
0098 A 1)
n-Switch Compressor
motor
0100 A Star contactor of the compressor Check star contactor and wiring.
Star contactor on? motor does not activate.
0101 A Star contactor of the compressor Check star contactor and wiring.
Star contactor off? motor does not deactivate.
0102 A Delta contactor of the compressor Check delta contactor and wiring.
Delta contactor on? motor does not activate.
0103 A Delta contactor of the compressor Check delta contactor and wiring.
Delta contactor off? motor does not deactivate.
0104 A High-voltage cell does not acti‐ Call KAESER SERVICE.
High-voltage cell on? vate.
0105 A High-voltage cell does not deacti‐ Call KAESER SERVICE.
High-voltage cell off? vate.
Consequences:
■ The yellow LED flashes.
■ The controller does not switch off the machine.
Warning messages are identified with the letter W.
The message numbers are not numbered consecutively.
In this table, you will see "%d" for a variable value, e.g. a number, duration or I/O address.
Complete possible causes and remedies for your defined message text (see chapter 8.11).
0044 W Cooling oil temperature too low. Check temperature switch, line
Oil temperature ↓ and connection.
Check the oil circuit.
Increase room temperature.
0045 W Test operation for the manual actua‐ Switch the power supply off and
DO test active tion of individual outputs is active. on again.
0046 W Network pressure has fallen below the Check air demand.
System pressure ↓ set 'network pressure low' value. Check cable runs and sensor con‐
Air consumption too high. nections.
Check the 'network pressure low'
warning value.
0047 W The machine does not produce com‐ Check the machine for leaks.
No pressure buildup pressed air. Check coupling and V-belt.
The working pressure does not rise Call KAESER SERVICE.
above 3.5 bar within the specified time
period.
The machine does not enter LOAD
mode
Minimum pressure/check valve defec‐
tive.
0048 W Re-grease the motor bearings. Re-grease the motor bearings.
Bearing lube h ⇞ Maintenance interval has elapsed.
0049 W Last maintenance was 1 year ago. Carry out the necessary mainte‐
Annual maintenance nance and reset the correspond‐
ing maintenance interval counter.
0050 W Maintenance interval has elapsed. Re-grease the fan bearing.
Fan bearing lube h ⇞
0051 W Last maintenance was 1 year ago. Carry out the necessary mainte‐
Double aggregate nance and reset the correspond‐
emergency operation! ing maintenance interval counter.
0053 W Condensate drain 2 faulty / not ready. Check the condensate drain and
Condensate drain 2 Too much condensate. conduits.
Line interrupted. Check the lines.
Condensate cannot be drained. Check ECO-DRAIN.
Check inlet conditions.
0058 W The electrical connection is interrup‐ Check the electrical connections.
SC2 <=> SC2 ted. Check the IP configuration.
communication error IP configuration incorrect
External message 1
0074 W 1)
External message 2
0075 W 1)
External message 3
0076 W 1)
External message 4
0077 W 1)
External message 5
0078 W 1)
External message 6
0081 W 1)
AnMod_p_1
0082 W 1)
AnMod_p_2
0083 W 1)
AnMod_p_3
0084 W 1)
AnMod_p_4
0085 W 1)
AnMod_T_1
0086 W 1)
AnMod_T_2
0087 W 1)
AnMod_T_3
0088 W 1)
AnMod_T_4
0089 W 1)
AnMod_I_1
0090 W 1)
AnMod_I_2
0092 W 1)
T-Switch inlet
temperature
0093 W 1)
p-Switch pi
0094 W 1)
T-Switch ADT
0095 W 1)
p-Switch pN
T-Switch PDT
0097 W Bus link via SIGMA NETWORK inter‐ Check bus lines and plug.
SAM 4.0 rupted
communication error
0098 W 1)
n-Switch Compressor
motor
0200 W Frequency converter in service mode. Terminate service mode.
Compressor motor FC
Service mode active
0201 W Frequency converter in service mode. Terminate service mode.
Compressor motor FC
Service mode active
0202 W Frequency converter in service mode. Terminate service mode.
Compressor motor FC
Service mode active
0203 W Frequency converter in service mode. Terminate service mode.
Compressor motor FC
Service mode active
0210 W Pressure transducer of the frequency Call KAESER SERVICE.
Compressor motor FC converter faulty
AI1 error
0230 W Pressure transducer of the frequency Call KAESER SERVICE.
Compressor motor FC converter faulty
AI0 error
0231 W Malfunction at compressor motor or its Call KAESER SERVICE.
Compressor motor FC frequency converter.
Alarm %d
0240 W Run time of the frequency converter Temporarily fully disconnect the
Compressor motor FC since last shut-down too large. machine from the power supply.
test shut-off required (Required for the safety func‐
tions.)
0243 W Malfunction at compressor motor or its Call KAESER SERVICE.
Compressor motor FC frequency converter.
Alarm %d
0251 W Frequency converter in service mode. Terminate service mode.
Oil-/air cooler fan FC
Service mode active
0253 W Frequency converter in service mode. Terminate service mode.
Oil cooler fan FC
Service mode active
0254 W Frequency converter in service mode. Terminate service mode.
Oil cooler fan FC
Service mode active
Complete the meaning of the message for your defined message text (see also chapter 8.11).
Message Meaning
0001 O Total duration until the machine is ready to start after pow‐
Delayed start (%ds) active er has been restored or after a communication error to the
master controller (e.g. SAM 4.0) or after switching on the
SAM manual mode.
0009 O The machine is switched on.
Compressor on
Message Meaning
0010 O The controller is switched on with the «ON» key.
Controller on
0011 O The machine can be switched on although the machine
Cold start release temperature is below the permissible starting temperature.
The machine can be switched on only as long as the mes‐
sage is displayed.
0027 O Request:
Power OFF → ON Switch the power supply off and on.
External message 1
0074 O 1)
External message 2
0075 O 1)
External message 3
0076 O 1)
External message 4
0077 O 1)
External message 5
0078 O 1)
External message 6
0081 O 1)
AnMod_p_1
0082 O 1)
AnMod_p_2
0083 O 1)
AnMod_p_3
0084 O 1)
AnMod_p_4
0085 O 1)
AnMod_T_1
0086 O 1)
AnMod_T_2
Message Meaning
0087 O 1)
AnMod_T_3
0088 O 1)
AnMod_T_4
0089 O 1)
AnMod_I_1
0090 O 1)
AnMod_I_2
0092 O 1)
p-Switch pi
0094 O 1)
T-Switch ADT
0095 O 1)
p-Switch pN
0096 O 1)
T-Switch PDT
0098 O 1)
Message Meaning
0551 O Short-term overload fault without shut-down occurred at
ADT channel error "channel open" ADT.
detected
0850 O IOM bus fault
IOSlot%d - bus error
0867 O Short-term overload fault without shut-down occurred at
AII%d.0%d - overload fault All.
Message Meaning
1377 O Short-term overload fault without shut-down occurred at
AII%d.0%d - overload fault All.
11 Maintenance
11.1 Changing the buffer battery
When SIGMA CONTROL 2 displays a warning message indicating that the integrated buffer bat‐
tery has discharged and requires replacement, please contact KAESER SERVICE.
2. Press «Enter».
The system information is displayed.
6.1bar 08:15AM 80° C Header
5.1.1.1 SIGMA CONTROL 2 MCS Menu
Software fluid_4.1.X Software version
·········
KAESER
PN 7.7601.0 Material number
SN 123456 Serial number
·········
13.2 Packing
➤ Follow the instructions in the machine's service manual.
13.3 Storage
➤ Follow the instructions in the machine's service manual.
13.4 Transporting
➤ Follow the instructions in the machine's service manual.
13.5 Disposal
Precondition SIGMA CONTROL 2 is de-commissioned.