Cooling Technology
Industrial Air Conditioner Combined With Heat Exchanger
Applications
◆ Telecom cabinets/shelters
Front Back
subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 이
Detail Drawing
Note:
1. Mounting gasket supplied (not shown)
2. Units: mm
subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 삼
Technical Data
Control Behavior
Tin
Alarm
TCON
P0
subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 사
1, P0—P1 & P1—P2 & P3—P4:
Compressor OFF, External Fan OFF, Heater ON and Internal Fan Running at 50% speed
2, P2—P3:
Compressor OFF, External Fan OFF, Heater OFF and Internal Fan Running at 50% speed
P7—P8:
Heater OFF, Both Internal Fan & External Fan run with Full speed ,
Compressor ON unless its cooling capacity is not higher than heat exchanging cooling
capacity(130*(Tin-Tout)).
P8—P9:
Heater OFF,
External Fan adjusts its speed from Full speed @ (TCON+TCOFF)/2 to the speed when Tin reaches P5 from
P4 following the pattern stated in 3rd point above,
Compressor ON & Internal Fan run with Full speed if heat exchanging cooling
capacity(130*(Tin-Tout))<1950W, otherwise, Compressor OFF & Internal Fan run with variable speed
following the pattern stated in 3rd point above.