Ficha Tecnica 4100 3109 - 1
Ficha Tecnica 4100 3109 - 1
Ficha Tecnica 4100 3109 - 1
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
EYE SAFETY HAZARD Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do
not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
SULFURIC ACID WARNING Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can destroy fabric.
Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with sulfuric acid, immediately
flush skin or eyes with water for 15 minutes and seek immediate medical attention.
FCC RULES AND REGULATIONS – PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system
operation verified.
NFPA 72® is a registered trademark of the National Fire Protection Association.
Introduction
The IDNet 2* card provides the Fire Alarm Control Panel (FACP) with one
isolated IDNet Signaling Line Circuit (SLC) (or channel) and with up to
four isolated loop outputs. This card is used with compatible** IDNet
and MAPNET II communicating devices and allows the system CPU to
communicate with up to 250 initiating devices, such as smoke sensors and
pull stations. Isolated IDNet communications provide overall operation
improvement, and isolated output loops allow a short circuit on one loop
to avoid impacting the other loops.
IDNet 2 Card IDNet 2+2 Card
There are two available configurations for the IDNet 2 card:
• 4100-3109 IDNet 2 card: This is the basic configuration which provides
the FACP with two Class B (or Class A) loop outputs that are isolated
from each other as well.
• 4100-3110 IDNet 2+2 card: In this configuration, the 4100-3109 IDNet IDNet Loop Card
2 card is fitted with two 4100-3111 IDNet Loop cards and provides the
FACP with four Class B (or Class A) isolated IDNet loops. Two isolated
loops are provided by the card and one isolated loop is added per IDNet
Loop card.
*= Unless specified otherwise, the term “IDNet 2” is used in this manual to
designate both the IDNet 2 and the IDNet 2+2 cards.
Note: The 4100-3111 IDNet Loop daughter card can be purchased separately and placed on a pre-installed IDNet 2 card that is not EPS-mounted.
However, once it is added to the IDNet card, the compatibility and programming requirements will become the same as with the IDNet 2+2 card.
Important: Verify FACP system programmer, executive, and slave software compatibility when installing, or replacing system components. Refer to the
Technical Support Information and Downloads website for compatibility information.
579-1169 Rev E
*05791169E*
4100-3109 IDNet 2, 4100-3110 IDNet 2+2 and 4100-3111 IDNet Loop card Installation Instructions
Card Layout
Compatibility
Hardware compatibility:
IDNet 2: 4100ES bays, EPS modules, 4100U bays.
IDNet 2+2: 4100ES bays, 4100U bays, ES-PS modules.
Software compatibility:
For use with revision 2.04 or higher of the ES Panel Programmer Software, and revision 12.08 of the 4100U Programmer and Master software.
** = Refer to IDNET and MAPNET II Addressable Device Communications Compatibility Chart S4090-0011
Card Layout
The IDNet 2 is a standard 4x5 card that can accommodate two IDNet Loop cards. Figure 1 highlights the feature elements of these cards.
B+ B- S A+ A- B+ B- S A+ A-
LOOP B
Class A/B IDNet Terminal
Jumper (P2) Block (TB1)
IDNet Loop Card
Connector Class A/B
(LOOP D) Jumper (P1)
1 2 3 4 5 6 7 8
(SW1)
LEDs
IDNET 2 IDNET 2
LED Identification
The IDNet 2 Card is equipped with 8 LEDs that report the card troubles. Table 1 identifies and describes the different LEDs.
Table 1: LED Definition
LED Name LED description LED Map
Loop A When a trouble occurs on a loop, the LED corresponding to that loop
Loop B illuminates.
Loop C
Loop D
Earth- Normally Off. Illuminates to indicate a negative earth fault.
A
Earth+ Normally Off. Illuminates to indicate a positive earth fault.
IDNet Normally off. Illuminates to indicate a problem with the IDNet channel:
B
LOOP
• Steady on indicates channel failure.
Comms Normally off. Turns on steady if the card is not communicating with the
FACP CPU.
C
TROUBLES
ON
OFF 1 2 3 4 5 6 7 8
SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8
Address
1 ON N O ON N O ON ON OFF 61 ON OFF OFF OFF OFF ON OFF
2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON
3 ON N O ON N O ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF
4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON
5 ON N O ON N O OFF ON OFF 65 OFF ON ON N O N O ON OFF
6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON
7 ON N O ON N O OFF OFF OFF 67 OFF ON ON N O N O OFF OFF
8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON
9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF
10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON
11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF
12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON
13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF
14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON
15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF
16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON
17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF
18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON
19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF
20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON
21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF
22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON
23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF
24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON
25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF
26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON
27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF
28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON
29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF
30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON
31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF
32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON
33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF
34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON
35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF
36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON
37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF
38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON
39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF
40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON
41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF
42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON
43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF
44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON
45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF
46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON
47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF
48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON
49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF
50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON
51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF
52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON
53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF N O N O ON OFF
54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON
55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF N O N O OFF OFF
56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON
57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF
58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON
59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF
60 ON OFF OFF OFF OFF ON ON
Installation
Mounting
The IDNet 2 card and the IDNet 2+2 card mount onto the Power Distribution Interface (PDI) in an FACP expansion cabinet. The IDNet 2 card can also
be installed in the expansion slot of an ES Power Supply Card (ES-PS) card.
To mount the IDNet 2 and IDNet 2+2 card:
1. Select an empty PDI connector. Insert the washer and the metal standoffs into the corresponding installation holes.
2. Insert the PDI connector on the back of the card into the PDI connector.
3. Use the provided hardware to secure the card.
Washers
PDI
#6 Screws
Standoffs
PDI Connector
(Reverse Side)
Note: When adding IDNet Loop cards to a pre-installed IDNet 2 card, it is important to remember that the properties of the IDNet 2 card must be
updated in the FACP programmer.
Plastic Snap-In
Standoff
Metal
Standoffs
#6 Screw
Connector
(Reverse Side)
IDNet Loop Card IDNet 2 Card
IDNet 2 Card
IDNet Loop Card
Wiring Overview
Each IDNet output from the IDNet 2 or IDNet Loop cards can be wired as a either an isolated Class A circuit or as two isolated Class B circuits.
Class A wiring provides an alternate communication path that allows communication to all devices to be maintained when a single open circuit
fault occurs. Class A wiring requires two wires to be routed from the IDNet 2 Primary Terminals (B+, B-) to each device, and then back to the IDNet
Secondary Terminals (A+, A-). Wiring is in/out, “T” tapping is not allowed.
Class B wiring allows “T” tapping. IDNet wiring is inherently supervised due to individual device level communications. End-of-line resistors are not
required.
Wiring Parameters
Table 2 identifies the card wiring parameters that must be considered when installing these cards.
Table 2: Card Wiring Parameters
Wiring Capacitance Parameters
Parameter Value
Maximum Supported Channel Capacitance; Total of all four Isolated The sum of line-to-line capacitance, plus the capacitance of either line-to-shield
Outputs. (if shield is present) = 0.6 μF (600 nF).
Capacitance between IDNet SLC wiring (between wires of the same 1 μF maximum (this is for multiple IDNet loops).
polarity; plus to plus, minus to minus).
Wiring Distance Limits (see note below).
Channel Loading Class B Wiring, Total Channel Wiring Parameters, Class A Wiring, Total Channel Wiring
Including T-Taps Parameters
Up to 125 devices 126 to 250 devices Up to 125 devices 126 to 250 devices
Total Loop Resistance 50 Ω maximum 35 Ω maximum 50 Ω maximum 35 Ω maximum
18 AWG (0.82 mm2) 4000 ft (1219 m) per run, 2500 ft (762 m) per run, 4000 ft (1219 m) per loop, 2500 ft (762 m) per loop,
12,500 ft (3810 m) total 10,000 ft (3048 m) total 12,500 ft (3810 m) total 10,000 ft (3048 m) total
16 AWG (1.31 mm2) 5000 ft (1524 m) per run, 2500 ft (762 m) per run, 5000 ft (1524 m) per loop, 2500 ft (762 m) per loop,
14 AWG (2.08 mm2) 12,500 ft (3810 m) total 10,000 ft (3048 m) total 12,500 ft (3810 m) total 10,000 ft (3048 m) total
12 AWG (3.31mm2)
Note: Maximum wiring distance is determined by either reaching the maximum resistance, the maximum capacitance, or the stated maximum dis-
tance, whichever occurs first. Class A maximum distances are to the farthest device on the loop from either “B” or “A” terminals. For Class B wiring, the
maximum distance to the farthest device is limited to the stated Class A wiring distances.
Wiring Considerations using 2081-9044 Note: External wiring must be shielded (for lightning suppression) and 2081-9044 Overvoltage Protectors
Overvoltage Protectors. must be installed at building exit and entrance locations.
(2081-9044 is UL listed to Standard Capacitance: Each protector adds 0.006 μF across the connected line.
1459, Standard for Telephone Resistance: Each protector adds 3 Ω per line of series resistance; both IDNet lines are protected; 6 Ω per
Equipment). protector will be added to total loop resistance.
Maximum distance of a single protected wiring run is 3270 ft (1 km).
Refer to document number 574-832: 2081-9044 Overvoltage Protector Installation Instructions for additional
information.
Class A Wiring
To wire the Loop terminals as a Class A circuit:
1. Set the jumper assigned to the loop to the “A” position, as shown in Figure 6.
- Loop A= Jumper P1 on the IDNet 2 card
- Loop B= Jumper P2 on the IDNet 2 card
- Loop C= Jumper P1 on the first IDNet Loop cards
- Loop D= Jumper P1 on the second IDNet Loop card
2. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield to
prevent it from coming in contact with other components. Metallic continuity of the shield must be
maintained and insulated throughout the entire length of the cable.
3. Route the wiring from the Primary Terminals (B+, B-) to the corresponding inputs on the first device.
4. Route wiring from the first device to the next as in/out. See Figure 7. Repeat for each device.
5. Route the wiring from the last device to the panel.
6. Connect the wiring to the corresponding Secondary Terminals (A+, A-).
Figure 6: Class A Jumper Setting
Devices
1 2 1 2 1 2
+
18 to 12 AWG
IDNet 2 Card
1. Set the jumper assigned to the loop to the “B” position, as shown in Figure 8.
- Loop 1 = Jumper P1 on the IDNet 2 card
- Loop 2 = Jumper P2 on the IDNet 2 card
- Loop 3 = Jumper P1 on the left IDNet Loop card
- Loop 4 = Jumper P1 on the right IDNet Loop card
2. Route wiring from the Primary Terminals (B+, B-) to the corresponding inputs on the first device.
It is possible to add up to 4 circuits per IDNet loop on the terminal block when using Class B wiring. See
Figure 9 for the diagram.
3. Route wiring from the first device to the next as in/out as shown in Figure 9. Repeat for each device.
4. Shielded wire is not recommended. If shielded wires are present, cut and tape off the shield at each
end (in the panel and at the last device in each run) to prevent it from coming in contact with other Figure 8: Class B Jumper Setting
components. Metallic continuity of the shield must be maintained and insulated throughout the entire
length of the cable.
Devices
2
IDNet CIRCUIT A 4
B+, B- B+ B- A+ A-
Terminals
TB1
B+ B- A+ A- B+ B- A+ A-
2 Circuit Configuration 4 Circuit Configuration
Programming
Adding the IDNet 2 to the Programmer
The IDNet 2 card must be added to the FACP through the ES Panel Programmer. For information on general programming instructions consult the
579-849 ES Panel Programmer.
Note:
The IDNet 2+2 card can be added to the programmer using the same steps as shown below. The difference is in selecting the 4100-3110/4100-3112
IDNet 2+2 card from the Available Hardware window instead of the 4100-3109 IDNet 2 card.
Troubleshooting
Troubleshooting
Refer to the tables below for a list of error messages that may appear on the FACP display when using the IDNet 2 card:
Table 3: Trouble Messages
Trouble Message Possible Cause
Extra Device Appears if one or more extra devices (i.e., devices that have not been configured for the IDNet channel) are found on
the system, or if a device is at an incorrect address.
Note: An extra device on address 253 or 254 indicates that a Loop Module has been detected but not programmed.
Only one trouble message appears, regardless of the number of extra devices found. Viewing the trouble log reveals
the extra device address. Devices with LEDs will light their LED steady to indicate the trouble as long as no alarms are
present in the system.
Wrong Device Appears when the device detected at the address does not match what is programmed in the system.
Earth Fault Search Appears while the IDNet 2 card is searching for earth faults on the IDNet channel. When this message is displayed, the
IDNet1+ card cannot show any alarms or other statuses.
Channel Fail Appears when devices have been configured, but none of the devices are communicating on the channel. This
message does not appear if there are no configured devices on the IDNet channel.
No Answer Appears when a device is missing, damaged, improperly configured,
or duplicate devices are present.
Note: A No Answer trouble on address 253 or 254 indicates a loop module has been programmed but not detected.
Bad Answer Appears when there is a faulty device, a noisy communications channel, or duplicate devices are present.
Output Abnormal Occurs during any of these conditions:
• When 24 V is not present on IDNet devices (MBZAM and MAZAM devices for example).
• When TrueAlarm sensor bases with relay driver outputs are not properly supervised.
• When isolator devices are in isolation mode.
Note: Additional troubleshooting information about duplicate devices, weak answers and other problems may be obtained through panel diagnostics.
Card Specifications
Card Specifications
Table 5: IDNet 2 Card Specifications
Operating Conditions:
Operating Temperature Range o o o
32 F - 120 F (0 C-49 C).
o
579-1169 Rev E