P9443-SID-4000ER-ZZZ001-revB K

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

11 10 9 8 7 6 5 4 3 2 1

LEGEND (IN ACCORDANCE WITH IEC 60617)


A AMMETER PLUG AND SOCKET

K M MOTOR CIRCUIT BREAKER K

MOTOR HEATER CONTACTOR

GENERAL POWER SUPPLY LINE 1 GENERAL POWER SUPPLY LINE 2 GENERAL POWER SUPPLY LINE 3 PACKAGE EQUIPMENT TRANSFORMER WITH
LOCAL CONTROL PANEL OFF CIRCUIT TAP CHANGER
POWER DEMAND : 100 MVA @ 380 kV POWER DEMAND : 100 MVA @ 380 kV POWER DEMAND : 100 MVA @ 380 kV VFD

VARIABLE SPEED DRIVE TRANSFORMER WITH


ON LOAD TAP CHANGER

ATS AUTOMATIC TRANSFER SYSTEM RECTIFIER

ACO AUTOMATIC CHANGE OVER INVERTER


J J
XXXX XXXX XXXX
G GENERATOR STATIC TRANSFER SWITCH
380kV / 33 kV 380kV / 33 kV 380kV / 33 kV ~
100MVA 100MVA 100MVA
HIGH SPEED TRANSFER SYSTEM BATTERY
HSTS

HSBT HIGH SPEED BUS TRANSFER

SCOPE LIMITS INTERLOCK

CABLE ELECTRICAL INTERLOCKING


I I
BUS DUCT
MV LINE 1 MV LINE 2 MV LINE 3

PROTECTION RELAY FUNCTIONS (IN ACCORDANCE WITH ANSI STANDARD)

25 SYNCHRO CHECK RELAY 51N TIME DELAY EARTH FAULT RELAY


26Q THERMOSTAT (2 THRESHOLDS) 51R ANTI-STALL PROTECTION
PARTNER 26W WINDING TEMPERATURE RELAY 59 OVER VOLTAGE RELAY
27 UNDER VOLTAGE RELAY 59N NEUTRAL OVER VOLTAGE RELAY
Protective relay
Protective relay
27 46 86
Protective relay
27 46 86
SIDEM 32 DIRECTIONAL POWER 63B BUCHHOLZ
27 46 86 3P 3P 3P
HSBT HSBT 50 N / 51 N 37 UNDER CURRENT RELAY PRESSURE RELIEF DEVICE FOR TR MAIN TANK
50 N / 51 N 63P

** * *
50 N / 51 N
H 01BBA01 50 / 51
NC NO
50 / 51 01BBC01
NC 50 / 51
01BBB01 40 FIELD RELAY / LOSS OF EXCITATION GROUND PROTECTION RELAY
H
33kV 3Ph, 60Hz, 2000A 20kA/3s 33kV 3Ph, 60Hz, 2000A 20kA/3s 33kV 3Ph, 60Hz, 2000A 20kA/3s 64
48/51L LOCKED ROTOR RELAY 64REF RESTRICTED EARTH FAULT RELAY
Protective relay Protective relay Protective relay Protective relay
27 27 27 27 49 THERMAL OVERLOAD RELAY 66 STARTS LIMIT RELAY
27 59 86 50 N 27 59 86 50 N 3P 3P 27 59 86 50 N 27 59 86 50 N
46 REVERSE PHASE / PHASE BALANCE RELAY Ac DIRECTIONAL OVER CURRENT RELAY
50 / 51 50 / 51 50 / 51 50 / 51 67
NO NO 50 INSTANTANEOUS OVERCURRENT RELAY OIL LEVEL RELAY
71Q
50BF BREAKER FAILURE 86 LOCKOUT RELAY

87B DIFFERENTIAL BUS BAR PROTECTION RELAY


50G INSTANTANEOUS EARTH FAULT RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT RELAY 87T DIFFERENTIAL PROTECTIVE RELAY TRANSFORMER

51 TIME DELAY OVERCURRENT RELAY 87M DIFFERENTIAL PROTECTIVE RELAY MOTOR

51G TIME OVERCURRENT GROUND RELAY


G

G
NOTES

01BBT01 01BBT03 01BBT04 01BBT02 1. Short circuit power supply values from Upstream plant (To be defined).
63 B 26 Q 63 B 26 Q 63 B 26 Q 63 B 26 Q
33kV / 13,8 kV 63 P 26 W
33kV / 13,8 kV 63 P 26 W
33kV / 13,8 kV 63 P 26 W
33kV / 13,8 kV 63 P 26 W 2. This drawing shows only typical feeders arrangement.
60/75MVA 60/75MVA 60/75MVA 60/75MVA
ONAN/ONAF 30A ONAN/ONAF 30A ONAN/ONAF 30A ONAN/ONAF 30A
Dyn11 Dyn11 Dyn11 Dyn11

F
*Main SWITCHGEAR SHORT-CIRCUIT VALUE CAN BE EQUAL OR GREATER THAN 40kA ACCORDING TO SHORT-CIRCUIT
CALCULATION NOTE. TO BE CONFIRMED DURING DETAIL ENGINEERING.
** MV SWITCHGEAR SHORT-CIRCUIT VALUE SHALL BE CONFIRMED DURING DETAIL ENGINEERING ACCORDING TO UPSTREAM
SHORT-CIRCUIT LEVEL

A C D B

REFERENCE DOCUMENTS
E
-P9443-SID-4000EL-ZZZ401 ELECTRICAL CONSUMERS LIST

D
B UPDATE 11/03/2024 CBO GJE RSM

A FIRST ISSUE 05/03/2024 CBO GJE RSM

REV NATURE OF REVISION DATE DRAWN CHECKED APPROVED

B
1, Rue GIOVANNI BATTISTA PIRELLI - BÂT A, 94417 SAINT-MAURICE CEDEX, FRANCE

B ' +33 1 49 95 76 76 7 +33 1 49 95 76 95


e-mail : contact@sidem-fr.com

JUBAIL 4&6
SCALE
KEY ONE LINE DIAGRAM
- N/A

PROJECT NUMBER DOCUMENT NUMBER REVISION POI FORMAT A

A P 9443 SID-4000ER-ZZZ001 B PRE A1


This document is the property of SIDEM. It cannot be used, reproduced,transmitted and/or disclosed, without prior written permission of SIDEM.

FILE: -
11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
LEGEND (IN ACCORDANCE WITH IEC 60617)
A AMMETER PLUG AND SOCKET

K M MOTOR CIRCUIT BREAKER K

MOTOR HEATER CONTACTOR

PACKAGE EQUIPMENT TRANSFORMER WITH


LOCAL CONTROL PANEL OFF CIRCUIT TAP CHANGER
VFD

VARIABLE SPEED DRIVE TRANSFORMER WITH


ON LOAD TAP CHANGER

ATS AUTOMATIC TRANSFER SYSTEM RECTIFIER

ACO AUTOMATIC CHANGE OVER INVERTER


J J
01MKA10 G GENERATOR STATIC TRANSFER SWITCH
~

HIGH SPEED TRANSFER SYSTEM BATTERY


GENSET HSTS
25 27 46 86
S= 4000 kVA G 32 40 49 59
COS j = 0.8 ~ 51N 50 BF HIGH SPEED BUS TRANSFER
HSBT

SCOPE LIMITS INTERLOCK


3P
50 / 51
NO CABLE ELECTRICAL INTERLOCKING
I A B I
BUS DUCT

3P 3P
50 / 51 50 / 51 PROTECTION RELAY FUNCTIONS (IN ACCORDANCE WITH ANSI STANDARD)
NO NO

25 SYNCHRO CHECK RELAY 51N TIME DELAY EARTH FAULT RELAY


26Q THERMOSTAT (2 THRESHOLDS) 51R ANTI-STALL PROTECTION
E 26W WINDING TEMPERATURE RELAY 59 OVER VOLTAGE RELAY
27 UNDER VOLTAGE RELAY 59N NEUTRAL OVER VOLTAGE RELAY
Protective relay
Protective relay 32 DIRECTIONAL POWER 63B BUCHHOLZ
27 46 86 27 46 86 3P
3P 3P
ATS 50 N / 51 N 50 / 51 37 UNDER CURRENT RELAY 63P PRESSURE RELIEF DEVICE FOR TR MAIN TANK
50 N / 51 N
H 01BBA02 13,8kV 3Ph, 60Hz, 3200A 40kA/3s
Protective relay
** Protective relay
50 / 51

Protective relay
NC

Protective relay
NC 50 / 51

Protective relay
13,8kV 3Ph, 60Hz, 3200A 40kA/3s ** Protective relay
NO
01BBB02 40 FIELD RELAY / LOSS OF EXCITATION
48/51L LOCKED ROTOR RELAY
64 GROUND PROTECTION RELAY
64REF RESTRICTED EARTH FAULT RELAY
H

Protective relay Protective relay 49 THERMAL OVERLOAD RELAY


27 27 66 STARTS LIMIT RELAY
50 51 50 51 46 49 86 66 50 51 3P 50 51 50 51 46 49 86 66 50 51
46 REVERSE PHASE / PHASE BALANCE RELAY Ac DIRECTIONAL OVER CURRENT RELAY
50 / 51 50G 50 / 51 50G 67
NO
51 LR 51G 51 LR 51G 50 INSTANTANEOUS OVERCURRENT RELAY OIL LEVEL RELAY
71Q
50BF BREAKER FAILURE 86 LOCKOUT RELAY

87B DIFFERENTIAL BUS BAR PROTECTION RELAY


VFD VFD VFD VFD VFD VFD 50G INSTANTANEOUS EARTH FAULT RELAY
~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51
SPARE ~ 51 LR 66 ~ 51 LR 66 M ~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 M ~ 51 LR 66 SPARE 50N INSTANTANEOUS NEUTRAL OVERCURRENT RELAY 87T DIFFERENTIAL PROTECTIVE RELAY TRANSFORMER
X1 X1 51 TIME DELAY OVERCURRENT RELAY 87M DIFFERENTIAL PROTECTIVE RELAY MOTOR
HP PUMP HP PUMP
51G TIME OVERCURRENT GROUND RELAY
M M
8000kW (x2)
M M M
8000kW (x3)
M
G
CAPACITOR BANK CAPACITOR BANK
G INTAKE PUMP LP PUMP 2ND PASS INTAKE PUMP LP PUMP 2ND PASS
3300kW (x2) 1600kW (x2) HP PUMP 3300kW (x1) 1600kW (x2) HP PUMP NOTES
3300kW (x1) 3300kW (x1)
1. Short circuit power supply values from Upstream plant (To be defined).
2. This drawing shows only typical feeders arrangement.

Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay
27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N
50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51

F
63 B 26 Q 63 B 26 Q
F 01BFT01 63 P 26 W 01BFT02 63 P 26 W
13,8kV / 0,4 kV 13,8kV / 0,4 kV *Main SWITCHGEAR SHORT-CIRCUIT VALUE CAN BE EQUAL OR GREATER THAN 40kA ACCORDING TO SHORT-CIRCUIT
3150kVA 3150kVA CALCULATION NOTE. TO BE CONFIRMED DURING DETAIL ENGINEERING.
** MV SWITCHGEAR SHORT-CIRCUIT VALUE SHALL BE CONFIRMED DURING DETAIL ENGINEERING ACCORDING TO UPSTREAM
SHORT-CIRCUIT LEVEL

3P 3P
ATS

01BFA11 380V 3Ph, 60Hz, 5000A 80kA/1s *


Protective relay
NC
3P

NO
NC
380V 3Ph, 60Hz, 5000A 80kA/1s
Protective relay
* 01BFB11
REFERENCE DOCUMENTS
E
27 27
50 51 50 51 -P9443-SID-4000EL-ZZZ401 ELECTRICAL CONSUMERS LIST

VFD VFD

~ 46 49 50 51 ~ 46 49 50 51
63 B 26 Q ~ 51 LR 66 ~ 51 LR 66 63 B 26 Q
01BFT03 63 P 26 W 01BFT04 63 P 26 W
13,8kV / 0,4 kV 13,8kV / 0,4 kV
3150kVA 3150kVA
M M
D
ERD PUMP ERD PUMP
300kW (x4) 300kW (x4)
D
3P 3P B UPDATE 11/03/2024 CBO GJE RSM
ATS

01BFA12
NC
380V 3Ph, 60Hz, 5000A 80kA/1s
Protective relay
* 3P

NO
380V 3Ph, 60Hz, 5000A 80kA/1s
Protective relay
* 01BFB12
NC
A

REV
FIRST ISSUE

NATURE OF REVISION
05/03/2024

DATE
CBO

DRAWN
GJE

CHECKED APPROVED
RSM

27 27
50 51 50 51

C
63 B 26 Q 63 B 26 Q
01BFT05 63 P 26 W VFD
46 49 50 51
VFD
46 49 50 51 01BFT06 63 P 26 W
~ ~
C 13,8kV / 0,4 kV ~ 51 LR 66 ~ 51 LR 66 13,8kV / 0,4 kV
2500kVA 2500kVA

M M

ERD PUMP ERD PUMP


300kW (x4) 300kW (x4)

3P 3P
ATS
B

B
01BFA13
NC

Protective relay
380V 3Ph, 60Hz, 4000A 80kA/1s *
Protective relay Protective relay
3P

NO
Protective relay
380V 3Ph, 60Hz, 4000A 80kA/1s
Protective relay
* 01BFB13

Protective relay
NC
1, Rue GIOVANNI BATTISTA PIRELLI - BÂT A, 94417 SAINT-MAURICE CEDEX, FRANCE

' +33 1 49 95 76 76 7 +33 1 49 95 76 95


27 27
50 51 50 51 50 51 50 51 50 51 50 51 e-mail : contact@sidem-fr.com

JUBAIL 4&6
SCALE
VFD
46 49 50 51
VFD
46 49 50 51
VFD
46 49 50 51
VFD
46 49 50 51
VFD
46 49 50 51
VFD
46 49 50 51
KEY ONE LINE DIAGRAM
~ ~ ~ ~ ~ ~
~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 - N/A

PROJECT NUMBER DOCUMENT NUMBER REVISION POI FORMAT A


M M M M M M

A CIP PUMP FLUSHING PUMP LIMESTONE WASH PUMP CIP PUMP FLUSHING PUMP LIMESTONE WASH PUMP
P 9443 SID-4000ER-ZZZ001 B PRE A1
350kW (x2) 450kW (x1) 250kW (x1) 350kW (x2) 450kW (x2) 250kW (x1)
This document is the property of SIDEM. It cannot be used, reproduced,transmitted and/or disclosed, without prior written permission of SIDEM.

FILE: -
11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
LEGEND (IN ACCORDANCE WITH IEC 60617)
A AMMETER PLUG AND SOCKET

K M MOTOR CIRCUIT BREAKER K

MOTOR HEATER CONTACTOR

PACKAGE EQUIPMENT TRANSFORMER WITH


LOCAL CONTROL PANEL OFF CIRCUIT TAP CHANGER
VFD

VARIABLE SPEED DRIVE TRANSFORMER WITH


ON LOAD TAP CHANGER

ATS AUTOMATIC TRANSFER SYSTEM RECTIFIER

ACO AUTOMATIC CHANGE OVER INVERTER


J J
G GENERATOR STATIC TRANSFER SWITCH
~

HIGH SPEED TRANSFER SYSTEM BATTERY


HSTS

HSBT HIGH SPEED BUS TRANSFER

SCOPE LIMITS INTERLOCK

CABLE ELECTRICAL INTERLOCKING


I C D E I
BUS DUCT

PROTECTION RELAY FUNCTIONS (IN ACCORDANCE WITH ANSI STANDARD)

25 SYNCHRO CHECK RELAY 51N TIME DELAY EARTH FAULT RELAY


26Q THERMOSTAT (2 THRESHOLDS) 51R ANTI-STALL PROTECTION
26W WINDING TEMPERATURE RELAY 59 OVER VOLTAGE RELAY
27 UNDER VOLTAGE RELAY 59N NEUTRAL OVER VOLTAGE RELAY
Protective relay
Protective relay BUCHHOLZ
27 46 86 3P 32 DIRECTIONAL POWER 63B
27 46 86 3P 3P
ATS 50 N / 51 N 50 / 51 37 UNDER CURRENT RELAY PRESSURE RELIEF DEVICE FOR TR MAIN TANK
50 N / 51 N 63P
H 01BBA03 13,8kV 3Ph, 60Hz, 3200A 40kA/3s
Protective relay
** Protective relay
50 / 51

Protective relay
NC

Protective relay
NC 50 / 51

Protective relay
13,8kV 3Ph, 60Hz, 3200A 40kA/3s ** Protective relay
NO
01BBB03 40 FIELD RELAY / LOSS OF EXCITATION
48/51L LOCKED ROTOR RELAY
64 GROUND PROTECTION RELAY
64REF RESTRICTED EARTH FAULT RELAY
H

Protective relay 27 27 Protective relay 49 THERMAL OVERLOAD RELAY


50 51 50 51 50 51 3P 50 51 50 51 50 51 66 STARTS LIMIT RELAY
46 49 86 66 46 49 86 66
46 REVERSE PHASE / PHASE BALANCE RELAY Ac DIRECTIONAL OVER CURRENT RELAY
50 / 51 50G 50 / 51 50G 67
NO
51 LR 51G 51 LR 51G 50 INSTANTANEOUS OVERCURRENT RELAY OIL LEVEL RELAY
71Q
50BF BREAKER FAILURE 86 LOCKOUT RELAY

87B DIFFERENTIAL BUS BAR PROTECTION RELAY


VFD VFD VFD VFD VFD VFD 50G INSTANTANEOUS EARTH FAULT RELAY
~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51 ~ 46 49 50 51
SPARE ~ 51 LR 66 ~ 51 LR 66 M ~ 51 LR 66 ~ 51 LR 66 ~ 51 LR 66 M ~ 51 LR 66 SPARE 50N INSTANTANEOUS NEUTRAL OVERCURRENT RELAY 87T DIFFERENTIAL PROTECTIVE RELAY TRANSFORMER
X1 X1
51 TIME DELAY OVERCURRENT RELAY 87M DIFFERENTIAL PROTECTIVE RELAY MOTOR
HP PUMP HP PUMP
51G TIME OVERCURRENT GROUND RELAY
M M
8000kW (x2)
M M M
8000kW (x2)
M
G
CAPACITOR BANK CAPACITOR BANK
G INTAKE PUMP LP PUMP 2ND PASS INTAKE PUMP LP PUMP 2ND PASS
3300kW (x1) 1600kW (x2) HP PUMP 3300kW (x1) 1600kW (x3) HP PUMP NOTES
3300kW (x1) 3300kW (x2)
1. Short circuit power supply values from Upstream plant (To be defined).
2. This drawing shows only typical feeders arrangement.

Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay Protective relay
27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N 27 59 86 50 N
50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51 50 / 51

F
63 B 26 Q 63 B 26 Q 63 B 26 Q 63 B 26 Q
01BHT13 63 P 26 W 01BFT07 63 P 26 W 01BFT08 63 P 26 W 01BHT14 63 P 26 W
F
13,8kV / 0,4 kV 13,8kV / 0,4 kV 13,8kV / 0,4 kV 13,8kV / 0,4 kV *Main SWITCHGEAR SHORT-CIRCUIT VALUE CAN BE EQUAL OR GREATER THAN 40kA ACCORDING TO SHORT-CIRCUIT
1250kVA 1600kVA 1600kVA 1250kVA CALCULATION NOTE. TO BE CONFIRMED DURING DETAIL ENGINEERING.
** MV SWITCHGEAR SHORT-CIRCUIT VALUE SHALL BE CONFIRMED DURING DETAIL ENGINEERING ACCORDING TO UPSTREAM
SHORT-CIRCUIT LEVEL
H F G I
3P 3P
ATS

01BFA14 380V 3Ph+N, 60Hz, 2500A 40kA/1s ** NC


3P

NO
NC
380V 3Ph+N, 60Hz, 2500A 40kA/1s ** 01BFB14
REFERENCE DOCUMENTS
E
Protective relay 27 27 Protective relay
Protective relay Protective relay Protective relay Protective relay
46 49 64 66 46 49 64 66 -P9443-SID-4000EL-ZZZ401 ELECTRICAL CONSUMERS LIST
49 50 / 51 49 50 / 51 49 50 / 51 49 50 / 51
50 / 51 50 / 51
E 51 LR 51 LR

63 B 26 Q M M M PACKAGE M M M PACKAGE
63 B 26 Q
01BFT09 63 P 26 W OR LCP OR LCP
01BFT10 63 P 26 W
13,8kV / 0,4 kV 13,8kV / 0,4 kV
30kWMPO50kW 50kWMPO100kW 100kWMPO300kW 30kWMPO50kW 50kWMPO100kW 100kWMPO300kW
1250kVA 1250kVA

D
3P 3P B UPDATE 11/03/2024 CBO GJE
ATS RSM

01BFA15
NC
380V 3Ph+N, 60Hz, 2000A 40kA/1s ** 3P

NO
380V 3Ph+N, 60Hz, 2000A 40kA/1s ** 01BFB15
NC
A

REV
FIRST ISSUE

NATURE OF REVISION
05/03/2024

DATE
CBO

DRAWN
GJE

CHECKED APPROVED
RSM

Protective relay 27 27 Protective relay


Protective relay Protective relay Protective relay Protective relay
46 49 64 66 46 49 64 66
49 50 / 51 49 50 / 51 49 50 / 51 49 50 / 51
50 / 51 50 / 51
51 LR 51 LR

63 B 26 Q
C
63 B 26 Q
01BFT11 63 P 26 W 01BFT12 63 P 26 W

C 13,8kV / 0,4 kV M M M PACKAGE M M M PACKAGE 13,8kV / 0,4 kV


OR LCP OR LCP
1250kVA 1250kVA
30kWMPO50kW 50kWMPO100kW 100kWMPO300kW 30kWMPO50kW 50kWMPO100kW 100kWMPO300kW

3P 3P
ATS
B

B
01BFA16
NC
380V 3Ph+N, 60Hz, 2000A 40kA/1s ** 3P

NO
380V 3Ph+N, 60Hz, 2000A 40kA/1s ** 01BFB16
NC
1, Rue GIOVANNI BATTISTA PIRELLI - BÂT A, 94417 SAINT-MAURICE CEDEX, FRANCE

' +33 1 49 95 76 76 7 +33 1 49 95 76 95


Protective relay 27 27 Protective relay
Protective relay Protective relay Protective relay Protective relay
46 49 64 66 46 49 64 66 e-mail : contact@sidem-fr.com
49 50 / 51 49 50 / 51 49 50 / 51 49 50 / 51
50 / 51 50 / 51
51 LR 51 LR
HASSYAN
SCALE
KEY ONE LINE DIAGRAM
M M M M M M -
PACKAGE
OR LCP
PACKAGE
OR LCP N/A
30kWMPO50kW 50kWMPO100kW 100kWMPO300kW 30kWMPO50kW 50kWMPO100kW 100kWMPO300kW
PROJECT NUMBER DOCUMENT NUMBER REVISION POI FORMAT A

A P 9443 SID-4000ER-ZZZ001 B PRE A1


This document is the property of SIDEM. It cannot be used, reproduced,transmitted and/or disclosed, without prior written permission of SIDEM.

FILE: -
11 10 9 8 7 6 5 4 3 2 1
11 10 9 8 7 6 5 4 3 2 1
LEGEND (IN ACCORDANCE WITH IEC 60617)
A AMMETER PLUG AND SOCKET

K M MOTOR CIRCUIT BREAKER K

MOTOR HEATER CONTACTOR

PACKAGE EQUIPMENT TRANSFORMER WITH


LOCAL CONTROL PANEL OFF CIRCUIT TAP CHANGER
VFD

TRANSFORMER WITH
F G VARIABLE SPEED DRIVE
ON LOAD TAP CHANGER

ATS AUTOMATIC TRANSFER SYSTEM RECTIFIER

ACO AUTOMATIC CHANGE OVER INVERTER


J J
G GENERATOR STATIC TRANSFER SWITCH
~

HIGH SPEED TRANSFER SYSTEM BATTERY


HSTS

3P 3P
ATS HSBT HIGH SPEED BUS TRANSFER
NC
01BHA17
**
380V 3Ph+N, 60Hz, 2000A 40kA/1s 4P

NO
**
380V 3Ph+N, 60Hz, 2000A 40kA/1s 01BHB17
NC

SCOPE LIMITS INTERLOCK


27 27

CABLE ELECTRICAL INTERLOCKING


I I
BUS DUCT

PROTECTION RELAY FUNCTIONS (IN ACCORDANCE WITH ANSI STANDARD)


PACKAGE PACKAGE PACKAGE PACKAGE
OR LCP OR LCP OR LCP OR LCP

25 SYNCHRO CHECK RELAY 51N TIME DELAY EARTH FAULT RELAY


PROCESS SIDEM UTILITIES SIDEM UTILITIES PROCESS
26Q THERMOSTAT (2 THRESHOLDS) 51R ANTI-STALL PROTECTION
26W WINDING TEMPERATURE RELAY 59 OVER VOLTAGE RELAY
27 UNDER VOLTAGE RELAY 59N NEUTRAL OVER VOLTAGE RELAY
32 DIRECTIONAL POWER 63B BUCHHOLZ
37 UNDER CURRENT RELAY 63P PRESSURE RELIEF DEVICE FOR TR MAIN TANK
H 40 FIELD RELAY / LOSS OF EXCITATION GROUND PROTECTION RELAY
H
64
48/51L LOCKED ROTOR RELAY 64REF RESTRICTED EARTH FAULT RELAY
49 THERMAL OVERLOAD RELAY 66 STARTS LIMIT RELAY
46 REVERSE PHASE / PHASE BALANCE RELAY Ac DIRECTIONAL OVER CURRENT RELAY
67
50 INSTANTANEOUS OVERCURRENT RELAY OIL LEVEL RELAY
71Q
50BF BREAKER FAILURE 86 LOCKOUT RELAY

87B DIFFERENTIAL BUS BAR PROTECTION RELAY


50G INSTANTANEOUS EARTH FAULT RELAY

50N INSTANTANEOUS NEUTRAL OVERCURRENT RELAY 87T DIFFERENTIAL PROTECTIVE RELAY TRANSFORMER

51 TIME DELAY OVERCURRENT RELAY 87M DIFFERENTIAL PROTECTIVE RELAY MOTOR

51G TIME OVERCURRENT GROUND RELAY


G
110Vdc 110Vdc
G
NOTES

1. Short circuit power supply values from Upstream plant (To be defined).
Lead Acid Lead Acid 2. This drawing shows only typical feeders arrangement.

F
01BRA20 230Vac, 60Hz, Ph+PE+N 230Vac, 60Hz, Ph+PE+N 01BRB20
F
*Main SWITCHGEAR SHORT-CIRCUIT VALUE CAN BE EQUAL OR GREATER THAN 40kA ACCORDING TO SHORT-CIRCUIT
CALCULATION NOTE. TO BE CONFIRMED DURING DETAIL ENGINEERING.
** MV SWITCHGEAR SHORT-CIRCUIT VALUE SHALL BE CONFIRMED DURING DETAIL ENGINEERING ACCORDING TO UPSTREAM
SHORT-CIRCUIT LEVEL

REFERENCE DOCUMENTS
DCS SUBDISTRIB. DCS E
CONTROL FOR CONTROL
-P9443-SID-4000EL-ZZZ401 ELECTRICAL CONSUMERS LIST
INSTRUMENTS
E
SUBDISTRIB.
FOR
INSTRUMENTS

01BVA20 110Vdc 110Vdc 01BVB20

D
B UPDATE 11/03/2024 CBO GJE RSM

MV SWITCHGEAR LV SWITCHGEAR MV SWITCHGEAR LV SWITCHGEAR A FIRST ISSUE 05/03/2024 CBO GJE RSM
CONTROL VOLTAGE CONTROL VOLTAGE CONTROL VOLTAGE CONTROL VOLTAGE REV NATURE OF REVISION DATE DRAWN CHECKED APPROVED

H I

C
SIDEM
C PARTNER 01BHT16
01BHT15 13,8kV / 0,4 kV
63 B 26 Q 63 B 26 Q
13,8kV / 0,4 kV 3150kVA
63 P 26 W 63 P 26 W
3150kVA

3P 3P
ATS
B

B
NC
01BHA18
*
380V 3Ph+N, 60Hz, 5000A 80kA/1s 4P

NO
*
380V 3Ph+N, 60Hz, 5000A 80kA/1s 01BHB18
NC
1, Rue GIOVANNI BATTISTA PIRELLI - BÂT A, 94417 SAINT-MAURICE CEDEX, FRANCE

' +33 1 49 95 76 76 7 +33 1 49 95 76 95


27 27
e-mail : contact@sidem-fr.com

JUBAIL 4&6
SCALE
KEY ONE LINE DIAGRAM
PACKAGE
OR LCP
PACKAGE
OR LCP - N/A
LIGHTING PANEL PARTNER UTILITIES HVAC PANEL PARTNER UTILITIES LIGHTING PANEL HVAC PANEL
PROJECT NUMBER DOCUMENT NUMBER REVISION POI FORMAT A

A P 9443 SID-4000ER-ZZZ001 B PRE A1


This document is the property of SIDEM. It cannot be used, reproduced,transmitted and/or disclosed, without prior written permission of SIDEM.

FILE: -