CTV Taicang

Job Information

Job01
TIG

Tag CCTV-000-0007 Model Number CVHF0570


Quantity 1
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

ASHRAE 90.1 - 2007 Add. M Complies


ASHRAE 90.1-2010 Complies
ASHRAE 90.1-2013 Complies
ASHRAE 90.1 - 2016 Complies

Unit Information
Model TCVHF Compressor size 570
Impeller size 280 Orifice size 710
Motor size 325 Refrigerant R-514A
Motor frequency 60. Hz Motor voltage 380
Unit Line Frequency 60. Hz Incoming line voltage 380
Evap shell size 050L Cond shell size 050L
Evap bundle size 580 Cond bundle size 500
Evap tube type IMCU Cond tube type TECU
Evap tube thickness 0.025" Cond tube thickness 0.025"
Evap passes Two pass evap water box Cond passes Two pass cond water box
AHRI NPLV.IP 0,3613 kW/ton IGV limit 90,00 deg

Design Information
Refrigeration capacity 500,0 tons Refrigerant charge 272 kg
Total power 279,1 kW Shipping weight 7491 kg
Cooling efficiency 0,5581 kW/ton Operating weight 8378 kg
LV AFD type UM Air-cooled AFD Control Power Voltage
Chiller heat rejected to ambient 4,76 MBh Application type Standard cooling
AFD heat rejected to ambient 29,75 MBh Free cooling option No
Evaporator Information
Entering fluid evap 12,50 C Evap fluid type water
Leaving fluid evap 7,00 C Evaporator fluid concentration N/A
Flow evap 76,1 L/s Fluid pressure drop evap 9,64 m H2O
Evap min flow rate 14,01 L/s Evap pressure drop min flow 0,35 m H2O
Evap max flow rate 102,7 L/s Evap pressure drop max flow 17,36 m H2O
Flow evap/refriferation capacity 2,413 gpm / ton Evap water box type non-marine
Evap fouling factor 0,0001000 hr-sq ft-deg F/Btu Evap water box pressure 150 psig

Condenser Information
Entering fluid cond 29,50 C Cond fluid type water
Leaving fluid cond 35,00 C Condenser fluid concentration N/A
Flow cond 89,2 L/s Fluid pressure drop cond 10,85 m H2O
Cond min flow rate 29,63 L/s Cond pressure drop min flow 1,49 m H2O
Cond max flow rate 108,6 L/s Cond pressure drop max flow 15,50 m H2O
Flow cond/refrigeration capacity 2,829 gpm / ton Cond water box type non-marine
Product Version 31.8.0.0
Selection code revision level 10140,00 Each Page 1 of 2
Report Date 24/05/2022 Data generation date 5/24/2022
CTV Taicang
Job Information

Job01
TIG

Tag CCTV-000-0007 Model Number CVHF0570


Quantity 1
Cond fouling factor 0,000250 hr-sq ft-deg F/ Btu Cond water box pressure 150 psig
Electrical Information
Motor LRA 2858 A Compressor motor RLA 508,40 A
Primary RLA (Incoming line) 490,5 A Min circuit ampacity 611 A
Max overcurrent protection 1000 A
Information for LEED Projects
Refrigeration capacity 500,0 tons Total power 279,1 kW
Refrigerant charge 272 kg AHRI NPLV.IP 0,3613 kW/ton

Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4) due to the R-514A
refrigerant GWP being less than 2.
Note: Trane recognizes and respects the U.S. Green Building Council® mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by
all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry
standard. Trane has exhaustively documented a leak rate of less than 0.5% for CenTraVac™ chillers (models CVHE, CVHF, CVHG,
CVHS, CVHM, CDHF, CDHG, CVHH and CDHH) and utilizes an average design refrigerant charge of less than 2 lb./ton. The overall
environmental performance of the CenTraVac chiller is verified in its product -specific Type III Environmental Product Declaration (EPD) in
accordance with ISO 14025, further demonstrating Trane’s commitment to safeguarding the environment.

The U.S. Green Building Council’s LEED® green building program is the preeminent program for the design, construction, maintenance and operations of
high-performance green buildings. It provides independent, third-party verification that a building project meets the highest green building and performance
measures.

Product Version 31.8.0.0


Selection code revision level 10140,00 Each Page 2 of 2
Report Date 24/05/2022 Data generation date 5/24/2022

You might also like