Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Omniksol 1PH 5 6 TL3 - Manual - EN

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

User Manual V1.

User Manual
-Installation
-Operation

Omniksol-5k-TL3
Omniksol-6k-TL3

Omnik New Energy Co., Ltd.


Catalog
1. Notes on this manual.................................................................................................................... 3
1.1 Scope of Validation ................................................................................................................................3
1.2 Symbols Used .........................................................................................................................................3
1.3 Target Group............................................................................................................................................4
2. Preparation.................................................................................................................................... 5
2.1 Safety Instructions .................................................................................................................................5
2.2 Explanations of Symbols on Inverter................................................................................................6
3. Product Information...................................................................................................................... 7
3.1 Overview ...................................................................................................................................................7
3.2 Major Characteristics ............................................................................................................................8
3.3 Datasheet ..................................................................................................................................................9
4. Packing checklist........................................................................................................................ 11
4.1 Assembly parts .....................................................................................................................................11
4.2 Product Appearance ............................................................................................................................12
4.3 Product Identification ..........................................................................................................................13
4.4 Further Information ..............................................................................................................................13
5. Installation................................................................................................................................... 14
5.1 Safety .......................................................................................................................................................14
5.2 Mounting Instructions .........................................................................................................................15
5.3 Safety Clearance ...................................................................................................................................16
5.4 Mounting Procedure ............................................................................................................................17
5.5 Safety lock ..............................................................................................................................................18
6. Electrical Connection ................................................................................................................. 19
6.1 Safety .......................................................................................................................................................19
6.2 AC Side Connection ............................................................................................................................19
6.3 DC Side Connection ............................................................................................................................21
7. Display ......................................................................................................................................... 26
7.1 LCD Panel ...............................................................................................................................................26
7.2 LCD Display ...........................................................................................................................................27
7.3 Instructions of Safety Standard selection when power-up .......................................................29
1
7.4 State Information ..................................................................................................................................30
8. Communication Setting.............................................................................................................. 31
8.1 GPRS Card .............................................................................................................................................31
8.2 Installation of GPRS/WiFi card .........................................................................................................32
8.3 Register on monitoring website .......................................................................................................35
8.4 Login monitoring System ...................................................................................................................38
8.5 WiFi card .................................................................................................................................................43
8.6 Netwoek Settings..................................................................................................................................44
8.7 Ethernet Card ........................................................................................................................................53
8.8 Installation of Ethernet card ..............................................................................................................54
8.9 RS485 card .............................................................................................................................................56
9. Recycling and Disposal.............................................................................................................. 61
10. Troubleshooting ......................................................................................................................... 62
11. Abbreviation................................................................................................................................ 64
12. Contact ........................................................................................................................................ 65

2
1. Notes on this manual
1.1 Scope of Validation
The main purpose of this User’s Manual is to provide instructions and detailed procedures
for installing, operating, maintaining, and troubleshooting the following three types of Omnik
Inverters:
 Omniksol-5k-TL3
 Omniksol-6k-TL3
Please keep this user manual all time available in case of emergency.
1.2 Symbols Used

DANGER

DANGER indicates a hazardous situation which, if not


avoided, will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not


avoided, can result in death or serious injury or moderate injury.

CAUTION

CAUTION indicates a hazardous condition which, if not avoided,


can result in minor or moderate injury.

3
NOTICE

NOTICE indicates a situation that can result in property


damage, if not avoided.

1.3 Target Group


• Chapter 1, 2, 3, 4, 7, 8, 9, 10, 11 and Chapter 12 are intended for anyone who is
intended to use Omnik Grid Tie Solar Inverter. Before any further action, the operators
must first read all safety regulations and be aware of the potential danger to operate
high-voltage devices. Operators must also have a complete understanding of this
device’s features and functions.

WARNING

Do not use this product unless it has been successfully installed


by qualified personnel in accordance with the instructions in
Chapter 5, “Installation”.

• Chapter 5 and Chapter 6 are only for qualified personnel who are intended to install
Or uninstall the Omnik Grid Tie Solar Inverter.

NOTICE

Hereby qualified personnel means he/she has the valid license


from the local authority in:
• Installing electrical equipment and PV power systems
(up to 1000 V).
• Applying all applicable installation codes.
• Analyzing and reducing the hazards involved in
performing electrical work.
• Selecting and using Personal Protective Equipment
(PPE).

4
2. Preparation
2.1 Safety Instructions

DANGER

DANGER due to electrical shock and high voltage DO


NOT touch the operating component of the inverter, it might
result in burning or death. TO prevent risk of electric shock
during installation and maintenance, please make sure that
all AC and DC terminals are plugged out. DO NOT stay close
to the instruments while there is severe weather conditions
including storm, lighting etc.

WARNING

The installation , service , recycling and disposal of the


inverters must be performed by qualified personnel only in
compliance with national and local standards and
regulations. Please contact your dealer to get the
information of authorized repair facility for any maintenance
or repairmen.

Any unauthorized actions including modification of product


functionality of any form will affect the validation of warranty
service; Omnik may deny the obligation of warranty service
accordingly.

NOTICE

Public utility only


The PV inverter designed to feed AC power directly into the
public utility power grid,do not connect AC output of the
device to any private AC equipment.

5
CAUTION

The PV inverter will become hot during operation; please


don’t touch the heat sink or peripheral surface during or
shortly after operation。Risk of damage due to improper
modifications. Never modify or manipulate the inverter or
other components of the system.

2.2 Explanations of Symbols on Inverter

Symbol Description

Dangerous electrical voltage


This device is directly connected to public grid, thus all
work to the inverter shall only be carried out by
qualified personnel.
DANGER to life due to high electrical voltage!
There might be residual currents in inverter because
of large capacitors. Wait 10 MINUTES before you
remove the front lid.
NOTICE, danger!
This device directly connected with electricity
generators and public grid.
Danger of hot surface
The components inside the inverter will release a log
of heat during operation, DO NOT touch aluminum
housing during operating.
An error has occurred
Please go to Chapter 10 “Trouble Shooting” to remedy the
error.

This device SHALL NOT be disposed of in


residential waste
Please go to Chapter 9 “Recycling and Disposal” for
proper treatments.
Without Transformer
This inverter does not use transformer for the isolation
function.

6
CE Mark
Equipment with the CE mark fulfils the basic
requirements of the Guideline Governing Low-Voltage
and Electromagnetic Compatibility.
No unauthorized perforations or modifications
Any unauthorized perforations or modifications are
strictly forbidden, if any defect or damage
(device/person) is occurred, Omnik shall not take any
responsibility for it.

3. Product Information
3.1 Overview
• Industrial Layout

7
• Excellent Heat Elimination

3.2 Major Characteristics


Omnik inverter has following characteristics which make Omnik inverter “High Efficiency,
High Reliability, High Cost Effective Ratio”

• Wide DC input voltage and current ranges, enables more PV panels connected.
• Wide MPP voltage range ensure high yield under various weather conditions.
• High MPP tracking accuracy, ensure the minimum power loses during converting.
• Complete set of protection methods.

Also, following protection methods are integrated in Omnik inverter:

• Internal overvoltage
• DC insulation monitoring
• Ground fault protection
• Grid monitoring
• Ground fault current monitoring
• DC current monitoring
• Integrated DC switch

8
3.3 Datasheet
Type Omniksol-5k-TL3 Omniksol-6k-TL3
Input(DC)
Max. PV Module Power [W] 6000 7200
Max. DC Voltage [V] 580 580
Nominal DC Voltage [V] 360 360
Operating MPPT Voltage
120 - 500 120 - 500
Range [V]
MPPT Voltage Range at
270 - 500 320 - 500
Nominal Power [V]
Start up DC Voltage [V] 150 150
Turn off DC Voltage [V] 120 120
Max. DC Current[A] A : 10 / B : 10 A : 10 / B : 10
Max. Short Circuit Current [A] A : 14 / B : 14 A : 14 / B : 14
Max. inverter back feed current
A:0/B:0 A:0/B:0
to the array [A]
Number of MPP trackers A:1/B:1 A:1/B:1
Number of DC Connection A:1/B:1 A:1/B:1
DC Connection Type Amphenol Connector Amphenol Connector
Output(AC)
Max. AC Apparent Power [VA] 5000 6000
Nominal AC Power [W] 5000 6000
Nominal Grid Voltage [V] 220 / 230 / 240 220 / 230 / 240
Nominal Grid Frequency [Hz] 50 / 60 50 / 60
Max. AC Current [A] 25 30
Maximum output fault
26 31
current[A]
Maximum output protection
28 33
current [A]
Grid Voltage Range [V]* 185 - 276 185 - 276
Grid Frequency Range [Hz]* 45 - 55 / 55 - 65 45 - 55 / 55 - 65
Power Factor 0.9i - 0.9c 0.9i - 0.9c
Total Harmonic Distortion
<3% <3%
(THD)
Night time Power Consumption
<1 <1
[W]
AC Connection Type Terminal Blocks Terminal Blocks
Efficiency
Max. Efficiency 98.1% 98.1%
Euro Efficiency 97.3% 97.3%
MPPT Efficiency 99.9% 99.9%

9
Safety and Protection
Array ground insulation resistance monitoring Output over current protection
Residual current monitoring
Array polarity reverse protection Output over/under voltage protection
Surge protection
Protection Functions
Array over voltage protection Output over/under frequency protection
Anti-island protection
Array over current protection Output short circuit protection
Over temperature protection
Protection Class Ⅰ(According to IEC 62103)
Overvoltage Category PV Ⅱ / Mains Ⅲ(According to IEC 62109-1)
Reference Standard
Safety Standard IEC/EN 62109-1,IEC/EN 62109-2
EN 61000-6-1,EN61000-6-3,EN 61000-6-2,EN61000-6-4,EN61000-3-2,EN 61000-3-
EMC Standard
3
VDE-AR-N 4105,VDE 0126-1-1,C10/11, G59/3,CEI 0-21
Grid Standard
EN50438,NB/T32004,IEC62116,IEC61727,IEC61683,IEC60068
Physical Structure
Dimensions (WxHxD) [mm] 343 * 425 * 136
Weight [kg] 17.3
Environmental Protection
IP 65(According to IEC 60529)
Rating
Cooling Concept Natural convection
Mounting Information Wall bracket
General Data
Operating Temperature Range
-25 to +60(derating above 45℃)
[℃]
Relative Humidity 0% to 100%,no condensation
Max. Altitude (above sea level)
2000
[m]
Noise Level [dB] <40
Environmental Category Rating Outdoor, suitable to wet locations
Pollution class III
UV resistance Yes
Isolation Type Transformerless
Display 2 LED,Backlight,2 * 16 Character LCD
Data Communication
RS485 / WiFi / GPRS optional
Interfaces
Guarantee 5 - 25 years optional
*The AC voltage and frequency range may vary depending on specific country grid

10
4. Packing checklist
4.1 Assembly parts
After you receive the Omnik inverter, please check if there is any damage on the carton,
and then check the inside completeness for any visible external damage on the inverter or any
accessories. Contact your dealer if anything is damaged or missing.

A B C D

E F G H

Object Quantity Description

A 1 Omnik inverter

B 2 pair DC connector

C 1 AC connector

D 4 Screw (ST6×50)

E 4 Expansion tube

F 1 User manual

G 1 Installation position scale

H 1 Wall mounting bracket

11
4.2 Product Appearance
• Front
A

B C

Object Description
A LED light(Green) – RUN
B LED light(Red) – FAULT
C Function key for displays and choice of language

• Bottom

A B C D

Object Description
A DC switch
B Plug connectors for DC input.
C WiFi/GPRS/RS485 interface
D Terminal for grid connection (AC output)

12
4.3 Product Identification
You can identify the inverter by the side nameplate. Information such as type of the
inverter and inverter specifications are specified on the side name plate. The name plate is on
the middle part of the right side of the inverter housing. And the following figure is the side
name plate example as on Omniksol-6k-TL3.

4.4 Further Information


If you have any further questions concerning the type of accessories or installation, please
check our website www.omnik-solar.com or contact our service hotline.

13
5. Installation
5.1 Safety

DANGER

DANGER to life due to potential fire or electricity shock.


DO NOT install the inverter near any inflammable or
explosive items. This inverter will be directly connected with
HIGH VOLTAGE power generation device; the installation
must be performed by qualified personnel only in
compliance with national and local standards and
regulations.

NOTICE

NOTICE due to the inappropriate or the harmonized


installation environment may jeopardize the life span
of the inverter.
Do not expose to direct sunlight to avoid power derating due
to increase in the internal temperature of the inverter.
Do not expose to rain and snow cover to enhance inverter life
time.
The installation site MUST have good ventilation condition.

14
5.2 Mounting Instructions

Max 15°

• Omnik inverter is designed for indoors and outdoors installation


• Please mount the inverter in the direction as illustrated above
• Install the inverter in the vertical direction is recommended, with a max.15 degrees
backwards.
• For the convenience of checking the LCD display and possible maintenance activities,
please install the inverter at eye level.
• Make sure the wall you selected is strong enough to handle the screws and bear the
weight of the inverter
• Ensure the device is properly fixed to the wall
• It is not recommended that the inverter is exposed to the strong sunshine, because the
excess heating might lead to power reduction
• The ambient temperature of installation site should be between -25 °C and +60 °C
• Make sure the ventilation of the installation spot, not sufficient ventilation may reduce the
performance of the electronic components inside the inverter and shorten the life of the
inverter

15
5.3 Safety Clearance
Observe the following minimum clearances to walls, other devices or objects to guarantee
sufficient heat dissipation and enough space for pulling the electronic solar switch handle.

Direction Minimum clearance


Above 30 cm
Below 40 cm
Sides 10 cm

16
5.4 Mounting Procedure
1. Mark 4 positions of the drill holes on the wall according to the wall mounting bracket in the
carton box.

2. First, according to the marks, drill 4 holes in the wall. Then, place 4 expansion tubes in the
holes using a rubber hammer. Next, make 4 screws through the mounting holes in the
bracket, then tighten the screws into the expansion tubes. So far, the wall mounting bracket
is fixed already.

3. Align both sides of the radiator on the hooks of the back panel, move the inverter until the
hooks completely into the slot of the radiator.

17
5.5 Safety lock
After the inverter is hanging up on the bracket, lock up the device and the bracket together
at the Lower Left Corner of the inverter (as the picture showed below).

Padlock

Recommended padlock dimension:

A φ
A.Shackle Diameter 5~7 mm
C
B B.Vertical Clearance 8~15 mm

C.Horizontal Clearance 12~20 mm

Stainless, solid hanger and secured lock cylinder

NOTICE

For further maintenance and possible repair, please keep the key
of the padlock in a safe place.

18
6. Electrical Connection
6.1 Safety

DANGER

DANGER to life due to potential fire or electricity shock. With


the inverter powered, comply with all prevailing national
regulations on accidents prevention. This inverter will be
directly connected with HIGH VOLTAGE power generation
device; the installation must be performed by qualified
personnel only in compliance with national and local
standards and regulations.

NOTICE

Electrical connections shall be carried out in accordance with


the applicable regulations, such as conductor sections, fuses,
PE connection.

6.2 AC Side Connection

DANGER

DANGER to life due to potential fire or electricity shock.

NEVER connect or disconnect the connectors under load.

6.2.1 Integrated RCD and RCM


The inverter is equipped with integrated RCD (Residual Current Protective Device) and
RCM(Residual Current Operated Monitor). The current sensor will detect the volume of the
leakage current and compare it with the pre-set value, if the leakage current exceeds the
permitted range, the RCD will disconnect the inverter from the AC load.

19
6.2.2 Assembly Instructions

NOTICE

Use 10-8AWG (6 – 10mm2) copper wire for all AC wiring


connections to Omnik inverter. Use only solid wire or stranded
wire.

NOTICE

Use a residual current protective device (residual


operating current: 100mA).

In order to reduce the line loss of AC side (no more than 1% of Pout), Omnik suggest that
the length of AC cable from the inverter to the distribution box should not exceed the limit
below.

Model Rated current Length of cable


2
6 mm 10 mm2
Omniksol-5k-TL3 21.7A 18m 30m
Omniksol-6k-TL3 26A 15m 25m

1) Strip the cable 12mm


12mm

2) Insert the striped cable into cord end terminal and insert the assembly into barrel.

20
3) Then the line will like the picture below.

4) Insert the finished 5 lines into AC cover assembly with the following sequence:

5) Open the plastic cover, use slot type screwdriver to press the shrapnel in the
indicated position, and then put the line in the right hole, please note the sequence
of the line shall in the right order: N,L,PE

6) Cover the assembly, tightly screwed and then screw the cable gland.

6.3 DC Side Connection

DANGER

DANGER to life due to potential fire or electricity shock.

NEVER connect or disconnect the connectors under load.

21
DANGER

NEVER connect the ground lead of PV module to the


inverter.

For Omniksol-5k/6k-TL3, there are two MPP Trackers, and the DC characteristics of the
mare illustrated as the following table.
MPP Max. DC Max. DC Max. DC
Inverter Type Tracker Power Voltage Current
Omniksol-5k-TL3 6000W 580V 10A /10A
2
Omniksol-6k-TL3 7200W 580V 10A /10A

In order to reduce the line loss of DC side (no more than 1% of Pin), Omnik suggest that
the length of DC cable for each cable section should not exceed the limit below.
Length of cable
Model
2.5 mm2 4 mm2
Omniksol-5k-TL3 50m 80m
Omniksol-6k-TL3 60m 96m

MC4 Assembly instructions

If, during self assembly, parts and tools other than those stated by MC are used or
if the preparation and assembly instructions described here are disregarded then neither
safety nor compliance with the technical data can be guaranteed.

For protection against electric shock, PV-connectors must be isolated from the
power supply while being assembled or disassembled.

The end product must provide protection from electric shock.

The use of PVC cables is not recommended.

Unplugging under load: PV plug connections must not be unplugged while under
load. They can be placed in a no load state by switching off the DC/AC converter or
breaking the DC circuit interrupter. Plugging and unplugging while under voltage is
permitted.

It is unadvisable to use non-tinned cables of type H07RN-F, since with oxidized


copper wires the contact resistances of the crimp connection may exceed the permitted
limits.
22
Disconnected connectors should be protected from dirt and water with sealing
caps.

Plugged parts are watertight IP67. They can’t be used permanently under water.
Do not lay the MC-PV connectors on the roof surface.

See the MC catalogue 2 Solar line for technical data and assembled parts.

PV-Female cable coupler PV-Male cable coupler

PV-KBT4 PV-KST4

17A(1,5mm2/14AWG)
Touch
Rated
protection, IP67/IP2X 22A(2,5mm2/ 12AWG)
current
mated/unmated
30A(4mm2,6mm2/ 10AWG)

-40℃...90℃ (IEC/CEI)
Ambient 1000V (IEC/CEI)
Rated
temperature -40℃ ...75℃(UL)
voltage 600V (UL)
range
-40℃ ...70℃(UL/AWG14)

Upper limiting
105°C (IEC/CEI) Safety class II
temperature

Tools required
(ill.1) Crimping tool incl. locator and built-in
crimping insert.
Type: PV-ES-CZM-18100
PV-ES-CZM-19100

(ill.2) Interchangeable crimping


inserts incl. hexagonal screwdriver A/F 2,5.
Type: PV-ES-CZM-18100
PV-ES-CZM-19100

(ill.3) Open-end spanner PV-MS 1 set = 2 pieces


Order No. 32.6024

23
(ill.4) PV-WZ-AD/GWD socket wrench insert to
tighten, Order No. 32.6006

(ill.5) PV-SSE-AD4 socket wrench insert to


secure PV-SSE-AD4, Order No. 32.6026

(ill.6) Open-end spanner A/F 15 mm

(ill.7) Torque screwdriver A/F 12 mm

(ill.8) Test plug PV-PST


Order No.: 32.6028

Cable preparation
(ill.9) Important: Cables with class 2, 5 or 6
construction can be connected. It is advantage-
ous to use tinned conductors. It is unadvisable to
use non-tinned cables of type H07RN-F, since
with oxidized copper wires the contact resistances
of the crimp connection may exceed the permitted
limits.

Check dimension b according to the following


table:

(ill.10) Strip cable insulation. L = 6-7, 5 mm. Take


care not to cut individual strands.
Recommended tool:
Stripping pliers PV-AZM, Order No.32.6027

24
Crimping
(ill.11) Notes to the operation of the crimping
pliers, see¬MA251-def (www.multicontact.com)

(ill.12) Push the crimped contact into the socket


resp. plug insulator until it engages. Pull lightly on
the lead to check that the metal part has
engaged.

Assembly control
(ill.13) Insert the test pin with the corresponding
side into the socket or plug to the end position. If
the contact is correctly assembled, the white
marking on the test pin
must be still visible.

(ill.14) Screw on the cable gland, hand-tight, with


the tools PV-MS. Or
Screw on the cable gland, with the tools PV-WZ-
AD/GWD and PV-SSE-AD4
In any case:
The tightening torque must be adapted to the
solar cables used in each specific case. Typical
values lie in a range between 2,5 Nm to 3 Nm.

Plugging and unplugging the cable coupler


without safety lock clip PV-SSH4

Plugging
(ill.15)
Plug the coupling together until they engage.
Check correct engagement by pulling on the
coupling.

Unplugging
(ill.16)
Compress the two snap-in springs (X) by hand or
with the PV-MS tool and separate the coupling.
Plugging and unplugging the cable coupler
without safety lock clip PV-SSH4

25
Refer to cable manufactures specification for minimum bending radius.

7. Display
7.1 LCD Panel

Object Description

A LED light(Green) – RUN


B LED light(Red) – FAULT
C Function key for displays and choice of language

The LCD panel is integrated in the front lid of the inverter, so it is easy for user to check
and set the data. In addition, the user can press the function key to illuminate the LCD screen.

NOTICE

Omnik inverter is not an aligned measuring instrument


for current, voltage or power consumption. A slight
deviation of a few percent points is intrinsic to the
system; the results from the inverter cannot be used for
grid balance calculations. An aligned meter will be
required to make calculations for the utility company.

26
7.2 LCD Display
The display content consists of 2 lines. The bottom line (Line 2) always displays the output
power (Pac = xxxx W). The top line (Line 1) shows current state information by default, and by
pressing function key it will display different operating information as the following flow chart
and table.
execution sequence name LCD example
1 Day total energy/kWh E-Today = xx.x kWh

2 Total energy/kWh E-Total = xxxxx kWh

3 PV Voltage/V Vpv = xxx.x V

4 PV Current/A Ipv = xx.x A

5 Grid voltage/V Vac = xxx.x V

6 Grid current/A Iac = xx.x A

7 Grid frequency/Hz Frequency = xx.x Hz

8 Models Omniksol-4k-TL3
9 Standard Italy

10 Version Version

11 Temperature Temperature

12 Language Language :English

13 S/N and IP address SN/IP

Date: 20xx-xx-xx
14 Time setting
Time : xx:xx:xx

15 Grid setting Set V/F Value

16 Protect setting Protect :xx

17 Coefficient setting Coefficient

18 Self Test(for Italy) Self Test

19 P(f)and Q(v) P(f)&Q(v)

20 Error Record Error Record

* Item 9 and 15 - 20 needs passwords. Contact your dealer or Omnik if you need to set them.

27
Short press the page can be performed. Long press to enter the page and setup.

Line 1 Description

Current state information: all possible content shows in the following table,
State information
reference to 7.4 for further information

E-today The energy generated today in kilo watt hours (kWh)

E-total The energy generated since starting up the inverter (kWh)

Vpv The present voltage of the solar generator

Ipv The present current of the solar generator

Vac The grid voltage

Iac The present grid current

Frequency The grid frequency

Model The model of the inverter

Standard Choose standard for different country, reference to 7.3 for further information

Version Long press to check the firmware version

Temperature Long press to check the temperature of the inverter

Language Long press to set language

SN/IP Long press to check S/N and IP address of the inverter

Date and Time Long press to set date and time

Grid setting Long press to set V/F value

Protect setting Long press to change protect settings

Coefficient setting Only used in factory

Self Test(for Italy) Long press to start self-test

P(f)and Q(v) Long press to set P(f)and Q(v) value

Error Record Long press to check error record

28
7.3 Instructions of Safety Standard selection when power-up
1. Attentions before the operation:

Only perform this operation when the accumulative generated electricity is less than 1kWh.

2. Operation steps are as following:

a) Power on the inverter with AC side connected.

Function button

b) Press the Function button until the first line of LCD displays “ Standard ” ,for example
“Italy”.

c) Hold the button for 5 seconds or more until the first line of LCD displays “Set”. Change
the standard by pressing the Function button one at a time.

d) When the LCD displays your desired Safety Standard, hold the Function button for 5
seconds or more until the first line of LCD shows ”Set OK”.

e) Cut down the AC power of the inverter and wait for 10 minutes .Then power on the
inverter with AC side connected again .The safety standard has been changed now.

29
7.4 State Information
State Display State information
Waiting Initialization & waiting
Wait Reconnects Reconnect
Checking’s Checking
Normal Normal Normal state
F00 GFCI Device Fault
F01 Island Fault
F03 PV Volt Low
F04 Consistency Fault
F05 Bus Volt Low
F06 Bus Volt High
F09 No Utility
F10 Ground Current Fault
F11 Bus Unbalance
F12 10min Over Volt
Fault
F13 Over Temp Fault
F15 PV Volt High
F17 Grid Volt Fault
F18 Isolation Fault
F19 Current DC Offset
F21 PV2 Over Current
F24 PV1 Over Current
F25 Relay Fault
F27 Inv Over Current
F29 Grid Freq Fault
Flash F/W Updating Update

About the further information for each fault, please reference toChapter“10.TROUBLESHOOTING”.

30
8. Communication Setting
8.1 GPRS Card
GPRS card is an optional device. If your inverter had installed the GPRS card, please
go to 8.3. Register on monitoring website.

After unpacking the box, please check the parts according to the below list. Contact the
manufacturer immediately when you find any damage, missing or wrong model.

No. Name Quantity

C A PV data 1
collector
B B GPRS 1
antenna
C Rubber 1
A washer

Omnik provide 2 kinds of GPRS cards. One is a standard GPRS card and the other one
has a card slot.

No. Name
A 14 pin connector
B I-PEX interface
A

31
C

B
No. Name
A 14 pin connector
B SIM card slot
C I-PEX Interface

The serial number is shown as below.

8.2 Installation of GPRS/WiFi card


Warning: Before installing the GPRS card to inverter, you must turn off both the AC side
and DC side of inverter to make sure personal safety.

32
Unscrew the four screws on the interface panel with the screwdriver as shown in Picture
above and keep the screws aside.

The standard connector has two holes. Use the single-hole rubber washer to take place of
the double-hole rubber washer.

Insert the GPRS antenna through the gland and screw the hex nut with a torque of 2.0
N.m.

33
Connect the data line into the I-PEX interface.

While using the second kind of GPRS card, just insert the SIM card into the card slot.
Then insert the GPRS card into the inverter.

Install the communication box back to the inverter. While the installation is completed,
Antenna can be turned in 360 degrees.

34
8.3 Register on monitoring website
The PV monitoring system of Omnik is supported by: IE8, Firefox, Chrome, and Safari.
Login the website http://www.omnikportal.com, click register to enter the user registration
page, follows the requirements for registration; please fill in the information for register. After
successful registration, enter the mailbox and activity the account, then to complete the
registration.

Click and enter the register interface

Choose the account type

35
Remarks: please read the < Omnik service agreement > carefully, the enclosure is the
cost list for all the countries; please choose your operators End User means the final
user

“*” you must fill it

Fill in the power station information

36
Fill in the power station information

After the register, you may enter next chapter 8.4 Login Monitoring System.

37
8.4 Login monitoring System
After the successful register and account activation, open the login interface as below.
Input the correct email and code. Enter the PV monitoring system. Then you can monitor and
manage the power station.

Input the
correct email
and code

Input the email and code

Power station list

User interface

38
List of power station

Back to user Enter the sharing Enter the configure


Not yet open interface case “company account”
interface

Add one case under your account Reset

Navigation Bar

39
Change
case
Energy saving
Case info search

Real-time power and generated energy switchover

Print current figure

Power station info

Main interface of Power Station

40
Internal temperature

Latest data collecting time

Real Time Interface

Parameter options
Choose the aim inverter

History Interface

41
Alert Interface

System Setting Interface

42
Add serial number

8.5 WiFi card


WiFi card is an optional device. If your inverter had installed the WiFi card, please go to
8.6. Network Settings. If your inverter had not installed the WiFi card, please go to 8.2.
Installation of GPRS/WiFi card first, then go to 8.6. Network Settings.

After unpacking the box, please check the parts according to the below list. Contact the
manufacturer immediately when you find any damage, missing or wrong model.

No. Name Quantity


B
PV data
A 1
collector
WiFi
B 1
antenna
C
Rubber
A C 1
washer

43
WiFi card is shown as below:
C

No. Name
A 14 pin connector
B Reset Button
C I-PEX Interface

Serial Number

8.6 Netwoek Settings


1) Prepare a computer or device, e.g. tablet PC and smart phone that enables WiFi
2) Obtain an IP address automatically
 Open Wireless Network Connection Properties, double click Internet Protocol
Version 4(TCP/IPv4)
 Select Obtain an IP address automatically, and click OK

44
3) Open wireless network connection and click View Wireless Networks
Select wireless network of the data logging module, no passwords required as default.
The network name consists of AP and the serial number of the product. Then click
Connect.

45
Connection successful
Notice: If AP_ (serial number of product) is not available in the wireless network list, there may be
problems in the connection or setting of data logging module. Please check if the WiFi had installed ok, and
inverter has been powered on.
Before troubleshooting, please inquire with your inverter installer whether you are allowed to
remove the cover of the inverter to trouble shoot the module. If not allowed, please contact
customer service.
4) Set parameters of WiFi module
(a) Open a web browser, and enter 10.10.100.254(the Default IP address of WiFi card,
you may set domain name access, please see the picture 6-14), then fill in username:
admin and password: admin, both of which are admin as default.
Recommended browsers: Internet Explorer 8+, Google Chrome 15+, Firefox 10+

Note:

① If the IP address shows 0.0.0.0 (factory value) on your LCD (Picture5-4-1), it is not a correct address.
There are 2 cases show 0.0.0.0:

 Not connect router rightly, you need reset to connect you router to make it right

 Card loose in the inverter, please check your inverter, see chapter 4:.WiFi Card Installation

② The default username & password :admin, admin, we suggest modify the username & password:

Step: choose Account, input your username &password.

46
admin
admin

(b) In the configuration interface of WiFi module, you can view general information of
the module.
Follow the setup wizard to start quick setting.

Click Wizard to start

47
Click Start to continue

Click Refresh to search available wireless networks


48
Select the wireless network you need to connect, then click Next

Notice:

① If the signal strength (RSSI) of the selected network is <10%, which means unstable connection,
please adjust the antenna of the router, or use a repeater to enhance the signal.

② We recommend router setting:

 Security setting: WPA2-personal


 Encryption type: AES

49
Enter the password for the selected network, then click Next

Select Enable to obtain an IP address automatically, then click Next


Notice:

① Turn off the firewall of the router

② Make sure the DHCP function of the router is enable

50
If setting is complete, the above page will display. Click OK to restart.

If setting is complete, the above page will display.


After your WiFi card set ok and get IP address from your router for example: 192.168.16.8,
(You may see the IP address from inverter)
Input: http://192.168.16.8/ will display the following page:
51
You may also add your domain name of WiFi card to easy access according below
picture , after you set ok, input http://wifi, you may also access the related page.

52
Now we finish the network setting, please go to 8.3. Register on monitoring website.

8.7 Ethernet Card


Ethernet card is an optional device. If your inverter had installed the Ethernet card,
please go to 8.3. Register on monitoring website. If your inverter had not installed the
WiFi card, please go to 8.8. Installation of Ethernet card first.

After unpacking the box, please check the parts according to the below list. Contact the
manufacturer immediately when you find any damage, missing or wrong model.

No. Name Quantity

A PV data 1
collector

53
The Ethernet card is shown as below.

No. Name
A RJ45 connector
A B B 14 pin connector
C Reset button

The serial number is shown as below.

8.8 Installation of Ethernet card


Warning: Before installing the Ethernet card to inverter, you must turn off both the AC side
and DC side of inverter to make sure personal safety.

Unscrew the four screws on the interface panel with the screwdriver as shown in Picture
above and keep the screws aside.

54
Wear the Ethernet cable into the waterproof terminals, and waterproof terminals and the
cover plate is installed.

Insert the Ethernet card into the inverter.

Connect the Ethernet cable to the Ethernet card.

55
Strengthen waterproof case closely back to the inverter. Then connect the other side of
the Ethernet cable to the router LAN port

8.9 RS485 card


RS485 card is used for external communication device. There are 3 connectors in the
RS485 card. The definition of the connectors is shown in the table.

CON 3
14 pin

connector
CON 2

CON 1
SD Card Slot

1 2 3 1 2 3 1 2

56 CON 1 CON 2 CON 3


Connector No. Name Description Connection

1 A1 RS485+ Signal

CON1 2 B1 RS485- Signal Wi-Fi/GPRS Kit

3 GND RS485 GND

1 A2 RS485+ Signal
CHIT DIN Meter
CON2 2 B2 RS485- Signal
(DDSU 666)
3 GND RS485 GND

1 OP Relay Operation
CON3 Alarm
2 NO Relay Normal Open

8.9.1 CON 1

CON 1 is used to communicate with Wi-Fi Kit and GPRS Kit. The connector of Kit is shown
as below.
Line sequence of T568B RJ45 KIT
1 -
1. orange with white 2 -
2. orange
3. green with white 3 -
4. blue 4 A1
RJ45 plug 5. blue with white 5 B1
6. green
7. brown with white 6 -
8. brown 7 GND
8 GND

The definition of the connector is shown in the table.


More details can be obtained in the user manual of GPRS / Wi-Fi Kit.

8.9.2 CON 2

57
CON 2 is only used to communicate with CHIT DIN Meter (DDSU 666). It can be applied
for solar projects of self-consumption without power export to the grid. It can ensure that the
power generated by solar system will not export to grid at anytime.
There are 2 types of meters. The first type of meter is connected into the power grid as
shown below.

58
The definition of the connector is shown in the table.

No. Meter CON


1 L(*Grid side)
2 L(Inverter side)
3 N
4 N
5 -
6 -
7 A
8 B

The second type of meter is used with CT as shown below.

59
The definition of the connector is shown in the table.

No. Meter CON


1 L
2 L
3 N
4 N
5 CT(*White)
6 CT(*Black)
7 A
8 B

More details can be obtained in the user manual of CHIT DIN Meter (DDSU 666).

CON 3

CON 3 is used to control the alarm LED. It is a pair of Normally open contacts.
The load capacity of the Relay is 230 V/0.5 A.

60
9. Recycling and Disposal
To comply with European Directive 2012/19/EU on waste Electrical and Electronic
Equipment and its implementation as national law, electrical equipment that has
reached the end of its life must be collected separately and returned to an approved
recycling facility. Any device that you no longer required must be returned to your dealer
or you must find an approved collection and recycling facility in your area.

Ignoring this EU Directive may have severe affects on the environment and your health.

WARNING

This device SHALL NOT be disposed of in


residential waste.

61
10. Troubleshooting
Fault No. Fault Info On Display Possible Reasons Solutions

1.Restart to check
F00 GFCI Device Fault Inverter GFCI Detector Issue 2.Re-Flash software
3.Replace part or inverter
No Grid or Local Grid Restart to check after local grid is stable
F01 Island Fault
Frequency Isn't Stable Close the protection from the inverter
1.Correct the installation (Add Panels
More)
F03 PV Volt Low DC voltage is below 150V
2.Re-Flash software
3.Replace part or inverter

The Data That Be Master And 1.Restart to check


F04 Consistency Fault Slave CPU Detected Is 2.Re-Flash software
Inconsistency 3.Replace part or inverter

1.Test Value Wrongly 1.Restart to check


F05 Bus Volt Low 2.Software Issue 2.Re-Flash software
3.Hardware Broken 3.Replace part or inverter

1.Test Value Wrongly 1.Restart to check


F06 Bus Volt High 2.Software Issue 2.Re-Flash software
3.Hardware Broken 3.Replace part or inverter

Measure AC voltage with a multi meter


F09 No Utility No AC voltage
Check the wires in AC cable
.Make inverter grounded well
1.Poor grounding
2.Change it to another standard with
F10 Ground Current Fault 2.It Often occurs in the rainy
wider
day.
protection range under authorization
1.Inverter Control Circuit
1.Restart to check
Problem
F11 Bus Unbalance 2.Re-Flash software
2.Values Of Two Rows Bus
3.Replace part or inverter
Capacitance Differ Too Much

Mean Value Within 10min Is


Change it to another standard with wider
F12 10min Over Volt Above 10% Of The Rated Grid
protection range under authorization
Voltage

The temperature of internal It happens rarely and can be used


F13 Over Temp Fault
device exceeds 80 ℃ Normally

62
1.Correct The Installation (Remove
DC Voltage Is Too High Due To Panels)
F15 PV Volt High
Wrong Installation 2.Re-Flash Software
3.Replace Part Or Inverter
Grid Voltage Detection Within
F17 Grid Volt Fault Change the grid voltage protection range
A Period Is Anomalous
1.Remove this Fault
Impedance To Ground Between
2.Change it to another standard with
F18 Isolation Fault Battery Positive and Negative
wider
Is Less Than 2 MΩ
protection range under authorization

A Phase Current Waveform


Change it to another standard with wider
F19 Current DC Offset That Be Detected Is Larger
protection range under authorization
Deviation

The input current of PV2 is over


1.Restart the inverter
rated value. May be there is
F21 PV2 Over Current 2.If the problem persists, please
something wrong with the
replace the inverter.
hardware
The input current of PV1 is over
1.Restart the inverter
rated value. May be there is
F24 PV1 Over Current 2.If the problem persists, please
something wrong with the
replace the inverter.
hardware
General error in inverter start
If the problem persists, please
F25 Relay Fault time, there may be damage of
replace the inverter.
relay

1.Restart the inverter to check


The inverter current is over
F27 Inv Over Current 2.If it doesn't get back to normal
rated value.
please replace inverter

Change it to another standard with


The grid frequency exceeds the
F29 Grid Freq Fault wider protection range under
set range
authorization

63
11. Abbreviation
LCD Liquid Crystal Display

LED Light Emitting Diode

MPPT Maximum Power Point Tracking

PV Photovoltaic

Vdc Voltage at the DC side

Vac Voltage at the AC side

Vmpp Voltage at the Maximum Power Point

Impp Amperage at Maximum Power Point

AC Alternating Current ( Form of electricity supplied by Utility


Company )

DC Direct Current ( Form of electricity generated by PV modules )

DC Switch Switch in the DC Circuit. Disconnects DC source from Inverter.


May be integrated or external to Inverter.

64
12. Contact
Omnik New Energy Co.,Ltd.(Headquarters)
Address: Third Floor,Building 3,No.63 Weixin Road,SIP,Suzhou,China
Tel: +86-512-6956-8216
Fax: +86-512-6295-6682
E-mail: sales @omnik-solar.com
sevice@omnik-solar.com
Website: www.omniksolar.com

Omnik German branch


Address: Omnik Gmbh Forsthausstr.8A 65479 Raunheim
Tel: +49(0) 1799762654
Mobile: +49(176) 30743149
E-mail: jingjing.zhang@omnik-solar.com

Omnik UK Service Partner


Address: 3 More London Riverside SE1 2RE,London
Tel: +86 512 69568216 8833
E-mail: Frank.Liu@omnik-solar.com

OmnikItaly Srl
Address: Via Francesco Baracca, 500043 Ciampino(Roma)
Tel: +39 06 211.26.522
Fax: +39 06 565.616.46
E-mail: info@omniksolar.it
Website: www.omniksolar.it

Omnik Netherlands Office


Address: Goudstraat 65,2718RD Zoetermeer, The Netherlands
Tel: +31 30265 7845
E-mail: lena.wang@omnik-solar.com

65
66
GUARANTEE CARD

Agency retention
------------------------------------------------------------------------------------------------------------

的 User information 得
Product Model

Product ID

Purchase Date

Customer Name

的 Historical Warranty 的
Warranty date Troubleshooting Finished date Customer Signature

Client retention

67
的 User Information 得
Product Model

Product ID

Purchase Date

Customer Name

的 Historical Warranty 的
Warranty date Troubleshooting Finished date Customer Signature

--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

的 Warranty Terms 的
1. Please fill in this card carefully and read the following warranty terms carefully to
ensure that the product is effectively guaranteed.
① User keeps the card carefully when purchasing the product and asks the seller to
seal it.
② Provide the warranty card when repairing the machine in the warranty period.
③ The information in this warranty card is true; otherwise it will not be valid.
④ Warranty period is 5 years(standard) □10 years(selectable,effective after
sealing )During the warranty period, if the product fails, the quality of the
original device or the production problem, the company provides free maintenance and
parts replacement.
2. The following reasons cannot be used normally in the warranty period.
① Cause damage for not following the instructions.
② All man-made or accidental product damage
③ Without the company's approved repair, modification or product seal sticker damage.
④ Aging bruising and scratches on the surface of the product.
3. After the warranty expires, the user can still get the maintenance services provided by
the company, but the corresponding expenses shall be paid.

68

You might also like