Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Rele Temporitzat Clip

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CONTA-ELECTRONICS

MFR 7
Multi-function timing relay

Instead of timing units with only one function, these


units offer the affordable possibility to implement several
common time functions, such as ON-delay, impulse-ON,
impulse-OFF, or pulsemonitoring. They reduce storage
costs, since only one unit is needed for all applications.

Features

• 7 Time functions

• 6 Time ranges 50 ms bis 10 h

• Control contact

• Wide-range input 24 to 48V DC / 24 to 240V AC

• Width, 17,5mm

• Installation design

• Relais output: 1 CO contact

• Easy to mount on TS35 DIN rail

• IP 20 protection

MFR 7

www.conta-clip.com

CONTA-CLIP Verbindungstechnik GmbH

Our ideas – your advantages


Otto-Hahn-Str. 7 · D-33161 Hövelhof, Germany
Phone +49 (0) 52 57 . 98 33-0 · Fax +49 (0) 52 57 . 98 33-33
MFR Multi-function timing relay

MFR 7

• Multi-function
• 7 Time functions
• 6 Time ranges 50 ms bis 10 h
• Control contact
• Wide-range input 24 to 48V DC / 24 to 240V AC
• Width, 17,5mm
• Installation design
• Relais output: 1 CO contact
• Easy to mount on TS35 DIN rail
• IP 20 protection

Type MFR 7 VPE


Cat. No. 16373.2 10
Dimensions (L x B x H) TS 35 x 7,5 90x17,5x57,9mm
Weight 44g
Functions
E, R, Ws, Wa, Bp, F, Wu (Wu = Ws with fixed jumper A1-B1)
Time ranges / Setting ranges
50 ms to 10 h
Displays With control contact
Green LED U/t ON Supply voltage applied
Green LED U/t flashing* Indicates time has expired
Yellow LED R ON/OFF* Position of output relay
Input circuit DC AC
Supply voltage (terminals A1 and A2) 24 to 48V DC, terminals A1 (+) - A2 (-) 24….240 V AC, terminals A1 - A2
Tolerance -15% / + 10 % -15% / + 10 %
Rated frequency - 48 tos 63 Hz
Rated consumption 0,4W 1W (8VA)
Power-on duration 100% 100%
Backup power time <20 ms <60 ms (230V AC) / <30ms (24V AC)
Recovery time >100 ms >100 ms
Release voltage > 30 % of min. supply voltage > 30 % of min. supply voltage
Control contact spannung
Input Terminals A1-B1 Without control contact
Can carry load yes
Min. control pulse duration DC min. 50 ms / AC min 100 ms
EN 03|16 Errors, changes and omissions excepted. All rights reserved.

Output circuit
Contact 1 CO
Rated voltage 250V
Switching capacity (ohmic load) 5A / 250V
Contact material AgNi
Fuse 5A flink
Mechanical lifespan 1 x 106 cycles
Electrical lifespan 1 x 105 cycles
Endurance with - without load 6/min - 1200/min
Accuracy
Basic accuracy < 1,5% (from scale reading)
Setting tolerance < 5% (from scale reading)
Repeat accuracy < 0,5% or ± 5 ms Function Wu (WS)
Temperature influence <0,05% / °C
General specifications
Contamination degree / overvoltage category (IEC61812-1) 2 / ll
Rated insulation voltage (IEC 61812-1) 300V (Input circuit / Output circuit)
Rated impulse voltage (IEC 61812-1) 2500V (Input circuit / Output circuit)
Insulation test voltage (IEC 61812-1) 1600V(Input circuit / Output circuit)
Ambient temperature / Storage temperature -20 to +50°C / -40 to +70°C
Relative humidity 25 to 75%
Protection degree housing / terminals IP40 / IP 20
Connection type / cross-section Screw connection / 0,25…2,5mm²
Stripping length / Torque 7 mm / max. 0,5 Nm

ON delay (E) OFF-delay with control contact (R) Impulse-ON with control contact (Ws)

Impulse-ON voltage controlled (Wu) Impulse-OFF with control contact (Wa) Dimensions

Flasher begin with delay (Bp) T-Flipflop (Toggle)