Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Apollo XP95

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Apollo XP95

Analogue addressable devices


from Channel Safety Systems
Apollo XP95
Analogue addressable devices
The XP95 range of analogue addressable fire detectors is advanced in
design, improved in performance and has unique features that benefit
the installer and the end user.

The detectors have been carefully researched and developed by the


Apollo design team and the range has undergone rigorous testing to
ensure that it meets not only European and other standards but also
the demands of today’s high technology environments.

XP95 detectors provide an alarm facility that automatically puts an


alarm flag on the data stream and reports its address when the pre-set
EN54 thresholds are exceeded.
Image shows from left to right F/CHBG/
Features IS/95, F/CHSM/P/95 & F/CHWB/95/AP
• Digital Protocol for error-free transmission • Wide range of compatible interface units
• Alarm Flag for fast alarm reporting • Wide range of compatible panels
• Alarm Address for fast location of alarm • Compatible with Series 65 and Discovery
• Automatic addressing with the patented XPERT card • Elegant, unobtrusive design
• Electronics-free, easy fit base • Wide range of products
• Ease of installation • Great flexibility in system design

GET INTERACTIVE
Scan the code for more information on the XP95 range and the related Fire Alarm Panels
www.channelsafety.co.uk/xp95-range/

Call Points
The XP95 Manual Call Point is compliant with EN54-11. The address of each
call point is set at the commissioning stage by means of a seven segment
DIL switch. The device features plug and play terminal connections and a
resettable element.

Features
• Plug and play terminal connections for fast wiring
• Allow wiring continuity testing before fitting
• Reports an alarm in under 0.2 seconds
• Resettable element
• Built in loop isolator
Image shows from left to right F/CHBG/IS/95 & F/CHBG/WP/95/1
Waterproof Dimensions and Weight
• 110mm(W) x 110mm(H) x 74mm(D)
• 180g
SPECIFICATIONS
89mm

Supply Voltage 17 - 28V DC


Communications Protocol 5 - 9V peak to peak
Max. Current Consumption 100μA
at 24V Quiescent
Power - Up Surge, 1 Second 1mA
Typical
93mm 59.5mm
Alarm LED on 4mA
Operating Temperature -20ºC to 60ºC
PRODUCT CODE DESCRIPTION
Humidity (no condensation) 0 - 95% Analogue addressable break glass – complete with
F/CHBG/IS/95
IP Rating IP45 isolator and flexible element
Weight 160g F/CHBG/WP/95/1 XP95 weatherproof break glass

2 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk


Optical Smoke Detectors
The XP95 Optical Smoke Detector works using the light scatter principle
and is ideal for applications where slow-burning or smouldering fires are
likely.

Features
• Can be used for applications where standard smoke detectors are
unsuitable
• Ideal environments that are dirty or smoky under normal conditions
• Ideal for use in environments with rapid temperature fluctuations
such as boiler rooms
• Reduction of false alarms

Ø 100mm
SPECIFICATIONS
Supply Voltage 17 - 28V DC
Quiescent Current 340μA average, 600μA peak
42mm

Power-up Surge Current 1mA


Duration of Power-up 0.3 seconds
Surge Current
Operating Temperature -20ºC to 60ºC
Storage Temperature -30ºC to 80ºC
Alarm LED Current 4mA
Humidity 0% - 95%
PRODUCT CODE DESCRIPTION IP Rating IP23D
F/CHSM/P/95 Optical smoke monitor less base Weight 105g

Heat Detectors
The XP95 Heat Detectors, monitor temperature by using a single
thermistor which provides a count output proportional to the external air
temperature.
The XP95 range features two heat detectors, standard and high
temperature. The standard heat detector is classified as an A2S device and
will report an alarm at 55°C. The high temperature detector, classified as a
CS device, will report an alarm at 90°C.

Features
• Ideal in environments that are dirty or smoky under natural
conditions
Image shows from left to right F/CHHM/95 & F/CHHM/HT/95 • Well suited for warehouses, loading bays and underground carparks
• Unaffected by wind or atmospheric pressure

Ø 100mm SPECIFICATIONS
Supply Voltage 17 - 28V DC
Quiescent Current 250μA average, 500μA peak
Power-up Surge Current 1mA
42mm

Duration of Power-up 0.3 seconds


Surge Current
Alarm Indicator Red light emitting diode (LED)
Operating Temperature -20ºC to 70ºC
Storage Temperature -30ºC to 80ºC
Alarm LED Current 2mA
PRODUCT CODE DESCRIPTION Humidity 0% - 95%
F/CHHM/95 Heat detector 55ºC less base IP Rating IP53
F/CHHM/HT/95 High temperature 90ºC heat detector less base Weight 105g

3 | revision 013-1 www.channelsafety.co.uk  0845 884 7000 @ sales@channelsafety.co.uk


Ionisation Detector
The XP95 Ionisation Smoke Detector uses a low activity radioactive foil to
detect fires by irradiating the air in the smoke chambers causing a current
flow. If smoke enters the chamber, the current flow is reduced leading to
an alarm.

Features
• Responds well to fast-burning, flaming fires
• Designed to operate in a variety of environments
• Minimal effects from the temperature, humidity, atmospheric
pressure
• Well protected against electromagnetic interference over a wide
frequency range

Ø 100mm
SPECIFICATIONS
Supply Voltage 17 - 28V DC
Quiescent Current 340μA average, 600μA peak

42mm
Power-up Surge Current 1mA
Duration of Power-up 0.3 seconds
Surge Current
Operating Temperature -20ºC to 60ºC
Storage Temperature -30ºC to 80ºC
Alarm LED Current 4mA
Humidity 0% - 95%
IP Rating IP23D PRODUCT CODE DESCRIPTION
Weight 105g F/CHSM/A/95 Ionisation smoke detector less base

Multi-Sensor Detector
The XP95 multisensor Detector contains an optical smoke sensor and a
thermistor temperature sensor whose outputs are combined to give the
final analogue value.

Features
• Sensitive to a wide range of fires
• Well suited for environments such as hotel bedrooms
• Unaffected by wind or atmospheric pressure

SPECIFICATIONS Ø 100mm
Operating Voltage Range 9-33V
Polarity Polarity insensitive
Quiescent current @ 15V <50μA
42mm

Alarm Current @ 2-8.5V - <1.5mA


10.5-15V - 25 ± 2mA
18-24V - <1.5mA
33V - <2mA
Maximum Rest Voltage 2V
Reset Time 1s
Maximum Supply 40ms
Interruption
EMC CE marked to EN50130-4 PRODUCT CODE DESCRIPTION
Weight 100g F/CHSM/M/95 Multi-sensor detector

4 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk


Mounting Base
The Mounting Base has a “one way only” fit allowing for simple
installation and maintenance. The mounting base is designed for use with
the Apollo XP95 optical and ionisation smoke detectors, as well as the heat
and multi-sensor units. Other Apollo devices require the XP95 mounting
base to connect to the addressable fire alarm panel.

The base is a zero insertion force base with dual finger receptacles of stain-
less steel into which the detector terminals slide. Cable connections of up
to 2.5mm diameter are made via captive cable clamps.

There are four double terminals and one single one

L1- Line IN and OUT, double terminal


L2 + Line IN and OUT, double terminal
Ø 100mm
+R Remote LED positive supply, double terminal
-R Remote LED negative supply, double terminal

The remaining single terminal is isolated and can be used to provide conti-
nuity of an earth or shield.
Universal address cards, known as XPERT cards are supplied with all bases,
8mm

Pre-printed and pre-punched address cards that will save time and increase
accuracy during commissioning.

Features
• XPERT Addressing
• One way fit of detector
• Locking feature to prevent un-authorised detector removal

PRODUCT CODE DESCRIPTION SPECIFICATIONS


F/BASE/95 Mounting base – series XP95 Weight 100g

Single Channel Input Output Unit

The Input/Output Unit provides a voltage-free, double pole changeover


(DPCO) relay output, a single monitored switch input and an un-monitored,
non-polarised opto-coupled input.

Features
• It can report fault, switch open and switch closed levels
• Three visible LED's
• Loop-Powered
• Capable of switching up to 30V at 1A
• Built in loop isolator

150mm
90mm

SPECIFICATIONS
Loop Operating Voltage 17 - 28V DC
Max. Current 28V
Switch Input Monitoring 9 - 11V DC
Depth of product
Voltage (Open Circuit
48mm
Condition)
Max. Cable Resistance 50Ω
Operating Temperature -20ºC to +70ºC

PRODUCT CODE DESCRIPTION Humidity 0 - 95%


Single channel input/output unit complete with IP Rating IP54
F/CHIO/1/95
isolator Weight 240g

5 | revision 013-1 www.channelsafety.co.uk  0845 884 7000 @ sales@channelsafety.co.uk


Mains Switching Input Output Unit
The Mains Switching Input/Output Unit provides a voltage-free, single pole
change-over relay output and a monitored switch input.

Features
• Supervises one or more normally-open switches connected to a
single pair of cables
• Three visable LEDs
• Capable of switching 250V AC at up to 5A
• Built in loop isolator

SPECIFICATIONS 150mm
Loop Operating Voltage 17 - 28V DC
Max. Current 2.5mA

90mm
Related Load (Resistive) 5A at 250V AC
Max. Switching Capacity 1.25kVA
Switch Input Monitoring 9 - 11V DC
Voltage (Open Circuit
Depth of product
Condition)
48mm
Max. Cable Resistance 50Ω
Operating Temperature -20ºC to +70ºC
Humidity 0 - 95% PRODUCT CODE DESCRIPTION
IP Rating IP54 Single channel input/output unit 230V contacts 1A
F/CHIO/1/95/240
Weight 240g complete with surface mounting enclosure

Three Channel Input Output Unit

The Three Channel Input/Output Unit provides three voltage-free, single


pole, changeover relay outputs and three monitored switch inputs.

Features
• Supervises one or more normally open switches on each of the three
inputs
• Loop-powered
• Capable of switching up to 30V at 1A on each of the three outputs
• Built in lopp isolator
SPECIFICATIONS
Loop Operating Voltage 17 - 28V DC
Max. Current 7.5mA
Switch Input Monitoring 9 - 11V DC
Voltage (Open Circuit 250mm
Condition)
Max. Cable Resistance 50Ω
175mm

Relay Output Contact 1A


Rating at 30V AC or DC
Isolator Rating 0.2Ω
Max. Continuous Current 1A
Depth of product
Max. Switching Current 3A 75mm
Max. Load 1A @ 30V
Operating Temperature -20ºC to +70ºC
Humidity 0 - 95%
IP Rating IP54 PRODUCT CODE DESCRIPTION
Weight 240g F/CHIO/3/95 Three channel input/output unit complete with isolator

6 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk


Isolating Base
The Isolating Base senses and detects short-circuit faults on XP95 loops and
spurs.

Features
• Up to 20 detectors or their equivalent load, may be installed between
isolating bases
• High brightness LED
• Detects wiring short-circuits
• Minimises disruption from short circuits

Ø 100mm

SPECIFICATIONS
Supply Voltage Range 17 - 28V DC
24mm Isolation Indicator Yellow LED, lit continuously in isolation
condition
Max. Current Consumption 43μA
Max. Line Current 3.0A
EMC BS 61000-6-3
Operating Temperature -20ºC - +60ºC
Storage Temperature -30ºC - +80ºC
Humditiy 0 - 95%
PRODUCT CODE DESCRIPTION Design Environment Indoor use only
F/CHIS/95/DB Short circuit isolator with detector base Weight 100g

Sounder Control Unit


The Sounder Control Unit is used to control the operation of a zone of
conventional sounders and report their status to the control panel.

Features
• Allows sounders to be operated continuously or pulsed; 1 second on,
1 second off
• May be synchronised with loop sounders
• Built in loop isolator

150mm

SPECIFICATIONS
Loop Operating Voltage 17 - 28V DC
90mm

Max. Current Consumption 4.7mA


Sounder Output 9 - 11V DC
Monitoring Voltage
Depth of product Max. Sounder Circuit 32V DC
48mm Voltage
Maximum Load 1A @ 30V
Operating Temperature -20ºC - +70ºC
Humidity 0 - 95%
PRODUCT CODE DESCRIPTION IP Rating IP54
F/CHSN/95 Sounder circuit controller complete with isolator Weight 240g

7 | revision 013-1 www.channelsafety.co.uk  0845 884 7000 @ sales@channelsafety.co.uk


Switch Monitor
The Switch Monitor is designed to monitor the state of one or more single
pole, volt-free contacts connected on a single pair of cables and to report
the status to Apollo compatible analogue control equipment.

Features
• Four input states - ‘normal’, ‘fault’, ‘pre-alarm’ and ‘alarm’
• Two visible LEDs
• Loop-Powered
• Built in loop isolator

SPECIFICATIONS 150mm
Loop Operating Voltage 17 - 28V DC
Max. Current Consumption 3.6mA

90mm
Max. Continuous Current 1A
Max. Switching Current 3A
Switch Input Monitoring 9 - 11V DC
Voltage
Depth of product
Max. Cable Resistance 50Ω
48mm
Operating Temperature -20ºC to +70ºC
Humidity 0 - 95%
IP Rating IP54 PRODUCT CODE DESCRIPTION
Weight 240g F/CHSW/95 Switch monitor complete with isolator

Zone Monitor Isolator


The Zone Monitor powers and controls the operation of a zone of up to 20
Apollo XP95 looped detectors.

Features
• Detects wiring short-circuits
• Minimises disruption from short-circuits
• Automatic de-isolation on the short-circuit removal
• Up to 20 detectors or their equivalent load, may be installed between
isolators
• Built in loop isolator

150mm
SPECIFICATIONS
Line Voltage 17 - 28V DC
Zone Voltage 19 ± 1V
90mm

End of Line Resistor Value 5.1k ± 5% 1/3W


Stabilisation Time on Power 4 seconds
Up
Max. Capacitor on Zone 50μF Depth of product
Terminals 48mm
Operating Temperature -20ºC to +70ºC
Humidity 0 - 95%
IP Rating IP54 PRODUCT CODE DESCRIPTION
Weight 240g F/CHZM/95 Zone monitoring unit complete with isolator

8 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk


Loop Powered Visual Indicator
The Loop-Powered Visual Indicator is a local-area visual indicator designed
for indoor use. The Visual Indicator has been developed as a supplement
to sounders for use in situations where there is a risk that sounders will not
be heard.

Features
• High intensity LEDs
• More reliable than xenon visual indicators
• Automatic LED check
• Lockable
• Wide angle of visibility
• Enables DDA compliance
• Synchronised flash
• Can be used with Discovery or XP95 devices

Ø 115mm

SPECIFICATIONS
Operating Voltage 17 - 28V DC
38mm

Quiescent Current 150μA


Consumption
Beacon Operated 3mA
Switch on Surge 1mA for 100ms
Operating Temperature -20ºC - +60ºC
Flash Rate 1Hz
Humidity 0% - 95%
PRODUCT CODE DESCRIPTION IP Rating IP23D
F/CHBN/95 XP95 loop powered visual indicator Weight 140g

Visual Indicator Base


The Visual Indicator Base is a loop-powered visual indicator combined with
a standard Intelligent Mounting Base. It is used to signal a fire alarm in
enclosed areas. The visual indicator base can be used with either a detector
fitted or with a cap as a stand-alone alarm device.

Features
• Visual indicator flash rate of once per second
• Synchronisation of visual indicator flash
• Individual and group addressing
• Unique visual indicator self-test
• Loop-powered
• Built-in Isolator
Ø 100mm • Red or white cover cap available
Base Dimensions and Weight Cover Dimensions and Weight
• Ø 100mm x 31mm • Ø 100mm x 9mm
• 109g • 20g
31mm

SPECIFICATIONS
Operating Voltage 17 - 28V DC
Protocol Pulses 5 - 9V
Current Consumption 300μA
PRODUCT CODE DESCRIPTION Operating Temperature -20ºC - +60ºC
F/CHBN/95/A Visual indicator base Humidity 0% - 95%
F/COVER/RD/1 Red cover for CHWB/BN/95/A IP Rating IP21D
F/COVER/WH/1 White cover for CHWB/BN/95/A Weight 109g

9 | revision 013-1 www.channelsafety.co.uk  0845 884 7000 @ sales@channelsafety.co.uk


Open Area Sounders & Indicators
The Open-Area Sounders and indicators are designed for use in open areas
and can be connected to an Apollo Discovery or XP95 system.

Features
• Self-test fault monitoring
• Choice of tones on standard device: Apollo, Slow Whoop and DIN
• Two volume settings 92dB(A) and 100dB(A)
• Individual and group addressing
• Sycronisation of tones and flashes
• Built in isolator
• Loop-powered
• IP65 rated
• Red and clear lens options available for F/CHWB/BN/95/AP
• F/CHWB/95/AP is available in white Image shows from left to right F/CHWB/95/AP & F/CHWB/BN/95/AP

104mm
SPECIFICATIONS
Operating Voltage 17 - 28V DC
Max. Loop Current 333μA
Consumption
Alarm Sounder 92/100dB 5mA
(A) Ø 97.5mm
Alarm Sounder Beacon 8mA
PRODUCT CODE DESCRIPTION
Max. Sound Output 100dB (A)
Open area XP95 sounder red IP65 complete with
Operating Temperature -20ºC - +60ºC F/CHWB/95/AP
isolator
IP Rating IP65 Open area XP95 sounder white IP65 complete with
F/CHWB/95/AP/WH
Weight F/CHWB/95/AP = 225g isolator
F/CHWB/BN/95/AP = 260g F/CHWB/BN/95/AP Open area XP95 sounder indicator red IP65

Sounder Indicator Base


The Sounder Visual Indicator Base is a loop-powered sounder and visual
indicator combined with a standard Intelligent Mounting Base. It is used to
signal a fire alarm in enclosed areas.

Features
• Two volume ranges 55-75dB(A) and 75-91dB(A)
• Visual indicator flash rate of once per second
• Synchronisation of ‘alert’ and ‘evacuate’ tones
• Synchronisation of visual indicator flash
• Individual and group addressing
• Unique acoustic and visual indicator self-test
• Built-in Isolator
Ø 115mm
38mm

SPECIFICATIONS
Operating Voltage 17 - 28V DC
Protocol Pulses 5 - 9V
Current Consumption 300μA
Operating Temperature -20ºC - +60ºC
PRODUCT CODE DESCRIPTION
Max. Sound Output at 90º 91dB (A)
Loop powered base sounder indicator – incorporates
Humidity 0% - 95% F/CHWB/BN/95/A
detector base
IP Rating IP21C Loop powered base sounder indicator – complete with
F/CHWB/BN/95/IS
Weight 160g loop isolator and detector base

10 | revision 013-1 www.channelsafety.co.uk 0845 884 7000 @ sales@channelsafety.co.uk


Base Sounder
The Integrated Base Sounder comprises of a base sounder with integral
mounting base and is for use with Discovery or XP95 ranges. It is designed
for indoor use.

Features
• Two tones
• Two volume ranges 55-75dB(A) and 75-91dB(A)
• Individual and group addressing
• Unique acoustic self-test
• Built-in isoltaor

Ø 115mm

38mm

SPECIFICATIONS
Operating Voltage 17 - 28V DC
Protocol Pulses 5 - 9V
Current Consumption <1.2mA
Max. Sound Output 91dB (A)
Operating Temperature -20ºC to 60ºC

PRODUCT CODE DESCRIPTION Humidity 0% - 95%


Loop powered intelligent base sounder – incorporates IP Rating IP21D
F/CHWB/IS/IN/95A
detector base Weight 140g

Compatible Panels
Firewatch Analogue Addressable Panels

FW1001 panels are available in single or double loop, 16 to 32 zone. Full compatibility with
Apollo XP95, Discovery and Hochiki ESP protocol devices.

FW9003 panels are available in 1, 2 or 5 loop. Each panel is capable of supporting Apollo
XP95, Discovery, Hochiki ESP and Nittan protocol devices.

FW9004 panels are available in 1, 2 or 4 loop. Supports Apollo XP95, Discovery & Hochiki
ESP protocol devices.

11 | revision 013-1 www.channelsafety.co.uk  0845 884 7000 @ sales@channelsafety.co.uk


‘Don't be afraid of fire’
*
Free Design Service
Fire Alarm - Emergency Lighting - Assistance

Channel Safety Systems offers a complete Design, Supply & Commissioning service:-

Fire Alarm. To BS.5839. Part 1 2002


Emergency Lighting. To BS. 5266. Part 1/7/8
Nurse Call Systems
Disabled Refuge Systems

Channel Safety Systems provide a dedicated design, supply and commissioning service for
Emergency Lighting, Fire Alarm and Assistance. We offer the Contractor and Wholesaler a
comprehensive service.

With over 35 years’ experience working within these sectors, Channel’s knowledge base is
extensive and is an invaluable resource for our customers. As Industry standards are ever-
changing, we make it our mission to keep abreast of regulatory and legal changes that affect
our clients.

As our Project Sales Engineers and Service Engineers are based across the UK, we offer a fast
and efficient service for design, site surveys, project management and all commissioning
and maintenance services requirements. All our external team members are fully qualified to
‘sign off ’ designs and Channel maintains all the relevant insurance policies which means the
legal onus is on us, not the contractor.
* The design service is free on the basis of receipt of order on contract award

Channel Safety Systems Limited, Petersfield Business Park, Bedford Road, Petersfield, Hampshire, GU32 3QA
Registered company no. 3853978