S6L1M-F4 Wdg.07 - Technical Data Sheet
S6L1M-F4 Wdg.07 - Technical Data Sheet
S6L1M-F4 Wdg.07 - Technical Data Sheet
STAMFORD industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant
section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and
AS1359. Other standards and certifications can be considered on request.
Quality Assurance
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
Page 1 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
Electrical Data
Insulation System H
Stator Winding Double Layer Concentric
Winding Pitch 2/3
Winding Leads 6
Winding Number 07
Number of Poles 4
IP Rating IP23
Page 2 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
1 Bearing 2 Bearing
SAE Adaptor SAE0,1 SAE0,1
Moment of Inertia 23.475 kgm² 22.95 kgm²
Weight Wound Stator 1098kg 1098kg
Weight Wound Rotor 966kg 924kg
Weight Complete Alternator 2326kg 2269kg
Shipping weight in a Crate 2369kg 2312kg
Packing Crate Size 170x90x153(cm) 170x90x153(cm)
Maximum Over Speed 2250 RPM for two minutes
Bearing Drive End - BALL 6224
Bearing Non-Drive End BALL 6317 BALL 6317
Page 3 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
60Hz
Page 4 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
PF Factor
< 0.5 1 For voltage rise multiply voltage dip by 1.25
0.5 0.97
0.6 0.93
0.7 0.9
0.8 0.85
0.9 0.83
Page 5 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
60Hz
Page 6 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
480V/60Hz
Page 7 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
S6L1M-F4 Wdg.07
De-Rates
All values tabulated above are subject to the following reductions:
- 5% when air inlet filters are fitted
- 3% for every 500 meters by which the operating altitude exceeds 1000 meters above mean sea level
- 3% for every 5°C by which the operational ambient temperature exceeds 40°C
- For any other operating conditions impacting the cooling circuit please refer to applications
Note: Requirement for operating in an ambient exceeding 60°C and altitude exceeding 4000 meters must be
referred to applications.
Note: Continuous development of our products means that the information contained in our data sheets can
change without notice, and specifications should always be confirmed with Cummins Generator
Technologies prior to purchase.
Page 8 S6L1M-F4_Wdg.07_A061J554_Rev.A_23.10.2018
Follow us @stamfordavk
news.stamford-avk.com