Cooling Load Calculation: ME 511 Aircondition and Ventilation Systems

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 13

Republic of the Philippines

CEBU TECHNOLOGICAL UNIVERSITY


MAIN CAMPUS
M. J. Cuenco Avenue Cor. R. Palma Street, Cebu City, Philippines
Website: http://www.ctu.edu.ph E-mail: thepresident@ctu.edu.ph
Phone: +6332 402 4060 loc. 1135

COLLEGE OF ENGINEERING

COOLING LOAD CALCULATION

ME 511
AIRCONDITION AND VENTILATION SYSTEMS

Submitted By:
Jacalan, John Paul B.
Glico, Jingle C.
Gella, Jerlyn Grace O.
Jumarito, Jerico R.
Milano, Vinard

Submitted To:

Engr. Aian Rey Caladcad, MSME

Instructor

“ A premier multi-disciplinary technological university “


DESIGN FORM FOR COOLING LOAD DETERMINATION

APPLICATION (PROJECT): COOLING LOAD CALCULATION OF FABRICATION/INNOVATION


LABORATORY 01

FLOOR DIMENSIONS (meters): 6.12 meters x 12.6 meters

CEILING HEIGHT (meters): 3.37 meters

SPACE AREA (meters): 77.12 m2

DESIGN FOR PEAK LOAD: DAY(Sunny) ROOM DESIGN CONDITION:

TIME OF DAY: 1400 hours TEMP.: 25 deg C

OUTDOOR TEMP: 34 deg C RH: 55%

Calculations for Zone 1:


Bedroom 1

I. External Cooling
Load

A. Roof

No roof since the area


is located at the first floor of the building.

B. Walls
From Ashrae 1997, Table 11, Chapter 28

Wall Construction:

Layer: Outside Surface Resistance, 100mm Face Brick, 200mm high density
concrete, Inside Surface Resistance, Finish

Material (Code Number) R(m2K/W)

Outside Surface Resistance(A0) 0.059

100mm Face Brick (A2) 0.036

200mm high density (C10) 0.177

Inside Surface Resistance (E0) 0.121

Finish (A6) 0.031

RTOTAL = 0.424 m2k/W


Overall Heat Transfer Coefficient, U

U = 1/Rt = 1/0.424

U = 2.358 W/m2K

For wall type:

From ASHRAE 1997, Table 33B, Chapter 28

Wall Types, Mass Evenly Distributed, for use with Table 32

For Secondary Material, Mass evenly distributed, R = 0.35 – 0.44

Principal wall material = C1

Then, wall type = Z

CLTDwall (Time of Interest : 1400 hrs)

From Table 8.3A, Cooling and Heating Load Calculation Manual

Wall Facing CLTDwall (1400)

E 26 ˚F

W 25 ˚F
From PAG-ASA annual (Summer 2019) Info

Tm = 34 ˚C = 93.2 ˚F

Tr = 23 ˚C = 73.4 ˚F

CLTDwall corrected = CLTDwall + (78-Tr) + (Tm – 85)

For the East Wall:

CLTDwall corrected = 26 ˚F + (78-73.4) ˚F + (93.2 – 85) ˚F

CLTDwall corrected = 38.8 ˚F = 3.78 ˚C

For the West Wall:

CLTDwall corrected = 25 ˚F + (78-73.4) ˚F + (93.2 – 85) ˚F

CLTDwall corrected = 37.8 ˚F = 3.22 ˚C

Wall Area :

East Wall

AwallE = (3.77m X 6.12m) = 23.07 m2

West Wall

AwallW = (3.77m X 6.12m) = 23.07 m2

The heat transfer between walls:

@East Wall : Qwall = (2.358 W/m2K)( 23.07 m2)( 3.78 ˚C) = 205.63 W

@West Wall : Qwall =(2.358 W/m2K)( 23.07 m2)( 3.22 ˚C) = 175.16W

C. Ceilings

From ASHRAE 1997, Chapter 24, Table 4

Material: Concrete

Overall Thermal Coefficient, U = 2.70 W/m2K

Ceiling Area
Area Ceiling = 77.12 m2

Thus,

Q ceiling = UA(Temp Difference)

Q ceiling = (2.70 W/m2K)(77.12 m2)(34 – 25) ˚C

Q ceiling = 1.874 kW

D. Floors

From ASHRAE 1997, Chapter 24, Table 4

Slab Floor

Overall Thermal Coefficient, U = 1.05 W/m2K

Floor Area

Area Ceiling = 77.12 m2

Thus,

Q floor = UA(Temp Difference)

Q floor = (1.05 W/m2K)(77.12 m2)(34 – 25) ˚C

Q floor = 730.61 W

E. Windows

E.1 Solar Load Through Glass

From ASHRAE 1997, Chaoter 27, Table 5

Overall Heat Transfer Coefficient, U:

For Glass Type, Heat Absorbing (Translucent)

U = 2.50 W/m2K

CLTD window

From ASHRAE 1997, Chapter 28, Table 34

Time of Interest: 1400 hours


CLTD = 8 ˚C = 46.4 ˚F

CLTDwindow corrected = CLTDwindow+ (78-Tr) + (Tm – 85)

CLTDwindow corrected = 46.4 ˚F + (78-73.4) ˚F + (93.2 – 85) ˚F

CLTDwindow corrected = 59.2 ˚F = 15.11 ˚C

Area of Window

Areawindow = 0.850m x 1.35m = 1.15 m2

Thus,

Q = UACLTD(Number of windows)

Q window = (2.50 W/m2K)(1.15 m2)(15.11 ˚C)(6)

Q window = 260.65 W

II. Internal Load

A. People

A.1 Sensible

Qsensible = NQsCLF

No. of Occupants = 40 people

From ASHRAE 1997, Chapter 28, Table 3

Degree of Activity: Moderately active: Sensible Heat, W: 75 W

Cooling Load Factor, CLF

From ASHRAE 1997, Chapter 28, Table 37

Hours in Space (Maximum) = 12 hours (Zone B)

Number of hour after entry to the space before turned on : 10 hours

Time of interest : 1400 hours (Summer)

CLF = 0.97

Thus,

Qsensible = (40)(75W)(0.97) = 2.91 kW


A2. Latent Heat

Qlatent = NQL

QL for Moderately active: 55 W

Qlatent = 40 person (55W)

Qlatent = 2.2 kW

B. Lights

Qlights = WFUTCLF for LED lights (8 pieces)

W = 12 watts x 8 = 96 W

From ASHRAE 1997, Chapter 28, Table 38

For zone type B, Operation: 12 hours

CLF = 0.97 FUT = 0.5

Thus,

Qlights = (96 W)(0.5)(0.97) = 46.56 W

Qlights = WFUTCLF for Fluorescent light (16 pieces)

W = 20 watts x 16 = 320 W

From ASHRAE 1997, Chapter 28, Table 38

For zone type B, Operation: 12 hours

CLF = 0.97 FUT = 0.5

Thus,

Qlights = (320 W)(0.5)(0.97) = 155.2 W

C. Appliances

1. Water Dispenser (500W) time of usage: 8hrs/day (average)

Fu = 8hrs/24hr = 0.33

Assume Fr = 1.0

From ASHRAE 1997, Chapter 28, Table 37


For Zone Type B: CLF = 0.98

Thus,

Qsensible = Qin x Fu x Fr x CLF

Qsensible = (500 W) (0.33) (1) (0.98) = 161.7 W

Qlatent = Qin x Fu

Qlatent = 500w (0.33) = 165W

D. Infiltration

From ASHRAE 1997, Chapter 25, Table 3

Material Description Size AL/Unit AL

Ceiling Drop 77.12 m2 1.8 138.82

Door Frame Wood 1 0.3 0.3

Doors Single 1 12 12

Electrical With Gasket 4 0.15 0.6


Outlets

Wiring Caulked 4 2 8

Walls High Density 24 m2 1.1 26.4


Block

Window Horizontal 1.15 m2 1.1 1.265

AL Total = 187.12
From ASHRAE 1997, Chapter 25, Table 6

Cs (stack coefficient) for multiple stack = 0.000435

Cw (wind coefficient) for multiple stacks = 0.000382

Temperature Difference = 34 ˚C – 25 ˚C = 9 ˚C

Max windspeed via timeanddate.com/weather/Philippines/cebu.city

V = 9 kmh = 2.5 m/s

Thus,
Qinfiltration= (AL/1000)((Cs(∆T)) + Cw(V)2)0.5

Qinfiltration= (187.12/1000)((0.000435(9˚C)) + 0.000382 (2.5 m/s)2)0.5

Qinfiltration= 0.015 m3/s x (3.28 ft/m)3 x (60s/min) = 31.45 CFM

For the Wo – Wi (During Summer, RH = 55% to 60%

Assume 55% RH

From the Psychrometric Chart,

To = 34 ˚C, Ti = 25 ˚C, RH = 55%


Wo = 0.0018 lbv/lba Wi = 0.00102 lbv/lba

Thus,

Qsensible = CpT(Qrate)

Qsensible = (1.05KJ/kgK)(9˚C)(0.015 m3/s)

Qsensible = 141.75 W

Qlatent = 4840(Qrate)(∆W)

Qlatent = 4840(31.45 CFM)(0.00078)

Qlatent = 34.80 W

E. Miscellaneous Sources

a. Ventilation

From ASHRAE Standard 62-2001, Table 2

Outdoor Requirement = 15 CFM

No. of Persons = 40

CFMtotal = 15(40) = 600 CFM

Thus,

Qsensible = 1.08CFM(∆T)

Qsensible = 1.08(600CFM)(93.2 – 73.4) ˚F

Qsensible = 3.76 kW

Qlatent = 4840 x CFM x ∆W

Qlatent = 4840 x 600 CFM x (0.0078)

Qlatent = 6.63 kW
EQUIPMENT SCHEDULE

INDOOR UNIT

DESIGNATION TYPE QUANTITY REFRIGERANT SELECTED DIMENSION


COOLING
CAPACITY (w x h x l) mm
(Kw)

FCU DUCT 1 R-32 10 (1400x 245 x 800)


CONNECTION
FBA100BVMA MIDDLE STATIC
PRESSURE TYPE

UNIT WEIGHT ELECTRICAL CHARACTERISTICS PIPING SIZE

INPUT POWER VOLT PHASE GAS LINE LIQUID LINE

47 3.01 Kw 220 V 1 15.9 mm 15.9 mm

OUTDOOR UNIT

DESIGNATION TYPE QUANTITY REFRIGERANT SELECTED DIMENSION


COOLING
CAPACITY (w x h x l) mm
(Kw)

ACCU WATER COOLED 1 R-32 10 (930x695x350)


CONDENSER
RZF100CVM

UNIT WEIGHT ELECTRICAL CHARACTERISTICS PIPING SIZE

INPUT POWER HP VOLT GAS LINE LIQUID LINE

64 1.6 Kw 2.14 220 15.9 mm 15.9 mm


INDOOR UNIT

OUTDOOR UNIT