Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

8040 NC Pilot

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Direct Acting 2/2

4 Gas Shutoff Valves


1/8" to 3/8" NPT
SERIES
8040

Features
• 2-way normally closed operation ^ #
• For gas pilot control of commercial and industrial
gas burners
• Direct lift with resilient soft seating for tight shut-off
• Valves provided with 1/8" NPT downstream pipe tap
with plug for routine testing
• Mountable in any position

Construction
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel NC

Springs 17-7 PH
Shading Coil Copper
Pipe Plug Zinc Plated Steel

Electrical
Watt Rating and
Power Consumption Spare Coil Family
Standard
Coil and AC General Purpose Explosionproof
Class of VA VA Ambient
Insulation Watts Holding Inrush Temp.°F AC AC
F 6.1 16 40 -40 to 125 238210 238214
Standard Voltages: 24, 120, 240 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz).

COMBUSTION

Solenoid Enclosures Approvals


Standard: Watertight, Types 1, 2, 3, 3S, 4, and 4X with 1/2" conduit hub. UL listed to standard 429 “Electrically Operated
Valves,” Guide YIOZ, File MP618 Safety Valves.
FM Approved to Class 7400 “Liquid and Gas Safety
Valve Response Time Shutoff Valves.”
Opening Time: Less than 1 second; Closing Time: Less than 1 second CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 010381.
2) Automatic Gas Valves Z21.21 (6.5), File 112872.
3) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 112872.

287
2/2
SERIES
8040 4
Specifications (English units)
Approx.
Gas Operating Pressure
Pipe Orifice Cv Max. Shipping
Capacity  Differential (psi) Agency
Size Size Flow Fluid Const. Weight
(ins.) (ins.) Factor Btu/hr. Min. Max. Temp.°F Catalog Number Ref. UL FM CSA Wattage  (lbs)
COMBUSTION (Fuel Gas)- NORMALLY CLOSED
1/8 5/16 1 53,700 0 15 125 8040H006 1    6.1 1.8
1/4 5/16 1.1 59,000 0 15 125 8040H007 1    6.1 1.8
3/8 5/16 1.2 64,400 0 15 125 8040H008 1    6.1 1.8
 = Safety Shutoff Valve;  1" W.C. Drop @ 2" W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity Gas.
 On 50 Hz service watt rating is 8.1; EF option approved to UL and CSA only.

Specifications (Metric units)


Approx.
Gas Operating Pressure
Pipe Orifice Kv Max. Shipping
Capacity  Differential (bar) Agency
Size Size Flow Fluid Const. Weight
(ins.) (mm) (m3/hr) Btu/hr. Min. Max. Temp.°C Catalog Number Ref. UL FM CSA Wattage  (kgs)
COMBUSTION (Fuel Gas)- NORMALLY CLOSED
1/8 8.000 0.9 53,700 0 1 52 8040H006 1    6.1 0.8
1/4 8.000 0.9 59,000 0 1 52 8040H007 1    6.1 0.8
3/8 8.000 1.0 64,400 0 1 52 8040H008 1    6.1 0.8
 = Safety Shutoff Valve;  1" W.C. Drop @ 2" W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity Gas.
 On 50 Hz service watt rating is 8.1; EF option approved to UL and CSA only.

Capabilities Chart
Solenoid Options Base Catalog Number Resilient Materials Standard Rebuild Kit
NEMA Type 3-9 High Temp. Junction Box Wiring Box Screw Terminal Aluminum NBR AC
EF HT - JKF 8040H006  318247
EF HT JB JKF 8040H007  318247
EF HT JB JKF 8040H008  318247
 = Standard. Other options may be available. All option combinations may not be available.
COMBUSTION

288
2/2
4 SERIES
8040

Dimensions inches (mm)

Const. Ref. 1

2.92 (74)

1.89 (48) 1.69 (43)

2.30
(58)

2.74
1.44
(70) 1/2 NPT
(37)

PIPE PLUG
1 PLACE

NPT
BOTH ENDS

COMBUSTION

289
290
COMBUSTION